Honeywell T6 Pro Programmable Thermostat Installation Instructions

Package Includes:

Optional Cover Plate Installation

Use the Optional Cover Plate when mounting the thermostat to an electrical junction box or to cover a paint gap from an old thermostat.

  1. Separate the Junction Box Adapter from the Cover Plate.
  2. Mount the Junction Box Adapter to the wall or an electrical box using the supplied screws. Ensure the Adapter Plate is level. Do not overtighten.
  3. Attach the UWP by hanging it on the top hook of the Junction Box Adapter and snapping the bottom of the UWP in place.
  4. Snap the Cover Plate onto the Junction Box Adapter.

UWP Mounting System Installation

  1. Turn off power at the breaker box or switch. Open the package to find the UWP.
  2. Position the UWP on the wall. Level and mark hole positions. Drill holes at marked positions and insert supplied wall anchors using a hammer. (Drill 7/32" holes for drywall).
  3. Pull the door open and insert the wires through the wiring hole of the UWP.
  4. Place the UWP over the wall anchors. Insert and tighten mounting screws. Do not overtighten. Tighten until the UWP no longer moves. Close the door.

Power Options

Insert R and C wires into designated terminals for primary AC power. The C terminal is optional if batteries are installed, but recommended. Remove wires by depressing the terminal tabs.

Insert AA batteries for primary or backup power.

Setting Slider Tabs

Set R Slider Tab: Use the built-in jumper (R Slider Tab) to differentiate between one or two transformer systems.

Note: Slider Tabs for U terminals should be left in place for T6 Pro models.

Wiring Terminal Designations

TerminalInputDescription
SInput for wired indoor or outdoor sensors (TH6320U and TH6220U only)
L/A - AHeat Pump fault input (Common (C) wire required for LA/A)
O/BChangeover valve
YCompressor contactor (stage 1)
Y2Compressor contactor (stage 2)
GFan Relay
C24VAC common. For 2 transformer systems, use common wire from cooling transformer.
UUnused
AUX - W2Auxiliary heat relay; Heat relay (stage 2)
EEmergency Heat relay
WHeat relay (stage 1)
KConnect to K on Wire Saver Module**
R24VAC power from heating transformer*
Rc24VAC power from cooling transformer*

Note: Not all terminals may be used. The most commonly used terminals are shaded.

* Terminal can be jumped using Slider Tab. See "Setting Slider Tabs".

** The THP9045A1023 Wire Saver Module is used on heat/cool systems when you only have four wires at the thermostat and need a fifth wire for a common wire. Use the K terminal in place of the Y and G terminals on conventional or heat pump systems to provide control of the fan and the compressor through a single wire; the unused wire then becomes your common wire. See THP9045 instructions for more information.

Wiring Conventional Systems: Forced Air and Hydronics

Shaded areas apply only to TH6320U/TH6220U or as noted.

1H/1C System (1 transformer)

Heat-only System

Heat-only System (Series 20) [5]

Heat-only System (power open zone valve) [5]

1H/1C System (2 transformers)

Heat-only System with Fan

Cool-only System

2H/2C System (1 transformer) [6]

NOTES

Wire specifications: Use 18- to 22-gauge thermostat wire. Shielded cable is not required.

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R-Slider Tab on UWP to the R setting. For more information, see "Setting Slider Tabs" on page 3.

[3] Optional 24VAC common connection.

[4] Common connection must come from cooling transformer.

[5] In ISU set Heat system type to Radiant Heat. Set number of cool stages to 0.

[6] In Installer Setup, set system type to 2Heat/2Cool Conventional.

Wiring Heat Pump Systems

Shaded areas apply only to TH6320U/TH6220U or as noted.

1H/1C Heat Pump System

2H/1C Heat Pump System [8]

2H/2C Heat Pump System (TH6320U only) [9]

3H/2C Heat Pump System (TH6320U only) [10]

Dual Fuel System (TH6320U / TH6220U only)

NOTES

Wire specifications: Use 18- to 22-gauge thermostat wire. Shielded cable is not required.

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R-Slider Tab on UWP to the R setting. For more information, see "Setting Slider Tabs" on page 3.

[3] Optional 24VAC common connection.

[7] In Installer Setup, set changeover valve to 0 (for cool changeover) or B (for heat changeover).

[8] In ISU set Heat system type to Heat pump. 1 compressor and 1 stage of backup heat.

[9] In ISU set Heat system type to Heat pump. 2 compressors and 0 stage of backup heat.

[10] In ISU set Heat system type to Heat pump. 2 compressors and 1 stage of backup heat.

