Air Conditioners RA14AZ
EndeavorTM Line Classic® Series iM Air Conditioners
RA14AZ
Cooling Efficiency up to: 14.3 SEER2/11.7 EER2 Nominal Sizes: 11/2 to 5 Ton [5.28 to 17.6 kW] Cooling Capacities: 17.1 to 55.5 kBTU [5.0 to 16.3 kW]
FORM NO. A11-337

Table of Contents RA14AZ

Table of Contents
Features & Benefits...................................................................3 Model Number Identification.....................................................4 Available SKUs..........................................................................4 General Data/Electrical Data.....................................................5 Accessories...............................................................................6 Weighted Sound Power............................................................6 Unit Dimensions........................................................................7 Clearances................................................................................8 Control Wiring...........................................................................9 Refrigerant Line Size Information...................................... 10-13 Performance Data...................................................................14 Limited Warranty.....................................................................16

2

Standard Feature Table
Feature R-410A Refrigerant Scroll Compressor Field Installed Filter Drier Front Seating Service Valves Internal Pressure Relief Valve Internal Thermal Overload Long Line capability Low Ambient capability with Kit 3-4-5 Expanded Valve Space Composite Basepan 2 Screw Control Box Access 15" Access to Internal Components Quick release louver panel design No fasteners to remove along bottom Optimized Venturi Airflow Powder coated paint Rust resistant screws QR code External gauge ports Service trays  = Standard

Features and Benefits RA14AZ

STANDARD FEATURES

18

24

30

36

42

48

60

























































































































































































































































































Features and Benefits
· Lighter Footprint & Less Environmental Impact from New 7mm Condenser Coil provided by a decrease in refrigerant requirements and an overall weight reduction
· Efficient Cooling up to 14.3 SEER2/11.7 EER2
· PlusOne Expanded Value Space: 3in ­ 4in ­ 5 in service valve space ­ provides a minimum working area of 27-square inches for easier access
· PlusOne Triple Service Access: 15 in wide, industry leading corner service access ­ makes repairs easier and faster. The two fastener, removable corner allows optimal access to internal unit components. Individual louver panels come out once fastener is removed, for faster coil cleaning and easier cabinet reassembly
· System Matching Simplicity ­ matches to all tiers of gas furnaces

· Modern cabinet aesthetics ­ High curb appeal with visually appealing design
· Curved louver panels ­ provide ultimate coil protection, enhance cabinet strength, and increased cabinet rigidity
· Diagnostic service window with two-fastener opening ­ provides access to the high and low pressure.
· External gauge port access ­ allows easy connection of "low-loss" gauge ports
· QR code ­ provides technical information on demand for faster service calls
· Fan motor harness with extra-long wires allows unit top to be removed without disconnecting fan wire.

3

Model Number Identification/Available SKUs RA14AZ

 Air Conditioners

R

A

14

A

Z

24

A

J

1

N

A

LHP

Brand Product Category

SEER2

Region Refrigerant

Capacity BTU/HR

Major Series

Voltage

Type

Controls

Minor Series Option Code

Rheem A - Air Conditioners

13.8/14.3 SEER2 A - All Z - R-410A

18 - 18,000 [5.28 kW] 24 - 24,000 [7.03 kW] 30 - 30,000 [8.79 kW] 36 - 36,000 [10.55 kW] 42 - 42,000 [12.31 kW] 48 - 48,000 [14.07 kW] 60 - 60,000 [17.58 kW]

A - 1st Design J - 1ph, 208-230/60 1 - Single Stage

N - Non-Communicating

A - 1st Design LHP - W/HLPC

[ ] Designates Metric Conversions

Available SKUs
Available Models RA14AZ18AJ1NA RA14AZ18AJ1NALHP RA14AZ24AJ1NA RA14AZ24AJ1NALHP RA14AZ30AJ1NA RA14AZ30AJ1NALHP RA14AZ36AJ1NA RA14AZ36AJ1NALHP RA14AZ42AJ1NA RA14AZ42AJ1NALHP RA14AZ48AJ1NA RA14AZ48AJ1NALHP R RA14AZ60AJ1NA A RA14AZ60AJ1NALHP

Brand Rheem

Product Category A - Air Conditioners

Description

EndeavorTM Line Classic ® Series 1 1/2 ton 14.3 SEER2 Single-Stage Air Conditioner-208/230/1/60

EndeavorTM Line Classic ® Series 1 1/2 ton 14.3 SEER2 Single-Stage Air Conditioner w/ High/Low Pressure-208/230/1/60

EndeavorTM Line Classic ® Series 2 ton 14.3 SEER2 Single-Stage Air Conditioner-208/230/1/60

EndeavorTM Line Classic ® Series 2 ton 14.3 SEER2 Single-Stage Air Conditioner w/ High/Low Pressure-208/230/1/60

EndeavorTM Line Classic ® Series 2 1/2 ton 14.3 SEER2 Single-Stage Air Conditioner-208/230/1/60

EndeavorTM Line Classic ® Series 2 1/2 ton 14.3 SEER2 Single-Stage Air Conditioner w/ High/Low Pressure-208/230/1/60

EndeavorTM Line Classic ® Series 3 ton 14.3 SEER2 Single-Stage Air Conditioner-208/230/1/60

EndeavorTM Line Classic ® Series 3 ton 14.3 SEER2 Single-Stage Air Conditioner w/ High/Low Pressure-208/230/1/60

EndeavorTM Line Classic ® Series 3 1/2 ton 14.3 SEER2 Single-Stage Air Conditioner-208/230/1/60

EndeavorTM Line Classic ® Series 3 1/2 ton 14.3 SEER2 Single-Stage Air Conditioner w/ High/Low Pressure-208/230/1/60

EndeavorTM Line Classic ® Series 4 ton 14.3 SEER2 Single-Stage Air Conditioner-208/230/1/60

EndeavorTM Line Classic ® Series 4 ton 14.3 SEER2 Single-Stage Air Conditioner w/ High/Low Pressure-208/230/1/60

EndeavorTM14 Line Classic ® Series 5 tAon 14.3 SEER2 Single-ZStage Air Conditioner-208/23204/1/60

