User Manual for AIMS models including: AIMS, Pure Sine Wave Inverter Charger, PICOGLF10W, PICOGLF60W

AIMS INVERTER CHARGER MANUAL 1-6KW 0421

Global LF Series Pure Sine Wave Inverter Charger User's Manual

Aims Power PICOGLF40W48V240V User Manual

Aims 4000 Watt Inverter Charger 48V 120/240V PICOGLF40W48V240V


File Info : application/pdf, 39 Pages, 24.99MB

PDF preview unavailable. Download the PDF instead.

PICOGLF40W48V240V-Manual
Global LF Series Pure Sine Wave Inverter Charger User's Manual
Version 9.0 PICOGLF10W-PICOGLF60W
04/2021

1

Table of Contents
1. Important Safety Information...................................................................................................................................... - 2 1-1. General Safety Precautions ............................................................................................................................. - 2 1-2. Precautions When Working with Batteries .............................................................................................. - 2 -
2. Introduction........................................................................................................................................................................ - 3 2-1. General Information .......................................................................................................................................... - 3 2-2. Application ............................................................................................................................................................ - 3 2-3. Mechanical Drawing .......................................................................................................................................... - 4 2-4. Features .................................................................................................................................................................. - 6 2-5. Electrical Performance ..................................................................................................................................... - 6 2.5.1 Inverter ....................................................................................................................................................... - 6 2.5.2 AC Charger ................................................................................................................................................. - 7 2.5.3 Transfer ......................................................................................................................................................- 10 2.5.4 Auto Frequency Adjust........................................................................................................................- 10 2.5.5 Power Saver.............................................................................................................................................- 10 2.5.6 Protections...............................................................................................................................................- 13 2.5.7 Remote Control ......................................................................................................................................- 13 2.5.8 LED Indicator ..........................................................................................................................................- 15 2.5.9 Audible Alarm.........................................................................................................................................- 17 2.5.10 FAN Operation .....................................................................................................................................- 17 2.5.11 DIP Switches .........................................................................................................................................- 18 2.5.12 Auto Generator Start..........................................................................................................................- 19 2.5.13 Other Features .....................................................................................................................................- 19 2.5.14 Automatic Voltage Regulation .......................................................................................................- 20 -
3 Installation .........................................................................................................................................................................- 21 3.1 Unpacking and Inspection .....................................................................................................................- 21 -
3-2. Location ................................................................................................................................................................- 22 3-3. DC Wiring.............................................................................................................................................................- 22 3-4. AC Wiring .............................................................................................................................................................- 24 3-5. Grounding ............................................................................................................................................................- 26 -
3.5.1 Automatic Neutral-to-Ground Connection ..................................................................................- 26 3.5.2 Disabling the Automatic Neutral-to-Ground Connection ......................................................- 27 3-6. Install Flange.......................................................................................................................................................- 29 4.Troubleshooting Guide.................................................................................................................................................- 31 5.Warranty............................................................................................................................................................................- 33 Specifications ........................................................................................................................................................................- 34 Appendix 1 - Circuit Schematics....................................................................................................................................- 37 Appendix 2 - Installation Diagram................................................................................................................................- 38 -
1

1. Important Safety Information
NOTE: Before using the inverter, read and save this manual.
1-1. General Safety Precautions
1-1-1. Do not expose the inverter to rain, snow, spray, bilge or dust. To reduce risk of hazard, do not cover or obstruct the ventilation openings. Do not install the inverter in a zero-clearance compartment. Overheating may result. Allow at least 12" of clearance around the inverter for air flow. Make sure that the air can circulate freely around the unit. A minimum air flow of 145CFM is required. 1-1-2. To avoid risk of fire and electronic shock, make sure that existing wiring is in good electrical condition and that the wire is not undersized. Do not operate the inverter with damaged or substandard wiring. 1-1-3. This equipment contains components which may produce arcs and/or sparks. To prevent fire and/or explosion do not install in compartments containing batteries or flammable materials or in a location which require ignition protected equipment. This includes any space containing gasoline-powered machinery, fuel tanks, or joints, fittings, or other connection between components of the fuel system. See Warranty for instructions for servicing the inverter. 1-1-4. Do not disassemble the Inverter Charger. It contains no user-serviceable parts. Attempting to service the Inverter Charger yourself may result in electrical shock or fire. Internal capacitors remain charged after all power is disconnected. 1-1-5. To reduce the risk of electrical shock, disconnect both AC and DC power from the Inverter Charger before attempting any maintenance or cleaning. Turning off controls will not reduce this risk
CAUTION: Equipment damage The output side of the inverter's AC wiring should at no time be connected to public power or a generator. This condition is far worse than a short circuit. If the unit survives this condition, it will shut down until corrections are made. Installation should ensure that the inverter's AC output is, at no time, connected to its AC input.
1-2. Precautions When Working with Batteries
1-2-1. If battery acid contacts skin or clothing immediately wash with soap and water. If acid enters eyes immediately rinse eyes with running cold water and seek immediate medical attention. 1-2-2. Never smoke or allow a sparks or flames near the battery. 1-2-3. Do not drop a metal tool on the battery. The resulting spark or short-circuit on the battery will cause an explosion. 1-2-4. Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a battery. A battery produces a short-circuit current high enough to weld any metal objects and will cause a severe burn. 1-2-5. To reduce the risk of injury, charge only deep-cycle lead acid, lead antimony, lead calcium gel cell, absorbed mat, LIFEPO4 lithium or NiCad/NiFe type rechargeable batteries. Other types of batteries may swell or burst causing personal injury and damage.
2

2. Introduction
2-1. General Information
The Global LF Series Pure Sine Wave Inverter Charger product line is a combination of an inverter, battery charger and auto AC transfer switch in one unit and has a peak conversion efficiency of 88%. It is packed with unique features and is one of the most advanced inverter chargers on the market today. It features power factor correction, sophisticated multi-stage charging and pure sine wave output with unprecedentedly high surge capability to meet demanding power needs of inductive loads without damaging the equipment.
When utility AC power cuts off (or falls out of acceptable range), the transfer relay is de-energized and the load is automatically transferred to Inverter mode. Once the qualified AC power is restored the relay is reenergized and the load is automatically reconnected to AC bypass mode. NOTE THE BYPASS RATING OF THE INVERTER (page 33) AND DO NOT EXCEED. DAMAGE MAY OCCUR AND VOID THE WARRANTY. The Global LF Series Inverter is equipped with a powerful four stage smart charger and includes an auto generator start feature. The overload capacity of the inverter charger products is 300% of continuous output for up to 20 seconds to reliably support tools and equipment. This is for inverter mode only. You can NOT bypass the surge rating of the inverter. This may cause permanent damage to the inverter.
Another important feature is that the inverter can be easily customized to Battery priority via a DIP switch. This helps to extract maximum power from the battery in renewable energy systems such as solar and wind. The Global LF Series Pure Sine Wave Inverter is suitable for renewable energy systems in work trucks, RV, marine and emergency appliances.
To get the most out of the power inverter, it must be operated and maintained properly. Please read the instructions in this manual before installing and operating.
2-2. Application
Power tools­circular saws, drills, grinders, sanders, buffers, weed and hedge trimmers, air compressors. Office equipment ­ computers, printers, monitors, facsimile machines, scanners. Household items ­ vacuum cleaners, fans, fluorescent and incandescent lights, shavers, sewing machines. Kitchen appliances ­ refrigerators, freezers, coffee makers, blenders, ice markers, toasters. Industrial equipment ­ metal halide lamp, high pressure sodium lamp. Home entertainment electronics ­ television, DVRs, video games, stereos, musical instruments, satellite equipment.
3

