Brand: MEAN WELL
The HRP-600N3 series is a 600W single output AC/DC ultra-high peak power supply. This series operates at 85~264VAC input voltage and offers models with DC outputs commonly demanded by industry. Each model is cooled by a built-in fan with ON-OFF control, suitable for temperatures up to 70°C. The HRP-600N3 can provide 350% short-duration peak power for motor applications and electromechanical loads requiring significantly higher power during start-up.
Example: HRP-600N3-24
Parameter | HRP-600N3-12 | HRP-600N3-24 | HRP-600N3-36 | HRP-600N3-48 |
---|---|---|---|---|
DC VOLTAGE | 12V | 24V | 36V | 48V |
RATED CURRENT | 53A | 27A | 17.5A | 13A |
CURRENT RANGE | 0~53A | 0~27A | 0~17.5A | 0~13A |
RATED POWER | 636W | 648W | 630W | 624W |
RIPPLE & NOISE (max.) Note.2 | 200mVp-p | 150mVp-p | 200mVp-p | 240mVp-p |
VOLTAGE ADJ. RANGE | 10.2~13.8V | 21.6~28.8V | 28.8~39.6V | 40.8~55.2V |
VOLTAGE TOLERANCE Note.3 | ±1.0% | ±1.0% | ±1.0% | ±1.0% |
LINE REGULATION | ±0.3% | ±0.2% | ±0.2% | ±0.2% |
LOAD REGULATION | ±0.5% | ±0.5% | ±0.5% | ±0.5% |
SETUP, RISE TIME | 1800ms, 50ms/230VAC | 3600ms, 50ms/115VAC at full load | 16ms/230VAC | 16ms/115VAC at full load |
HOLD UP TIME (Typ.) | 16ms/230VAC | 1800ms, 50ms/230VAC | 3600ms, 50ms/115VAC at full load | 16ms/115VAC at full load |
VOLTAGE RANGE Note.4 | 85~264VAC | 120~370VDC | ||
FREQUENCY RANGE | 47~63Hz | |||
POWER FACTOR (Typ.) | PF>0.94/230VAC | PF>0.98/115VAC at full load | ||
EFFICIENCY (Typ.) | 88% | 88% | 89% | 89% |
AC CURRENT (Typ.) | 7.6A/115VAC 3.6A/230VAC | |||
INRUSH CURRENT (Typ.) | 35A/115VAC 70A/230VAC | |||
LEAKAGE CURRENT | <2mA/240VAC | |||
OVERLOAD PROTECTION | Output power >105% rated for more than 5 seconds then shut down o/p voltage, re-power on to recover. Constant current limiting for output power >380% rated for more than 5 seconds and then shut down o/p voltage, re-power on to recover. | |||
OVER VOLTAGE | 14.4~16.8V | 30~34.8V | 41.4~48.6V | 57.6~67.2V |
OVER TEMPERATURE | Shut down o/p voltage, recovers automatically after temperature goes down | |||
DC OK SIGNAL | PSU turn on: 3.3~5.6V; PSU turn off: 0~1V | |||
FAN CONTROL (Typ.) | Load 35±15% or RTH2≥50°C Fan on | |||
WORKING TEMP. | -40~+70°C (Refer to "Derating Curve") | |||
WORKING HUMIDITY | 20~90% RH non-condensing | |||
STORAGE TEMP., HUMIDITY | -40~+85°C, 10~95% RH non-condensing | |||
TEMP. COEFFICIENT | ±0.03%/ °C (0~50°C) | |||
VIBRATION | 10~500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes | |||
OPERATING ALTITUDE Note.5 | 5000 meters | |||
SAFETY STANDARDS | UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004, AS/NZS 62368.1 approved | |||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | |||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25°C/70% RH | |||
EMC EMISSION (Parameter) | Standard | Test Level / Note | ||
Conducted | BS EN/EN55032 | Class B | ||
Radiated | BS EN/EN55032 | Class B | ||
Harmonic current | BS EN/EN61000-3-2 | Class A | ||
Voltage Flicker | BS EN/EN61000-3-3 | - | ||
EMC IMMUNITY (Parameter) | Standard | Test Level / Note | ||
ESD | BS EN/EN61000-4-2 | Level 3, 8KV air; Level 2, 4KV contact | ||
RF field | BS EN/EN61000-4-3 | Level 3, 10V/m | ||
EFT/Burst | BS EN/EN61000-4-4 | Level 3, 2KV | ||
Surge | BS EN/EN61000-4-5 | Level 4, 4KV/Line-FG; 2KV/Line-Line | ||
Conducted | BS EN/EN61000-4-6 | Level 3, 10V | ||
Magnetic Field | BS EN/EN61000-4-8 | Level 4, 30A/m | ||
Voltage Dips and Interruptions | BS EN/EN61000-4-11 | 95% dip 0.5 periods, 30% dip 25 periods, 95% interruptions 250 periods | ||
MTBF | 1380.2K hrs min. Telcordia TR/SR-332 (Bellcore); 191.8K hrs min. MIL-HDBK-217F (25°C) | |||
DIMENSION | 218*105*61.5mm (L*W*H) | |||
PACKING | 1.39Kg; 8pcs/12.1Kg/1.58CUFT |
The power supply supports peak power operation, allowing for higher output power for short durations. The average output power (Pav) is calculated using the formula: Pav = (Ppk * t + Pnpk * (T - t)) / T
, where Ppk is peak output power, Pnpk is non-peak output power, t is peak power width, and T is the period. The duty cycle (Duty = t / T * 100%
) must be less than or equal to 35%.