A

EndeavorTM Line Classic ® Series 5 ton 14.3 SEER2 Single-Stage Air Conditioner w/ High/Low Pressure-208/230/1/60

SEER2 13.8/14.3 SEER2

Region A - All S - Southeast N - North

Refrigerant Z - R-410A

Capacity BTU/HR 18 - 18,000 [5.28 kW 24 - 24,000 [7.03 kW] 30 - 30,000 [8.79 kW 36 - 36,000 [10.55 kW] 42 - 42,000 [12.31 kW] 48 - 48,000 [14.07 kW] 60 - 60,000 [17.58 kW]

Major Series A - 1st Design

J - 1p C - 3p D - 3p

RA14AZ18AJ1NA RA14AZ18AJ1NALHP RA14AZ24AJ1NA RA14AZ24AJ1NALHP RA14AZ30AJ1NA RA14AZ30AJ1NALHP RA14AZ36AJ1NA 4 RA14AZ36AJ1NALHP RA14AZ42AJ1NA

Classic ® Series 1 1/2 ton 14.3 SEER2 Single-Stage Air Conditioner-208/230/1/60 Classic ® Series 1 1/2 ton 14.3 SEER2 Single-Stage Air Conditioner w/ High/Low Pressure-208/230/1/60 Classic ® Series 2 ton 14.3 SEER2 Single-Stage Air Conditioner-208/230/1/60 Classic ® Series 2 ton 14.3 SEER2 Single-Stage Air Conditioner w/ High/Low Pressure-208/230/1/60 Classic ® Series 2 1/2 ton 14.3 SEER2 Single-Stage Air Conditioner-208/230/1/60 Classic ® Series 2 1/2 ton 14.3 SEER2 Single-Stage Air Conditioner w/ High/Low Pressure-208/230/1/60 Classic ® Series 3 ton 14.3 SEER2 Single-Stage Air Conditioner-208/230/1/60 Classic ® Series 3 ton 14.3 SEER2 Single-Stage Air Conditioner w/ High/Low Pressure-208/230/1/60 Classic ® Series 3 1/2 ton 14.3 SEER2 Single-Stage Air Conditioner-208/230/1/60
®

General Data/Electrical Data RA14AZ

General Data
Model No. Nominal Tonnage Valve Connections
Liquid Line O.D. ­ in. Suction Line O.D. ­ in. Refrigerant (R410A) furnished oz.¹ Compressor Type Outdoor Coil Net face area ­ Outer Coil Net face area ­ Inner Coil
Tube diameter ­ in. Number of rows Fins per inch
Outdoor Fan Diameter ­ in.
Number of blades Motor hp CFM RPM watts
Shipping weight ­ lbs. Operating weight ­ lbs.
Electrical Data

RA14AZ18 1.5
3/8 3/4 94
10.9 10.5 0.276
2 24
20 2 1/7 2156 1075 152 151 144

GENERAL DATA

RA14AZ24

RA14AZ30

2.0

2.5

3/8

3/8

3/4

3/4

115

120

13.3 12.9 0.276
2 24
24 2 1/6 2723 825 161 185 178

14.3 13.9 0.276
2 24
24 2 1/6 2830 825 165 171 164

RA14AZ36 3.0
3/8 3/4 124 Scroll
16.4 15.9 0.276
2 24
24 2 1/6 2991 825 145 185 178

RA14AZ42 3.5
3/8 7/8 149
19.5 18.8 0.276
2 24
24 3 1/5 3655 850 214 236 229

RA14AZ48 4.0
3/8 7/8 153
19.5 18.8 0.276
2 24
24 3 1/5 3655 850 214 228 221

RA14AZ60 5.0
3/8 7/8 203
32.5 -- 3/8 1 22
26 3 1/3 5178 910 271 294 287

Line Voltage Data (Volts-Phase-Hz)

208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60

Maximum overcurrent protection (amps)²

20

25

30

30

40

40

60

Minimum circuit ampacity³

14

18

19

20

24

24

40

Compressor

Rated load amps

9

12

14

13

18

18

26

Locked rotor amps

43

60

68

83

110

102

150

Condenser Fan Motor

Full load amps

0.8

0.8

0.8

0.8

1.0

1.0

2.8

Locked rotor amps

1.5

1.5

1.7

1.7

2.6

2.6

--

¹Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional refrigerant charge required. ²HACR type circuit breaker of fuse. ³Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.

151

185

171

185

236

228

294

144

178

164

178

229

221

287

5

Accessories/Weighted Sound Power RA14AZ

Accessories

Model No.

RA14AZ18

Compressor crankcase heater*

44-17402-44

Low ambient control

RXAD-A08

Compressor sound cover Compressor hard start kit Compressor time delay

68-23427-26 SK-A1
RXMD-B01

Low pressure control High pressure control

RXAC-A07 RXAB-A07

Liquid Line Solenoid (24 VAC, 50/60 Hz)

Solenoid Valve 200RD2T3TVLC

Solenoid Coil

61-AMG24V

Liquid Line Solenoid

Solenoid Valve 200RD2T3TVLC

(120/240 VAC, 50/60 Hz) Solenoid Coil 61-AMG120/240V

Classic Top Cap w/Label

91-101123-21

*Crankcase Heater recommended with Low Ambient Kit.

