Bettis XTE3000
Partial Stroke Test

Installation, Operation and Maintenance Manual
DTDE 536 Rev. 1 February 2022

Revision Details
February 2022

Installation, Operation and Maintenance Manual
DTDE 536 Rev. 1

Revision Details

Revision 1

Date February 2022

Description Migration to new Template

Prepared

Checked

Approved

Revision Details

Installation, Operation and Maintenance Manual
DTDE 536 Rev. 1

Table of Contents
February 2022

Table of Contents
Section 1: Partial Stroke Test (PST)
Partial Stroke Test (PST) .......................................................................................... 1
Section 2: Parameters of Partial Stroke Test
Parameters of Partial Stroke Test............................................................................. 3
Section 3: Command to Initiate the PST Cycle
Command to Initiate the PST Cycle.......................................................................... 4
Section 4: Reset of PST Cycle
Reset of PST Cycle ................................................................................................... 5
Section 5: PST Curves and PST Baseline
PST Curves and PST Baseline ................................................................................... 6
Section 6: PST Report and Warning
PST Report and Warning ......................................................................................... 7
Section 7: Remote Signalling
Remote Signalling................................................................................................... 8
Section 8: Local Operator Interface
8.1 Procedure to Initiate PST by Local Command................................................. 9 8.2 Procedure to Select the BASELINE ................................................................. 9 8.3 Procedure to Set PST Parameters ................................................................ 10

Table of Contents

i

Notes
February 2022

Installation, Operation and Maintenance Manual
DTDE 536 Rev. 1
This page intentionally left blank

Installation, Operation and Maintenance Manual Section 1: Partial Stroke Test (PST)

DTDE 536 Rev. 1

February 2022

NOTE:
This Manual gives instruction regarding only the Partial Stroke Test function of XTE3000; detailed and complete information for setting and control of the Electric Actuator XTE3000 are in the Installation, Operation and Maintenance Manual of XTE3000, which is part of the mandatory instructions documentation.

! WARNING
It is assumed that installation, setting, commissioning, maintenance and repair works on XTE3000 are carried out by qualified personnel and checked by responsible specialists.

Section 1: Partial Stroke Test (PST)

The function Partial Stroke Test (PST) of XTE3000 is used to check the actuator and valve functionality while they are in service in the pipeline. The test is performed only if the actuator is fully open or closed.
PST function is available only if the setting of parameter "Restricted, Interlock mode" of XTE3000 is "Advanced." In the above condition the hardwired inputs B4 and B5 of XTE3000 terminal board work as input commands to initiate the PST cycle. Firmware version of XTE3000 base card should be > = 9.00.
Table 1 shows the operation of the above inputs in function of parameter "Interlock mode," in the "VIEW and SETUP menu, Restricted," (see Installation, Operation and Maintenance Manual of XTE3000).

Table 1.

XTE3000 Parameter "Restricted, Interlock mode"
advanced

Terminal B4 of XTE3000 terminal board
PST in Open direction

standard

Interlock in Open direction

Terminal B5 of XTE3000 terminal board PST in Close direction
Interlock in Close direction

The PST cycle (Partial Stroke Test) consists of the following steps:

·

To drive the electrical motor to move the valve to the configured position (PST travel)

·

To measure the time to reach the configured position (T-PST)

·

To stop the motor when configured position is reached and measure the over-travel

% (OV-TR)

·

To stay in position for a configured time

·

To drive of the motor to move the valve in opposite direction to the initial position

·

To measure the time to return to the initial position (T-RET)

Partial Stroke Test (PST)

1

Section 1: Partial Stroke Test (PST) Installation, Operation and Maintenance Manual

February 2022

DTDE 536 Rev. 1

Figure 1 and Figure 2 shows the actuator position % versus time in case of PST in closing and opening direction.

Figure 1 Position %
100
Cmd to initiate PST
0

T-PST

Stay in position

T-RET

100 PST travel %
Over-travel % (OV-TR)
PST in closing direction

Time seconds

Figure 2
Position %
Cmd to initiate PST 0

T-PST

Stay in position

T-RET

PST in closing direction
Over-travel % (OV-TR) PST travel %
Time seconds

2

Partial Stroke Test (PST)

Installation, Operation and Maintenance Manual
DTDE 536 Rev. 1

Section 2: Parameters of PST
February 2022

Section 2: Parameters of Partial Stroke Test

The following parameters are available in the local operator interface of XTE3000, VIEW and SETUP menu, ACTUATOR SETUP, PST SETUP routine, to set PST function behavior:

1.

