Strap-on Temperature Transmitter With LCD
TDSO Series - Installation Instructions

INTRODUCTION
The single point strap-on temperature transmitter has a precision platinum RTD encapsulated in an 38.1mm x 12.7mm (1.5"x 0.5") aluminum plate. A 25.4 cm (10") S/S Pipe clamp is provided to secure the assembly to various sizes of pipes. All probes are constructed to provide excellent heat transfer, fast response and are potted to resist moisture penetration. A transmitter that provides a high accuracy signal with excellent long term stability, low hysteresis and fast response is available with various ranges. A compact Polycarbonate enclosure with a hinged and gasketed cover is provided for ease of installation.
BEFORE INSTALLATION
Read these instructions carefully before installing and commissioning the temperature transmitter. Failure to follow these instructions may result in product damage. Do not use in an explosive or hazardous environment, with combustible or flammable gases, as a safety or emergency stop device or in any other application where failure of the product could result in personal injury. Do not exceed the device ratings.
MOUNTING
The strap-on transmitter installs directly onto any pipe where an immersion sensor with thermowell cannot be installed.

Once a suitable spot is selected, remove a small block of insulation, if present. It is recommended that thermal compound be used to improve heat transfer. Spread a liberal amount on the pipe. Open the worm gear clamp by swiveling the worm gear away from the clamp and pull the clamp apart, as shown in Figure 1.

Place the sensor plate on the selected mounting area and wrap clamp around the pipe. Re-insert clamp under the worm gear and pull until snug. Lock in place by swiveling the worm gear towards the clamp. Tighten worm gear clamp by using a standard screw driver or hex nut driver as shown in Figure 2.

Figure 1

The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on the latch on the right side of the enclosure, at the same time pulling on the cover, as illustrated in Figure 3.

A 1/2" NPT threaded connection hole is provided in the bottom of the enclosure. Screw the EMT connector or cable gland connector in until tight. See Figure 4. It is recommended that weatherproof conduit or cable gland fittings be used. An optional 1/2" NPT to M16 thread adapter and cable gland fitting is available.

Figure 2

Make wiring connections as per the "Wiring" illustrations on Page 2.

Swing door closed until securely latched. For added security, 2 screws are provided that may be installed in the integrated screw tabs. See Figure 5.

Figure 3

Figure 4

Figure 5

Thread adapter and cable gland fitting

IN-GE-TDSOXXX-003

EMT Connector Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com

Page 1

WIRING
· Deactivate the 24 Vac/dc power supply until all connections are made to the device to prevent equipment damage. · Use 14-22 AWG shielded wiring for all connections and do not locate the device wires in the same conduit with wiring used to supply
inductive loads such as motors. Make all connections in accordance with national and local codes. · The temperature transmitter comes with the temperature sensor pre-wired to the transmitter board. If removal is required for installation
then it may be re-wired as shown in Figure 6. · Pull at least six inches of control wire into the enclosure, then complete the wiring connection according to the wire diagram for the
applicable power supply and output signal type as shown in Figure 7. · Connect the DC positive or the AC voltage hot side to the PWR terminal. For voltage output or AC power, the supply Common is connected
to the COM terminal. The device is reverse voltage protected and will not operate if connected backwards. It has a half-wave power supply so the supply Common is the same as the signal Common. See Figure 7. · The analog output is available on the OUT terminal. Check the controller Analog Input to determine the proper connection before applying power as shown in Figure 7. · Once all connections are made and checked, power can be applied.

Figure 6

2 wire temperature sensor wiring to transmitter

Negative (Grey) No Polarity
SEN
Excitation (Grey) No Polarity

SENSOR

Figure 7

Transmitter Wiring to Controller

Wiring for 0-5 or 0-10 Vdc output signal and 24 Vdc power from controller

Wiring for 4-20 mA loop-powered output and external 24 Vdc power from controller

PWR COM OUT
PRINTED IN CANADA

SPECIFICATIONS:
Sensor Type:.........................................1000 ohm platinum RTD Sensor Accuracy:...............................±0.3°C (±0.94°F) @ 0°C (32°F) Wire Material:......................................PVC insulated, parallel bonded, 22 AWG Probe Sensing Range:.....................-40 to 100°C (-40 to 212°F) Probe Material:...................................Machined aluminum heat sink Probe Dimensions:...........................38.1mm x 12.7mm (1.5"x 0.5") Output Signal:.....................................4-20 mA current loop, 0-5 vdc, or 0-10 vdc
(factory configured) Transmitter Accuracy:.....................±0.2% of span, including linearity Power Supply:.....................................15 to 30 Vdc, 12 to 28 Vac Consumption (max):........................20 mA for current, 11 mA for voltage Protection Circuitry:.........................Reverse voltage protected and output limited Output Drive @ 24 Vdc:..................Current: 700  max for output,
Voltage: 20K  min for output LCD Display Units:.............................°C or °F (factory configured) Display Range:....................................3 digit for -88.8 to 888 as required Display Size: .........................................38.1mm W x 16.5 mm H (1.5" to 0.65") Digit Height: ........................................11.4 mm (0.45") plus °C/°F symbol Ambient Operating Range:..........0 to 50°C (32 to 122°F), 0-95 %RH Enclosure:..............................................Grey polycarbonate UL94-V0, IP65 (NEMA 4X)
Optional thread adapter (1/2" NPT to M16) and cable gland fitting Wiring Connections:........................Screw terminal block (14 to 22 AWG) Country of Origin:.............................Canada

DIMENSIONS
99.7 mm 3.925"

112.5 mm 4.43"

Wiring for 0-5 or 0-10 Vdc output signal and with external 24 Vdc power supply

Wiring for 4-20 mA loop-powered output and external 24 Vdc power supply

24 Vdc Power Supply

24 Vdc Power Supply

Wiring for all output signals with external 24 Vac power transformer

53.7 mm 2.11"

112.5 mm 4.43"

0.5" NPT

Machined Aluminum Heat Sink

254 mm (10") S/S Pipe Clamp

IN-GE-TDSOXXX-003