2-3. Mechanical Drawing
1000W-6000W DC Battery Side
1000W & 1500W AC Side and do NOT include a AC terminal block
4

2000W & 3000W AC Side and include outlet and AC terminal block 4000W-6000W AC Side and only include AC terminal block
5

2-4. Features
High overload ability up to 300% of rated power (20 sec Low quiescent current, low power "Power Saving Mode" to conserve energy Automatic Generator Start 4-step intelligent battery charger, PFC (Power Factor Correction for charger 8 pre-set battery type selector switch plus de-sulphation for completely flat batteries Powerful charge rate of up to 115Amp, selectable from 0% 100% (based on model) 10 ms typical transfer time between battery and AC, guarantees power continuity LCD or LED remote controls (optional 15s delay before transfer when AC resumes, extra protection for loads when used with generator Allows start up and throughput power with depleted batteries 30A/40A (bypass current) Multiple controlled cooling fans Extensive protections against various harsh situations 13VDC battery recovery point, dedicated for renewable energy systems
2-5. Electrical Performance
2.5.1 Inverter
Topology The Global LF inverter/charger is built according to the following topology. Invert: Full Bridge Topology. Charge: Isolated Boost Topology.
It works bi-directionally: in one direction it converts DC power from the battery to AC power (Inverter Mode) and in the other direction it converts external AC power to DC power to charge the batteries (AC Mode). The same power components are used in both directions, resulting in high-energy transfer efficiency with fewer components.
When operating in inverter mode, the direct current (DC) that enters the inverter from the batteries is filtered by a large input capacitor and switched "On" and "Off" by the Metal Oxide Silicon Field Effect Transistors (MOSFET) at a rate of 50 Hz or 60Hz, in this step the DC is converted to low voltage synthesized sine wave AC using an H-bridge configuration and high frequency PWM (Pulse Width Modulation) technique. It is then directed into the transformer which steps the low AC voltage up to 230 or 120 volts. The unit has a 16bit, 4.9MHZ microprocessor to control the output voltage and frequency as the DC input voltage and/or output load varies.
Because of the high efficiency MOSFETs and the heavy transformers, it outputs PURE SINE WAVE AC with an average THD of 10% (min 3%, max 20% under full linear loads) depending on load connected and battery voltage. The peak DC to AC conversion efficiency of the Global LF series is >88%.
Don't parallel the AC output of the inverters to increase power capacity as they have no stacking functionality.
6

Overload Capacity: The Global LF series inverters have high overload capacities, making it ideal to handle demanding loads.
1. For 110%<Load<125%(±10%), no audible alarm for 14 minutes, beeps 0.5s every 1s in the 15th minute, and Fault (Turn off) after the 15th minute. 2. For 125%<Load<150%(±10%), beeps 0.5s every 1s and Fault (Turn off) after 1 minute. 3. For 300%  Load>150%(±10%), beeps 0.5s every 1s and Fault (Turn off) after 20s. Caution: After the inverter is switched on, it takes time for it to self-diagnose and ready to deliver full power. Hence, always switch on the load(s) after a few seconds of switching on the inverter. Avoid switching on the inverter with the load already switched on. This may prematurely trigger the overload protection. When a load is switched on, it may require an initial higher power surge to start. If multiple loads are being powered, they should be switched on one by one so that the inverter is not overloaded by the higher starting surge if all the loads are switched on at once.
2.5.2 AC Charger
The inverter charger is equipped with an active PFC (Power Factor Corrected) multistage battery charger. The PFC feature is used to control the amount of power used to charge the batteries in order to obtain a power factor as close as possible to 1. Unlike other inverters whose max charging current decreases according to the input AC voltage, the Global LF series charger is able to output max current as long as the input AC voltage is in the range of 164-243VAC(95-127VAC for 120V model), and AC frequency is in the range of 48-54Hz(58-64Hz for
60Hz model). The Global LF series inverter has a very rapid charge current available, and the max charge current can be adjusted from 15%-100% (based on model) via a liner switch to the right of the battery type selector. This will be helpful if you are using our powerful charger on a small capacity battery bank. Fortunately, the liner switch can effectively reduce the max charging current to 15-20% of its peak (based on model). Choosing "0" on the Battery Type Selector will disable the charging function.
Caution: Turn the charge current control switch gently to avoid breakage due to over-turning. Not covered under warranty.
There are 3 charging stages: Bulk Charging: (fast charge LED solid) this is the initial stage of charging. While Bulk Charging, the charger supplies the battery with controlled constant current. The charger will remain in Bulk charge until the Absorption charge voltage (determined by the Battery Type selection) is achieved. A software timer will measure the time from A/C start until the battery charger reaches 0.3V below the boost voltage, then take this time asT0 and T0×10 = T1.
Absorb Charging:(fast charge LED blinking) This is the second charging stage when the fast charge LED is flashing and begins after the absorb voltage has been reached. Absorb Charging provides the batteries with a constant voltage and reduces the DC charging current in order to maintain the absorb voltage setting. In this period, the inverter will start a T1 timer; the charger will keep the boost voltage in Boost CV mode until the T1 timer has run out. Then drop the voltage down to the float voltage. The timer has a minimum time of 1 hour and a maximum time of 12 hours.
Float Charging: (float charge LED solid) The third charging stage occurs at the end of the Absorb Charging time. While Float charging, the charge voltage is reduced to the float charge voltage (determined by the Battery Type selection*). In this stage, the batteries are kept fully charged and ready if needed by the inverter.
7

If the AC is reconnected or the battery voltage drops below 12Vdc/24Vdc, the charger will restart the above cycle. If the charge maintains the float state for 10 days, the charger will deliberately reset the cycle to protect the battery.

Battery Type Selector
Switch setting 0 1 2 3 4 5 6 7 8 9

Description Charger Off Gel USA AGM 1 AGM 2 Sealed lead acid Gel EURO Open lead acid Lithium battery De-sulphation Not used

Boost / Vdc

Float / Vdc

14.0

13.7

14.1

13.4

14.6

13.7

14.4

13.6

14.4

13.8

14.8

13.8

14.4

14.4

15.5 (4 Hours then Off)

For 24V X 2, for 48V X 4. (X= multiply)
*Check the required charging specifications with the battery manufacturer. The chart above is just a guide.
De-sulphation The de-sulphation cycle (switch position 8) is a very dangerous setting if you do not know what you are doing. Before attempting to use this cycle you must clearly understand what it does and when and how you would use it.