PST mode: OFF, AUTO, MANUAL

--

OFF: PST function disabled

--

AUTO: PST cycle carried out automatically and cyclically with time interval set by

the parameter PERIOD and at time set by the parameter HOUR of DAY

--

MANUAL: PST cycle carried out on receiving of a remote hardwired PST signal

or by local command available in the "VIEW and SETUP menu, Maintenance

functions" of XTE3000

--

MAN-AUTO: both automatic and manual mode initiate the PST function

2.

PERIOD: time interval between PST's in days, configurable from 1 - 1000, in PST mode "AUTO"

3.

HOUR of DAY: hour of PST, in hour, configurable from 0 - 23, in PST mode "AUTO"

4.

PST TRAVEL: position travel during PST cycle, in % of position, configurable from 5 - 40.

If actuator is fully open it moves from 100% to "100-PST TRAVEL %", if actuator is fully

closed it moves from 0% to "PST TRAVEL %"

5.

MAX T-PST: max time allowed carrying out the PST TRAVEL, measured in % of relevant

BASELINE time, configurable from 1 - 1000%

6.

MAX PST T-RET: max time allowed to return to initial position, measured in % of relevant

BASELINE time, configurable from 1 - 1000%

7.

PAUSE: time of stay in position of actuator, in seconds, configurable from 2 - 255 seconds

8.

MAX PST OV-TR: max position over-travel allowed to actuator during PST cycle, in

percentage of position , configurable from 1 - 100

Parameters of PST

3

Section 3: Command to PST Cycle
February 2022

Installation, Operation and Maintenance Manual
DTDE 536 Rev. 1

Section 3: Command to Initiate the PST Cycle

PST cycle initiates only if:

·

actuator is fully open or closed

·

local selector of actuator is in REMOTE or LOCAL

·

local STOP, remote STOP (only in the option 4 wires mode) and ESD are not active

The parameter "PST mode" sets the following modes to initiate PST cycle:

·

"AUTO": the PST cycle initiates at the hour set by the parameter HOUR of DAY and when

the time past from the last PST is equal to parameter PERIOD. The test is performed if the

actuator local selector is in LOCAL or REMOTE.

·

"MANUAL": if the XTE3000 local selector is in REMOTE, the PST is performed on receiving

of the hardwired command on the XTE3000 terminal board. Terminal B4 is the input to

perform PST in open direction and terminal B5 is the input to perform PST in close direction.

Refer to relevant electrical diagram for wiring details. If the XTE3000 local selector is in

LOCAL, the PST can be initiated by the command available in the menu "VIEW and SETUP

menu, SETUP, MAINTENANCE routines, PST cmd".

·

"MAN-AUTO": both conditions described in "AUTO" and "MANUAL" initiate PST action.

4

Command to PST Cycle

Installation, Operation and Maintenance Manual
DTDE 536 Rev. 1

Section 4: Reset of PST Cycle
February 2022

Section 4: Reset of PST Cycle

PST cycle aborts in the following conditions:

·

To move the XTE3000 Local selector to OFF, LOCAL or REMOTE while PST cycle

is in progress

·

Alarm of electrical actuator XTE3000

·

To press the Local STOP pushbutton

·

To press the remote STOP command (only if option "4-wires" is used, see Installation,

Operation and Maintenance Manual of XTE3000, Section 5.6, Remote Control)

·

ESD command

Reset of PST Cycle

5

Section 5: PST Curves and Baseline Installation, Operation and Maintenance Manual