[11] Dual fuel with Y2 only for TH6320U.

Thermostat Mounting

  1. Push excess wire back into the wall opening.
  2. Close the UWP door. It should remain closed without bulging.
  3. Align the UWP with the thermostat, and push gently until the thermostat snaps in place.
  4. Turn the power on at the breaker box or switch.

Set the Time and Date

Time

  1. Press Menu on your thermostat.
  2. Press + or - to go to TIME. Press Select.
  3. Press + or - to choose between 12 or 24 hour. Press Select.
  4. Use + or - to adjust the hour. Press Select.
  5. Use + or - to adjust the minutes. Press Select to exit Time menu.

Date

  1. If previously setting time, continue to Step 2. If at the Home screen, press Menu on your thermostat.
  2. Press + or - to go to DATE. Press Select.
  3. Use + or - to adjust year. Press Select.
  4. Use the + or - to adjust month. Press Select.
  5. Use the + or - to adjust day. Press Select to save and exit Date menu.

System Operation Settings

  1. Press the Mode button to cycle to the next available System mode.
  2. Cycle through the modes until the required System mode is displayed and leave it to activate.

System modes: Auto, Heat, Cool, Em Heat, Off

Fan Operation Settings

  1. Press the Fan button to cycle to the next available Fan mode.
  2. Cycle through the modes until the required Fan mode is displayed and leave it to activate.

Fan modes: Auto, On, Circ

Alerts or Reminders

  1. Press Menu, and then press $\rightarrow$ until display shows ALRT.
  2. Press Select to display which alert(s) are present.
  3. The word SNZE (SNOOZE) appears.
  4. Press Select again to snooze the reminder for 7 days.
  5. To clear the alert, press Select, and then press $\rightarrow$ to go to CLER (Clear).
  6. Press Select to clear the reminder.

* Some alerts cannot be snoozed or cleared. Please call your local heating and cooling professional if this occurs. The heating and cooling system may require service.

Installer Setup (ISU)

  1. Press and hold CENTER and + buttons for approximately 3 seconds to enter the advanced menu.
  2. Press Select to enter ISU.
  3. Press Select to cycle through menu setup options.
  4. Press + or - to change values or select from available options.
  5. Press Select and confirm your settings or press Back to ignore changes and return to the ISU menu screen to continue editing another setup option.
  6. To finish the setup process and save your settings, press Home and return to the Home screen.

Note: A complete list of all setup (ISU) parameters and options follows.

Advanced Setup Options (ISU)

Note: Depending on system settings, not all options may be available.

