Neptronic Pressurized Condensate Return System (PCR)

For use with SKD Direct Steam Injection Humidifiers

Installation Instructions and User Manual

READ AND SAVE THESE INSTRUCTIONS

Document Reference: PCR Manual-250908-R2-ESL

Foreword and Safety Instructions

Neptronic Company Overview

Founded in 1976, Neptronic is a private corporation that designs, manufactures, and distributes products for the HVAC industry. Their product line includes intelligent controllers, electronic actuators, actuated valves, humidifiers, and electric heaters.

Products are designed and manufactured by over 250 dedicated employees in a 7,500 m² (80,000 ft²) state-of-the-art facility in Montreal, Canada. Utilizing a vertical integration model, the entire manufacturing chain is under one roof, from software and hardware development to SMT circuit board assembly, sheet metal fabrication, and product testing, ensuring products are engineered to last.

Neptronic holds several national and international patents and, with a continued commitment to research and development, provides innovative products and technologies for the HVAC industry. Exporting over 85% of sales, they have an exclusive distribution network globally.

About the Manual

These installation and operation instructions are developed to facilitate the installation of the Pressurized Condensate Return System.

  • Strict application of these instructions ensures conformity of installation and operation per manufacturer's recommendations.
  • Application of these instructions is a condition for warranty application.
  • Application of these instructions does not ensure conformity to procedures, regulations, or local codes regarding electrical installation and connection to local water supply.

© 2025: All rights reserved. This document cannot be reproduced totally or partially by any means without prior written authorization of Neptronic.

Electricity

⚠️ All work concerned with electrical installation MUST only be performed by skilled and qualified technical personnel such as an electrician or a technician with appropriate training. The customer is always responsible for ensuring the suitability of the technical personnel.

Please observe the local regulations concerning the provision of electrical installations.

Correct Use

Neptronic systems and products are designed only for humidification use. Any other application is not considered appropriate for the intended purpose. The manufacturer cannot be made liable for any damage resulting from incorrect use.

General Warranty

This product is subject to the terms and conditions described at http://www.neptronic.com/Sales-Conditions.aspx.

Overview

Product Description

The objective of the Neptronic patent-pending pressurized condensate return (PCR) system is to return condensate generated within the steam dispersion tubes of a direct steam humidifier back to the boiler for the following reasons:

By design, the PCR system eliminates the need for a heat exchanger, making inspections and de-scaling work unnecessary. It requires no specific maintenance regimen as it is an empty vessel.

With the PCR system, no maintenance means no downtime. All critical components are externally located and easily accessible. Critical functions are monitored and controlled in real-time by the independent PCR Electronic Controller. The controller can be stand-alone or integrated into a Building Automation System via BACnet MS/TP or Modbus.

PCR Means Maintenance Free

This innovative, patent-pending Neptronic technology simplifies installation, provides maintenance-free and energy-efficient operation, and enables system monitoring for direct steam applications.

Principle of Operation

Illustration 1 – Principle of Operation: A schematic showing the flow of condensate. Steam from a header flows to a drain port (1), then into a PCR tank (2). An ESC controller manages a steam supply valve (3) to empty the PCR tank into the condensate return (5). A check valve (4) prevents backflow to the header, and another check valve (7) prevents backflow from the condensate return to the PCR tank. A relief valve (6) is also present. The ESC controller is shown with its components.

Specifications

Handling and Lifting

⚠️ The Pressurized Condensate Return System MUST always be handled and lifted with care and must remain in its original packaging for as long as possible prior to installation.

Unpacking

The Pressurized Condensate Return System is shipped inside carton boxes or in a wooden crate. Remove packing and skids prior to commissioning.