February 2022

DTDE 536 Rev. 1

Section 5: PST Curves and PST Baseline
During PST cycle, the actuator position % and the relevant time are collected in the RAM memory of XTE3000. At the end of PST cycle, the PST profile (position versus time) is memorized in the permanent memory. The memory contains up to 16 PST profiles. When a new set of data is available, the oldest profile is deleted and the new one is stored.
By the command "SET PST REFERENCE", available in the local operator interface, option "VIEW and SETUP menu, SETUP, MAINTENANCE" routines, 1 out off 16 "PST curves" can be copied and frozen in the "PST BASELINE" memory.
The BASELINE curve can also be done by the PST command, available in the "VIEW and SETUP menu, SETUP, MAINTENANCE, PST cmd" routines. By selecting the option "BASELINE" the PST command causes the PST cycle execution and the collected data are saved in the PST BASELINE memory.
The "PST BASELINE" can be updated only by a new "SET PST BASELINE" command. By the comparison between PST BASELINE and PST curves, the XTE3000 can produce status and warning useful in maintenance operation.
By PC or PDA and DCMlink software tool, the curves can be read from XTE3000 and then visualized and compared in a graph.

Figure 3

Example of PST in opening

PST curve in opening: gray line BASELINE curve: black line

Figure 4

PST curve details

PST curve details

6

PST Curves and Baseline

Installation, Operation and Maintenance Manual Section 6: PST Report and Warning

DTDE 536 Rev. 1

February 2022

Section 6: PST Report and Warning

At the end of PST cycle, the new data collected are compared with the BASELINE and the setpoints "MAX T-PST, MAX PST T-RET, MAX PST OV-TR to produce the following status and warnings:

Table 2. Status Passed Reset T-PST T-RET OV-TR
Failed

Description Test OK
test aborted failed time T-PST
failed time T-RET
PST over-travel at least two of T-PST, T-RET, OV-TR, reset

Warning -
PST T-PST T-RET OV-TR
Failed

Note No message on the
XTE3000 display
See reset conditions
See parameter MAX T-PST
See parameter MAX PST T-RET
See parameter MAX PST OV-TR
-

Warning can be viewed by the local operator interface of XTE3000 or by a PC/PDA connected via Bluetooth interface. Warnings are also recorded in the warning log registers (see Installation, Operation and Maintenance Manual of XTE3000, VIEW and SETUP menu, maintenance routines).

PST Report and Warning

7

Section 7: Remote Signalling
February 2022

Installation, Operation and Maintenance Manual
DTDE 536 Rev. 1

Section 7: Remote Signalling

The following conditions can be individually configured to switch the auxiliary relays As1 - As8.

·

PST active: PST cycle in progress.

·

PST failed: it summarizes T-PST, T-RET, OV-TR and reset. The status of relay "PST failed"

can be reset by a manual reset of warning via actuator local operator interface or

alternatively by a new PST command.

8

Remote Signalling

Installation, Operation and Maintenance Manual Section 8: Local Operator Interface

DTDE 536 Rev. 1

February 2022

Section 8: Local Operator Interface

When PST cycle is in progress, the display of XTE3000 shows the message "PST ON".

PST ON -------------

LOCAL

PST ON -------------

REMOTE next

8.1

The following paragraphs report the instructions to operate with PST function by the Local Operator Interface of XTE3000 (refer to Installation, Operation and Maintenance Manual of XTE3000, Section 9.1.5 for detailed instruction relevant to configuration options.
Procedure to Initiate PST by Local Command

8.2

1.

Move the local selector in OFF and then simultaneously press OPEN and STOP. Select

the language, enter the password and press YES to select SETUP MODE (see Installation,

Operation and Maintenance Manual of XTE3000, Section 9.1.5, Local Controls).

2.

Press NO and again NO until the display shows MAINTENANCE. Press YES.

3.

Press NO to scroll the list of options and press YES when the display shows "PST cmd".

4.

Press YES to confirm "NEW BASELINE disabled", press YES to execute a normal PST cycle,

press NO and then YES to execute a "NEW BASELINE".

5.

Press YES to confirm and then move the local selector in LOCAL.

6.

PST cycle starts, the XTE display shows the message "PST ON".

7.

At the end of PST cycle, the message "PST ON" disappears and actuator is available to

normal operations.

Procedure to Select the BASELINE

1.

Move the local selector in OFF and then simultaneously press OPEN and STOP. Select

the language, enter the password and press YES to select SETUP MODE (see Installation,

Operation and Maintenance Manual of XTE3000, Section 9.1.5, Local Controls).

