Neptronic Pressurized Condensate Return System (PCR)
For use with SKD Direct Steam Injection Humidifiers
Installation Instructions and User Manual
READ AND SAVE THESE INSTRUCTIONS
Document Reference: PCR Manual-250908-R2-ESL
Foreword and Safety Instructions
Neptronic Company Overview
Founded in 1976, Neptronic is a private corporation that designs, manufactures, and distributes products for the HVAC industry. Their product line includes intelligent controllers, electronic actuators, actuated valves, humidifiers, and electric heaters.
Products are designed and manufactured by over 250 dedicated employees in a 7,500 m² (80,000 ft²) state-of-the-art facility in Montreal, Canada. Utilizing a vertical integration model, the entire manufacturing chain is under one roof, from software and hardware development to SMT circuit board assembly, sheet metal fabrication, and product testing, ensuring products are engineered to last.
Neptronic holds several national and international patents and, with a continued commitment to research and development, provides innovative products and technologies for the HVAC industry. Exporting over 85% of sales, they have an exclusive distribution network globally.
About the Manual
These installation and operation instructions are developed to facilitate the installation of the Pressurized Condensate Return System.
- Strict application of these instructions ensures conformity of installation and operation per manufacturer's recommendations.
- Application of these instructions is a condition for warranty application.
- Application of these instructions does not ensure conformity to procedures, regulations, or local codes regarding electrical installation and connection to local water supply.
© 2025: All rights reserved. This document cannot be reproduced totally or partially by any means without prior written authorization of Neptronic.
Electricity
⚠️ All work concerned with electrical installation MUST only be performed by skilled and qualified technical personnel such as an electrician or a technician with appropriate training. The customer is always responsible for ensuring the suitability of the technical personnel.
Please observe the local regulations concerning the provision of electrical installations.
Correct Use
Neptronic systems and products are designed only for humidification use. Any other application is not considered appropriate for the intended purpose. The manufacturer cannot be made liable for any damage resulting from incorrect use.
General Warranty
This product is subject to the terms and conditions described at http://www.neptronic.com/Sales-Conditions.aspx.
Overview
Product Description
The objective of the Neptronic patent-pending pressurized condensate return (PCR) system is to return condensate generated within the steam dispersion tubes of a direct steam humidifier back to the boiler for the following reasons:
- Eliminate the need for a drain
- Reuse condensate and avoid waste
- Increase energy efficiency
By design, the PCR system eliminates the need for a heat exchanger, making inspections and de-scaling work unnecessary. It requires no specific maintenance regimen as it is an empty vessel.
With the PCR system, no maintenance means no downtime. All critical components are externally located and easily accessible. Critical functions are monitored and controlled in real-time by the independent PCR Electronic Controller. The controller can be stand-alone or integrated into a Building Automation System via BACnet MS/TP or Modbus.
PCR Means Maintenance Free
- Real-time status and monitoring.
- No systematic verification required.
- No de-scaling required.
- No downtime.
- No flooding of header.
This innovative, patent-pending Neptronic technology simplifies installation, provides maintenance-free and energy-efficient operation, and enables system monitoring for direct steam applications.
Principle of Operation
- The header's integrated slope forces accumulated condensate to the drain port (1), which then flows into the PCR tank (2).
- When the tank level setpoint is attained, the ESC controller opens the Steam supply valve (3) to empty the PCR tank (2) into the Condensate return (5) system.
- The check valve (4) prevents steam pressure from reversing into the header.
- The ESC controller continues to monitor the tank's condensate level and temperature.
- When the PCR tank (2) is empty, the ESC controller closes the Steam supply valve (3) and opens the Relief valve (6) to partially relieve pressure in the PCR tank (2) and allow the flow of condensate from the header to the PCR tank(2).
- With the Relief valve (6) open, the check valve (7) prevents backflow from the Condensate return (5) to the PCR tank (2).
Specifications
Handling and Lifting
⚠️ The Pressurized Condensate Return System MUST always be handled and lifted with care and must remain in its original packaging for as long as possible prior to installation.
Unpacking
The Pressurized Condensate Return System is shipped inside carton boxes or in a wooden crate. Remove packing and skids prior to commissioning.