RA14AZ24 44-17402-44 RXAD-A08 68-23427-26
SK-A1 RXMD-B01 RXAC-A07 RXAB-A07 200RD2T3TVLC 61-AMG24V 200RD2T3TVLC 61-AMG120/240V 91-101123-21

RA14AZ30 44-17402-44 RXAD-A08 68-23427-26
SK-A1 RXMD-B01 RXAC-A07 RXAB-A07 200RD2T3TVLC 61-AMG24V 200RD2T3TVLC 61-AMG120/240V 91-101123-21

RA14AZ36 44-17402-44 RXAD-A08 68-23427-26
SK-A1 RXMD-B01 RXAC-A07 RXAB-A07 200RD2T3TVLC 61-AMG24V 200RD2T3TVLC 61-AMG120/240V 91-101123-21

RA14AZ42 44-17402-45 RXAD-A08 68-23427-25
SK-A1 RXMD-B01 RXAC-A07 RXAB-A07 200RD2T3TVLC 61-AMG24V 200RD2T3TVLC 61-AMG120/240V 91-101123-21

RA14AZ48 44-17402-45 RXAD-A08 68-23427-25
SK-A1 RXMD-B01 RXAC-A07 RXAB-A07 200RD2T3TVLC 61-AMG24V 200RD2T3TVLC 61-AMG120/240V 91-101123-21

RA14AZ60 44-17402-45 RXAD-A08 68-23427-25
SK-A1 RXMD-B01 RXAC-A07 RXAB-A07 200RD2T3TVLC 61-AMG24V 200RD2T3TVLC 61-AMG120/240V 91-101123-21

WeightedMoSdeol Nuon. d Power Level (dBA)RA14AZ18

Compressor crankcase

44-17402-44

ULnoiwt Saimzebi-enVtocltoangtero,lSeries

Standard Rating (dBA)

12R5XAD-A08

CompresRsAo1r4sAoZu1n8d cover

70.7

4688.2-23427-26

CompresRsAo1r4hAaZrd24start kit

75.7

46.5SK-A1

RA14AZ24

RA14AZ30

RA14AZ36

44-17402-44

44-17402-44

44-17402-44

TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)

250

RXAD-5A0008

100R0XAD-A08 2000

RXAD4-0A0008

56.0 68-2346217.-926

616.80-23427-26 56.5 68-2345237.-526

62.0

SK-A681.1

64.5 SK-A1 60.8

SK-5A51.2

ComprReAss1o4rAtZim30e delay

76.8

48R.2XMD-B01 62.5 RXMD6-B80.81

65R.8XMD-B01 62.0 RXMD5-7B.021

Low preRssAu1r4eAcZo3n6trol

76.1

48R.4XAC-A07 58.7

High preRsAsu1r4eAcZo4n2trol RA14AZ48

72.5

46R.6XAB-A07 55.3

74.0

45.4

55.7

Liquid LRinAe1S4oAlZen6o0id

75.8

43.4

59.8

(24 VAC, 50/60 Hz)

Solenoid Valve

200RD2T3TVLC

NOTE: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI)

Solenoid Coil

61-AMG24V

RXAC-6A70.37 RXAB-6A30.97
64.2 67.2 200RD2T3TVLC
61-AMG24V

65.R5XAC-A07 62.6

62.R1XAB-A07 59.4

62.9

60.8

65.5

62.7

200RD2T3TVLC

61-AMG24V

RXAC5-A80.87 RXAB5-A50.27
56.7 59.2 200RD2T3TVLC
61-AMG24V

RA14AZ42
44-17402-45
800R0XAD-A08 456.87-23427-25 48.4 SK-A1 49.R6XMD-B01 52.R1XAC-A07 48.R2XAB-A07 51.2 53.1 200RD2T3TVLC
61-AMG24V

Liquid Line Solenoid (120/240 VAC, 50/60 Hz)

Solenoid Valve Solenoid Coil

200RD2T3TVLC 61-AMG120/240V

200RD2T3TVLC 61-AMG120/240V

200RD2T3TVLC 61-AMG120/240V

200RD2T3TVLC 61-AMG120/240V

200RD2T3TVLC 61-AMG120/240V

Classic Top Cap w/Label Unit Size -
Voltage, Series
RA14AZ18
RA14AZ24
RA14AZ30
RA14AZ36
RA14AZ42
RA14AZ48

91-101123-21 Standard Rating (dBA)
70.7
75.7
76.8
76.1
72.5
74.0

91-1011T2Y3P-2IC1AL OCTAVE9B1A-1N0D11S2P3E-C2T1RUM (dBA w91it-h1o0u1t1t2o3n-e2a1djustment) 91-101123-21

125

250

500

1000

2000

4000

8000

48.2

56.0

61.9

61.0

56.5

53.5

45.7

46.5

62.0

68.1

64.5

60.8

55.2

48.4

48.2

62.5

68.8

65.8

62.0

57.2

49.6

48.4

58.7

67.3

65.5

62.6

58.8

52.1

46.6

55.3

63.9

62.1

59.4

55.2

48.2

45.4

55.7

64.2

62.9

60.8

56.7

51.2

RA14AZ60

75.8

43.4

59.8

67.2

65.5

62.7

59.2

53.1

Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instrucitons for inform length and additional refrigerant charge required.
6

Unit Dimensions

MODEL NO.
RA14AZ18 RA14AZ24 RA14AZ30 RA14AZ36 RA14AZ42 RA14AZ48 RA14AZ60

H (Height)

INCHES

mm

25.00

635

25.00

635

27.00

686

31.00

787

35.00

889

35.00

889

51.00

1295

OPERATING

L (Length)

INCHES

mm

29.75

756

33.75

857

33.75

857

33.75

857

33.75

857

33.75

857

35.75

908

W (Width)

INCHES

mm

29.75

756

33.75

857

33.75

857

33.75

857

33.75

857

33.75

857

35.75

908

H (Height)

INCHES

mm

26.50

673

26.50

673

28.50

724

32.50

826

36.50

927

36.50

927

52.50

1334

SHIPPING

L (Length)

INCHES

mm

32.38

822

36.38

924

36.38

924

36.38

924

36.38

924

36.38

924

38.38

975

Unit Dimensions RA14AZ

W (Width)

INCHES

mm

32.38

822

36.38

924

36.38

924

36.38

924

36.38

924

36.38

924

38.38

975

[ ] Designates Metric Conversions

Unit Dimen-

MODEL

OPERATING H (Height)

INCHES

mm

RA14AZ18

25.00

635

RA14AZ24

25.00

635

RA14AZ30

27.00

686

RA14AZ36

31.00

787

RA14AZ42

35.00

889

RA14AZ48

35.00

889

RA14AZ60

51.00

1295

ST-A1226-02-00

7

Clearances RA14AZ

8

WALL

CLEARANCES
WALL

6 (152.4)

24 (609.6) Service

12 (304.8)
6 (152.4)

WALL
24 (609.6) Service

12 (304.8)

6 (152.4)

12 (304.8)

24 (609.6) Service

WALL
24 (609.6) Service

24 (609.6) Service

18 (457.2)

24 (609.6)
24 recommended 6 minimum

24 (609.6)
24 recommended 6 minimum

NOTE: NUMBERS IN () = mm
IMPORTANT: When installing multiple units in an alcove, roof well or partially enclosed area, ensure there is adequate ventillation to prevent re-circulation of discharge air.