8

What causes sulphation? This can occur with infrequent use of the batteries or if the batteries have been discharged low enough that they will not accept a charge. This cycle is a very high voltage charge cycle designed to try to break down the sulphated crust that is preventing the plates from taking a charge and allowing the plates to clean up and accept a charge once again. Charging depleted batteries The Global LF series inverter allows a generator to start up and through power (bypass) after batteries are depleted. See top of page 10 for generator recommendation. For 12VDC models: after the battery voltage goes below 10V and the power switch is kept in the "ON" position and the inverter stays connected to the battery and the battery voltage doesn't drop below 9V, the inverter will be able to charge the battery once qualified AC inputs are present. Before the battery voltage goes below 9VDC, the charging can be activated when the switch is turned to "OFF", then to "ON". When the voltage goes below 9VDC, and you accidentally turn the switch to OFF or disconnect the inverter from the battery, the inverter will not be able to charge the battery once again, because the CPU loses memory during this process. For 24VDC models: multiply all VDC by 2. For 48VDC models: multiply all VDC by 4. Charging current for each model
The charging capacity will go to peak charge rate in approximately 3 seconds. This may cause a generator to drop frequency, making the inverter transfer to battery mode. It is recommended to gradually put the charging load on the generator by switching the charging switch from min to max. Together with the 15s switch delay our inverter gives the generator enough time to spin up. This will depend on the size of the generator and rate of charge. As a general rule, the Bulk Charging Current should be limited to 20% of the capacity of the battery bank. Higher charging current may be used if permitted by the battery manufacturer.
9

:DUQLQJ,WHPVWRQRWHD QGDUHQRWFRYHUHGXQGHUZDUUDQW\
7RVHWWKHFKDUJHF XUUHQWFRQWUROV ZLWFKXVHDVPDOOMHZHOHU¶VVW\OHIODWKHDGVFUHZGULYHU DQGJHQWO\WXUQWRDYRLGE UHDNDJHGXHWRRYHUWXUQLQJ
7RJXDUDQWHHWKHEHVWS HUIRUPDQFHR IWKHEXLOWLQ$& FKDUJHUZKHQWKH$& LQSXWLVIURPD JHQHUDWRUWKHVWDQGE\JHQHUDWRUV KRXOGEHRIDWOHDVWKLJKHUFDSDFLW\WKDQWKH LQYHUWHU([DPSOHLI\RXDUHXVLQJDZDWWLQYHUWHUWKHJHQHUDWRUP XVWEHZ DWWVRU ODUJHU,IXVLQJDZDWWLQYHUWHUWKHJHQHUDWRUPXVWEHZ DWWRUODUJHUDQGVRRQ :DUQLQJ2SHUDWLQJZLWKDQXQGHUUDWHGJHQHUDWRUR UJHQHUDWRUZ LWKXQTXDOLILHGZDYHIRUP PD\FDXVHS UHPDWXUHIDLOXUHDQGLVQRWFRYHUHGXQGHUZ DUUDQW\

7UDQVIHU
6ZLIW3RZHU7UDQVIHU :KLOHLQWKH6WDQGE\0RGHWKH$ &LQSXWRIWKHLQYHUWHULVFRQWLQXDOO\PRQLWRUHG:KHQHYHU$ &SRZHUIDOOV EHORZWKHORZ$ &YROWDJHWULSYROWDJH9 $ &GHIDXOWVHWWLQJIRU9 $ &WKHLQYHUWHUDXWRPDWLFDOO\ WUDQVIHUVEDFNWRWKH,QYHUW0RGHZLWKPLQLPXPSRZHULQWHUUXSWLRQWR\RXUDSSOLDQFHVDVORQJDVWKH LQYHUWHULVWXUQHGRQ7 KHWUDQVIHUIURP6WDQGE\PRGHWR,QYHUWHUPRGHRFFXUVLQDSSUR[LPDWHO\ PLOOLVHFRQGVIt is the sameIURP,QYHUWHUPRGHWR6WDQGE\PRGH7KLVWUDQVIHUWLPHLVXVXDOO\IDVWHQRXJKWR NHHS\RXUHTXLSPHQWLQFOXGLQJFRPSXWHUVSRZHUHGXSWKXVRXULQYHUWHUFDQEHXVHGDVDOLQHLQWHUDFWLYH 836
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
7UDQVIHU'HOD\ 7KHUHLVDVHFRQGGHOD\IURPWKHWLPHWKHLQYHUWHUVHQVHVWKDWFRQWLQXRXVO\TXDOLILHG$ &LVSUHVHQWDWWKH LQSXWWHUPLQDOVWRZKHQWKHWUDQVIHULVPDGH7 KLVGHOD\LVEXLOWLQWRSURYLGHVXIILFLHQWWLPHIRUDJHQHUDWRUWR VSLQXSWRDVWDEOHYROWDJHDQGIUHTXHQF\DQGDYRLGUHOD\FKDWWHULQJ7 KHLQYHUWHUZLOOQRWWUDQVIHUWR generator until it has locked onto the generator's output. This delay is also designed to avoid frequent VZLWFKLQJZKHQLQSXWXWLOLW\LVXQVWDEOH

2.5.4 Auto Frequency Adjust
7KHIDFWRU\GHIDXOWFRQILJXUDWLRQIRULQYHUWHUVVROGLQ$ PHULFDQPDUNHWLV+] ,I WKHRXWSXWIUHTXHQF\QHHGVWREH FKDQJHGWKLVLV GRQHE\SXWWLQJLQ D YDOLGLQSXW3RZHU6RXUFHWRWKH inverter's input linHV2QFHWKHLQYHUWHUYDOLGDWHVWKHLQSXWWKHRXWSXWZLOODXWRPDWLFDOO\FKDQJH 127(7KH LQYHUWHUZLOORXWSXWIDFWRU\VHWIUHTXHQF\RI+]FRQWUROOHGZLWK',3VZLWFKSRVLWLRQ

2.5.5    

7KHUHDUHGLIIHUHQWZRUNLQJVWDWXVHVIRURXU*OREDO/ )LQYHUWHU

"WPhoewnetrhOe np"owanedr

"Power Off". switch is in "Unit

Off"

position,

the

inverter

LVSRZHUHGRII

10

When the power switch is turned to either "Power Save ON" or "Power ON", the inverter is powered on. The Power Saver function is designed to conserve battery power when AC power is not or rarely required by the loads. In this mode, the inverter pulses the AC output looking for an AC load (IE. electrical device). Whenever an AC load (greater than 50-100 watts depending on model) is turned on, the inverter recognizes the need for power and automatically starts inverting and output goes to full voltage. When there is no load (or less than 50-100 watts depending on model) detected, the inverter automatically goes back into search mode to minimize energy consumption from the battery bank. In "Power saver on" mode, the inverter will draw power mainly in sensing moments, thus the idle consumption is significantly reduced. The inverter will detect a load for 250ms every 3 seconds (DOP switch#3 position 1). Note: The minimum power of a load to take inverter out of sleep mode (Power Saver On) is 50 Watts for inverters 1000-3000 watts and 100 Watts for 4000-6000 watts. The Global LF Series is designed with extremely low idle power consumption, only a mere 0.8-1.8% of its rated power.
11

Global LF Series Idle Power Consumption (in Watts)

