CTP Series Current Transmitters

INSTALLATION INSTRUCTIONS

WARNING
Failure to follow these instructions will result in death or serious injury.

AVERTISSEMENT
Le non-respect de ces instructions entraîne un risque de blessures graves, voire la mort.

WARNING
This product can expose you to chemicals including 1,3 Butadiene, which is known to the State of California to cause cancer and reproductive harm. For more information, go to www.P65Warnings.ca.gov
DESCRIPTION
The CTP current transmitters monitor the current flow for various electrical equipment. Measured current level is converted into a linear and proportional 0 - 5/10 Vdc or 420mA output signal, which can be monitored by a Building Management, DDC, or PLC controller. Current sensors with switch selectable current ranges provide optimal resolution for greater measuring accuracy. . These current sensors should be used in load trending (current monitoring) type applications.
The split core design make installations easy since no wires need to be disconnected during the installation process.
May be mounted on the conduction (codes permitting) or fix mounted flexibility including DIN rail compatibility.

WARNING
Hazard of electrical shock, explosion, and arc flash · Follow ALL requirements in NFPA 70E for safe work practices and for Personal Protective Equipment (USA) and other applicable local codes when installing this product · Only qualified electrical personnel should install this product · Read, understand, and follow all instructions thoroughly · Install only on insulated conductors · Lock out and tag out all power sources prior to installation. Use properly rated voltage sensing instrument to determine no voltage is present
AVERTISSEMENT
Risque d'électrocution, d'explosion et d'arcs électriques · Respectez TOUTES les exigences de la norme NFPA 70E en matière de pratiques de travail sécuritaires et d'équipement de protection individuelle (É.-U.) ainsi que tous les codes locaux lorsque vous installez ce produit. · Seul le personnel qualifié dans le domaine électrique est autorisé à installer ce produit. · Lisez, comprenez et respectez scrupuleusement toutes les instructions. · N'installez que sur les conducteurs isolés. · Verrouillez et étiquetez toutes les sources d'alimentation avant l'installation. Utilisez un détecteur avec la tension nominale appropriée pour déterminer l'absence de tension.

31-00430-01

CTP SERIES CURRENT TRANSMITTERS

WARNING
Automated equipment may start without warning · Equipment monitored/operated by this device may start without warning. Keep clear of apparatus at all times
IMPORTANT · Only qualified trade installers should install this product · This product is not intended for life-safety applications · Do not install in hazardous or classified locations · The installer is responsible for all applicable codes · This product must be installed in a suitable electrical enclosure · Clamp sensor around INSULATED CONDUCTOR ONLY, 600VAC MAX to be monitored.
AVERTISSEMENT
L'équipement automatisé peut commencer sans avertissement. · L'équipement surveillé/exploité par cet appareil peut commencer sans avertissement. Éloignez-le de l'appareil en tout temps.
IMPORTANT · Seuls les installateurs spécialisés sont autorisés à installer ce produit. · Ce produit n'est pas destiné aux applications de sécurité ou de sauvetage. · Ne l'installez pas dans des endroits dangereux ou classés comme tels. · L'installateur est responsable de tous les codes applicables. · Ce produit doit être installé dans un boîtier électrique approprié. · Pincez le capteur UNIQUEMENT SUR LE CONDUCTEUR ISOLÉ (600 VCA max.) à surveiller.
INSTALLATION
Disconnect, lock out and tag out all power supplies during installation
1. Determine mounting location for the sensor near the conductor to be monitored. The sensor should be located AT LEAST 1/2" from any uninsulated conductor.
2. Sensor features a flexible iris which allows the sensor to hang on the conductor if local codes permit. A bracket is included for screw mounting or attaching to DIN rail. For screw mounting, drill two 3/32" pilot holes using the bracket as a template; ensure no drill shavings are present in enclosure. Attach bracket with screws provided.

3. Clamp sensor around INSULATED CONDUCTOR ONLY, 600VAC MAX to be monitored.
4. Snap the sensor into the mounting bracket. 5. Wire the output of the sensor to a control panel ana-
log input. Sensor is self-powered. 12 to 30vdc excitation is required for 4-20mA output models (CTP-A20A and CTP-A-120A). Tighten terminals to 3.5 inlb.
SETUP
1. Sensors are factory calibrated to three ranges. CTP10V-200A is calibrated to 200A full-scale. No field calibration is required.
2. Move selector switch to desired factory calibrated range setting. Selected range should be greater than the maximum motor current.

CONTROLLER

NOTE: Device IS polarity sensitive.