ST-A1225-01-00

Control Wiring
FIGURE 2
CONTROL WIRING FOR GAS OR OIL FURNACE

FOR TYPICAL GAS OR OIL HEAT
BR ­ BROWN WIRE YL ­ YELLOW WIRE X ­ WIRE CONNECTION

TYPICAL THERMOSTAT SUBBASE
Y G WR

TYPICAL CONDENSING UNIT

YL

X

BR

X

TYPICAL GAS OR OIL FURNACE
R W G Y C

Control Wiring/Application Guidelines RA14AZ

*IF MAXIMUM OUTLET TEMPERATURE RISE IS DESIRED, IT IS RECOMMENDED THAT W1 (W/BK) AND W2 (W/BL) BE JUMPERED TOGETHER.

FOR TYPICAL ELECTRIC HEAT

TYPICAL THERMOSTAT SUBBASE
Y G WR

BR ­ BROWN WIRE R ­ RED WIRE YL ­ YELLOW WIRE
W/BK ­ WHITE WIRE WITH BLACK STRIPE G/BK ­ GREEN WIRE WITH BLACK STRIPE
PU ­ PURPLE WIRE (NOT USED)
X ­ WIRE CONNECTION

TYPICAL CONDENSING UNIT

*·

YL

X

BR

X

TYPICAL ELECTRIC HEAT LOW VOLTAGE JUNCTION BOX

X

W/BL

X

R

X

W/BK

X

G/BK

X

YL

X

BR

PU

Application Guidelines
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01 -in. wc. 2. Minimum outdoor operation air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C). 3. Maximum outdoor operating air temperature is 125°F (51.7°C). 4. For reliable operation, unit should be level in all horizontal planes. 5. Use only copper wire for electric connections at unit. Aluminum and clad aluminum are not acceptable for the type of connector
provided. 6. Do not apply capillary tube indoor coils to these units. 7. Factory-supplied filter drier must be installed.

9

Refrigerant Line Size Information RA14AZ
10

Refrigerant Line Size Information

Allowable Unit Size Liquid Line
Size

Allowable Suction Line
Size

Apply Long Line Guidelines if Linear Line Length Exceeds Those Shown Below (Feet)
(-)A14AZ

14.3 SEER2 Single-Stage Air-Conditioners

< 25

26-50

51-75

76-100

Equivalent Length (Feet) 101-125 126-150

151-175

176-200

201-225

Maximum Vertical Rise (Outdoor Unit Below Indoor Unit) * / Capacity Multiplier

1/4"

5/8"

N/A

25 / 1.00

50 / 0.99

62 / 0.98

1.5 Ton **SEE NOTE 3

5/16" 3/8" 1/4" 5/16"

5/8" 5/8" 3/4"** 3/4"**

223

25 / 1.00

50 / 0.99

75 / 0.98

148

25 / 1.00

50 / 0.99

75 / 0.98

N/A

25 / 1.00

50 / 1.00

62 / 0.99

223

25 / 1.00

50 / 1.00

75 / 0.99

3/8"

3/4"**

148

25 / 1.00

50 / 1.00

75 / 1.00

1/4"

5/8"

N/A

25 / 0.99

50 / 0.98

21 / 0.97

5/16"

5/8"

213

25 / 0.99

50 / 0.98

75 / 0.97

3/8"

5/8"

2 Ton

1/4"

3/4"

142

25 / 0.99

50 / 0.98

75 / 0.97

N/A

25 /1.00

50 / 1.00

21 / 0.99

5/16"

3/4"

213

25 /1.00

50 / 1.00

75 / 0.99

3/8"

3/4"

142

25 / 1.00

50 / 1.00

75 / 0.99

5/16"

5/8"

N/A

25 / 0.99

50 / 0.98

75 / 0.96

3/8"

5/8"

2.5 Ton

5/16"

3/4"

117

25 / 0.99

50 / 0.98

75 / 0.96

175

25 / 1.00

50 / 0.99

75 / 0.99

3/8"

3/4"

117

25 / 1.00

50 / 0.99

75 / 0.99

5/16"

5/8"

N/A

25 / 0.99

50 / 0.97

66 / 0.94

3/8"

5/8"

85

25 / 0.99

50 / 0.97

75 / 0.94

5/16"

3/4"

128

25 / 1.00

50 / 0.99

66 / 0.98

3/8"

3/4"

3 Ton

1/2"

3/4"

85

25 / 1.00

50 / 0.99

75 / 0.98

43

25 / 1.00

50 / 0.99

75 / 0.98

5/16"

7/8"

128

25 / 1.00

50 / 1.00

66 / 1.00

3/8"

7/8"

85

25 / 1.00

50 / 1.00

75 / 1.00

1/2"

7/8"

43

25 / 1.00

50 / 1.00

75 / 1.00

3/8"

3/4"

102

25 / 0.99

50 / 0.98

75 / 0.97

1/2"

3/4"

3.5 Ton

3/8"

7/8"

51

25 / 0.99

50 / 0.98

75 / 0.97

102

25 / 1.00

50 / 1.00

75 / 0.99

1/2"

7/8"

51

25 / 1.00

50 / 1.00

75 / 0.99

NOTES: 1)  Do not exceed 200 ft linear line length. 2)  *Do not exceed 100 ft vertical separation if outdoor unit is above indoor unit. 3) **3/4" suction line should only be used for 1.5 ton systems if outdoor unit is below or at same level as indoor to assure proper oil return. 4)  Always use the smallest liquid line allowable to minimize refrigerant charge. 5)  Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed. 6)  Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