Model NO PICOGLF10W12V230V PICOGLF10W12V120V PICOGLF10W24V230V PICOGLF10W24V120V PICOGLF15W12V230V PICOGLF15W12V120V PICOGLF15W24V230V PICOGLF15W24V120V PICOGLF20W12V230V PICOGLF20W12V120V PICOGLF20W24V230V PICOGLF20W24V120V PICOGLF20W48V230V PICOGLF20W48V120V PICOGLF30W12V230V PICOGLF30W12V120V PICOGLF30W24V230V PICOGLF30W24V120V PICOGLF30W48V230V PICOGLF30W48V120V PICOGLF40W12V120V PICOGLF40W24V230V PICOGLF40W24V120V PICOGLF40W48V230V PICOGLF40W48V120V PICOGLF50W24V230V PICOGLF50W24V230VS PICOGLF50W48V230V PICOGLF50W48V230VS PICOGLF60W24V230V PICOGLF60W24V230VS PICOGLF60W48V230V PICOGLF60W48V230VS

Power Saver Off 12.5 12.5 15 16.5 12.5 13.5 15 16.5 25 28 24.5 26.5 25 28 50 55 38.5 46.5 45 50 44.5 48 52.5 48 55.5
62.5

Power Saver On (3Secs) 7.5 7.5 8.4 9 7.5 8 8.4 9 11.7 12.7 11.5 12.2 11.7 12.7 20 21.7 16.2 18.9 18.4 20 18.2 19.4 20.9 19.4 21.9
24.2

68.5

26.2

76.8

29

80.7

30.3
Not all models listed are available

When in the search sense mode, the green power LED will blink and the inverter will make a ticking sound.
12

At full output voltage, the green power LED will light steadily and the inverter will make a steady humming sound. When the inverter is used as an "uninterruptible" power supply the search sense mode or "Power Saver On" function should be defeated.
Exceptions Some devices when scanned by the load sensor cannot be detected. Small fluorescent lights and inductive loads are the most common example. (Try altering the plug polarity by turning the plug over.) Some computers and sophisticated electronics have power supplies that do not present a load until line voltage is available. When this occurs, each unit waits for the other to begin. To drive these loads either a small companion load must be used to bring the inverter out of its search mode, or the inverter may be programmed to remain at full output voltage (Power On mode).
2.5.6 Protections
 AC input over voltage protection/AC input low voltage protection  Low battery alarm/high battery alarm  Over temperature protection/overload protection  Short circuit protection (1s after fault)  Back feeding protection
When over temperature /overload occur, after the fault is cleared, the master switch needs to be reset to restart the inverter. The low battery voltage trip point can be customized from a defaulted value of 10VDC to 10.5VDC thru SW1 on the DIP switch. The inverter will go to over temp protection when the heat sink temp. 105ºC(221), and go to fault (shutdown Output) after 30 seconds. The switch needs be reset to activate the inverter. The Global LF series inverter has back feeding protection which avoids presenting an AC voltage on the AC input terminal in inverter mode. When a fault is cleared, the inverter will need to be reset to start working.
*We don't recommend connecting AC input to a GFCI circuit as it will cause the supply GCFI to pop
intermittently and fail to supply power to the charger and bypass power through inverter.
2.5.7 Remote Control
In addition to the switch panel on the front (or top) of the inverter, there are two optional remotes, for some models. An LCD remote panel that provides more detailed info or an LED remote that provides on/off with a few LED indicators. The LCD remote panel connects to the RJ45 port on the DC side of the inverter displays several statuses of the inverter (sold separately Part # REMOTELF). Use with port labeled LCD remote. If you want a more simple on/off remote, consider the LED remote (sold separately Part # REMOTELFLED). Use with port labeled LED remote. Not available on all models.
If an extra switch panel is connected to the inverter via "remote control port", together with the panel on the inverter case, the two panels will be connected and operated in parallel. Whichever first switches from "Off" to "Power saver off" or "Power saver on", it will power the inverter on.
If the commands from the two panels conflict, the inverter will operate according to the following priority: Power saver on> Power saver off> Power off Only when both panels are turned to the "Unit Off" position, will the inverter be powered off. The max length of the cable is 60 feet.
13

Remote LED - REMOTELFLED The remote LED has on/off and power save switch. There are also 3 indicator LEDs for the battery charger, inverter mode and faults.
Remote LCD - REMOTELF The remote LCD displays detailed information of the inverter.

1

6

2

7

3

8

4

5

9

(1) Shore/ Generator voltage

(6) Output voltage

(2) DC voltage on inverter

(7) Output frequency

(3) Load when inverting

(8) Bypass/ inverter mode

(4) Low/high voltage, over temp, overload

(9) Battery state of charge graph

(5) Fault condition

NOTE: The battery icon is just an image and does not represent battery capacity. The bar graph will change based on battery voltage (2). If using lithium, you will could an instant drop on the graph.

*A push button on the left of the panel can be used to turn off the LCD screen and save 0.1A current draw on the battery.
14

Display screen provides the following info:  Input AC Voltage  Output AC  Voltage Battery  Voltage Output  Frequency  Output Load  Work Mode  Alarm Fault  Battery Capacity WARNING ONLY USE REMOTELF WITH PORT LABELED LCD. ONLY USE REMOTELFLED WITH PORT LABELED LED. IF YOU PLUG INTO THE WRONG PORT, YOU CAN FRY THE INVERTER AND NOT CONVERED UNDER WARRANTY. Never cut the remote cable when the cable is attached to inverter and battery is connected to the inverter. Even if the inverter is turned off, it will damage the remote PCB inside if the cable is short circuited during cutting.
2.5.8 LED Indicator Lights/Status
15

2.5.8 Remote Control Status
16

2.5.9 Audible Alarm

Battery Voltage Low Battery Voltage High
Invert Mode Overload
Over Temperature

Inverter green LED lit, and the buzzer beeps 0.5s every 5s. Inverter green LED lit, and the buzzer beeps 0.5s every 1s and Fault after 60s.
(1)110%<load<125%(±10%), No audible alarm in 14 minutes, Beeps 0.5s every 1s in 15th minute and Fault after 15 minutes; (2)125% <load<150%(±10%), Beeps 0.5s every 1s and Fault after 60s; (3)Load>150%(±10%), Beeps 0.5s every 1s and Fault after 20s;
Heat sink temp. 105ºC(221), Over temp red LED Lighting, beeps 0.5s every 1s;

2.5.10 FAN Operation
For 1-3KW models, there is one multiple controlled DC fan which starts to work according to the below logic. For 4-6KW models, there is one multiple controlled DC fan and one AC fan. The DC fan will work in the same way as the 1-3KW models, while the AC fan will work once there is AC output from the inverter. So when the inverter is in power saver mode, the AC fan will work from time to time in response to the pulse sent by the inverter in power saver mode. The Operation of the DC fan at the DC terminal side is controlled by the following logic:

Condition

Enter Condition

Leave condition

Speed

HEAT SINK
TEMPERATURE
CHARGER CURRENT
LOAD Percentage (INV MODE)

T  140
149 T < 185 T > 185 I  15%
20%< I  50%Max I > 50%Max Load < 30%
30%  Load < 50% Load  50%

T > 149
T  140 or T  185 T  176 I  20%
I 15% or I > 50%Max I  40%Max Load  30%
Load  20% or Load  50% Load  40%

OFF
50% 100% OFF 50% 100% OFF 50% 100%

Allow at least 12 inches of clearance around the inverter for air flow. Make sure that the air can circulate freely around the unit. Fan noise level <60db at a distance of 3 feet

17

2.5.11 DIP Switches
On the DC end of inverter, there are 5 DIP switches that enable users to customize some of the inverter charger's functions.