Equipment Included

Component Details
PCR tank Material: 304 stainless steel
Ports: 4 NPT 1/2" (DN15) ports for condensate inlet, condensate outlet, steam supply and steam relief
Mounting holes: 4 mounting holes with diameter of 3/8" (10mm)
Check valves Condensate inlet: Swing check valve with open delta P of 0.5 PSI (3.5 kPa), NPT 1/2" (DN15)
Condensate outlet: Spring inline check valve with open delta P of 2 PSI (13.8 kPa), NPT 1/2" (DN15)
Actuated valves Steam supply: Neptronic BM000F actuator with ball valve
Steam relief: Neptronic VT000 linear actuator with zone valve

Dimensions

Illustration 2 - PCR50 Dimensions: Technical drawings showing the top, side, and front views of the PCR tank with dimensions labeled in inches and millimeters. Includes port locations and mounting hole details. The main tank body is approximately 13.76" (349mm) high, with a width of 10.1" (258mm) and depth of 13.5" (343mm). Ports are 1/2" NPT, and mounting holes are 3/8" diameter.

PCR Capacity

The PCR capacity is obtained based on the system differential pressure (ΔP), which is defined as:

ΔP = Psupply – Precovery

Psupply: Steam supply pressure to the humidifier. Steam supply pressure may decrease after opening steam supply valve. Size piping and pressure relief valve accordingly.

❗ Important: Ensure that the steam supply pressure does not exceed 15 psi (103 kPa).

Precovery: Pressure from condensate recovery system. For vented systems, this pressure is equivalent to 1 psi (7 kPa) for every 27” (686mm) of condensate rise. It is not recommended to connect the PCR and steam trap outlets together. Additional design considerations must be taken into account for pressurized returns.

Once the system differential pressure (ΔP) is obtained, the PCR capacity can be obtained using the following table:

ΔP (psi) [kPa] Condensate Capacity (lb/hr) [kg/hr]
6 to 14 [41 to 97] 100 [45]
5 [34] 90 [41]
4 [28] 75 [34]

❗ Important: It is not recommended to connect the PCR system to the condensate return line if the differential pressure (ΔP) is below 4 psi (28 kPa).

Installation Overview

⚠️ All installation work must comply with local regulations.

⚠️ All work related to the installation of the Pressurized Condensate Return System MUST only be performed by skilled and qualified technical personnel such as plumbers or technicians with appropriate training. The customer is responsible for ensuring their suitability.

For the installation of the Pressurized Condensate Return System and associated components, there are no specific tooling requirements.

Installation Method Statement

The installation involves the following steps:

Illustration 3 – Installation Steps Overview: A simplified diagram showing the general layout of the PCR system installation, numbering the key steps from 1 to 8 (Step 8 is 'Configure Electronic Steam Controller (ESC)').

Step 1 - Install SKD Humidifier

Install the PCR tank and related peripherals after the SKD humidifier's standard elements are installed. Please follow the supplied Multi-Steam Series or Jacketed Series instructions to install the:

  • Steam distribution system
  • Steam control valve
  • Steam separator
  • Temperature sensor
  • Steam traps

Step 2 – Secure PCR Tank

Select the location and secure the PCR tank to the ground using the four mounting holes on the mounting bracket under the PCR tank. Ensure that there is a distance of at least 6" (152mm) between the bottom of the header and the bottom of the PCR tank.

Illustration 4 - Distance Between PCR Tank and Header: A side view illustrating the required minimum vertical distance between the bottom of the steam header and the bottom of the PCR tank.
Illustration 5 – PCR Tank Mounting: Diagrams showing the PCR tank from different angles, highlighting the mounting holes (4x Ø 3/8" (10mm)) and their dimensions.

Step 3 – Connect PCR Tank to Drain Port

Connect the provided swing check valve to the condensate inlet port of the PCR tank. Orient the check valve vertically and levelled so that the head is pointing in the up direction. Connect the NPT 1/2" (DN15) piping between the PCR tank's inlet port and the steam distribution system's drain port. Ensure to respect the minimum distance between the bottom of the PCR tank and the top of the header as detailed in Step 2.

Illustration 6 - PCR Tank to Drain Port: A diagram showing how the PCR tank connects to the steam distribution system's drain port via a swing check valve.

Step 4 – Install the Steam Relief Valve

Install the provided steam relief valve (VT000 actuator with a normally open globe valve) between the relief valve ports of the header and the PCR tank as shown below. Set the "Rotation Direction" DIP switch to "Valve normally open".

