CyTime™ SER-32e Option Module Quick Start Guide

Document Revision: IB-eXM-03, May - 2023

Introduction

The CyTime™ SER-32e Sequence of Events Recorder (SER) is designed to provide precise, time-stamped event reporting for up to 32 input channels. This capability is crucial for enabling root-cause analysis and advanced system diagnostics.

The SER-32e features two (2) expansion module option slots, allowing users to expand its functionality by adding up to 16 additional inputs or up to 16 additional outputs. The available option modules are:

Any combination of these option modules can be utilized within the SER-32e's expansion slots.

Package Contents:

Configuration – Web Interface

Configuration of the CyTime SER-32e Digital Inputs and Relay Outputs can be accomplished using the device's secure web server.

To connect a PC to the SER-32e:

  1. Connect your PC to the SER using a standard Ethernet patch cable.
  2. Set your PC to use a static IP address of 169.254.0.11.
  3. Apply power to the SER.
  4. Open a standard web browser, such as Microsoft™ Edge or Google™ Chrome.
  5. Type the SER's default IP address (169.254.0.10) or the assigned IP address into your web browser.
  6. Enter the default user name (admin) and password (csi_serial number) and click "Login".
  7. Click the "Setup" tab to configure Inputs, Outputs, and Groups.

Technical Specifications

A summary of technical specifications for the input and output modules is provided below. Detailed technical specifications are available in their respective User Guides.

Digital Input Module

ParameterSpecification
Voltage, operating24 Vdc, (-15% to +10%) Class 2 / LPS
Input impedance10K ohms resistive
Current draw (max.)1 mA
Must turn ON voltage20 Vdc
Must turn OFF voltage9 Vdc
Turn ON/OFF time (max.)0.5 ms
Isolation2.5 kV (capacitive isolation)
Wire size supported#24 to #12 AWG
Operating temperature-13°F to 158°F (-25 to +70°C)

[Scan QR code for Digital Input Module Users Guide]

Relay Output Module

ParameterSpecification
Signal typeForm A, normally open
Voltage, operating17.5 to 36 Vdc, (24 Vdc nominal), Class 2 / LPS
Current capacity0.5 A per relay output (2 A per group, 4 A total)
Surge current2 A for 10 seconds, (max.)
Leakage current< 2µ mA at 24 Vdc
ON-state voltage drop< 0.5 volts at 0.5A
Response time< 0.1 ms OFF to ON/ON to OFF
Fault sensingOverload, over-temp.
Fault reportingStatus LED, LCD, web page
Isolation2 kV Output to output, Input to output, Output to Earth 5 kV Output to communications
Wire size supported#24 to #12 AWG
Operating temperature-13°F to 140°F (-25 to +60°C)

[Scan QR code for Relay Output Module Users Guide]

Wiring Overview

Detailed instructions for wiring and installation of Input/Output modules are provided in their respective User Guides.

Digital Input Wiring

The Digital Input Module has 8 isolated digital inputs, each sharing a common return, wired as shown. Control power for the module is provided by the SER.

Diagram Description: Illustration of Digital Input Module wiring. It shows 8 digital inputs (labeled 01 to 08) connected to a common return. Control power is provided by the SER. A note indicates 'Fuse, 1A (Optional)' and '24Vdc, 1mA Class 2 or LPS'.

Wiring Recommendation: 18 AWG (Belden 8760) shielded twisted pair cable is recommended for all input and output connections.

Relay Output Wiring

The Relay Output Module has 8 solid-state relay outputs, each sharing a common return and requiring a 24 Vdc wetting source, wired as shown below. Control power for the module is provided by the SER-32e. Each output is rated for 24 Vdc, 500 mA, max load.

Diagram Description: Illustration of Relay Output Module wiring. It shows 8 solid-state relay outputs (labeled R1 to R8) connected to a common return. A 24 Vdc wetting source is required. Control power is provided by the SER-32e. A note indicates 'Fuse, 4A max (sized per load)' and '24 VDC Class 2 or LPS'.

Wiring Recommendation: 18 AWG (Belden 8760) shielded twisted pair cable is recommended for all input and output connections.

Installation of Option Modules

SER-32e option modules are designed to be mounted in one (1) of the two (2) expansion module option slots provided (refer to the SER-32e front panel diagram, slots #3 - #4). To install an option module, follow the steps below:

  1. Refer to the Safety Precautions section for electrical safety guidance, proper PPE, and procedures.
  2. Remove control power from the SER.
  3. Monitor the LED indicators on the Power Control module until they are all OFF.
  4. Remove the blank cover from the desired option module slot by pressing the two latches on the top and bottom of the cover and pulling it out. It is recommended to retain the cover for future use.
  5. [Scan QR code for installation video]
  6. Align the module in the guide rails with the connector on the right side of the module.
  7. Insert the module into the option slot by pressing it into the SER until the latches "click" into place.
  8. Reapply control power to the SER.
  9. Confirm the SER recognizes the option module by viewing the Monitoring Status screen on either the SER display or web page.

Safety Precautions

⚠️ DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Failure to follow these instructions can result in death or serious injury.

SER-32e Front Panel Diagram Description

Diagram of the SER-32e front panel showing numbered ports:

  1. Ethernet
  2. Time Sync IN or OUT
  3. Expansion Module Slot #1
  4. Expansion Module Slot #2
  5. Power Control Module
  6. Touchscreen
  7. Inputs (32)
  8. Trigger OUT / RS-485
  9. Control Power
Models: CyTime SER-32e Option Module, CyTime SER-32e, Option Module, Module

PDF preview unavailable. Download the PDF instead.

IB-eXM-03 Adobe PDF Library 17.0 Adobe InDesign 18.2 (Macintosh)

Related Documents

Preview Cyber Sciences CyTime SER PTP Field Upgrade Kit Instruction Bulletin
Instructions for installing the PTP Field Upgrade Kit on Cyber Sciences CyTime SER-3200 and SER-2408 Sequence of Events Recorders. Covers firmware updates, license key activation, and PTP configuration.