Equipment Included
Component | Details |
---|---|
PCR tank | Material: 304 stainless steel Ports: 4 NPT 1/2" (DN15) ports for condensate inlet, condensate outlet, steam supply and steam relief Mounting holes: 4 mounting holes with diameter of 3/8" (10mm) |
Check valves | Condensate inlet: Swing check valve with open delta P of 0.5 PSI (3.5 kPa), NPT 1/2" (DN15) Condensate outlet: Spring inline check valve with open delta P of 2 PSI (13.8 kPa), NPT 1/2" (DN15) |
Actuated valves | Steam supply: Neptronic BM000F actuator with ball valve Steam relief: Neptronic VT000 linear actuator with zone valve |
Dimensions
PCR Capacity
The PCR capacity is obtained based on the system differential pressure (ΔP), which is defined as:
ΔP = Psupply – Precovery
Psupply: Steam supply pressure to the humidifier. Steam supply pressure may decrease after opening steam supply valve. Size piping and pressure relief valve accordingly.
❗ Important: Ensure that the steam supply pressure does not exceed 15 psi (103 kPa).
Precovery: Pressure from condensate recovery system. For vented systems, this pressure is equivalent to 1 psi (7 kPa) for every 27” (686mm) of condensate rise. It is not recommended to connect the PCR and steam trap outlets together. Additional design considerations must be taken into account for pressurized returns.
Once the system differential pressure (ΔP) is obtained, the PCR capacity can be obtained using the following table:
ΔP (psi) [kPa] | Condensate Capacity (lb/hr) [kg/hr] |
---|---|
6 to 14 [41 to 97] | 100 [45] |
5 [34] | 90 [41] |
4 [28] | 75 [34] |
❗ Important: It is not recommended to connect the PCR system to the condensate return line if the differential pressure (ΔP) is below 4 psi (28 kPa).
Installation Overview
⚠️ All installation work must comply with local regulations.
⚠️ All work related to the installation of the Pressurized Condensate Return System MUST only be performed by skilled and qualified technical personnel such as plumbers or technicians with appropriate training. The customer is responsible for ensuring their suitability.
For the installation of the Pressurized Condensate Return System and associated components, there are no specific tooling requirements.
Installation Method Statement
The installation involves the following steps:
- Step 1 - Install SKD Humidifier
- Step 2 - Secure PCR Tank
- Step 3 - Connect PCR Tank to Drain Port
- Step 4 - Install Steam Relief Valve (VT000)
- Step 5 - Install Steam Supply Valve (BM000F)
- Step 6 - Connect PCR Tank to Condensate Return
- Step 7 - Strainer Installation
Step 1 - Install SKD Humidifier
Install the PCR tank and related peripherals after the SKD humidifier's standard elements are installed. Please follow the supplied Multi-Steam Series or Jacketed Series instructions to install the:
- Steam distribution system
- Steam control valve
- Steam separator
- Temperature sensor
- Steam traps
Step 2 – Secure PCR Tank
Select the location and secure the PCR tank to the ground using the four mounting holes on the mounting bracket under the PCR tank. Ensure that there is a distance of at least 6" (152mm) between the bottom of the header and the bottom of the PCR tank.
Step 3 – Connect PCR Tank to Drain Port
Connect the provided swing check valve to the condensate inlet port of the PCR tank. Orient the check valve vertically and levelled so that the head is pointing in the up direction. Connect the NPT 1/2" (DN15) piping between the PCR tank's inlet port and the steam distribution system's drain port. Ensure to respect the minimum distance between the bottom of the PCR tank and the top of the header as detailed in Step 2.
Step 4 – Install the Steam Relief Valve
Install the provided steam relief valve (VT000 actuator with a normally open globe valve) between the relief valve ports of the header and the PCR tank as shown below. Set the "Rotation Direction" DIP switch to "Valve normally open".
1) Rotation Direction Settings:
- OFF (Valve normally closed): Red wire = Close (up), White wire = Open (down)
- ON (Valve normally open): Red wire = Close (down), White wire = Open (up)
For more details concerning installation of the actuator and valve, please refer to the instruction manual provided with the product.