Switch NO SW1(Utility Priority) SW1(Battery Priority) SW2(230V) SW2(120V) SW3 SW4 SW5

Switch Function
Low Battery Trip Point
AC Input Range AC Input Range Power Save Override Frequency Switch Battery/AC Priority

Position: 0 10.0VDC 10.5VDC 184-253VAC 100-135VAC Inverter Off 50Hz AC Priority

Position: 1 10.5VDC 11.5VDC 154-264VAC(40-70Hz) 90-135VAC(40-70Hz) Saver On 3 sec 60Hz Battery Priority

Low Battery Trip Volt (SW1) Deep discharge of the lead acid battery will cause losses in capacity and early aging. In some applications a different low voltage disconnection level may be preferred. For example, in solar applications, users may intend to have less DOD to prolong the battery life cycle. While for mobile applications, users may intend to have more DOD to fully use the battery capacity available, minimizing onboard weight.
For 12VDC models, the Low Battery Trip Volt is set at 10.0VDC by default. It can be customized to 10.5VDC using SW1. This is to prevent batteries from over-discharging while there is only a small load applied on the inverter. multiply*2 for 24VDC, multiply*4 for 48VDC
AC Input Range(SW2) There are different acceptable AC input ranges for different kinds of loads. For some relatively sensitive electronic devices, a narrow input range of 184-253VAC (100-135V for 120VAC model) is required to protect them. While for some resistive loads that work in a wide voltage range, the input AC range can be customized to 154-264VAC (90-135V for 120VAC model). This helps to power loads with the most AC input power without frequently switching to the battery bank. In order to make the inverter accept dirty power from a generator, put SW2 to position "1", the inverter will bypass an AC input with a wider voltage and frequency (40-70Hz for 50Hz/60Hz). The AC charger will also work in a wider voltage and frequency range (42-68Hz for 50Hz/60Hz).
As mentioned, this will avoid frequent switching between battery and generator, but the low quality power may affect some sensitive loads. The pros and cons should be considered when dealing with sensitive loads.
NOTE: This is for bypass only! The charger has a different voltage range and may not operate at full rated current. Refer to Section 2.5.2 AC Charger.
Power Saver Override ON/OFF (SW3) The factory default for SW3 is Position 0. Position 1 will allow the Power Save feature of the inverter to detect a load for 250ms every 3 seconds. If a load is detected, the inverter will output AC Power. If SW3 is moved to Position 0. This will prevent the sense pulse from being sent out, even if inverter is in Power Save mode via Main Power switch. No power will be output unless Shore Power input is present. Only then will the battery charger and AC throughput operate when SW3 is in Position 0.
Frequency Switch (SW4): The output frequency of the inverter can be set at either 50Hz or 60Hz by SW4. 50Hz most common in Europe and Africa.

18

AC/Battery Priority (SW5): The inverter charger is designed with AC priority as default. This means, when AC input is present, the battery will charge first, and the inverter will transfer the input AC to power the load. Only when the AC input is stable for a continuous period of 15 days will the inverter start a battery inverting cycle to protect the battery. After 1 normal charging cycle AC throughput will be restored. The AC Priority and Battery Priority switch is SW5. When you choose battery priority, the inverter will invert from battery first and then AC input when battery voltage drops. Only when the battery voltage reaches the low voltage alarm point(10.5V for 12V,21Vdc for 24Vdc, 42Vdc for 48Vdc) will the inverter transfer to AC Input, charge battery, and switch back to battery when the battery is fully charged. This function is most common for wind/solar systems using utility power as back up.
Note: In battery priority mode, when qualified AC inputs for the first time and the battery voltage is below 12.5Vdc (12.5Vdc for 12Vdc, 25Vdc for 24Vdc, 51Vdc for 48Vdc, the inverter will go into battery priority mode only after a cycle of bulk charging and absorb charging is finished. The inverter will not go into float charging mode.
2.5.12 Auto Generator Start
BEFORE YOU USE A GENERATOR, MAKE SURE IT IS SIZED TO HANDLE THE INVERTER. To guarantee the best performance of the built in AC charger and when the AC input is from a generator, the standby generator should be at least 150% higher capacity than the inverter. Operating with an under-rated generator or generator with unqualified wave form may cause premature failure which is not covered under warranty. Example: If you are using a 2000 watt inverter charger, your generator must be 3000 watts or larger. If you are using a 3000 watt inverter charger, your generator must be 4500 watt or larger, and so on.
The inverter is able to start up a generator when battery voltage drops. When the inverter goes into low battery alarm, it can send a signal to start a generator and turn the generator off after battery charging is completed. The auto gen start feature will only work with generators that have an automatic starting function. The generator must have start and stop controls [an electric starter and electric choke (for gasoline units)], and the safety sensors to be able to start and stop automatically. There is an open/close relay that will short circuit the positive and negative cables from a generator start control. The input DC voltage can vary, but the max current the relay can carry is 16 amps. The Auto Gen Start terminal pins are not polarized. These two pins can also be used as dry contacts to send out "Low Battery Voltage" signal to an external alarm device. Use 18 AWG speaker wire for this application.
2.5.13 Other Features
Battery Temperature Sensing
Applying the proper charge voltage is critical for achieving optimum battery performance and longevity. The ideal charge voltage required by batteries changes with battery temperature.
The Battery Temperature Sensor allows the charger to continuously adjust charge voltage based on actual battery temperature. Temperature compensation of charge voltage assures that the battery receives the proper charge voltage as battery temperature varies. The temp sensor sends precise information to the charger, which automatically adjusts voltage to help ensure full battery charge depending on the ambient temperature of your battery.
When the battery voltage is over 104 it will reduce the charging voltage by 0.1Vdc with every degree of temperature rise. AIMS recommends using the battery sensor to protect your batteries and to provide optimal charging. The Bat Temp Sensor attaches to the side of a battery, closest to the negative terminal using electrical tape or silicon.
19

Inverter Condition Charger Mode
Inverter Mode

Temp on BST BTS  122 BTS  104
104  BTS  122
BTS  122

Operation Automatically turns off charger Automatically turns on charger Increases the low voltage shut down point by 0.5Vdc Over Temp Fault

Battery voltage recovery start After low battery voltage shut off (10V for 12V model or 20V for 24V model or 40V for 48V model), the inverter is able to restore operation after the battery voltage recovers to 13V/26V/52V (with power switch still in the "On" position). This function helps users and saves time and extra labor to reactivate the inverter when the low battery voltage returns to an acceptable range in renewable energy systems. The built in battery charger will automatically reactivate as soon as city/generator AC has been stable for 15 seconds.

WARNING Never leave the loads unattended, some loads (like a heater) may cause accidents in such cases. It is better to shut everything off after low voltage trip than to leave your load on, due to the risk of fire.
Conformal Coating AIMS Power's entire line of Global LF inverters have been processed with a conformal coating on the PCB, making it water, rust, and dust resistant as well as corrosion resistant. While these units are designed to withstand corrosion from the salty air, they are not splash proof.

