MDT KNX Push-button: Operating Instructions and Technical Data
This document provides operating instructions and technical data for MDT KNX Push-buttons, intended for authorized electricians only.
Technical Data
Technical Data | BE-TA55x2.02 | BE-TA55x2.G2 | BE-TA55x4.02 | BE-TA55x4.G2 | BE-TA55x6.02 | BE-TA55x8.02 | BE-TA55x6.G2 | BE-TA55x8.G2 |
Number of rockers | 2 | 2 | 4 | 4 | 6 | 8 | 6 | 8 |
Number of bicoloured LEDs (TA55P / TA55T) | 2 | 2 | 4 | 4 | 6 | 8 | 6 | 8 |
Orientation LED (TA55P / TA55T) | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Temperature sensor (TA55T) | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Specification KNX interface | TP-256 | TP-256 | TP-256 | TP-256 | TP-256 | TP-256 | TP-256 | TP-256 |
Available KNX databank | ab ETS5 | |||||||
Max. conductor cross section | 0.8 mm Ø, single core | |||||||
KNX busconnection terminal | KNX Bus | |||||||
Power Supply | < 0.3 W | |||||||
Power Consumption KNX bus typ. | < 0.3 W | |||||||
Ambient temperature range | 0 ... +45 °C | |||||||
Protection classification | IP20 | |||||||
Dimensions (W x H x D) | 55 mm x 55 mm x 13 mm |
Operating Instructions KNX Push-button
For authorised electricians only
Product Models: KNX Taster 55, BE-TA550x.x2, KNX Taster Plus 55, BE-TA55Px.x2, KNX Taster Plus TS 55, BE-TA55Tx.x2
General Safety Instructions - Important safety notes
Danger High Voltage
- The device must only be installed and connected by qualified electricians. Observe country-specific regulations and valid KNX guidelines. Devices are approved for use in the EU and bear the CE mark. Use in the USA and Canada is prohibited.
Connection terminals, operating and display elements
Front view
The front view shows the button layout and status LEDs. The numbering indicates the different button areas and LEDs.
Key:
- 1 - KNX busconnection terminal
- 2 - Programming key
- 3 - Red programming LED
- 4 - Status indication LED (TA55P/TA55T)
- 5 - Orientation LED (TA55P/TA55T)
- 6 - Temperature sensor (TA55T)
- 7 - Operating buttons
Rear view
The rear view shows the connection terminal for the KNX bus.
Assembly and Connection KNX Push-button
- Connect the KNX push-button to the KNX bus.
- Install the KNX push-button into the switch box.
- Switch on KNX power supply.
Exemplary circuit diagram BE-TA55xx.x2
A diagram shows a simple connection of the KNX push-button to the KNX/EIB Bus.
Description KNX Push-button
The MDT Taster triggers KNX/EIB telegrams after a button press, depending on the parameterization. The buttons can be parameterized as button pairs (two-rocker) or as single buttons. In addition to dimmer/blinds, contact type, and block communication objects, numerous functions are available. The MDT Taster Plus features 4 integrated logic modules. Sending a second object is possible via the logic modules. The central labeling field with a cover foil allows for individual labeling of the push-button. The labeling template can be found on the MDT website in the download area. MDT Taster Plus series additionally features an orientation light and a bicoloured (red/green) LED per rocker. These can be controlled with internal or external objects. It is possible to display 3 states with one LED, e.g., LED off = 'absent', LED green = 'present', LED red = 'window open'.
The MDT Taster Plus TS 55 has an additional temperature sensor for detecting the room temperature.
Fits 55mm systems/ranges:
- GIRA Standard 55, E2, E22, Event, Esprit
- JUNG A500, Aplus, Acreation, AS5000
- BERKER S1, B3, B7 glass
- MERTEN 1M, M-Smart, M-Plan, M-Pure
The MDT Taster is intended for installation in switch boxes. Installation must be carried out in dry indoor areas.
Note: The product database can be found at www.mdt.de\Downloads.html
Commissioning KNX Push-button
- Assign the physical address and create the application program in the ETS.
- Load the physical address and the application program into the KNX Taster. Press the programming button when prompted.
- The red LED turns off after successful programming.