2.

Press NO and again NO until the display shows MAINTENANCE. Press YES.

3.

Press NO to scroll the list of options and press YES when the display shows "PST REFERENCE".

4.

In the menu SEL. CURVE select the curve number. Press NO to change, press YES to confirm.

The most recent curve is the n° 16 is and the oldest one is the n° 1.

5.

Press YES to confirm. The display shows the message REFERENCE OK. Now the new

BASELINE is the curve selected at the previous step.

6.

The display returns to "SET PST REFERENCE". Press simultaneously YES and NO to exit

from menu.

Local Operator Interface

9

Section 8: Local Operator Interface Installation, Operation and Maintenance Manual

February 2022

DTDE 536 Rev. 1

8.3

Procedure to Set PST Parameters

Move the local selector in OFF and then press simultaneously
OPEN and STOP

Press NO to scroll the list of languages and press YES when
the display shows the desired language
and to switch to next step

Press NO to select SETUP MODE

Enter password

Press YES to select SETUP
MODE

Press YES to select ACTUATOR SETUP and switch to next step

Detailed instructions of XTE3000 menu are in the Installation, Operation and Maintenance Manual of XTE3000, Section 9.1.5, Local Controls.

10

Local Operator Interface

Installation, Operation and Maintenance Manual Section 8: Local Operator Interface

DTDE 536 Rev. 1

February 2022

Press NO to scroll the list of options and press YES when the display shows
"PST SETUP"
Press YES if desired option is MANUAL and switch to next parameter PERIOD
Press NO to change PERIOD. Press YES to set the PERIOD and switch to next parameter HOUR of DAY
Press NO to change PST TRAVEL. Press YES to set the PST TRAVEL and switch to next parameter MAX T-PST
Press NO to change MAX PST T-RET. Press YES
to set the MAX PST T-RET and switch to next parameter PAUSE
Press NO to change MAX
PST OV-TR. Press YES to set the MAX PST OV-TR. and
switch to PST SETUP

Press NO to select PST MODE.
Options available are OFF, MANUAL,
MAN-AUTO
Press YES if desired option is MAN-AUTO and switch to next parameter
PERIOD
Press NO to change HOUR
of DAY. Press YES to set the HOUR of DAY and switch to next parameter
PST TRAVEL
Press NO to change MAX T-PST. Press YES to set the MAX T-PST and switch to next parameter MAX
PST T-RET
Press NO to change PAUSE. Press YES to set the PAUSE and switch to next parameter MAX
PST OV-TR
Press simultaneously YES and NO to
exit from PST SETUP menu

Local Operator Interface

11

World Area Configuration Centers (WACC) offer sales support, service,
inventory and commissioning to our global customers. Choose the WACC or sales office nearest you:

NORTH & SOUTH AMERICA

MIDDLE EAST & AFRICA

19200 Northwest Freeway Houston TX 77065 USA T +1 281 477 4100

P. O. Box 17033 Jebel Ali Free Zone Dubai T +971 4 811 8100

Av. Hollingsworth 325 Iporanga Sorocaba SP 18087-105 Brazil T +55 15 3413 8888
ASIA PACIFIC
No. 9 Gul Road #01-02 Singapore 629361 T +65 6777 8211

P. O. Box 10305 Jubail 31961 Saudi Arabia T +966 3 340 8650
24 Angus Crescent Longmeadow Business Estate East P.O. Box 6908 Greenstone 1616 Modderfontein Extension 5 South Africa T +27 11 451 3700

No. 1 Lai Yuan Road Wuqing Development Area Tianjin 301700 P. R. China T +86 22 8212 3300

EUROPE
Holland Fasor 6 Székesfehérvár 8000 Hungary T +36 22 53 09 50

Strada Biffi 165 29017 Fiorenzuola d'Arda (PC)
Italy
T +39 0523 944 411

For complete list of sales and manufacturing sites, please visit www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com

www.emerson.com/bettis
VCIOM-15051-EN ©2022 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. BettisTM is a mark of one of the Emerson family of companies. All other marks are property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.


MCM Plus Adobe PDF Library 16.0; modified using iTextSharp™ 5.5.10 ©2000-2016 iText Group NV (AGPL-version)