1) Rotation Direction Settings:

  • OFF (Valve normally closed): Red wire = Close (up), White wire = Open (down)
  • ON (Valve normally open): Red wire = Close (down), White wire = Open (up)
Illustration 7 – VT000 Actuator DIP Switch Settings: A diagram of the VT000 actuator showing DIP switch positions for "Valve normally open" or "Valve normally closed" settings.
Illustration 8 - Steam Relief Valve Installation: A diagram showing the placement of the steam relief valve between the header and the PCR tank, with connection points labeled (4A, 4B, 4C). It notes a maximum distance of 8" (203mm) between the relief valve and PCR tank.

For more details concerning installation of the actuator and valve, please refer to the instruction manual provided with the product.

Step 5 – Install the Steam Supply Valve

Install the provided steam supply valve (BM000F actuator with a NPT 1/2" (DN15) ball valve) between the tee and the supply valve port of the PCR tank as shown below. Ensure the actuator is in the fail-safe close position. Set the DIP switches as follows:

  • Rotation: CW
  • Fail safe return: at 0°
  • PWM mode: 25 sec.
Illustration 9 – BM000F Actuator DIP Switch Settings: A diagram of the BM000F actuator showing DIP switch settings for rotation direction (CW/CCW), fail-safe return (0°/90°), and PWM mode (25-sec pulse / 5-sec pulse).

❗ Important: The valve must be installed as close as possible to the PCR tank on the vertical piping line at a maximum of 8" (203mm) from the PCR tank.

❗ Important: Ensure that the steam supply pressure does not exceed 15 psi (103 kPa).

Illustration 10 – PCR Steam Supply Valve Installation: A diagram illustrating the installation of the steam supply valve between the tee and the PCR tank, showing maximum distance requirements (8" (203mm) max. downstream of tee and upstream of steam separator).

Positioning the PCR Steam Control Valve

Install the actuated valve between 20 to 30 degrees from vertical in order to reduce the convection heat to the actuator.

Illustration 11 - Flow Direction: A diagram showing the flow direction through the steam supply valve.
Illustration 12 – Tilt Angle: A diagram showing the recommended tilt angle for the steam control valve.

For more details concerning installation of the actuator and valve, please refer to the instruction manual provided with the product.

Step 6 – Connect PCR tank to Condensate Return

Connect the provided spring inline check valve to the condensate outlet port of the PCR tank. Orient the check valve vertically and levelled so that the head is pointing in the up direction. Then connect the NPT 1/2" (DN15) piping between the PCR tank's outlet port and the condensate return line.

Illustration 13 - PCR Condensate Return: A diagram showing the connection of the PCR tank's condensate outlet to the condensate return line via a spring inline check valve.

Step 7 – Strainer Installation

Install the strainer within six linear feet (1.83 linear meters) from the steam separator, reducing the pipe length for the strainer and the first Pressurized Condensate Return System component.

Illustration 14 - Strainer Installation: A diagram showing the placement of the strainer relative to the steam separator.

Electronic Steam Controller (SKDESC)

Models

Description

The Electronic Steam Controller SKDESC is made specifically for Neptronic SKD-M (Multi-Steam) Humidifiers.

Features

Technical Specifications

Description SKDESC-MP SKDESC-MBP SKDESC-MDP
Power Supply 24 Vac
Power Consumption 50 VA
Relay Output 2 relay
Relay Rating 125 Vac, resistive load 10 amps
Communication BACnet Modbus
Operating Temperature 32°F to 122°F (0°C to 50°C)
Storage Temperature -22°F to 122°F (-30°C to 50°C)
Relative Humidity 5 to 95% non-condensing
Weight 1.4 lb. (635 g)
Dimensions A = 6.3" | 160mm
B = 5" | 126mm
C = 2.25" | 57mm

Wiring

Neptronic strongly recommends that all Neptronic products be wired to a separate grounded transformer and that transformer shall service only Neptronic products. This precaution will prevent interference with, and/or possible damage to incompatible equipment.