# ISUISU NameISU Options (factory default in bold)
120Scheduling Options0= Non-Programmable, 2=5-2 Programmable, 3=5-1-1 Programmable, 4= T-Day Programmable
125Temperature Indication Scale0= Fahrenheit, 1= Celsius
130Outdoor Sensor (TH6320U / TH6220U only)0= None, 1= Wired Outdoor Sensor
200Heating System Type1= Conventional Forced Air Heat, 2= Heat Pump, 3= Radiant Heat, 5= None (Cool Only)
205Heating Equipment TypeConventional Forced Air Heat: 1= Standard Efficiency Gas Forced Air, 2= High Efficiency Gas Forced Air, 3= Oil Forced Air, 4= Electric Forced Air, 5= Hot Water Fan Coil
Heat Pump: 7= Air to Air Heat Pump, 8= Geothermal Heat Pump
Radiant Heat: 9= Hot Water Radiant Heat, 12= Steam
218Reversing Valve 0/B0= 0/B in Cool, 1= B/0/B in Heat
220Cool Stages / Compressor Stages (200=Conv / 200=HP)0, 1, 2 (Note: Only 1 compressor stage available on TH6210U and TH6220U models if configured for heat pump)
221Heat Stages / Backup Heat StagesHeat Stages: 1, 2
Backup Heat Stages: 0, 1
230Fan Control in Heat1= Equipment Controls Fan, 2= Thermostat Controls Fan
253Aux/E terminal control (Fixed to "0" setting on all models except TH6320U)0= Drive both Aux & E together, 1= Aux and E independent
255Backup Heat Source (Heat Pump Only) (TH6320U / TH6220U only)1= Electric Forced Air, 2= Gas/Oil Forced Air (or Fossil Forced Air)
256Emergency Heat Source (TH6320U only)1= Electric Forced Air, 2= Gas/Oil Forced Air (or Fossil Forced Air)
260External Fossil Fuel Kit (TH6320U / TH6220U only)0= Thermostat Controls Backup Heat, 1= External Fossil Fuel Kit Controls Backup Heat
300System Changeover0= Manual, 1= Automatic
303Auto Changeover Differential0°F to 5°F (0.0°C to 2.5°C) (Note: Differential is NOT deadband. Honeywell uses an advanced algorithm that fixes deadband at 0°F. The differential setting is the minimum number of degrees from set-point needed to switch from the last mode running (heat or cool) to the opposite mode when the thermostat is in auto-changeover. This is more advanced than previous thermostats.)
340Backup Heat Droop0= Comfort, 2°F to 15°F (Note: 0 (comfort) setting only available if backup heat (ISU 255) is set to electric.)
350Upstage Timer for Backup Heat0= Off, 1= 30 minutes, 2= 45 minutes, 3= 60 minutes, 4= 75 minutes, 5= 90 minutes, 6= 2 hours, 7= 3 hours, 8= 4 hours, 9= 5 hours, 10= 6 hours, 11= 8 hours, 12= 10 hours, 13= 12 hours, 14= 14 hours, 16= 16 hours
355Compressor Lockout / Balance Point-- = Off, 5°F to 60°F (in 5°F increments), -15.0°C to 15.5°C (in 2.5°C or 3.0°C increments) (Note: Use a wired sensor to set compressor lockout / balance point on TH6320U / TH6220U.)
356Outdoor Lockout Backup Heat-- = Off, 5°F to 65°F (in 5°F increments), -15.0°C to 18.5°C (in 2.5°C or 3.0°C increments)
365Compressor Cycle Rate (Stage 1)1-6
366Compressor Cycle Rate (Stage 1)1-6
370Heating Cycle Rate (Stage 1)1-12
371Heating Cycle Rate (Stage 2)1-12
375Heating Cycle Rate Auxiliary Heat1-12
378Heating Cycle Rate Emergency Heat (TH6320U only)1-12
387Compressor Protection0= Off, 1-5 minutes
425Adaptive Intelligent Recovery0= No, 1= Yes (Note: Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier, ensuring the indoor temperature will match the setpoint at the scheduled time.)
430Minimum Cool Setpoint50°F to 99°F (50°F), 10.0°C to 37.0°C (10.0°C)
431Maximum Heat Setpoint40°F to 90°F (90°F), 4.5°C to 32.0°C (32.0°C)
435Keypad Lockout0= None, 1= Partial, 2= Full
500Is Indoor Temperature Sensor WIRED to your system? (TH6320U / TH6220U only)0= No, 1= Yes
515Indoor Sensor type (TH6320U / TH6220U only)0= 10k, 1= 20k
520Which Sensors will be used for TEMPERATURE Control? (Multiple Sensors are Averaged) (TH6320U / TH6220U only)1= Thermostat Only, 2= Wired Only, 3= Average
702Number of Air Filters0-2
711Air Filter 1 Replacement Reminder0= Off, 1= 10 Run Time Days, 2= 20 Run Time Days, 3= 30 Run Time Days, 4= 45 Run Time Days, 5= 60 Run Time Days, 6= 90 Run Time Days, 7= 120 Run Time Days, 8= 150 Run Time Days, 9= 30 Calendar Days, 10= 45 Calendar Days, 11= 60 Calendar Days, 12= 75 Calendar Days, 13= 3 Calendar Months, 14= 4 Calendar Months, 15= 5 Calendar Months, 16= 6 Calendar Months, 17= 9 Calendar Months, 18= 12 Calendar Months, 19= 15 Calendar Months
712Air Filter 2 Replacement Reminder0= Off, 1= 10 Run Time Days, 2= 20 Run Time Days, 3= 30 Run Time Days, 4= 45 Run Time Days, 5= 60 Run Time Days, 6= 90 Run Time Days, 7= 120 Run Time Days, 8= 150 Run Time Days, 9= 30 Calendar Days, 10= 45 Calendar Days, 11= 60 Calendar Days, 12= 75 Calendar Days, 13= 3 Calendar Months, 14= 4 Calendar Months, 15= 5 Calendar Months, 16= 6 Calendar Months, 17= 9 Calendar Months, 18= 12 Calendar Months, 19= 15 Calendar Months
1400Backlighting0= On Demand, 1= Continuous (Note: Common wire needed for continuous.)
1401Backlight brightness1-5 (Note: Only displayed if continuous backlight selected.)
1410Clock Format12 / 24
1415Daylight Saving Time0= Off, 1= On
1420Temperature Display Offset-3 to 3 F (0), -1.5 to 1.5 C (0)

Installer System Test

To perform a System Test:

  1. Press and hold CENTER and + buttons for approximately 3 seconds to enter the advanced menu.
  2. Use + to go to TEST. Press Select to enter System Test.
  3. Use + to change between Heat, Cool, Fan, Em Heat, or Ver (thermostat version information). Press Select.
  4. Press + to turn stages on one at a time, and press - to turn them off.
  5. Use the Home button to exit the System Test.