Step 5 – Install the Steam Supply Valve
Install the provided steam supply valve (BM000F actuator with a NPT 1/2" (DN15) ball valve) between the tee and the supply valve port of the PCR tank as shown below. Ensure the actuator is in the fail-safe close position. Set the DIP switches as follows:
- Rotation: CW
- Fail safe return: at 0°
- PWM mode: 25 sec.
❗ Important: The valve must be installed as close as possible to the PCR tank on the vertical piping line at a maximum of 8" (203mm) from the PCR tank.
❗ Important: Ensure that the steam supply pressure does not exceed 15 psi (103 kPa).
Positioning the PCR Steam Control Valve
Install the actuated valve between 20 to 30 degrees from vertical in order to reduce the convection heat to the actuator.
For more details concerning installation of the actuator and valve, please refer to the instruction manual provided with the product.
Step 6 – Connect PCR tank to Condensate Return
Connect the provided spring inline check valve to the condensate outlet port of the PCR tank. Orient the check valve vertically and levelled so that the head is pointing in the up direction. Then connect the NPT 1/2" (DN15) piping between the PCR tank's outlet port and the condensate return line.
Step 7 – Strainer Installation
Install the strainer within six linear feet (1.83 linear meters) from the steam separator, reducing the pipe length for the strainer and the first Pressurized Condensate Return System component.
Electronic Steam Controller (SKDESC)
Models
- SKDESC-MP
- SKDESC-MBP with BACnet Communication
- SKDESC-MDP with Modbus Communication
Description
The Electronic Steam Controller SKDESC is made specifically for Neptronic SKD-M (Multi-Steam) Humidifiers.
Features
- Conserves energy and eliminates condensate (dry operation)
- Manages isolating and modulating valves
- Pre-heats tube channel jackets only on demand for humidity
- Automatic temperature sensor adjustment
- On/Off or Modulating control
- Selectable internal or external control
- Configurable proportional control band & dead band
- Selectable Fahrenheit or Celsius scale
- BACnet or Modbus models available
- 24 Vac power supply (by others)
- Easy start up and troubleshooting
- Backlit LCD with simple icon and text driven menus
Technical Specifications
Description | SKDESC-MP | SKDESC-MBP | SKDESC-MDP |
---|---|---|---|
Power Supply | 24 Vac | ||
Power Consumption | 50 VA | ||
Relay Output | 2 relay | ||
Relay Rating | 125 Vac, resistive load 10 amps | ||
Communication | BACnet | Modbus | |
Operating Temperature | 32°F to 122°F (0°C to 50°C) | ||
Storage Temperature | -22°F to 122°F (-30°C to 50°C) | ||
Relative Humidity | 5 to 95% non-condensing | ||
Weight | 1.4 lb. (635 g) | ||
Dimensions |
A = 6.3" | 160mm B = 5" | 126mm C = 2.25" | 57mm |
Wiring
Neptronic strongly recommends that all Neptronic products be wired to a separate grounded transformer and that transformer shall service only Neptronic products. This precaution will prevent interference with, and/or possible damage to incompatible equipment.
Terminal Block Usage
Step | Description | Terminal Block | Pin |
---|---|---|---|
Step 6, "Control Mode" = extern | Used for external control signal | TB9 | Pin 1 |
Step 6, "Control Mode” = intern and Step 11, “Extern Humidty Setpnt" = on | Used for external setpoint signal | TB1 | Pin 4 |
Step 18, "Duct High limit sensor" = digital | Used for connecting high limit sensor (Digital) | TB10 | Pin 1 |
Step 18, “Duct High limit sensor" = analog | Used for connecting high limit sensor (Analog) |
Symbols Used in this Manual
- Humidity: ?
- Temperature: ?️
- Communication/Network: ?
- Air Flow: ?
- Timer/Clock: ⏰
Configuration Options
General Settings
-
"WORKING CAPACIT IN PCT"
Default: 100%
Range: 10 to 100%
Increment: 5%This option enables adjustment of the maximum demand capacity of the full system capacity in %. This is a factory setting; consult Neptronic before changing.