43 / 0.98 98 / 0.98 100 / 0.98 43 / 0.99 98 / 0.99 100 / 0.99
NR 87 / 0.96 100 / 0.96
NR 87 / 0.99 100 / 0.99 70 / 0.94 100 / 0.94 70 / 0.98 100 / 0.98 49 / 0.92 95 / 0.92 49 / 0.98 95 / 0.98 100 / 0.98 49 / 0.99 95 / 0.99 100 / 0.99 88 / 0.96 100 / 0.96 88 / 0.99 100 / 0.99

24 / 0.97 93 / 0.97 100 / 0.97 24 / 0.99 93 / 0.99 100 / 0.99
NR 77 / 0.95 100 / 0.95
NR 77 / 0.98 100 / 0.98 59 / 0.93 98 / 0.93 59 / 0.98 98 / 0.98 32 / 0.90 89 / 0.90 32 / 0.97 89 / 0.97 100 / 0.97 32 / 0.99 89 / 0.99 100 / 0.99 80 / 0.95 100 / 0.95 80 / 0.99 100 / 0.99

5 / 0.97 88 / 0.97 100 / 0.97 5 / 0.99 88 / 0.99 100 / 0.99
NR 69 / 0.94 100 / 0.94
NR 69 / 0.98 100 / 0.98 48 / 0.91 94 / 0.91 48 / 0.97 94 / 0.97
NR NR 15 / 0.96 84 / 0.96 100 / 0.96 15 / 0.99 84 / 0.99 100 / 0.99 72 / 0.94 100 / 0.94 72 / 0.98 100 / 0.98

NR 83 / 0.96 100 / 0.96
NR 83 / 0.99 100 / 0.99
NR 61 / 0.93 98 / 0.93
NR 61 / 0.98 98 / 0.98 36 / 0.90 90 / 0.90 36 / 0.96 90 / 0.96
NR NR NR 78 / 0.95 100 / 0.95 NR 78 / 0.98 100 / 0.98 65 / 0.92 100 / 0.92 65 / 0.97 100 / 0.97

NR 78 / 0.96 100 / 0.96
NR 78 / 0.98 100 / 0.98
NR 53 / 0.92 95 / 0.92
NR 53 / 0.97 95 / 0.97
NR NR 25 / 0.96 86 / 0.96 NR NR NR 72 / 0.94 100 / 0.94 NR 72 / 0.98 100 / 0.98 57 / 0.91 100 / 0.91 57 / 0.97 100 / 0.97

NR 73 / 0.95 100 / 0.95
NR 73 / 0.98 100 / 0.98
NR 45 / 0.91 92 / 0.91
NR 45 / 0.97 93 / 0.97
NR NR 13 / 0.95 82 / 0.95 NR NR NR 67 / 0.93 100 / 0.93 NR 67 / 0.98 100 / 0.98 49 / 0.90 100 / 0.90 49 / 0.96 100 / 0.96

226-250
NR 68 / 0.94 100 / 0.94
NR 68 / 0.98 100 / 0.98
NR 37 / 0.90 89 / 0.90
NR 37 / 0.96 90 / 0.96
NR NR NR 78 / 0.95 NR NR NR 61 / 0.93 100 / 0.93 NR 61 / 0.97 100 / 0.97 NR NR 42 / 0.96 100 / 0.96

Refrigerant Line Size Information (con't.)

Allowable Unit Size Liquid Line
Size

Allowable Suction Line
Size

Apply Long Line Guidelines if Linear Line Length Exceeds Those Shown Below (Feet)
(-)A14AZ

14.3 SEER2 Single-Stage Air-Conditioners

< 25

26-50

51-75

76-100

Equivalent Length (Feet) 101-125 126-150

151-175

176-200

201-225

Maximum Vertical Rise (Outdoor Unit Below Indoor Unit) * / Capacity Multiplier

3/8"

3/4"

110

25 / 0.99 50 / 0.98 75 / 0.96

1/2"

3/4"

4 Ton

3/8"

7/8"

55

25 / 0.99 50 / 0.98 75 / 0.96

110

25 / 1.00 50 / 0.99 75 / 0.99

1/2"

7/8"

55

25 / 1.00 50 / 0.99 75 / 0.99

3/8"

3/4"

0

25 / 0.99 50 / 0.97 75 / 0.94

1/2"

3/4"

0

25 / 0.99 50 / 0.97 75 / 0.94

3/8"

7/8"

5 Ton

1/2"

7/8"

0

25 / 1.00 50 / 0.99 75 / 0.98

0

25 / 1.00 50 / 0.99 75 / 0.98

3/8"

1-1/8"

0

25 / 1.01 50 / 1.01 75 / 1.00

1/2"

1-1/8"

0

25 / 1.01 50 / 1.01 75 / 1.00

NOTES: 1)  Do not exceed 200 ft linear line length. 2)  *Do not exceed 100 ft vertical separation if outdoor unit is above indoor unit. 3) **3/4" suction line should only be used for 1.5 ton systems if outdoor unit is below or at same level as indoor to assure proper oil return. 4)  Always use the smallest liquid line allowable to minimize refrigerant charge. 5)  Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed. 6)  Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

77 / 0.95 100 / 0.95 77 / 0.98 100 / 0.98 61 / 0.92 100 / 0.92 61 / 0.97 100 / 0.97 61 / 1.00 100 /1.00

67 / 0.93 100 / 0.93 67 / 0.97 100 / 0.97 46 / 0.90 100 / 0.90 46 / 0.96 100 /0.96 46 / 0.99 100 / 0.99

57 / 0.92 100 / 0.92 57 / 0.97 100 / 0.97
NR NR 32 / 0.95 100 / 0.95 32 / 0.99 100 / 0.99

46 / 0.91 100 / 0.91 46 / 0.96 100 / 0.96
NR NR 18 / 0.94 97 / 0.94 18 / 0.99 97 / 0.99

NR NR 36 / 0.96 100 / 0.96 NR NR NR 95 / 0.94 NR 95 / 0.99

NR NR 26 / 0.95 99 / 0.95 NR NR NR 92 / 0.93 NR 92 / 0.99

226-250
NR NR 15 / 0.95 97 / 0.95 NR NR NR 89 / 0.92 NR 89 / 0.98

13.4 - 14.3 SEER2 Single-Stage Air-Conditioners Unit Size Allowable Allowable Apply Long

