Installation Guide for NOTIFIER models including: AM2020, AM2020 Fire and Security Alarm Control Panel with DIA-2020 Display Interface, Fire and Security Alarm Control Panel with DIA 2020 Display Interface, Security Alarm Control Panel with DIA-2020 Display Interface, Alarm Control Panel with DIA-2020 Display Interface, Control Panel with DIA-2020 Display Interface, DIA-2020 Display Interface, Display Interface

Click here to download

Notifier AM2020 w-DIA-2020 Software Release Summary - Fire Alarm Resources - Free fire alarm PDF manuals, documents, installation instructions, and technical specifications


File Info : application/pdf, 4 Pages, 943.51KB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676770490
12 Clintonville Road Northford, CT 06472-1610 203-484-7161 FAX: 203-484-7118
Software Release Summary for the Notifier AM2020
Fire/Security Control Panel with the DIA-2020 Display Interface
Assembly

AROM6N

This document covers Release 6.0 Software as it affects the following ROMs:

AROM6N-AMG AROM6N-DIA

AROM6N-SIB

AROM6N-CPU

AROM6N-LIB

AROM6N-XPP

AROM6N-AMGX4 AROM6N-AMGZC AROM6N-LIB-B

AROM6N-AMGZCF

CAUTION - System Reacceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72-1993 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.

www.PDF-Zoo.com

firealarmresources.com

I1 Document 15414
07/18/97 Revision
P/N 15414:I1 ECN 97-294

AROM6N Inventory List
The following replacement ROMs must be ordered individually according to your system requirements. AROM6Ns cannot be used in conjunction with earlier ROMs. All system ROMs must be upgraded at the same time. (See Compatibility Warning)

AROM6N-AMG (standard AMG operation at Annunciator address 29, 30, 31, or 32)

Includes: EPROM for AMG-1/AMG-E Document # 15744 Document # 15889

"Field Change Procedure for the AM2020 and AFP1010" "Voice Alarm Multiplex-2020"

AROM6N-AMGX4 (for use with 5th through 8th AMG in one system at

Annunciator address 25, 26, 27, or 28)

Includes: EPROM forAMG-1/AMG-E Document # 15744 Document # 15889

"Field Change Procedure for the AM2020 and AFP1010" "Voice Alarm Multiplex-2020"

EPROM

Part #

AROM6N-AMG ---------- 73284

AROM6N-AMGX4 ------ 73295

AROM6N-AMGZC ----- 73529

AROM6N-AMGCF ------ 73534

AROM6N-CPU ----------- 73549

AROM6N-DIA ------------ 73547

AROM6N-LIB ------------ 73539

AROM6N-LIB-B -------- 73540

AROM6N-SIB ------------ 73496

AROM6N-XPP ----------- 73679

AROM6N-AMGZC

(for zone coded AMG operation occupying addresses 2, 3, 4, and 5)

Includes:

EPROM for AMG-1/AMG-E

Document # 15744

"Field Change Procedure for the AM2020 and AFP1010"

Document # 15889

"Voice Alarm Multiplex-2020"

AROM6N-AMGZCF

(for zone coded AMG operation occupying addresses 2, 3, 4, and 5)

Includes:

EPROM for AMG-1/AMG-E

Document # 15744

"Field Change Procedure for the AM2020 and AFP1010"

Document # 15889

"Voice Alarm Multiplex-2020"

AROM6N-CPU
Includes: EPROM for CPU-2020 Document # 15744 Document # 15337

"Field Change Procedure for the AM2020 and AFP1010" "The AM2020/AFP1010 Fire Alarm Control Panel Operator's Instructions"

AROM6N-DIA
Includes: EPROM for DIA-2020 DIA-2020 Label Document # 15987 Document # 15744 Document # 15088 Document # 15088SUP

'LED Instruction Sheet' "Field Change Procedure for the AM2020 and AFP1010" "The AM2020/AFP1010 Manual" Supplement to Document 15088

AROM6N-LIB/AROM6N-LIB-B

Includes: EPROM for LIB-200 Document # 15744

"Field Change Procedure for the AM2020 and AFP1010"

AROM6N-SIB
Includes: EPROM for SIB-2048 Document # 15744

"Field Change Procedure for the AM2020 and AFP1010"

AROM6N-XPP
Includes: EPROM for XPP-1 Document # 15744 Document # 15888

"Field Change Procedure for the AM2020 and AFP1010" "The XP Series Transponder System"

2

15414-I1 07/18/97

www.PDF-Zoo.com

firealarmresources.com

Field Change Procedure. (Document # 15744) provides instructions for mechanical replacement of the ROMs.
DIA-2020 EPROM PROG. P/N 73547
DIA-2020 Label. Provides a quick reference to the ROM software level currently installed in the AM2020 DIA-2020 Assembly. Place this label on the inside of the DIA-2020 door during installation of the AROM6N-DIA.
AC POWER
FIRE ALARM
TROUBLE/ SECURITY ALARM
DISPLAY TROUBLE
SIGNAL SILENCE
15454 Mylar Security LED Overlay When software is upgraded to this level, the label shown above must be placed over the existing DIA-2020 LED legend (if the existing legend differs from the above).