-
"SEPARAT TEMPER OFFSET"
Default: 0
Range: -10 to 10°C [-18 to 18°F]
Increment: 0.1°C [0.1°F]Compare displayed temperature with a known value. Use arrow buttons to offset or calibrate the sensor.
-
"PCR TEMPER OFFSET"
Default: 0
Range: -10 to 10°C [-18 to 18°F]
Increment: 0.1°C [0.1°F]Compare the displayed temperature of the sensor in the PCR tank with a known value. Use arrow buttons to offset or calibrate the sensor.
Control Modes
-
"CONTROL MODE"
Default: Extern
Range: Intern, Extern, NetSelect the desired control mode:
- Intern: Humidifier controlled by the SKDESC controller.
- Extern: Humidifier controlled by an external signal (AI, DI).
- Net: Humidifier controlled over the network (SKDESC-MBP and SKDESC-MDP models only).
-
"DEMAND SIGNAL RANGE"
Default: 2-10 Vdc
Range: 0-10 Vdc, 2-10 VdcAppears only if "Extern" is selected. Select the desired relative humidity sensor signal at input AI1.
-
"NETWORK ROOM HUMIDTY”
Default: OFF
Range: OFF, ONAvailable only on SKDESC-MBP and SKDESC-MDP models. Select ON to control humidity over the network.
-
"ROOM HUMIDTY OFFSET IN PCT"
Default: 0% RH
Range: -10 to 10% RH
Increment: 0.1% RHAppears only if "Network room Humidity" is OFF. Compare displayed humidity with a known value to offset or calibrate the sensor.
-
"ROOM HUMIDTY SIGNAL RANGE"
Default: 2-10 Vdc
Range: 0-10 Vdc, 2-10 VdcAppears only if "Network room Humidity" is OFF. Select the desired signal range.
-
"EXTERN HUMIDTY SETPNT”
Default: OFF
Range: OFF, ONAppears only if "Net" or "Intern" is selected. Select ON to use an external setpoint for humidity.
-
"SETPNT SIGNAL RANGE"
Default: 2-10 Vdc
Range: 0-10 Vdc, 2-10 VdcAppears only if "Net" or "Intern" is selected and "Extern Humidity Setpoint" is ON. Select the desired relative humidity sensor signal.
-
"INTERN HUMIDTY SETPNT IN PCT"
Default: 40% RH
Range: 10% to 90% RH
Increment: 1% RHAppears only if "Net" or "Intern" is selected and "Extern Humidity Setpoint" is OFF. Set the desired humidity setpoint in % RH.
-
"CONTROL DEAD BAND IN PCT"
Default: 2.0% RH
Range: 0% to 5% RH
Increment: 0.1% RHAppears only if "Intern" is selected. The deadband is the interval where no action occurs to prevent repeated activation-deactivation cycles.
-
"CONTROL PROP RAMP IN PCT"
Default: 5.0%
Range: 1% to 10%
Increment: 0.1%Appears only if "Intern" is selected. Proportional control applies effort based on proximity to setpoint. Example: 100% demand at start of ramp, decreasing as setpoint is approached.
-
"CONTROL INTEGRA TIME IN SEC"
Default: 0 seconds
Range: 0 to 600 sec
Increment: 1 secAppears only if "Intern" is selected. Set the integral time for the humidity ramp. Cumulates difference between setpoint and actual reading for additional push.
-
"CONTROL DERIVAT TIME IN SEC"
Default: 0 seconds
Range: 0 to 25.5 sec
Increment: 0.1 secAppears only if "Intern" is selected. Set the derivative time for the humidity ramp. Dampens or predicts control effort to minimize overshoot.
Duct High Limit Sensor Settings
-
"DUCT HIGH LIMIT SENSOR"
Default: Digital (On/Off)
Range: Disable, Analog, Digital (On/Off), NetworkAppears only if "Intern" is selected. Select the desired type of high limit sensor. Analog option refers to AI3 input.
-
"DUCT MIN SETPNT IN PCT"
Default: 15% RH
Range: 0 to MAX SETPNT
Increment: 1% RHAppears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the minimum duct humidity setpoint.
-
"DUCT MAX SETPNT IN PCT"
Default: 65% RH
Range: MIN SETPNT to 100% RH
Increment: 1% RHAppears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the maximum duct humidity setpoint.