2.5.14 Automatic Voltage Regulation
The automatic voltage regulation function is for full series of APS Pure Sine Wave Inverter/ Charger except Instead of simply bypassing the input AC to power the loads, the APS series inverter stabilizes the input AC voltage to a range of 230V/120V±10%. Connected with batteries, the APS Series inverter will function as a UPS with max transfer time of 10 ms. With all of the unique features our inverter provides, it will bring you long-term trouble-free operation.

20

APS Function (Optional)
Acceptable Input Voltage Range (Vac) Nominal Input Voltages (Vac) (A) Line low loss N/W (On battery) (B) Line Low comeback N/W (On Boost) (C) Line 2nd boost threshold (On Boost) (D) Line 2nd boost comeback (On Normal) (E) Line 1st boost threshold (On Boost) (F) Line 1st boost comeback (On Normal) (G) Line buck comeback (On Normal) (H) Line buck threshold (On Buck) (I) Line high comeback (On Buck) (J) Line high loss (On Battery)

APS Series

LV (NA/JPN)

0-160

100

110

120

220

75/65 84/72 92/78 168/143

80/70 89/77 97/83 178/153

**

**

**

**

**

**

**

**

90

99

108

198

93

103

112

205

106

118

128

235

110

121

132

242

115

127

139

253

120

132

144

263

HV (INTL)

0-300

230

240

176/150 183/156

186/160 193/166

**

**

**

**

207

216

215

225

246

256

253

264

266

278

276

288

3 Installation
3.1 Unpacking and Inspection
Carefully remove the inverter charger from its shipping package and inspect all contents. Verify the following items are included: · The PICOGLF Inverter Charger · Red and black DC terminal covers · AC terminal block cover with two Phillips screws · Two Flange nuts and 4 Phillips screws (installed on the DC terminals). · PICOGLF Series Owner's Manual
If items appear to be missing or damaged, contact AIMS Power. If at all possible, keep your shipping box and all packaging. It will help protect your inverter from damage if it ever needs to be returned for service. Save your proof-of-purchase as a record of ownership; it will also be needed if the unit should require warranty work. The serial number is on the side of the inverter and does NOT start with an 8.
21

3-2. Location
Follow all the local regulations to install the inverter. Install the equipment in an INDOOR location that is dry, clean, free from dust, cool and with good ventilation. Working temperature: -14 to 122 | Storage temperature: 40 to 158 | Relative Humidity: 0% to 95, non-condensing | Cooling: forced airc Do not install upside down (top side facing down). CAUTION: Some models are heavy. Use proper lifting techniques during installation to prevent personal injury.
WARNING! The inverter should not be installed in an area that allows dust, fumes, insects or rodents to enter or block the inverter's ventilation openings. This area must also be free from any risk of condensation, water or any other liquid that can enter or fall on the inverter. All inverters have been processed with a conformal coating on the PCB, making them humid, rust, and dust resistant but not completely protected. While these units are designed to withstand corrosion from the salty air, they are not splash proof. DO NOT GET WET. The inverter's life is uncertain if used in these types of environments, and inverter failures under these conditions are not covered under warranty.
Installation Tools / Materials
You will need the following tools to install the inverter and the battery temperature sensor.
 Wire stripper  Crimping tools for fastening lugs and terminals on DC cables  Phillips screwdriver: #2 & slow scredriver 1/4" wide blade  Electrical tape or silicone for bat temp sensor  Needle-nose pliers  Wrench for DC terminals: 9/16"
Materials
You will need the following materials to complete your installation:
 Correct size DC battery cables  Terminals and/or crimp connectors for DC cables  Copper wire for DC grounding: No. 8 AWG.  Terminal or crimp connector for DC grounding cable (for 1/4" stud size)  AC output and input wire.  If the AC ground wire is stranded, each ground wire requires a ring terminal  Six 1/4"­20 1.25" length steel screws or bolts to mount the inverters
3-3. DC Wiring
It is recommended that the battery bank be kept as close as possible to the inverter. The following is a suggested wiring option for 12 feet of DC cable. Follow the minimum wire size. If the DC cable is longer than 12 feet, increase the size of cable to reduce voltage drop.
WARNING! The inverter charger must be connected to a battery bank in order to turn on and transfer AC power.
22

Power 1KW 1KW 1.5KW 1.5KW 2KW 2KW 2KW 3KW 3KW 3KW 4KW 4KW 4KW 5KW 5KW 6KW 6KW

DC Input voltage 12V 24V 12V 24V 12V 24V 48V 12V 24V 48V 12V 24V 48V 24V 48V 24V 48V

Wire Gauge AWG 1/0 AWG 4 AWG 1/0 AWG 4 AWG 1/0 AWG 1/0 AWG 4 AWG 4/0 AWG 1/0 AWG 4 AWG 4/0 AWG 1/0 AWG 1/0 AWG 4/0 AWG 1/0 AWG 4/0 AWG 1/0

Battery cables must be crimped (or preferably, soldered and crimped) copper compression lugs unless aluminum mechanical lugs are used. Soldered connections alone are not acceptable. High quality, UL-listed battery cables are available. These cables are color-coded with pressure crimped, sealed ring terminals.

Battery terminal must be clean to reduce the resistance between the DC terminal and cable connection. A buildup of dirt or oxidation may eventually lead to the cable terminal overheating during periods of high current draw. Use a stiff wire brush and remove all dirt and corrosion from the battery terminals and cables.

Reducing RF interference To reduce the effect of radiated interference, twist the DC cables. To further reduce RF interference, shield the cables with sheathing /copper foil / braiding. Taping battery cables together to reduce inductance Do not keep the battery cables far apart. In case it is not convenient to twist the cables, keep them taped together to reduce their inductance. Reduced inductance of the battery cables helps to reduce induced voltages. This reduces ripple in the battery cables and improves performance and efficiency.
23

3-4. AC Wiring
The AC terminal is rated for wires of 8 AWG to 20 AWG, we recommend using 10 to 8 AWG wire to connect to the ac terminal block. When in AC mode the AC input power will supply both the loads and AC charger, a thicker wire gauge for AC input is required. Please consult a qualified electrician about the specific wire gauge required in terms of wire material and inverter power. There are several ways of connecting the terminal block depending on the model. All the wirings are CE compliant. call our tech support if you are not sure about how to wire any part of your inverter.
STOP: DON'T WIRE UNTIL YOU CONFIRM THE MODEL NUMBER OF YOUR INVERTER. NOTE WHETHER YOU HAVE A 120 SINGLE PHASE OR 120/240V SPLIT PHASE.

Do not loosen or touch the rear set screws on the terminal block.

Wiring Option 1 240V single phase / 120V single phase Input: Ground + Hot line + Neutral Output: Neutral + Hot line + Ground

Option 1

24

Wiring Option 2 240V split phase Input: Ground + Hot line 1 + Hot line 2 - 240 Vac Output: Hot line 1 + Hot line 2 + Neutral - 240 Vac

Wiring Option 3 240V split phase Input: Ground + Hot line 1 + Hot line 2 - 240 Vac Output: Hot line 2 +Neutral - 120 Vac

Note: In such case, each output hot line can only carry a max of half the inverter's rated capacity.