Illustration 15 – Wiring Diagram: A detailed wiring diagram for the ESC controller, showing connections to various sensors, actuators, and power sources. Includes terminal block labels and descriptions.

Terminal Block Usage

Step Description Terminal Block Pin
Step 6, "Control Mode" = extern Used for external control signal TB9 Pin 1
Step 6, "Control Mode” = intern and Step 11, “Extern Humidty Setpnt" = on Used for external setpoint signal TB1 Pin 4
Step 18, "Duct High limit sensor" = digital Used for connecting high limit sensor (Digital) TB10 Pin 1
Step 18, “Duct High limit sensor" = analog Used for connecting high limit sensor (Analog)

Symbols Used in this Manual

Controls Menu (637)

Entering Programming Mode

To enter the Programming Mode, perform the following steps:

  1. Press * to start and enter password.
  2. Enter the password 637 within 1 minute. After entering the correct password, press * to proceed. If you enter the wrong password, the controller returns to normal operation mode.
  3. Use the arrow buttons or to navigate the menu.
  4. Press * to enter edit mode of the displayed value.
  5. Once in edit mode, use the arrow buttons or to change values. Changed values are automatically saved.
  6. Press * to exit edit mode of the displayed value.
  7. Return to step 3 or press ESC to exit the mode. Auto exits after 5 minutes without any action.

Menu Options

  1. "LANGUAG"
    Default: ENG (English)
    Range: ENG (English)
    Only English available at the moment.
  2. "METRIC DISPLAY UNITS"
    Default: ON
    Range: ON (metric units - °C, kg H2O/Hr), OFF (imperial units - °F, lbs H2O/Hr)
    Select the desired measurement system.

Configuration Options

General Settings

  1. "WORKING CAPACIT IN PCT"
    Default: 100%
    Range: 10 to 100%
    Increment: 5%

    This option enables adjustment of the maximum demand capacity of the full system capacity in %. This is a factory setting; consult Neptronic before changing.

  2. "SEPARAT TEMPER OFFSET"
    Default: 0
    Range: -10 to 10°C [-18 to 18°F]
    Increment: 0.1°C [0.1°F]

    Compare displayed temperature with a known value. Use arrow buttons to offset or calibrate the sensor.

  3. "PCR TEMPER OFFSET"
    Default: 0
    Range: -10 to 10°C [-18 to 18°F]
    Increment: 0.1°C [0.1°F]

    Compare the displayed temperature of the sensor in the PCR tank with a known value. Use arrow buttons to offset or calibrate the sensor.

Control Modes

  1. "CONTROL MODE"
    Default: Extern
    Range: Intern, Extern, Net

    Select the desired control mode:

    • Intern: Humidifier controlled by the SKDESC controller.
    • Extern: Humidifier controlled by an external signal (AI, DI).
    • Net: Humidifier controlled over the network (SKDESC-MBP and SKDESC-MDP models only).
  2. "DEMAND SIGNAL RANGE"
    Default: 2-10 Vdc
    Range: 0-10 Vdc, 2-10 Vdc

    Appears only if "Extern" is selected. Select the desired relative humidity sensor signal at input AI1.

  3. "NETWORK ROOM HUMIDTY”
    Default: OFF
    Range: OFF, ON

    Available only on SKDESC-MBP and SKDESC-MDP models. Select ON to control humidity over the network.

  4. "ROOM HUMIDTY OFFSET IN PCT"
    Default: 0% RH
    Range: -10 to 10% RH
    Increment: 0.1% RH

    Appears only if "Network room Humidity" is OFF. Compare displayed humidity with a known value to offset or calibrate the sensor.

  5. "ROOM HUMIDTY SIGNAL RANGE"
    Default: 2-10 Vdc
    Range: 0-10 Vdc, 2-10 Vdc

    Appears only if "Network room Humidity" is OFF. Select the desired signal range.