4 Ton

3/8"

1/2"

3/8"

1/2"

5 Ton

3/8"

1/2"

5 Ton

3/8"

1/2"

3/8"

1/2"

3/4" 3/4" 7/8" 7/8" 3/4" 3/4" 7/8" 7/8" 1-1/8" 1-1/8"

(-)A13NZ 148 74 148 74 78 39 78 39 78 39

(-)A14AZ 110 55 110 55 0 0 0 0 0 0

Equivalent < 25 Maximum 25 / 0.99 25 / 0.99 25 / 1.00 25 / 1.00 25 / 0.99 25 / 0.99 25 / 1.00 25 / 1.00 25 / 1.01 25 / 1.01

26-50
50 / 0.98 50 / 0.98 50 / 0.99 50 / 0.99 50 / 0.97 50 / 0.97 50 / 0.99 50 / 0.99 50 / 1.01 50 / 1.01

51-75
75 / 0.96 75 / 0.96 75 / 0.99 75 / 0.99 75 / 0.94 75 / 0.94 75 / 0.98 75 / 0.98 75 / 1.00 75 / 1.00

76-100 101-125 126-150 151-175 176-200 201-

77 / 0.95 100 / 0.95 77 / 0.98 100 / 0.98 61 / 0.92 100 / 0.92 61 / 0.97 100 / 0.97 61 / 1.00 100 /1.00

67 / 0.93 100 / 0.93 67 / 0.97 100 / 0.97 46 / 0.90 100 / 0.90 46 / 0.96 100 /0.96 46 / 0.99 100 / 0.99

57 / 0.92 100 / 0.92 57 / 0.97 100 / 0.97 NR NR 32 / 0.95 100 / 0.95 32 / 0.99 100 / 0.99

46 / 0.91 100 / 0.91 46 / 0.96 100 / 0.96 NR NR 18 / 0.94 97 / 0.94 18 / 0.99 97 / 0.99

NR NR 36 / 0.96 100 / 0.96 NR NR NR 95 / 0.94 NR 95 / 0.99

NR NR 26 / 0 99 / 0 NR NR NR 92 / 0 NR 92 /

Refrigerant Line Size Information RA14AZ
11

Refrigerant Line Size Information RA14AZ
12

Refrigerant Line Size Information

Unit Size

Allowable Liquid Line
Size mm [in.]

Allowable Suction Line
Size mm [in.]

Apply Long Line Guidelines if Linear Line Length Exceeds Those Shown Below (Feet)
(-)A14AZ

14.3 SEER2 Single-Stage Air-Conditioners

< 8

8-15

16-23

24-30

Equivalent Length (Meters)

31-38

39-46

47-53

54-61

Maximum Vertical Rise (Outdoor Unit Below Indoor Unit) * / Capacity Multiplier

62-69

6.35 [1/4] 15.88 [5/8]

N/A

8 / 1.00 15 / 0.99 19 / 0.98

5.3 KW 7.94 [5/16] 15.88 [5/8]

68

[1.5 Ton] 9.53 [3/8] 15.88 [5/8]

45

**SEE 6.35 [1/4] 19.05 [3/4]**

N/A

NOTE 3 7.94 [5/16] 19.05 [3/4]**

68

8 / 1.00 8 / 1.00 8 / 1.00 8 / 1.00

15 / 0.99 15 / 0.99 15 / 1.00 15 / 1.00

23 / 0.98 23 / 0.98 19 / 0.99 23 / 0.99

9.53 [3/8] 19.05 [3/4]**

Metric

8 / 1.00 15 / 1.00 23 / 0.99

6.35 [1/4] 15.88 [5/8]

N/A

8 / 0.99 15 / 0.98 6 / 0.97

7.94 [5/16] 15.88 [5/8]

59

8 / 0.99 15 / 0.98 23 / 0.97

7.0 KW 9.53 [3/8] 15.88 [5/8]

39

8 / 0.99 15 / 0.98 23 / 0.97

[2 Ton] 6.35 [1/4] 19.05 [3/4]

N/A

8 / 1.00 15 / 1.00 6 / 0.99

7.94 [5/16] 19.05 [3/4]

59

8 / 1.00 15 / 1.00 23 / 0.99

9.53 [3/8] 19.05 [3/4]

39

8 / 1.00 15 / 1.00 23 / 0.99

7.94 [5/16] 15.88 [5/8]

N/A

8 / 0.99 15 / 0.98 23 / 0.96

8.8 KW 9.53 [3/8] 15.88 [5/8]

36

8 / 0.99 15 / 0.98 23 / 0.96

[2.5 Ton] 7.94 [5/16] 19.05 [3/4]

53

8 / 1.00 15 / 0.99 23 / 0.99

9.53 [3/8] 19.05 [3/4]

36

8 / 1.00 15 / 0.99 23 / 0.99

7.94 [5/16] 15.88 [5/8]

N/A

8 / 0.99 15 / 0.97 20 / 0.94

9.53 [3/8] 15.88 [5/8]

26

8 / 0.99 15 / 0.97 23 / 0.94

7.94 [5/16] 19.05 [3/4]

39

8 / 1.00 15 / 0.99 20 / 0.98

10.6 KW 9.53 [3/8] 19.05 [3/4]

26

8 / 1.00 15 / 0.99 23 / 0.98

[3 Ton] 12.70 [1/2] 19.05 [3/4]

13

8 / 1.00 15 / 0.99 23 / 0.98

7.94 [5/16] 22.23 [7/8]

39

8 / 1.00 15 / 1.00 20 / 1.00

9.53 [3/8] 22.23 [7/8]

26

8 / 1.00 15 / 1.00 23 / 1.00

12.70 [1/2] 22.23 [7/8]

13

8 / 1.00 15 / 1.00 23 / 1.00

9.53 [3/8] 19.05 [3/4]

31

8 / 0.99 15 / 0.98 23 / 0.97

12.3 KW 12.70 [1/2] 19.05 [3/4]

15

8 / 0.99 15 / 0.98 23 / 0.97

[3.5 Ton] 9.53 [3/8] 22.23 [7/8]