-
"DUCT PROP RAMP IN PCT"
Default: 5.0%
Range: 1% to 10%
Increment: 0.1%Appears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the proportional ramp for control.
-
"DUCT INTEGRA TIME IN SEC"
Default: 0 seconds
Range: 0 to 600 sec
Increment: 0.1Appears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the integral time for the humidity ramp.
-
"DUCT DERIVAT TIME IN SEC"
Default: 0 seconds
Range: 0 to 25.5 sec
Increment: 0.1 secAppears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the derivative time for the humidity ramp.
-
"HIGH LIMIT SETPNT IN PCT"
Default: 80% RH
Range: 10% to 90% RH
Increment: 1% RHAppears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the high limit relative humidity setpoint.
-
"HIGH LIMIT PROP RAMP IN PCT"
Default: 10.0 %
Range: 0% to 20%
Increment: 0.1%Appears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the high limit proportional ramp.
-
"HIGH LIMIT HUMIDTY OFFSET IN PCT"
Default: 0% RH
Range: -10% RH to 10% RH
Increment: 0.1% RHAppears only if "Analog" is selected for Duct High Limit Sensor. Adjusts the relative humidity reading of the high limit sensor.
-
"HIGH LIMIT SIGNAL RANGE"
Default: 2-10 Vdc
Range: 0-10 Vdc, 2-10 VdcAppears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Selects the high limit signal range.
-
"HIGH LIMIT MAX DEMAND IN PCT"
Default: No default (information display only)
Appears only if the Duct High Limit Sensor type is not disabled. Displays the actual reading of the high limit sensor.
Service and Delay Settings
-
"END OF SEASON DELAY IN HR"
Default: 100 hours
Range: 100 to 250 hours
Increment: 5 hoursIndicates that the isolation valve will be turned off after 100 hours if there is no demand.
-
"SERVICE DELAY IN HR"
Default: 5000 hours
Range: 1000 to 5000 hours
Increment: 500 hoursSet the number of hours running at 100% capacity before servicing is due.
-
"SERVICE RUNTIME IN HR"
Default: No default (information display only)
Displays the running time in hours at 100% capacity since the last service. To reset, press edit and hold ▲ and ▼ keys.
-
"RUNS WHILE SERVICE ALARM"
Default: ACt (active)
Range: INACT (Inactive), ACt (active)
Select ACt to run even when servicing is due. Select INACt to turn off the system when servicing is due.
-
"TOTAL RUNTIME IN HR"
Default: No default (information display only)
Displays the running time in hours at 100% capacity.
Fallback and Network Settings
-
"PCR FALLBACK"
Default: Off
Range: Off, On
Determines PCR system operation during water level or temperature sensor failure. OFF stops the system; ON allows continued function based on internal timers.
-
"NETWORK AUTO BAUD RATE"
Default: ON
Range: ON, OFFAvailable on SKDESC-MBP and SKDESC-MDP models. Enable or disable Auto Baud Rate detection. If enabled, baud rate is auto-configured. If disabled, select manually (Step 36).
-
"NETWORK BAUD RATE"
Default: No default (information display only)
Range: BACnet: 9.6k, 19.2k, 38.4k, 76.8k; Modbus: 9.6k, 19.2k, 38.4k, 57.6kAvailable on SKDESC-MBP and SKDESC-MDP models. Select baud rate if "Network auto baud rate" is OFF.
-
"NETWORK ADDRESS"
BACnet Default: 0 (Range: 0 to 254)
Modbus Default: 1 (Range: 1 to 246)
Available on SKDESC-MBP and SKDESC-MDP models. Select the desired address.
-
"DEVICE INSTANCE"
Default: 0153001
Range: No, Yes
Select Yes to change the device instance; No modifies it automatically per MAC address.
-
"NETWORK PARITY"
Default: None
Range: None, Odd, EvenAvailable on Modbus models (SKDESC-MDP). Select parity control.
-
"NETWORK STOP BITS"
Default: 1
Range: 1, 2Available on Modbus models (SKDESC-MDP). Select network stop bits.