  6. "EXTERN HUMIDTY SETPNT”
    Default: OFF
    Range: OFF, ON

    Appears only if "Net" or "Intern" is selected. Select ON to use an external setpoint for humidity.

  7. "SETPNT SIGNAL RANGE"
    Default: 2-10 Vdc
    Range: 0-10 Vdc, 2-10 Vdc

    Appears only if "Net" or "Intern" is selected and "Extern Humidity Setpoint" is ON. Select the desired relative humidity sensor signal.

  8. "INTERN HUMIDTY SETPNT IN PCT"
    Default: 40% RH
    Range: 10% to 90% RH
    Increment: 1% RH

    Appears only if "Net" or "Intern" is selected and "Extern Humidity Setpoint" is OFF. Set the desired humidity setpoint in % RH.

  9. "CONTROL DEAD BAND IN PCT"
    Default: 2.0% RH
    Range: 0% to 5% RH
    Increment: 0.1% RH

    Appears only if "Intern" is selected. The deadband is the interval where no action occurs to prevent repeated activation-deactivation cycles.

  10. "CONTROL PROP RAMP IN PCT"
    Default: 5.0%
    Range: 1% to 10%
    Increment: 0.1%

    Appears only if "Intern" is selected. Proportional control applies effort based on proximity to setpoint. Example: 100% demand at start of ramp, decreasing as setpoint is approached.

  11. "CONTROL INTEGRA TIME IN SEC"
    Default: 0 seconds
    Range: 0 to 600 sec
    Increment: 1 sec

    Appears only if "Intern" is selected. Set the integral time for the humidity ramp. Cumulates difference between setpoint and actual reading for additional push.

  12. "CONTROL DERIVAT TIME IN SEC"
    Default: 0 seconds
    Range: 0 to 25.5 sec
    Increment: 0.1 sec

    Appears only if "Intern" is selected. Set the derivative time for the humidity ramp. Dampens or predicts control effort to minimize overshoot.

Duct High Limit Sensor Settings

  1. "DUCT HIGH LIMIT SENSOR"
    Default: Digital (On/Off)
    Range: Disable, Analog, Digital (On/Off), Network

    Appears only if "Intern" is selected. Select the desired type of high limit sensor. Analog option refers to AI3 input.

  2. "DUCT MIN SETPNT IN PCT"
    Default: 15% RH
    Range: 0 to MAX SETPNT
    Increment: 1% RH

    Appears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the minimum duct humidity setpoint.

  3. "DUCT MAX SETPNT IN PCT"
    Default: 65% RH
    Range: MIN SETPNT to 100% RH
    Increment: 1% RH

    Appears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the maximum duct humidity setpoint.

  4. "DUCT PROP RAMP IN PCT"
    Default: 5.0%
    Range: 1% to 10%
    Increment: 0.1%

    Appears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the proportional ramp for control.

  5. "DUCT INTEGRA TIME IN SEC"
    Default: 0 seconds
    Range: 0 to 600 sec
    Increment: 0.1

    Appears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the integral time for the humidity ramp.

  6. "DUCT DERIVAT TIME IN SEC"
    Default: 0 seconds
    Range: 0 to 25.5 sec
    Increment: 0.1 sec

    Appears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the derivative time for the humidity ramp.

  7. "HIGH LIMIT SETPNT IN PCT"
    Default: 80% RH
    Range: 10% to 90% RH
    Increment: 1% RH

    Appears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the high limit relative humidity setpoint.

  8. "HIGH LIMIT PROP RAMP IN PCT"
    Default: 10.0 %
    Range: 0% to 20%
    Increment: 0.1%

    Appears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Sets the high limit proportional ramp.

  9. "HIGH LIMIT HUMIDTY OFFSET IN PCT"
    Default: 0% RH
    Range: -10% RH to 10% RH
    Increment: 0.1% RH

    Appears only if "Analog" is selected for Duct High Limit Sensor. Adjusts the relative humidity reading of the high limit sensor.