Warning: If only using a 120V load, use Hot line 1 + Neutral, when the load power is more than 50% of the inverter's rated power then use Hot line 2 + Neutral.

Options 3

Option 2

PICOGLF4012120240VS ONLY!
Option 1 Input: Ground + Hot line + Neutral for 120V AC Output: Hot line + Neutral - 120V AC

Option 1

Option 2 Input: Hot line + Neutral + Ground 120V AC Output: Hot line + Neutral - 120V AC

Warning: If only using a 120V load, use Hot line 1 + Neutral, when the load power is more than 50% of the inverter's rated power then use Hot line 2 + Neutral.

Option 2

Option 3

Input: Ground + Hot line +

Neutral - 120V AC

Output: Hot line + Netural + Hot line -

Option 3

240/120V AC

25

Caution:
Wiring Option 2 and Wiring Option 3 are designed for split phase models 120/240V. 240 Volt input and 120/240 Volt output. Wiring Option 1 for single phase models only. Model# PICOGLF4012120240VS ONLY. This inverter is 120 AC input to 120/240 AC output.
WARNING
For split phase models, AC input neutral is not required in wiring. Never connect input neutral to output neutral. Damage will occur and is not covered under warranty. Always switch on the inverter before plugging in any appliance.
WARNING
The output voltage of this unit must never be connected in its input AC terminal, overload or damage may occur. *We don't recommend connecting AC input to a GFCI circuit as it will cause the supplied GCFI to pop intermittently and fail to supply power to the charger and bypass power through inverter. Always switch on the inverter before plugging in any device.
3-5. Grounding
Connect an 8 AWG or bigger copper wire between the grounding terminal on the inverter and the earth grounding system or the vehicle chassis.
3.5.1 Automatic Neutral-to-Ground Connection
All single phase 120Vac inverters are equipped with automatic neutral-to-ground switching. These inverters use an internal relay that automatically connects the AC neutral output to the vehicle/boat's safety ground ("bonding" it) in Inverter Mode and disconnects it ("un-bonding" it) when they have connected to a qualified external AC source.
This design avoids two neutral-to-ground connections from existing at the same time, thereby preventing an electrical shock hazard between the vehicle/boat's neutral and the external AC source's neutral.
26

2 sablienAgt ic  
d tion
In some installations, this feature must be disabled. To accommodate these situations, the automatic Neutral-to-Ground Connection system can be defeated, so it will not bond the neutral in any mode of operation. If you are not sure whether you must disable this feature, please refer to local code requirements. There is a section of green wire with the insulated connector at the left side of the AC terminal block. This insulated connector connects the neutral and ground inside the inverter while inverting. Pull the two ends of the insulated connector apart to separate the green wire; this will prevent the neutral and ground from connecting inside this inverter. If possible, use electrical tape to insulate the disconnected ends, move the two ends away from each other and push back out of the way. Typically, when connecting to a house panel (after disconnecting city power from it) is when you would disconnect this connection as a house panel already has the neutral to ground bond. In a standalone system or in a vehicle, you would want to keep this connection.
. all 
W to 15 
W to 30 
27

W to 60 
e Vew
28

4. Troubleshooting Guide

Troubleshooting contains information about how to troubleshoot possible error conditions while using the Global LF Inverter & Charger. The following chart is designed to help you quickly pinpoint the most common inverter failures.
Indicator and Buzzer

Status

Item CC

Indicator on top cover

LED on Remote Switch

SHORE POWER
ON

INVERTER ON

FAST CHG

FLOAT CHG

OVER TEMP TRIP

OVER LOAD TRIP

POWER SAVER
ON

BATT CHG

INVERTER

Alarm



×



×

×

×

×



×

×

Line

CV



Mode

Float



×

, blink ×

×

×

×



×

×

×

×



×

×

×



×

×

Standby



×

×

×

×

×

×

×

×

×

Inverter On ×



×

×

×

×

×

×



×

Inverter

Mode

Power Saver

×

×

×

×

×

×



×

×

×

Buzzer
× × × × ×
×

Battery Low

×



×

×

×

×

×

×





Beep 0.5s every 5s

Battery High

×



×

×

×

×

×

×





Beep 0.5s every 1s

Overload

On Invert

×

Mode



×

×

×



×

×





Refer to "Audible alarm"

Inverter Mode

Over-Temp On Invert

×

Mode



×

×



×

×

×





Beep 0.5s every 1s

Over-Temp

On Line



Mode

×



×



×

×



×



Beep 0.5s every 1s

Over Charge



×



×

×

×

×



×



Beep 0.5s every 1s

Fan Lock

×

×

×

×

×

×

×

×

×

× Beep continuous

Battery High

×



×

×

×

×

×

×



× Beep continuous

Inverter

Mode

×

×

×

×

×



×

×

×

× Beep continuous

Fault Overload

Mode

Output Short

×

×

×

×

×



×

×

×

 Beep continuous

Over-Temp ×

×

×

×



×

×

×

×

× Beep continuous

Over Charge

×

×



×

×

×

×



×

× Beep continuous

Back Feed Short

×

×

×

×

×

×

×

×

×

× Beep continuous

29

Symptom

Possible Cause

Recommended Solution

Inverter will not turn on during initial power up.

Batteries are not connected, loose battery-side connections.
Low battery voltage.

Check the batteries and cable connections. Check DC fuse and breaker.
Charge the battery.

No AC output voltage and no indicator lights ON.

Inverter has been manually transitioned to OFF mode.

AC output voltage is low and the inverter turns loads OFF in a Low battery. short time.

Press the switch to Power saver on or Power saver off position.
Check the condition of the batteries and recharge if possible.

Charger is inoperative and unit AC voltage has dropped out-of-

will not accept AC.

tolerance

Check the AC voltage for proper voltage and frequency.

Charger is supplying a lower charge rate.
Charger turns OFF while charging from a generator.

Charger controls are improperly set.
Low AC input voltage.
Loose battery or AC input connections.
High AC input voltages from the generator.

Refer to the section on adjusting the "Charger Rate".
Source qualified AC power.
Check all DC /AC connections.
Load the generator down with a heavy load. Turn the generator output voltage down.

Sensitive loads turn off temporarily when transferring between grid and inverting.

Inverter's Low voltage trip voltage may be too low to sustain certain loads.

Choose narrow AC voltage in the DIP switch, or Install a UPS if possible.