31

8 / 1.00 15 / 1.00 23 / 0.99

12.70 [1/2] 22.23 [7/8]

15

8 / 1.00 15 / 1.00 23 / 0.99

NOTES: 1)  Do not exceed 200 ft linear line length. 2)  *Do not exceed 100 ft vertical separation if outdoor unit is above indoor unit. 3) **3/4" suction line should only be used for 1.5 ton systems if outdoor unit is below or at same level as indoor to assure proper oil return. 4)  Always use the smallest liquid line allowable to minimize refrigerant charge. 5)  Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed. 6)  Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

13 / 0.98 30 / 0.98 30 / 0.98 13 / 0.99 30 / 0.99 30 / 0.99
NR 27 / 0.96 30 / 0.96
NR 27 / 0.99 30 / 0.99 21 / 0.94 30 / 0.94 21 / 0.98 30 / 0.98 15 / 0.92 29 / 0.92 15 / 0.98 29 / 0.98 30 / 0.98 15 / 0.99 29 / 0.99 30 / 0.99 27 / 0.96 30 / 0.96 27 / 0.99 30 / 0.99

7 / 0.97 28 / 0.97 30 / 0.97 7 / 0.99 28 / 0.99 30 / 0.99
NR 23 / 0.95 30 / 0.95
NR 23 / 0.98 30 / 0.98 18 / 0.93 30 / 0.93 18 / 0.98 30 / 0.98 10 / 0.90 27 / 0.90 10 / 0.97 27 / 0.97 30 / 0.97 10 / 0.99 27 / 0.99 30 / 0.99 24 / 0.95 30 / 0.95 24 / 0.99 30 / 0.99

2 / 0.97 27 / 0.97 30 / 0.97 2 / 0.99 27 / 0.99 30 / 0.99
NR 21 / 0.94 30 / 0.94
NR 21 / 0.98 30 / 0.98 15 / 0.91 29 / 0.91 15 / 0.97 29 / 0.97
NR NR 5 / 0.96 26 / 0.96 30 / 0.96 5 / 0.99 26 / 0.99 30 / 0.99 22 / 0.94 30 / 0.94 22 / 0.98 30 / 0.98

NR 25 / 0.96 30 / 0.96
NR 25 / 0.99 30 / 0.99
NR 19 / 0.93 30 / 0.93
NR 19 / 0.98 30 / 0.98 11 / 0.90 27 / 0.90 11 / 0.96 27 / 0.96
NR NR NR 24 / 0.95 30 / 0.95 NR 24 / 0.98 30 / 0.98 20 / 0.92 30 / 0.92 20 / 0.97 30 / 0.97

NR 24 / 0.96 30 / 0.96
NR 24 / 0.98 30 / 0.98
NR 16 / 0.92 29 / 0.92
NR 16 / 0.97 29 / 0.97
NR NR 8 / 0.96 26 / 0.96 NR NR NR 22 / 0.94 30 / 0.94 NR 22 / 0.98 30 / 0.98 17 / 0.91 30 / 0.91 17 / 0.97 30 / 0.97

NR 22 / 0.95 30 / 0.95
NR 22 / 0.98 30 / 0.98
NR 14 / 0.91 28 / 0.91
NR 14 / 0.97 28 / 0.97
NR NR 4 / 0.95 25 / 0.95 NR NR NR 20 / 0.93 30 / 0.93 NR 20 / 0.98 30 / 0.98 15 / 0.90 30 / 0.90 15 / 0.96 30 / 0.96

70-76
NR 21 / 0.94 30 / 0.94
NR 21 / 0.98 30 / 0.98
NR 11 / 0.90 27 / 0.90
NR 11 / 0.96 27 / 0.96
NR NR NR 24 / 0.95 NR NR NR 19 / 0.93 30 / 0.93 NR 19 / 0.97 30 / 0.97 NR NR 13 / 0.96 30 / 0.96

Refrigerant Line Size Information (con't.)

Unit Size

Allowable Liquid Line
Size mm [in.]

Allowable Suction Line
Size mm [in.]

Apply Long Line Guidelines if Linear Line Length Exceeds Those Shown Below (Feet)
(-)A14AZ

14.3 SEER2 Single-Stage Air-Conditioners Equivalent Length (Meters)

< 25

26-50

51-75

76-100 101-125 126-150 151-175

176-200

201-225

Maximum Vertical Rise (Outdoor Unit Below Indoor Unit) * / Capacity Multiplier

9.53 [3/8] 19.05 [3/4]

34

8 / 0.99 15 / 0.98 23 / 0.96

14.1 KW 12.7 [1/2] 19.05 [3/4]

17

8 / 0.99 15 / 0.98 23 / 0.96

[4 Ton] 9.53 [3/8] 22.23 [7/8]

34

8 / 1.00 15 / 0.99 23 / 0.99

12.7 [1/2] 22.23 [7/8]

17

8 / 1.00 15 / 0.99 23 / 0.99

9.53 [3/8] 19.05 [3/4]

0

8 / 0.99 15 / 0.97 23 / 0.94

12.7 [1/2] 19.05 [3/4]

0

8 / 0.99 15 / 0.97 23 / 0.94

17.6 KW 9.53 [3/8] 22.23 [7/8]

0

[5 Ton] 12.7 [1/2] 22.23 [7/8]

0

9.53 [3/8] 28.58 [1-1/8]

0

8 / 1.00 8 / 1.00 8 / 1.01

15 / 0.99 15 / 0.99 15 / 1.01

23 / 0.98 23 / 0.98 23 / 1.00

12.7 [1/2] 28.58 [1-1/8]

0

8 / 1.01 15 / 1.01 23 / 1.00

NOTES: 1)  Do not exceed 200 ft linear line length. 2)  *Do not exceed 100 ft vertical separation if outdoor unit is above indoor unit. 3) **3/4" suction line should only be used for 1.5 ton systems if outdoor unit is below or at same level as indoor to assure proper oil return. 4)  Always use the smallest liquid line allowable to minimize refrigerant charge. 5)  Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed. 6)  Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