  10. "HIGH LIMIT SIGNAL RANGE"
    Default: 2-10 Vdc
    Range: 0-10 Vdc, 2-10 Vdc

    Appears only if "Analog" or "Network" is selected for Duct High Limit Sensor. Selects the high limit signal range.

  11. "HIGH LIMIT MAX DEMAND IN PCT"
    Default: No default (information display only)

    Appears only if the Duct High Limit Sensor type is not disabled. Displays the actual reading of the high limit sensor.

Service and Delay Settings

  1. "END OF SEASON DELAY IN HR"
    Default: 100 hours
    Range: 100 to 250 hours
    Increment: 5 hours

    Indicates that the isolation valve will be turned off after 100 hours if there is no demand.

  2. "SERVICE DELAY IN HR"
    Default: 5000 hours
    Range: 1000 to 5000 hours
    Increment: 500 hours

    Set the number of hours running at 100% capacity before servicing is due.

  3. "SERVICE RUNTIME IN HR"
    Default: No default (information display only)

    Displays the running time in hours at 100% capacity since the last service. To reset, press edit and hold and keys.

  4. "RUNS WHILE SERVICE ALARM"
    Default: ACt (active)
    Range: INACT (Inactive), ACt (active)

    Select ACt to run even when servicing is due. Select INACt to turn off the system when servicing is due.

  5. "TOTAL RUNTIME IN HR"
    Default: No default (information display only)

    Displays the running time in hours at 100% capacity.

Fallback and Network Settings

  1. "PCR FALLBACK"
    Default: Off
    Range: Off, On

    Determines PCR system operation during water level or temperature sensor failure. OFF stops the system; ON allows continued function based on internal timers.

  2. "NETWORK AUTO BAUD RATE"
    Default: ON
    Range: ON, OFF

    Available on SKDESC-MBP and SKDESC-MDP models. Enable or disable Auto Baud Rate detection. If enabled, baud rate is auto-configured. If disabled, select manually (Step 36).

  3. "NETWORK BAUD RATE"
    Default: No default (information display only)
    Range: BACnet: 9.6k, 19.2k, 38.4k, 76.8k; Modbus: 9.6k, 19.2k, 38.4k, 57.6k

    Available on SKDESC-MBP and SKDESC-MDP models. Select baud rate if "Network auto baud rate" is OFF.

  4. "NETWORK ADDRESS"
    BACnet Default: 0 (Range: 0 to 254)
    Modbus Default: 1 (Range: 1 to 246)

    Available on SKDESC-MBP and SKDESC-MDP models. Select the desired address.

  5. "DEVICE INSTANCE"
    Default: 0153001
    Range: No, Yes

    Select Yes to change the device instance; No modifies it automatically per MAC address.

  6. "NETWORK PARITY"
    Default: None
    Range: None, Odd, Even

    Available on Modbus models (SKDESC-MDP). Select parity control.

  7. "NETWORK STOP BITS"
    Default: 1
    Range: 1, 2

    Available on Modbus models (SKDESC-MDP). Select network stop bits.

  8. "NETWORK FALLBACK TIMEOUT"
    Default: 0 sec
    Range: 0 to 900 sec
    Increment: 1 sec

    Appears if "Net" is selected for Control Mode. Sets network fallback timeout. Alarm generated if no communication occurs for this period.

  9. "NETWORK FALLBACK SETPOINT"
    Default: 0.0%
    Range: 0% to 100%
    Increment: 0.1%

    Appears if "Net" is selected for Control Mode. Determines humidifier function during network communication failure. Example: 20% means constant 20% demand.

  10. "NETWORK FALLBACK COUNTER"
    Default: No default (information display only)
    Range: 0 to 900 sec

    Appears if "Net" is selected for Control Mode. Displays time remaining before fallback alarm.

Signal and Output States

  1. "CONTROL OUTPUT SIGNAL IN MV"
    Default: No default (information display only)

    Displays humidifier steam control valve output in mV.

  2. "PCR SUPPLY SIGNAL IN MV"
    Default: No default (information display only)

    Displays the PCR steam supply valve output in mV.