A graph illustrates the relationship between Duty (%) and Peak Output Power (W) for 12V models and 24V/36V/48V models, showing derating at higher peak power levels and different input voltages (100Vac, 200Vac).
Example (24V model):
Given Vin = 200V, Duty_max = 25%, Rated Power (Pav) = 648W, Peak Power (Ppk) = 1500W.
The peak power width (t) must be ≤ 5 seconds, and the period (T) must be ≥ 20 seconds (calculated as t / Duty_max = 5s / 25% = 20s).
The non-peak output power (Pnpk) is calculated as: Pnpk = (Pav * T - Ppk * t) / (T - t)
. For this example, Pnpk ≤ 364W.
The remote sensing feature compensates for voltage drops that occur in the load wiring, up to 0.5V. This ensures more stable voltage delivery to the load. The sensing connections (+S and -S) should be made directly at the load terminals and use twisted pair wiring for accuracy.
Diagram shows the +S and -S pins (CN100 Pin 3 and Pin 4) connected to the load, with sense lines twisted.
The DC-OK signal is a TTL level signal that indicates the status of the power supply. It is HIGH (3.3V ~ 5.6V) when the PSU is turned ON and LOW (0V ~ 1V) when the PSU is turned OFF.
Diagram shows the DC-OK signal pin (CN100 Pin 1) and GND pin (CN100 Pin 2) for monitoring PSU status.
The block diagram illustrates the power conversion process. It starts with AC input (I/P) passing through an EMI filter. This is followed by an active inrush current limiter, rectifiers and PFC (Power Factor Correction) circuit, and then the main power switching stage. The output stage includes rectifiers and filters, with a detection circuit monitoring Overload Protection (OLP), Over Voltage Protection (OVP), and Over Temperature Protection (OTP). Control signals from PFC Control and PWM Control manage the switching. The output provides DC voltage (+V, -V) and includes sensing terminals (+S, -S) and a DC OK signal. The PWM frequency is 80KHz. Frame Ground (FG) is also indicated.
This graph shows the relationship between ambient temperature (°C) on the x-axis and load percentage (%) on the y-axis. It indicates that the power supply can operate at 100% load up to a certain temperature (around 50°C), after which derating is required. The curve shows a linear decrease in allowable load as temperature increases towards 70°C. A note indicates "Normal load only" up to 50°C.
This graph plots Input Voltage (V) on the x-axis against Load percentage (%) on the y-axis. It shows that the power supply can operate at full load (100%) across a wide input voltage range (85V to 264V). As the input voltage decreases towards 85V, the allowable output load may need to be derated slightly, as indicated by the curve.
The power supply has a compact enclosure with dimensions of 218mm (Length) x 105mm (Width) x 61.5mm (Height).
Air Flow Direction: Indicated as flowing from the front (I/P) to the back (O/P).
Mounting: Features mounting holes for M4 screws (L=6mm for output side, L=4mm for both sides).
Pin No. | Assignment |
---|---|
1 | AC/L |
2 | AC/N |
3 | FG [Frame Ground] |
Pin No. | Assignment |
---|---|
1~2 | -V |
3~4 | +V |
Connector Type: HRS DF11-4DP-2DS or equivalent
Pin No. | Assignment | Terminal |
---|---|---|
1 | DC-OK | [DC OK Signal] |
2 | GND | [Ground] |
3 | +S | [Sense +] |
4 | -S | [Sense -] |
Diagrams show the physical layout of the unit, including input/output terminals, connector CN100, and an SVR1 (Voltage Adjustment) potentiometer.