System Test System Status

Shaded areas apply only to TH6320U/TH6220U or as noted.

SystemStatus CodeDescription
Heat0All Off
1Heat Stage 1 on
2Heat Stage 2 also on
3Heat Stage 3 also on
Cool0All Off
1Cool Stage 1 on
2Cool Stage 2 also on
Em Heat0All Off
1Em Heat on
Fan0Fan Off
1Fan On

Specifications

Temperature Ranges

Working Ambient Temperature

32°F to 120°F (0°C to 48.9°C)

Operating Ambient Temperature

37°F to 102°F (2.8°C to 38.9°C)

Shipping Temperature

-20°F to 120°F (-28.9°C to 48.9°C)

Operating Relative Humidity

5% to 90% (non-condensing)

Physical Dimensions

4-1/16"H x 4-1/16"W x 1-5/32"D (103.5 mm H x 103.5 mm W x 29 mm D)

Electrical Ratings

TerminalVoltage (50/60Hz)Running Current
W Heating20-30 Vac0.02-1.0 A
(Powerpile)750 mV DC100 mA DC
W2 (Aux) Heating20-30 Vac0.02-1.0 A
E Emergency Heat20-30 Vac0.02-0.5 A
Y Compressor Stage 120-30 Vac0.02-1.0 A
Y2 Compressor Stage 220-30 Vac0.02-1.0 A
G Fan20-30 Vac0.02-0.5 A
O/B Changeover20-30 Vac0.02-0.5 A
L/A Input20-30 Vac0.02-0.5 A

Troubleshooting

Display is blank

Heating or cooling system does not respond

Temperature settings do not change

"Cool On" or "Heat On" is flashing

Aux heat runs in cooling

Cool runs with a call for heat

Cautions

Customer Assistance

For assistance with this product, please visit customer.honeywell.com.

Or call Honeywell Customer Care toll-free at 1-800-468-1502.

PDF preview unavailable. Download the PDF instead.

640275 FcsP55 PDFium PDFium

Related Documents

Preview Honeywell FocusPRO TH6220D Programmable Thermostat Installation Guide
Comprehensive installation guide for the Honeywell FocusPRO TH6220D Programmable Thermostat, covering product application, system types, power options, wiring, installer setup, system testing, troubleshooting, and specifications.
Preview T6 Pro Programmable Thermostat Installation and User Guide | Honeywell Home
Comprehensive installation instructions and user guide for the Honeywell T6 Pro Programmable Thermostat, covering mounting, wiring, power options, settings, and system testing.
Preview Honeywell VisionPRO TH8000 Series Thermostat Installation Guide
Comprehensive installation guide for the Honeywell VisionPRO TH8000 Series programmable thermostat, covering wallplate installation, wiring, installer setup, system testing, special functions, and specifications.
Preview Honeywell TH8320U and TH8321U Touch Screen Programmable Thermostats Installation Guide
Comprehensive installation instructions for Honeywell TH8320U and TH8321U Touch Screen Programmable Thermostats, covering application, wiring, system setup, and troubleshooting.
Preview Honeywell PRO 1000/2000 Series Programmable and Non-Programmable Thermostats Installation Manual
Installation manual for Honeywell PRO 1000 and 2000 series programmable and non-programmable thermostats. Covers system types, installation steps, wiring, settings, and specifications.
Preview Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Installation Instructions
This document provides comprehensive installation, setup, and operation instructions for the Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat. It covers wallplate installation, power options, detailed wiring diagrams for conventional and heat pump systems, thermostat mounting, installer setup procedures, system testing, specifications, and customer assistance.
Preview Honeywell T Series Non-Connected Thermostats: Simple Selection & Installation Guide
Explore the Honeywell T Series non-connected thermostats, including T4 Pro, T6 Pro, and T1 Pro. This guide details simple selection, standardized installation with the UWP system, and easy upsell opportunities for contractors.
Preview Honeywell TH3210D Non-Programmable Digital Thermostat Installation Guide
Comprehensive installation guide for the Honeywell TH3210D Non-Programmable Digital Thermostat, covering wiring, setup, and troubleshooting for 24 VAC heat pump systems.