  3. "ISOLAT VALVE OUTPUT STATE"
    Default: No default (information display only)
    Range: INACT (closed), ACt (open)

    Displays whether the isolating valve is open or closed.

  4. "PCR RELIEF VALVE OUTPUT STATE"
    Default: No default (information display only)

    Displays whether the PCR relief valve is open or closed.

  5. "ALARM RELAY OUTPUT STATE"
    Default: No default (information display only)
    Range: INACt (closed), ACt (open)

    Displays whether the alarm relay is open or closed.

  6. "STEAM ON OUTPUT RELAY OUTPUT STATE"
    Default: No default (information display only)
    Range: INACt (closed), ACt (open)

    Displays whether the steam output relay is open or closed.

  7. "SEPARAT TEMPER INPUT SIGNAL IN MV"
    Default: No default (information display only)

    Displays the separator temperature sensor reading in mV.

  8. "DEMAND INPUT SIGNAL IN MV"
    Default: No default (information display only)

    Appears only if "Extern" is selected for Control Mode. Displays the demand reading in mV.

  9. "ROOM HUMIDITY INPUT SIGNAL IN MV"
    Default: No default (information display only)

    Does not appear if "Network room Humidty" is OFF. Displays the relative humidity reading of the room in mV.

  10. "SETPNT INPUT SIGNAL IN MV"
    Default: No default (information display only)

    Appears only if "Extern Humidty Setpnt" is ON. Displays the setpoint reading in mV.

  11. "HIGH LIMIT INPUT SIGNAL IN MV"
    Default: No default (information display only)

    Appears only if "Analog" is selected for Duct High Limit Sensor. Displays the high limit sensor reading in mV.

  12. "WATER LEVEL INPUT SIGNAL IN MV"
    Default: No default (information display only)

    Displays the reading in mV of the water level sensor inside the PCR tank.

  13. "EXTERN DEMAND INPUT STATE"
    Default: No default (information display only)
    Range: INACt (closed), ACt (open)

    Appears only if "Extern" is selected for Control Mode. Displays if the demand is open or closed.

  14. "AIR FLOW INPUT STATE"
    Default: No default (information display only)
    Range: INACt (closed), ACt (open)

    Displays if the air flow switch is open or closed.

  15. "HIGH LIMIT SWITCH INPUT STATE"
    Default: No default (information display only)
    Range: INACT (closed), ACt (open)

    Appears only if "Digital" is selected for Duct High Limit Sensor. Displays if the high limit switch is open or closed.

  16. "INTRLCK INPUT STATE"
    Default: No default (information display only)
    Range: INACt (closed), ACt (open)

    Displays if the interlock is open or closed.

  17. "MICRO TEMPER"
    Default: No default (information display only)

    Displays whether the microcontroller temperature is in °C or °F mode.

  18. "PCB TEMPER"
    Default: No default (information display only)

    Displays whether the PCB temperature is in °C or °F mode.

Alarms and Notifications

The following is a list of alarms and notifications displayed by the Steam Controller under different conditions. The alarm symbol, ⚠️, is displayed along with all alarms and notifications.

Display Description
no air flow Alarm Indicates that the air flow sensor is not detected.
- control valve is closed
- isolating valve is closed
high limit cutout Alarm Indicates that the duct humidity has exceeded the high limit level.
- control valve is closed
- isolating valve is closed
- alarm relay is activated
service warning Alarm Indicates that the servicing is due in less than 100 hours.
Service the unit and reset the unit at Step 31 "SERVICE RUNTIME IN HR" by pressing the arrow keys , for three seconds.
service unit Alarm Indicates that the service is due. This alarm won't stop the system from running unless you've set the option to inact at Step 32 "runs while service alarm".
- control valve is closed
- isolating valve is closed
- alarm relay is activated
inter lock Alarm Indicates that the inter lock is activated.
- control valve is closed
- isolating valve is closed
- alarm relay is activated
flooded separate steam trap Failure Indicates that either the separator steam trap is flooded or the temperature is too low.
- control valve is closed
- alarm relay is activated
separat temper sensor Failure Indicates that the separator sensor is defective.
- control valve is closed
- isolating valve is closed
- alarm relay is activated
PCR temper sensor Failure Indicates that the PCR tank's temperature sensor is defective.
- control valve is closed
- isolating valve is closed
- alarm relay is activated
room humidity sensor Failure Indicates that the room humidity sensor has failed.
- control valve is closed
- isolating valve is closed
- alarm relay is activated
high limit humidity sensor Failure Indicates that the high limit humidity sensor has failed.
- control valve is closed
- isolating valve is closed
- alarm relay is activated
PCR Water Level sensor Failure Indicates that the PCR tank's water level sensor has failed.
- control valve is closed
- isolating valve is closed
- alarm relay is activated