The HRP-600N3 series complies with the following safety standards: UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004, AS/NZS 62368.1.
Input to Output, Input to FG, Output to FG: 100M Ohms / 500VDC / 25°C / 70% RH.
Parameter | Standard | Test Level / Note |
---|---|---|
Conducted | BS EN/EN55032 | Class B |
Radiated | BS EN/EN55032 | Class B |
Harmonic current | BS EN/EN61000-3-2 | Class A |
Voltage Flicker | BS EN/EN61000-3-3 | - |
Parameter | Standard | Test Level / Note |
---|---|---|
ESD | BS EN/EN61000-4-2 | Level 3, 8KV air; Level 2, 4KV contact |
RF field | BS EN/EN61000-4-3 | Level 3, 10V/m |
EFT/Burst | BS EN/EN61000-4-4 | Level 3, 2KV |
Surge | BS EN/EN61000-4-5 | Level 4, 4KV/Line-FG; 2KV/Line-Line |
Conducted | BS EN/EN61000-4-6 | Level 3, 10V |
Magnetic Field | BS EN/EN61000-4-8 | Level 4, 30A/m |
Voltage Dips and Interruptions | BS EN/EN61000-4-11 | 95% dip 0.5 periods, 30% dip 25 periods, 95% interruptions 250 periods |
Note 6: The power supply is considered a component for installation into final equipment. EMC tests were performed on a 360mm*360mm metal plate. The final equipment must be re-confirmed for EMC compliance.
Mean Time Between Failures (MTBF):
For detailed installation instructions, please refer to the official manual:
File Info : application/pdf, 6 Pages, 722.60KB
DocumentDocument![]() |
MEAN WELL HRP-150N Series: 150W Single Output AC/DC Power Supply with PFC Explore the MEAN WELL HRP-150N series, a 150W single output AC/DC power supply featuring a full-range universal input, active PFC, high efficiency, and 250% peak power capability for demanding industrial applications. Learn about features, specifications, and applications. |
![]() |
MEAN WELL Industrial Power Supply Catalog - Comprehensive Product Guide Explore the extensive MEAN WELL Industrial Power Supply Catalog, featuring a wide range of standard switching power supplies, AC/DC converters, adapters, and more. Find detailed specifications, model numbers, and features for industrial, medical, and specialized applications. |
![]() |
MEAN WELL Power Supply Catalog - Standard Switching Power Supplies Comprehensive catalog of MEAN WELL's reliable power solutions, including AC/DC enclosed power supplies, external adapters, DC/DC converters, DC/AC inverters, and more. Featuring detailed specifications and product information. |
![]() |
MEAN WELL Power Supplies Catalog - August 2020 Explore the comprehensive MEAN WELL Power Supplies Catalog for August 2020. This catalog details a wide range of AC/DC and DC/DC power supplies, including industrial, medical, DIN rail, open frame, and adaptor series, with detailed specifications and model information. |
![]() |
MEAN WELL RST-5000 Series 5000W Single Output Power Supply Discover the MEAN WELL RST-5000 series, a high-performance 5000W single output enclosed AC/DC power supply. Ideal for industrial automation, test equipment, and electric vehicles, it offers wide input range, high efficiency, and advanced control features. |
![]() |
MEAN WELL HRPG-1000N3 Series: 1000W Ultra-High Peak Power Supply Datasheet Detailed specifications, features, applications, and functional descriptions for the MEAN WELL HRPG-1000N3 series of 1000W ultra-high peak power supplies. Includes technical data, block diagrams, and connection details for industrial applications. |
![]() |
MEAN WELL LRS-600N2 Series 600W Single Output Power Supply Specifications Explore the MEAN WELL LRS-600N2 series, a 600W single-output enclosed power supply. This document details specifications, features, applications, and model encoding for industrial automation, control systems, and electronic equipment. |
![]() |
MEAN WELL RSP-1000 Series 1000W Single Output Power Supply Datasheet Comprehensive datasheet for the MEAN WELL RSP-1000 series 1000W single output AC/DC power supplies. Details include electrical specifications, features like active PFC and current sharing, applications in industrial automation, functional manual for remote control and voltage programming, mechanical dimensions, and safety certifications. Optimized for search engines. |