GND

INSULATED PRIMARY AC CONDUCTOR 600VAC MAX

v

AI
AI

+ -
0-10VDC Output

30 60 120
Sensed Amperage
Range

Fig. 1. Wiring CTP-5V, CTP-10V Product Application Limitation: Honeywell products are not designed for life or safety applications. Honeywell products are not intended for use in critical applications such as nuclear facilities, human implantable device or life support. Honeywell is not liable, in whole or in part, for any claims or damages arising from such uses.

CONTROLLER
Vdc V+

NOTE: Device IS polarity sensitive. AI

INSULATED PRIMARY AC CONDUCTOR 600VAC MAX

v

V+

+ -
4-20mA 12-30VDC Loop

30 60 120
Sensed Amperage
Range

Fig. 2. Wiring CTP-A

31-00430--01

2

CTP SERIES CURRENT TRANSMITTERS

TECH TIPS
On low current loads, wrap sensor multiple times to increase sensitivity
CAUTION
Do not exceed sensor maximum current. The current detected by the sensor will increase 1X with each wrap.
MISE EN GARDE
Ne dépassez pas l'intensité maximale du capteur. L'intensité détectée par le capteur augmentera de 1X à chaque enroulement.
To monitor loads greater than the current sensor maximum rating Use a properly rated 5A CT as shown below

MISE EN GARDE
Un CT de 5 A peut produire des tensions dangereuses. Installez les CT conformément aux directives du fabricant. Terminez le câblage secondaire du CT avant d'alimenter le conducteur principal.

Table 1. Troubleshooting

Symptom

Cause

Remedy

Sensor output is over Amperage is above See Tech Tip for monitoring

maximum output range selected maximum loads greater than current

(5V, 10V, 20 mA)

range

sensor maximum rating

No output or wrong output voltage

Wiring error Incorrect scaling

Check polarity Check ground connection
Verify controller scaling

No output current

No excitation voltage
Backward wiring

Check excitation voltage Check polarity

Wrong output current Incorrect scaling Verify controller scaling

200-500 AMPS

2-5 AMPS

500:5A CT

RECYCLING
Product should not be thrown away in regular trash. Instead, it should be recycled according to local municipality.

OPERATION

Selected Range

Factory calibrated

CAUTION
5A CT's can present hazardous voltages. Install CT's in accordance with manufacturers instructions. Terminate the CT secondary wiring before energizing primary conductor. Remember to consider the ratio of the CT secondary to the sensor full-scale range to determine sensor output. Example: A 300:5A CT will produce 5 amps max, which is 1/6th of the 30 amp full-scale range of the CTP-A-120A. Applying this ratio (1/6) to the 16mA output range (20mA 4mA) gives a 2.67mA signal change for a reading of 6.67mA at 300 A.

Load Amps

0A
0 V 0 mA

Sensor Output 5 V or 10 V
20 mA

Analog current sensors output signal proportional to monitored current.

Typical load status applications include: · Load trending · Monitoring process motors and pumps · Electric heater current monitoring

3

31-00430--01

CTP SERIES CURRENT TRANSMITTERS

Table 2. Specification by Product

Product Number

Output Type

CTP-A-20A

Loop-powered 4-20 mA

CTP-A-120A Loop-powered 4-20 mA

CTP-5V-20A

Self-powered 0-5 VDC

CTP-10V-120A Self-powered 0-10 VDC

CTP-10V-200A Self-powered 0-10 VDC

Range(s) 5/10/20 A 30/60/120 A 5/10/20 A 30/60/120 A Fixed, 200 A

Max Current
200 A
200 A
100 A
200 A
200 A

Specification Accuracy Ambient Temperature Rating Insulation Class
Sensor Power
Frequency Range Dimensions ( LxWxH)
Sensor Aperture Environmental

Rating +/-2% F.S. over 10 to 100% range
-15~60 ° C
600V RMS. For use on insulated conductors only! Use minimum 75 ° C insulated conductor
Induced, 12 to 30 VDC max for loop powered sensors 50/60Hz
2.94" x 2.23" x 0.82" (1.4" H with optional relay module) 0.75"
Pollution Degree 2 (non-conductive/noncondensing)

3PZS E516382

RoHS Compliant

Honeywell Building Technologies In the U.S.: Honeywell 715 Peachtree Street NE Atlanta, GA 30308 customer.honeywell.com

® U.S. Registered Trademark ©2020 Honeywell International Inc. 31-00430--01 M.S. 09-20 Printed in United States

