HydroZone-Instructions-r8
Model 6001
Single Zone Switching Relay
120 VAC Input

Installation Instructions and Operating Manual
· LED INDICATORS · ZONE FAULT INDICATOR · AUTOMATIC CIRCULATOR SHORT CYCLE PROTECTION · AVAILABLE COMMON TERMINAL FOR SMART THERMOSTATS · TEST BUTTON · 10 VA TRANSFORMER TO PROVIDE THERMOSTAT POWER · TWO SPDT RELAYS · FUSED OUTPUTS WITH SPARES INCLUDED · EXTRA L2 TERMINAL FOR EASE OF WIRING

Ratings Output relays .......... 6 Amps per contact Combined outputs.. 12 Amps RWC input .............. 24 VAC, 10 VA Fuses ...................... 16 A, slow blow

Read these instructions completely before proceeding with the installation. Retain instructions for future reference.
WARNING Electrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before installing or servicing control. Only qualified personnel may install or service this control in accordance with local codes and ordinance
WARNING Frozen pipes/water damage. Central heating systems are prone to shut down as a result of power or fuel outages, safety related fault conditions or equipment failure. Installation of freeze protection monitoring or other precautions is recommended for unattended dwellings in climates subject to sustain below-freezing temperatures.
126 Bailey Road · North Haven, CT 06473 · (203) 776-0473 · FAX (203) 764-1711 · www.hydrolevel.com

MOUNTING INSTRUCTIONS
1. Position the enclosure against a flat wall surface or boiler jacket and mark the top center keyhole location A.
2. Start a screw in the marked location and hang the control on the screw.
3. Add screws to the lower right and lower left mounting holes B and tighten all three screws.

A

POWER ZONE

C W R

TEST

LOAD 2

LOAD 1

WIRING
WARNING Electrical shock hazard. To prevent electrical shock,death or equipment damage, disconnect power supply before installing or servicing control. Only qualified personnel may install or service this control in accordance with local codes and ordinances.
All wiring must comply with the National Electric Code or any other state or local codes or regulations.
TERMINAL DESIGNATIONS
Low Voltage/Thermostat R 24 VAC for the thermostat R terminal W 24 VAC for the thermostat W terminal C 24 VAC common for powered thermostats Note: A closed switch between R and W will
create a call for heat and energize the relay outputs.
Line Voltage L1 120 VAC hot L2 120 VAC neutral
Switching Contacts COM1 Common terminal for load 1 NO1 Normally open terminal NC1 Normally closed terminal COM2 Common terminal for load 2 NO2 Normally open terminal NC2 Normally closed terminal

B

B

TYPICAL SINGLE ZONE WIRING
THERMOSTAT
COM T T
C W R
OPTIONAL COMMON

POWER ZONE

C W R

TEST

LOAD 2

LOAD 1

TT
BOILER CONTROL

FACTORY JUMPER
HEATING CIRCULATOR

L2 NEUTRAL L1 HOT

120 VAC

WIRING -- continued

SENSOR

24VAC INPUT

AC1

AC2

POWER ZONE

C W R

TEST

LOAD 2

LOAD 1

INDIRECT TANK WIRING WITH PRIORITY ­ POWERED LIMIT SWITCH
See Terminal Designations on previous page.

BOILER

ZC

CONTROL ZR

FACTORY JUMPER
INDIRECT CIRCULATOR

L2 NEUTRAL

120 VAC

L1 HOT

INDIRECT TANK
THERMOSTAT

INDIRECT TANK WIRING WITH PRIORITY ­ NON-POWERED LIMIT SWITCH
See Terminal Designations on previous page.

POWER ZONE

C W R

TEST

LOAD 2

LOAD 1

FACTORY JUMPER

BOILER

ZC

CONTROL ZR

INDIRECT CIRCULATOR

L2 NEUTRAL L1 HOT

120 VAC

OPERATING INSTRUCTIONS
Operation
A call for heat between terminals R and W will energize both relays at the same time.
LOAD 1 can be used to control a circulator. For convenience, a jumper has been factory installed between terminals L1 and COM1.
LOAD 2 can be used as dry contacts to signal the boiler that there is a call for heat. Terminals COM2 and NO2 are the contacts that will close on a call to R and W.
Note: Both relay outputs are rated for 6 amps so either output, LOAD 1 or LOAD 2 can be used to control a circulator pump.
Test Button
Push the test button on the circuit board to test the output terminal wiring. Pressing the test button will simulate a call on the thermostat input and turn on the "ZONE" LED. The relays will both close to verify the desired operation. When the zone is not calling for heat (by thermostat or test button), the "ZONE" LED will be off.
Zone Fault Indicator
A Blinking "ZONE" LED indicates the zone has been calling for a consecutive 3 hours and has not been satisfied. This could indicate a bad circulator and should be investigated. If the "ZONE" LED is blinking but your circulator is operating per it's instruction manual, please contact tech support.
The LED will only blink when the zone call is a continuous 3 hours and the "ZONE" LED will return to normal operation when the zone call ends.

DIMENSIONS AND LED INDICATORS
Solid "POWER" LED ­ Control is powered up
Solid "ZONE" LED ­ Call for heat
Blinking "ZONE" LED ­ Zone Fault Indicator Zone has been calling for consecutive 3 hours and has not been satisfied. (Could indicate a bad circulator)

POWER ZONE

MODEL 6001

SPARE FUSES INSIDE COVER

LIMITED MANUFACTURER'S WARRANTY

We warrant products manufactured by Hydrolevel Company to be free from defects in material and workmanship for a period of two years from the date of manufacture or one year from the date of installation, whichever occurs first. In the event of any claim under this warranty or otherwise with respect to our products which is made within such period, we will, at our option, repair or replace such products or refund the purchase price paid to us by you for such products. In no event shall

Hydrolevel Company be liable for any other loss or damage, whether direct, indirect, incidental or consequential. This warranty is your EXCLUSIVE remedy and shall be IN PLACE OF any other warranty or guarantee, express or implied, including, without limitation, any warranty of MERCHANTABILITY or fitness for a particular purpose. This warranty may not be assigned or transferred and any unauthorized transfer or assignment thereof shall be void and of no force or effect.

126 Bailey Road · North Haven, CT 06473 · (203) 776-0473 · FAX (203) 764-1711 · www.hydrolevel.com