-
"NETWORK FALLBACK TIMEOUT"
Default: 0 sec
Range: 0 to 900 sec
Increment: 1 secAppears if "Net" is selected for Control Mode. Sets network fallback timeout. Alarm generated if no communication occurs for this period.
-
"NETWORK FALLBACK SETPOINT"
Default: 0.0%
Range: 0% to 100%
Increment: 0.1%Appears if "Net" is selected for Control Mode. Determines humidifier function during network communication failure. Example: 20% means constant 20% demand.
-
"NETWORK FALLBACK COUNTER"
Default: No default (information display only)
Range: 0 to 900 sec
Appears if "Net" is selected for Control Mode. Displays time remaining before fallback alarm.
Signal and Output States
-
"CONTROL OUTPUT SIGNAL IN MV"
Default: No default (information display only)
Displays humidifier steam control valve output in mV.
-
"PCR SUPPLY SIGNAL IN MV"
Default: No default (information display only)
Displays the PCR steam supply valve output in mV.
-
"ISOLAT VALVE OUTPUT STATE"
Default: No default (information display only)
Range: INACT (closed), ACt (open)
Displays whether the isolating valve is open or closed.
-
"PCR RELIEF VALVE OUTPUT STATE"
Default: No default (information display only)
Displays whether the PCR relief valve is open or closed.
-
"ALARM RELAY OUTPUT STATE"
Default: No default (information display only)
Range: INACt (closed), ACt (open)
Displays whether the alarm relay is open or closed.
-
"STEAM ON OUTPUT RELAY OUTPUT STATE"
Default: No default (information display only)
Range: INACt (closed), ACt (open)
Displays whether the steam output relay is open or closed.
-
"SEPARAT TEMPER INPUT SIGNAL IN MV"
Default: No default (information display only)
Displays the separator temperature sensor reading in mV.
-
"DEMAND INPUT SIGNAL IN MV"
Default: No default (information display only)
Appears only if "Extern" is selected for Control Mode. Displays the demand reading in mV.
-
"ROOM HUMIDITY INPUT SIGNAL IN MV"
Default: No default (information display only)
Does not appear if "Network room Humidty" is OFF. Displays the relative humidity reading of the room in mV.
-
"SETPNT INPUT SIGNAL IN MV"
Default: No default (information display only)
Appears only if "Extern Humidty Setpnt" is ON. Displays the setpoint reading in mV.
-
"HIGH LIMIT INPUT SIGNAL IN MV"
Default: No default (information display only)
Appears only if "Analog" is selected for Duct High Limit Sensor. Displays the high limit sensor reading in mV.
-
"WATER LEVEL INPUT SIGNAL IN MV"
Default: No default (information display only)
Displays the reading in mV of the water level sensor inside the PCR tank.
-
"EXTERN DEMAND INPUT STATE"
Default: No default (information display only)
Range: INACt (closed), ACt (open)
Appears only if "Extern" is selected for Control Mode. Displays if the demand is open or closed.
-
"AIR FLOW INPUT STATE"
Default: No default (information display only)
Range: INACt (closed), ACt (open)
Displays if the air flow switch is open or closed.
-
"HIGH LIMIT SWITCH INPUT STATE"
Default: No default (information display only)
Range: INACT (closed), ACt (open)
Appears only if "Digital" is selected for Duct High Limit Sensor. Displays if the high limit switch is open or closed.
-
"INTRLCK INPUT STATE"
Default: No default (information display only)
Range: INACt (closed), ACt (open)
Displays if the interlock is open or closed.
-
"MICRO TEMPER"
Default: No default (information display only)
Displays whether the microcontroller temperature is in °C or °F mode.
-
"PCB TEMPER"
Default: No default (information display only)
Displays whether the PCB temperature is in °C or °F mode.
Alarms and Notifications
The following is a list of alarms and notifications displayed by the Steam Controller under different conditions. The alarm symbol, ⚠️, is displayed along with all alarms and notifications.
