InnovairFlex™ Series DNRA Duct Smoke Detector
by Honeywell
Description
The InnovairFlex™ Series DNRA is an intelligent, non-relay photoelectric duct smoke detector. It features a pivoting housing compatible with both square and rectangular footprints, allowing mounting to round or rectangular ducts. The DNRA detector can be used with the 7100-C Series System.
Note: The InnovairFlex™ Series DNRA requires the Velociti® Series ASD-PL2FRA Sensor and AOM-2RFA if relays are needed for fan control.
This unit is designed for challenging conditions, operating in airflow speeds from 100 to 4,000 feet per minute, temperatures from -4°F to 158°F (-20°C to 70°C), and humidity from 0% to 95% (non-condensing).
An improved cover design isolates the sensor head from the low-flow feature for simple maintenance. A cover tamper feature provides a trouble signal if the sensor cover is removed or improperly installed. The InnovairFlex housing includes a 3/4-inch conduit knockout and ample space for easy wiring and relay module mounting.
The detector can be customized to meet local codes and specifications without additional wiring. The InnovairFlex product line is compatible with previous Innovair models, including remote test accessories.
WARNING: Duct smoke detectors have specific limitations. They are NOT a substitute for open area smoke detectors, early warning detection, or a building's regular fire detection system.
Refer to CAN/ULC® 5524 for additional duct smoke detector application information.
Features
- Photoelectric, integrated low-flow technology.
- Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to 20.32 m/sec).
- Versatile mounting options: square or rectangular configuration.
- Broad operating temperature range (-4°F to 158°F) and humidity range (0% to 95% non-condensing).
- Patented sampling tube installs from front or back of the detector without tools.
- New cover tamper signal.
- Increased wiring space with a 3/4-inch conduit knockout.
- Space within housing to accommodate relay module mounting.
- Easily accessible code wheels on sensor head (sold separately).
- Clear cover for convenient visual inspection.
- ULC® Listed.
- Remote testing capability.
- Requires communication line power only.
Architectural/Engineering Specifications
The air duct smoke detector shall be a System Sensor InnovairFlex™ DNRA Intelligent Non-Relay Photoelectric Duct Smoke Detector. The detector housing shall be ULC Listed specifically for use in air handling systems. The flexible housing fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4,000 ft/min (0.5 m/sec to 20.32 m/sec). The unit shall provide a trouble signal if the sensor cover is removed or improperly installed. Local testing is possible via magnetic switch or remote testing using the RTS151KEY-A remote test station. Terminal connections use a strip and clamp method for 12–18 AWG wiring.
Physical Specifications
| Specification | Value |
|---|---|
| Size: | |
| Rectangular Dimensions | 37 cm (14.38 in) Length; 12.7 cm (5 in) Width; 6.6 cm (2.5 in) Depth |
| Square Dimensions | 19.7 cm (7.75 in) Length; 22.9 cm (9 in) Width; 6.35 cm (2.5 in) Depth |
| Weight | 1.6 lb (0.73 kg) |
| Operating Temperature Range | –4° to 158°F (–20° to 70°C) |
| Storage Temperature Range | –22° to 158°F (–30° to 70°C) |
| Operating Humidity Range | 0% to 95% relative humidity non-condensing |
| Air Duct Velocity | 100 to 4000 ft/min (0.5 to 20.32 m/sec) |
| DCOIL - (if included) | 17.5 - 26.4 VDC, 0.95mA max. |
Electrical Ratings
For information on electrical specifications, refer to the Detector Head Installation Manual.
Accessory Current Loads at 24 VDC
| Device | Standby | Trouble |
|---|---|---|
| RA100ZA | 0 mA | 12 mA Max. |
| RTS151KEY-A | 0 mA | 12 mA Max. |
Installing the InnovairFlex Sampling Tube
The InnovairFlex sampling tube can be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing the front or rear locking tab. (Figure 3 illustrates the front locking tab).
Figure 1: Image showing the InnovairFlex sampling tube installation.
Figure 2: Image showing the InnovairFlex sampling tube installation.
Figure 3: Image showing the InnovairFlex sampling tube installation, highlighting the front locking tab.
Wiring Diagrams
Figure 4: System Wiring Diagram for DNRA. Depicts connections from a ULC/FM Listed Control Panel to detectors in a loop, showing COMM. LINE (+/-) and RA (+/-) connections.
Figure 5: DNRA to RA100ZA wiring diagram. Shows connection of DNRA to a RA100ZA unit for a remote alarm LED option.
Figure 6: DNRA to RTS151KEY-A wiring diagram. Illustrates connections for a DNRA detector head with "R" remote test capability to the RTS151KEY-A remote test station, including test coil, communication, RA/RTS, and power connections. It notes the need for an external 24 VDC power supply for the RTS151KEY-A test coil circuit, which must be ULC Listed.
Important Notes
- The use of the RTS151KEY-A requires the installation of an accessory coil, DCOIL, sold separately. For additional information, refer to the DNRA Installation Manual.
- The RTS151KEY-A test coil circuit requires an external 24 VDC power supply which must be ULC Listed.
Accessories
System Sensor provides system flexibility with a variety of accessories, including two remote test stations and different means of visible system annunciation. All duct smoke detector accessories are ULC Listed.
Figure 7: Image of RTS151KEY-A remote test station with key lock.
Figure 8: Image of RA100ZA remote annunciator alarm LED.
Figure 9: Image of ASD-PL2FRA intelligent photoelectric smoke sensor.
Ordering Information
| Part Number | Description |
|---|---|
| Main Unit | |
| DNRA | Intelligent non-relay photoelectric low-flow duct smoke detector |
| ASD-PL2FRA | Intelligent photoelectric smoke sensor with remote test capability in duct applications |
| Accessories | |
| DCOIL | Remove test coil required with RTS151KEY-A |
| DST1 | Metal sampling tube duct width up to 1 ft (0.3m) |
| DST1.5 | Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m) |
| DST3 | Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 1.2 m) |
| DST5 | Metal sampling tube duct widths 4 ft to 8 ft (1.2 to 2.4 m) |
| DST10 | Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m) |
| DH400OE-1 | Weatherproof enclosure |
| M02-09-00 | Telescoping Test Magnet |
| P48-21-00 | End cap for metal sampling tubes |
| RA100ZA | Remote annunciator alarm LED |
| RTS151KEY-A | Remote test station with key lock |