Operating Menu Display

Power Up

Upon power up, the LCD illuminates and all segments appear for 2 seconds. The thermostat then displays its serial number, model, and revision for 2 seconds. In the Operation Mode, the information is displayed automatically in a sequence. If you wish to scroll the information quickly, use the , arrow keys.

Humidity Levels

The following humidity levels are displayed:

Control Parameters

The following control parameters are displayed:

Temperature Levels

The following temperature level is displayed:

Initial Verification

⚠️ Any installation work must be carried out by suitably qualified personnel.

Installation

Electrical

Drain if Required

Steam Supply

Controls

Start-Up Procedure

Start-up

Proceed to start-up the humidifier as follows:

Safety Test

Reset the Setpoint and Control Mode

End

Notes

(Blank section for notes as per PDF)

PDF preview unavailable. Download the PDF instead.

PCR Manual-250908-R2-ESL Microsoft Word for Microsoft 365

Related Documents

Preview Neptronic Pressurized Condensate Return System (PCR) Installation and User Manual
Comprehensive installation and user manual for the Neptronic Pressurized Condensate Return System (PCR), designed for use with SKD-J Direct Steam Injection Humidifiers. Covers principle of operation, specifications, installation steps, controller configuration, wiring, and troubleshooting.
Preview Neptronic SKD-J Series Direct Steam Injection Humidifier: Installation and User Manual
Installation instructions and user manual for the Neptronic SKD-J Series Direct Steam Injection Humidifier. Covers product features, configurations, installation steps, safety, and operation for HVAC systems.
Preview Neptronic Multi-Steam SD/HD Direct Steam Injection Humidifier Installation and User Manual
Comprehensive installation, operation, and programming guide for the Neptronic Multi-Steam SD/HD series direct steam injection humidifiers. Includes product overview, technical specifications, safety precautions, detailed installation steps, wiring diagrams, controller configuration, and alarm/notification information.
Preview Neptronic SKDESC-xB Series BACnet Communication Module User Guide
This user guide provides comprehensive information on configuring and utilizing the Neptronic SKDESC-xB Series Electronic Steam Controller with its BACnet Communication Module, detailing setup, properties, and object types for building automation networks.
Preview Neptronic Multi-Steam Steam Dispersion System: Installation and User Manual
Comprehensive installation and user manual for the Neptronic Multi-Steam Steam Dispersion System, covering product overview, characteristics, assembly, mechanical installation, steam supply connection, startup procedures, maintenance, and troubleshooting.
Preview Neptronic SKR Series Steam Humidifier Installation and User Manual
Comprehensive installation and user manual for the Neptronic SKR series steam humidifiers, covering setup, operation, maintenance, and troubleshooting.
Preview Neptronic SKR Series Steam Humidifier with SDU Module: Installation and User Manual
Comprehensive installation and user manual for the Neptronic SKR series steam humidifier with SDU module. Covers setup, operation, maintenance, troubleshooting, and electrical diagrams.
Preview Neptronic SKS4 Series Steam to Steam Humidifier - Installation and User Manual
This official Installation Instructions and User Manual for the Neptronic SKS4 Series Steam to Steam Humidifier provides detailed guidance on safety, installation, operation, maintenance, and troubleshooting for HVAC professionals. It covers unit setup, steam dispersion, electrical connections, and technical specifications.