AROM6N Special Features/Notes for the DIA-2020
Selectable Drift Compensation
This feature makes the NFPA 72-1993, Chapter 6 sensitivity calibrated test for intelligent detectors software selectable. NOTE: When the software provided with this upgrade kit is installed, the NFPA 72-1993, Chapter 6 Sensitivity Calibrated Test and Drift Compensation features will be automatically disabled. The installer must re-enable Drift Compensation (See the AM2020/AFP1010 Programming Manual, Document 15334) in order to restore the NFPA 72-1993, Chapter 6 Sensitivity Calibrated Test and Drift Compensation features.
UL1076/UL1610 Security
This feature allows the AM2020/AFP1010 to act as a combination fire/security protective signaling system. The AM2020/ AFP1010 is suitable for use as a Grade AA, Grade A, or Grade B Central Station and Proprietary Burglar Alarm Protected Premises and Receiving Unit, only after all installation requirements outlined and programming guidelines described in the AM2020/AFP1010 manuals have been adhered to. This feature utilizes four new software type IDs: SARM, SACM, SSYM, and SEQM in addition to a new control-bytime function SDEL.
UL864 Revised Standard for DACT Operation
The Fire Alarm Control Panel must delay the reporting of A.C. power loss to the digital alarm communicator. A new software type ID, DACT, is used with a CMX control module to accomplish this.
Zone Coded Voice
For female zone coded voice, the AMG1 requires the installation of both an AROM6N-AMGZCF chip and a VROM135 chip.

www.PDF-Zoo.com

firealarmresources.com

3 15414-I1 07/18/97

Previous AM2020 Software Releases
(The following features are included in the current software release)

ROMSC1-2020 · Enhanced Time/Date Input Format · Keyboard Operation and Terminal Supervi sion · Disabling the Piezo Sounder · Enhanced READ STATUS Options · Finding the Parentheses Keys · Latching LEDs on the SLC Loop · Self-Restoring Initiating Device Troubles · Peripheral Communication Rate
ROMSC2-2020 · Enhanced Read Status Option · System and Point Status Reports · Terminal Status Line Enabling · Detector Sensitivity Selection · Initiating Device Tracking Option · Software Type I.D. Grouping · Event-Pending Software Types · CPU/DIB Communications Failure Signal · P-80 Printer Troubleshooting Tip
ROMSC3-2020 (Rev A) · Maintenance Alert · Low Chamber Value
ROMSC3-2020 (Rev B, & C) · Maintenance Alert · Low Chamber Value · Display Monitor Capacity
ROMSC3-2020 (Rev D) · Maintenance Alert. · Low Chamber Value · Display Monitor Capacity. · Hardware/Software Compatibility.
AROM-4 (Rev A, B, C, D , E & F) · AMG-1 Address Change · ALL CALL Function · AMG-1 Functions · Dual Stage Operation (for Canada only) · XPP-1 Relay Mapping Change

· Non-Latching Inputs · ISIB Isolation · Annunciators · CGAS, AMNET, and AUTOPLEXOR
Compatibility Warning · History Mode · Disable · Control · Signal Silence/Signal Cut-out Times · Local Mode · Signal Silence Operation · Type I.D.'s · Time/Date · PRN-2 Paper Out/Off-line · NFPA · Terminal Beep
AROM5 (Rev A) · Battery Charger Control · Block Acknowledge · Control-By-Time · Control Module Reporting · Day/Night Sensitivity · Device Blink · Disabled Zones · Event Reminder · Expanded Read Status Functions · Expanded Status Line · Expanded User Reports · LED Latching · Local Printer · New Type I.D.'s · NIB Trouble Reporting · Non-Alarm Module Reporting · Periodic Detector Test · Prior/Next/Autostep Keys · Remote Page · Upload/Download of AM2020 Programming · Verification Counter Reset · Walk Test

AROM5 (Rev B - C) · Zone Coded Synthesized Chime · Zone Coded Voice
AROM5 (Rev D - F) · New AMG Boards
AROM5 (Rev G-I) · 72E Sensitivity Calibrated Test · Drift Compensation · Manual Reset of automatically activated control modules.
AROM6N (Rev A-B) · Selectable Drift Compensation · UL1076/UL1610 Security
AROM6N (Rev C-F) · Revised Standard for DACT Operation
AROM6N (Rev G-H) · Zone Coded Voice (Female)

Compatibility Warning
Software Combinations: All software part numbers are not compatible with each other. Improper mixing of software part numbers may compromise LifeSafety functions. If in doubt about the compatibility of a particular software combination, consult the factory.

CGAS, AMNET and AUTOPLEXOR

This software is not compatible with earlier versions of CGAS, AMNET and AUTOPLEXOR systems. Software in these items must be upgraded for compatibility.