Noise from Transformer/case*

Applying specific loads such as hair drier

Remove the loads

*The reason for the noise from transformer and/or case
When in inverter mode sometimes the transformer and/or case of the inverter may vibrate and make noise. If the noise comes from transformer: According to the characteristics of our inverter, there is one type of load which most likely may cause rattles of transformer. That is a half wave load: A load that uses only half a cycle of the power. This tends to cause an imbalance of the magnetic field of the transformer, reducing its rated working frequency from 20KHz to, say, maybe 15KHz (it varies according to different loads). In such a case the frequency of noise falls exactly into the range (200Hz-20KHz) that human ears can hear. The most common load of such kind is a hair drier. If the noise comes from the case: Normally when loaded with inductive loads, the magnetic field generated by the transformer keeps attracting or releasing the steel case at a specific frequency. This may also cause noise. Reducing the load power or using an inverter with bigger capacity will normally solve this problem. The noise will not do any harm to the inverter or the loads.
30

5. Warranty
We offer a 1 year limited warranty. The following cases are not covered under warranty.
1. DC reverse polarity. The inverter is NOT designed with DC reverse polarity protection. A reverse polarity may severely damage the inverter.
2. Wrong or loose AC wiring. 3. Operation in a moist or unsanitary environment. 4. Water damage, lightning strikes, short circuit from dirt/dust build-up 5. Operating with an undersized generator or generator with unqualified wave form.
AIMS Power Warranty Instructions: This product is designed using the most modern digital technology and under very strict quality control and testing guide lines. If, however you feel this product is not performing as it should, please contact us: techsupport@aimscorp.net or (775)359-6703. We will do our best to resolve your concerns. If the product needs repair or replacement, make sure to keep your receipt/invoice, as that will need to be sent back along with the package and RA# prepaid to AIMS. You have a full 1 year warranty from date of purchase. This warranty is valid worldwide with the exception that freight and duty charges incurred outside the contiguous 48 United States will be prepaid by customer. Except as provided above, AIMS makes no warranty of any kind, express or implied, including without limitation the implied warranties of merchantability and fitness for a particular purpose. In no event shall AIMS be liable for indirect, special or consequential damages. This warranty only applies to AIMS Power branded products. All other name brand products are warranted by and according to their respective manufacturer. Please do not attempt to return non-AIMS Power branded products to AIMS Power. For additional products such as:
- Modified Sine Wave Inverters - Pure Sine Wave Inverters - Solar Charge Controllers - Inverter Chargers - Custom Cut Cables - Batteries - Solar Panels - Generators Please visit our web site: www.aimscorp.net
To find out where to buy any of our products, you may also e-mail:sales@aimscorp.net or call (775)3596703.
31

Specifications

Global Low Freq Series Inverter & AC Charger

Electrical Specifications

Inverter Output

Model Continuous Output Power
Surge Rating(20s)
Capable of Starting Electric Motor
Output Waveform
Nominal Efficiency
Line Mode Efficiency
Power Factor
Nominal Output Voltage rms

1KW 1000W 3000W
1HP

Output Voltage Regulation

Output Frequency Short Circuit Protection Typical transfer Time THD

Nominal Input Voltage

DC Input

Minimum Start Voltage
Low Battery Alarm
Low Battery Trip High Voltage Alarm & Fault High DC Input Recovery Low Battery voltage recover Idle ConsumptionSearch Mode
Input Voltage Range

Charge

Input Frequency Range

Output Voltage

Charger Breaker

Rating(230Vac)

10A

Charger Breaker

Rating(120Vac)

10A

1.5KW 2KW

3KW

4KW 5KW 6KW

1500W 2000W 3000W 4000W 5000W 6000W

4500W 6000W 9000W 12000W 15000W 18000W

1.5HP

2HP

3HP

4HP

5HP

6HP

Pure sine wave/Same as input (bypass mode)
>88%(Peak)
>95%
0.9-1.0 100-110-120Vac / 220-230-240Vac
Model specific

±10% RMS

50/60Hz ±0.3Hz Yes, Current Limit Function (Fault after 1sec)
10ms(Max) < 10% 12.0Vdc
(*2 for 24Vdc, *4 for 48Vdc) 10.0Vdc
10.5Vdc / 11.0Vdc 10.0Vdc / 10.5Vdc
16.0Vdc

15.5Vdc

13.0Vdc

< 50 W when Power Saver On

Narrow: 100~135VAC / 194~243VAC; Wide: 90~135VAC / 164~243VAC;
Narrow: 47-55±0.3Hz for 50Hz, 57-65±0.3Hz for 60Hz Wide:40-70±0.3Hz for 50Hz/60Hz
Depends on battery type

10A

10A

20A

20A

30A

30A

20A

20A

30A

40A

Max Charge Rate Over Charge Protection Shutdown

See specific charge rates in "2.5.2 AC Charger" section 15.7V for 12Vdc (*2 for 24Vdc, *4 for 48Vdc) See charger section 2.5.2
32

Battery type

Fast Vdc (*2 for 24V and *4 for 48V) Float Vdc

Gel U.S.A

14.0

13.7

A.G.M 1

14.1

13.4

A.G.M 2

14.6

13.7

Sealed Lead Acid

14.4

13.6

Gel Euro

14.4

13.8

Open Lead Acid (flooded)

14.8

13.8

Lithium battery

14.4

14.4

De-sulphation

15.5 for 4hrs

Remote Control

Yes. Optional

Input Voltage Waveform

Sine wave (Grid or Generator)

Nominal Voltage

120Vac

230Vac

Low Voltage Trip

80V/90V±4%

184V/154V±4%

Low Voltage re engage

90V/100V±4%

194V/164V±4%

High Voltage Trip

140V±4%

253V±4%

High Voltage re engage

135V±4%

243V±4%

Max Input AC Voltage

150VAC

270VAC

Nominal Input Frequency

50Hz or 60Hz (Auto detect)

Bypass & Protection

Low Frequency Trip
Low Frequency Re-engage

Narrow: 47±0.3Hz for 50Hz, 57±0.3Hz for 60Hz Wide:40±0.3Hz for 50Hz/60Hz
Narrow: 48±0.3Hz for 50Hz, 58±0.3Hz for 60Hz Wide:42±0.3Hz for 50Hz/60Hz

High Frequency Trip

Narrow: 55±0.3Hz for 50Hz, 65±0.3Hz for 60Hz Wide: 70Hz for 50Hz/60Hz

High Frequency Reengage

Narrow: 54±0.3Hz for 50Hz, 64±0.3Hz for 60Hz Wide: 68Hz for 50Hz/60Hz

Output Short Circuit Protection

Circuit breaker

Bypass Breaker Rating (230Vac)

10A

15A

20A

30A

30A

40A

40A

Bypass Breaker Rating (120Vac)

20A

20A

30A

40A

50A

Mounting

Wall/Ground mount

Inverter Dimensions(L*W*H)

15*8.5*7"

17.5*8.5*7"

23.5*8.5*7"

Mechanical Specification

Inverter Weight
Shipping Dimensions(L*W*H)

Shipping Weight

Display

35.27lbs 37.48 lbs 44.1 lbs 52.91 lbs 77.16 lbs 97 lbs 99.21 lbs

20.75*12.75*12.5"

23.5*13*12.5"

30.5*14.25*13.75"

39.68 lbs

41.89 lbs

48.51 lbs 57.32 lbs Status LEDs

81.57 lbs

101.41 lbs

103.61 lbs

Standard Warranty

1 Year

Specifications in this manual are subject to change without prior notice.

33

34

Appendix 1 - Circuit Schematics
Circuitry scheme for models with automatic ground to neutral connection
Inverter Mode

AC Mode

Figure 33

Figure 34
35

Appendix 2 - Installation Diagram *DC shunt is not required 36

614-01206-08

04/21 37



References

Microsoft Word 2016