Display | Description |
---|---|
no air flow Alarm | Indicates that the air flow sensor is not detected. - control valve is closed - isolating valve is closed |
high limit cutout Alarm | Indicates that the duct humidity has exceeded the high limit level. - control valve is closed - isolating valve is closed - alarm relay is activated |
service warning Alarm | Indicates that the servicing is due in less than 100 hours. Service the unit and reset the unit at Step 31 "SERVICE RUNTIME IN HR" by pressing the arrow keys ▲, ▼ for three seconds. |
service unit Alarm | Indicates that the service is due. This alarm won't stop the system from running unless you've set the option to inact at Step 32 "runs while service alarm". - control valve is closed - isolating valve is closed - alarm relay is activated |
inter lock Alarm | Indicates that the inter lock is activated. - control valve is closed - isolating valve is closed - alarm relay is activated |
flooded separate steam trap Failure | Indicates that either the separator steam trap is flooded or the temperature is too low. - control valve is closed - alarm relay is activated |
separat temper sensor Failure | Indicates that the separator sensor is defective. - control valve is closed - isolating valve is closed - alarm relay is activated |
PCR temper sensor Failure | Indicates that the PCR tank's temperature sensor is defective. - control valve is closed - isolating valve is closed - alarm relay is activated |
room humidity sensor Failure | Indicates that the room humidity sensor has failed. - control valve is closed - isolating valve is closed - alarm relay is activated |
high limit humidity sensor Failure | Indicates that the high limit humidity sensor has failed. - control valve is closed - isolating valve is closed - alarm relay is activated |
PCR Water Level sensor Failure | Indicates that the PCR tank's water level sensor has failed. - control valve is closed - isolating valve is closed - alarm relay is activated |
Initial Verification
⚠️ Any installation work must be carried out by suitably qualified personnel.
Installation
- Ensure that the humidifier is installed properly according to the installation manual.
- Check that steam distributors are properly installed into the ventilation duct.
- Ensure that there is no leakage on the Pressurized Condensate Return System piping.
Electrical
- Confirm that 24Vac is present between tab 1&4 of terminal block TB5 on the SKDESC Steam Controller.
Drain if Required
- If there is a steam trap on the header, confirm that the drain piping is properly connected with a pitch of at least 1¼" (6.5mm) per foot (300mm). There is no header on the single tube channel configuration and therefore there is no steam trap on the header.
Steam Supply
- Ensure that the steam supply is on.
- Ensure that there is no leakage on the steam piping when the steam supply is on.
Controls
- Ensure that a high limit duct humidistat is installed, properly connected to the SKDESC and the setpoint is properly adjusted.
- Verify that the room humidistat or returned air duct humidistat is installed, properly connected to the SKDESC, and the setpoint is properly adjusted.
- Turn on the power at the disconnect switch.
- Confirm the control setup of the humidifier. The humidifier is factory set with EXTERNAL control setup, which means that the humidity demand is controlled by the room or duct humidistat.
- Ensure that the type of signal (0-10 Vdc, 2-10 Vdc or 4-20 mA) of the humidistat corresponds to the type set in the humidifier control set-up.
Start-Up Procedure
Start-up
Proceed to start-up the humidifier as follows:
- Make sure that the steam is supplied to the Pressurized Condensate Return System.
- Switch on the SKDESC.
- Make sure that there is no alarm. If the A6 alarm stays on, it means that the steam does not reach the separator or there is a problem with evacuating the condensate from the separator steam trap.
- Wait for a call for humidity or create it by setting the SKDESC "CONTROL MODE" to Internal (step #6), and the "EXTERN HUMIDTY SETPNT" to OFF (step #11). Then, adjust the setpoint to a higher value than the room humidity reading (operation mode B).
- Once the temperature is high enough, the control valve will open slowly.
- The start-up is complete and the humidifier is now functional.
Safety Test
- Check for steam or condensate leakage while the humidifier is in operation.
- Check the location of the airflow switch in the system and its operation by stopping the fan or by disconnecting the air pressure connection. With no air movement in the duct, SKDESC will automatically stop the humidifier by closing the control valve.
Reset the Setpoint and Control Mode
- If the humidity setpoint is controlled by the SKDESC, reset the setpoint to the desired relative humidity % (set #20) as suits the room.
- If the humidity setpoint is controlled by another device than the SKDESC (typically by the BMS), set the internal control signal to OFF.
End
- The humidifier is ready for normal operation.
Notes