24 / 0.95 30 / 0.95 24 / 0.98 30 / 0.98 19 / 0.92 30 / 0.92 19 / 0.97 30 / 0.97 19 / 1.00 30 / 1.00

20 / 0.93 30 / 0.93 20 / 0.97 30 / 0.97 14 / 0.90 30 / 0.90 14 / 0.96 30 /0.96 14 / 0.99 30 / 0.99

17 / 0.92 30 / 0.92 17 / 0.97 30 / 0.97
NR NR 10 / 0.95 30 / 0.95 10 / 0.99 30 / 0.99

14 / 0.91 30 / 0.91 14 / 0.96 30 / 0.96
NR NR 5 / 0.94 30 / 0.94 5 / 0.99 30 / 0.99

NR NR 11 / 0.96 30 / 0.96 NR NR NR 29 / 0.94 NR 29 / 0.99

NR NR 8 / 0.95 30 / 0.95 NR NR NR 28 / 0.93 NR 28 / 0.99

226-250
NR NR 5 / 0.95 30 / 0.95 NR NR NR 27 / 0.92 NR 27 / 0.98
< 25

26-50

45

34

8 / 0.99 15 / 0.98 23 / 0.96 24 / 0.95 20 / 0.93 17 / 0.92 14 / 0.91

NR

NR

NR

23

17

8 / 0.99 15 / 0.98 23 / 0.96 30 / 0.95 30 / 0.93 30 / 0.92 30 / 0.91

NR

NR

NR

45

34

8 / 1.00 15 / 0.99 23 / 0.99 24 / 0.98 20 / 0.97 17 / 0.97 14 / 0.96 11 / 0.96

8 / 0.95

5 / 0.95

23

17

8 / 1.00 15 / 0.99 23 / 0.99 30 / 0.98 30 / 0.97 30 / 0.97 30 / 0.96 30 / 0.96 30 / 0.95 30 / 0.95

24

0

8 / 0.99 15 / 0.97 23 / 0.94 19 / 0.92 14 / 0.90

NR

NR

NR

NR

NR

12

0

8 / 0.99 15 / 0.97 23 / 0.94 30 / 0.92 30 / 0.90

NR

NR

NR

NR

NR

24

0

8 / 1.00 15 / 0.99 23 / 0.98 19 / 0.97 14 / 0.96 10 / 0.95 5 / 0.94

NR

NR

NR

12

0

8 / 1.00 15 / 0.99 23 / 0.98 30 / 0.97 30 /0.96 30 / 0.95 30 / 0.94 29 / 0.94 28 / 0.93 27 / 0.92

24

0

8 / 1.01 15 / 1.01 23 / 1.00 19 / 1.00 14 / 0.99 10 / 0.99 5 / 0.99

NR

NR

NR

12

0

8 / 1.01 15 / 1.01 23 / 1.00 30 / 1.00 30 / 0.99 30 / 0.99 30 / 0.99 29 / 0.99 28 / 0.99 27 / 0.98

Refrigerant Line Size Information RA14AZ
13

Performance Data RA14AZ

Performance Data @ AHRI Standard Conditions ­ Cooling

Designated Tested Combination (DTC)

Outdoor Unit

Indoor Coil

Total Capacity BTU/H [kW]

Net Sensible BTU/H [kW]

Net Latent BTU/H [kW]

SEER2

EER2 Indoor CFM [L/s]

RA14AZ18AJ1

RCFZ2417STAN

17100 [5.0]

13100 [3.8]

4000 [1.2]

14.3

11.7

600 [283.2]

RA14AZ24AJ1

RCFZ2417STAN

22800 [6.7]

17000 [5.0]

5800 [1.7]

14.3

11.7

735 [346.9]

RA14AZ30AJ1

RCFZ3617STAN

28600 [8.4]

20800 [6.1]

7800 [2.3]

14.3

11.7

910 [429.5]

RA14AZ36AJ1

RCFZ3617STAN

34200 [10.0]

25000 [7.3]

9200 [2.7]

14.3

11.7

1030 [486.1]

RA14AZ42AJ1

RCFZ4821STAN

39500 [11.6]

28500 [8.4]

11000 [3.2]

14.3

11.7

1295 [611.2]

RA14AZ48AJ1

RCFZ4821STAN

46000 [13.5]

32500 [9.5]

13500 [4.0]

13.8

11.2

1420 [670.2]

RA14AZ60AJ1

RCFZ6024STAN

55500 [16.3]

39500 [11.6]

16000 [4.7]

13.8

11.2

1595 [752.8]

NOTE: This data includes DTC (Designated Test Combination) ratings and is for reference purposes only. A full listing of official ratings and system match-ups, along with downloadable certificates, can be accessed from the AHRI website: www.ahridirectory.org.

[ ] Designates Metric Conversions
17100 [5.0] 22800 [6.7] 28600 [8.4] 34200 [10.0] 39500 [11.6] 46000 [13.5] 55500 [16.3]

13100 [3.8] 17000 [5.0] 20800 [6.1] 25000 [7.3] 28500 [8.4] 32500 [9.5] 39500 [11.6]

4000 [1.2] 5800 [1.7] 7800 [2.3] 9200 [2.7] 11000 [3.2] 13500 [4.0] 16000 [4.7]

14.3

11.7

600 [283.2]

14.3

11.7

735 [346.9]

14.3

11.7

910 [429.5]

14.3

11.7

1030 [486.1]

14.3

11.7

1295 [611.2]

13.8

11.2

1420 [670.2]

13.8

11.2

1595 [752.8]

14

Notes RA14AZ
15

GENERAL TERMS OF LIMITED WARRANTY*
Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.
*For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.

Conditional Parts (Registration Required)..................................Ten (10)Years

In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.

Rheem Heating, Cooling & Water Heating · 5600 Old Greenwood Road Fort Smith, Arkansas 72908 · www.rheem.com

Rheem Canada Ltd./Ltée · 125 Edgeware Road, Unit 1 Brampton, Ontario · L6Y 0P5

PRINTED IN U.S.A. 3/22 QG FORM NO. A11-337


Adobe InDesign 16.4 (Macintosh) Adobe PDF Library 16.0