Instruction Manual for LENNOX models including: LCT Series, LCT Series Rooftop Units, Rooftop Units
stallation instructions and all applicable codes. See acces- sories section ... WI RI NG. SEE I AQ. WI RI NG DI AGRAM. GN. D. MODBUS. CABLE. W/ RJ - 45. 1.
UNIT INFORMATION 100142 Service Literature LCT SERIES 25 & 30 ton LCT302 - 360 With R-454B The LCT302H / 360H (25 and 30 ton) units are configured to order units (CTO) with a wide selection of factory-installed options. Optional electric heat is factory-or field-installed in LCT units. Electric heat operates in single or multiple stages depending on the kW input size. 30kW through 120kW heat sections are available.. Units may contain a supply air blower equipped with a variable frequency drive A96 (VFD) which varies supply air CFM. If the unit must be lifted for service, rig unit by attaching four cables to the holes located in the unit base rail (two holes at each corner). Refer to the installation instructions for the proper rigging technique. WARNING Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance, or an operating electric heater). Do not pierce or burn. Be aware that refrigerants may not contain an odor. WARNING If this appliance is conditioning a space with an area smaller than TAmin or stored in a space with an area smaller than A min as defined by this instruction, then that space must be without continuously operating open flames (e.g. an operating gas appliance) or other potential ignition sources (e.g. an operating electric heater or similar hot surface). A flame-producing device may be installed in the same space if the device is provided with an effective flame arrest system. WARNING Auxiliary devices which may be potential ignition sources shall not be installed in the duct work. Examples of potential ignition sources are hot surfaces with a temperature exceeding 700°C and electric switching components. False ceilings or drop ceiling may be used as a return air plenum only if the unit being installed has a Refrigerant Detection System installed. All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out with work in confined spaces being avoided. Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. Table of Contents Options / Accessories . . . . . . . . . . . . . . . . . . .Page 3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . .Page 7 Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9 Electric Heat / Electrical Data . . . . . . . . . . . . . Page 14 Unit Parts Arrangement . . . . . . . . . . . . . . . . . . Page 19 I-Unit Components . . . . . . . . . . . . . . . . . . . . . . Page 21 RDS Sensors . . . . . . . . . . . . . . . . . . . . . . Page 28 II-Placement and Installation . . . . . . . . . . . . . . .Page 35 III-Start Up - Charging. . . . . . . . . . . . . . . . . . . . Page 35 IV-System Service Checks . . . . . . . . . . . . . . . . Page 42 V-Maintenance . . . . . . . . . . . . . . . .. . . . . . . . . .Page 42 VI-Accessories . . . . . . . . . . . . . . . . . . . . . . . . .Page 44 VII-Decommissioning. . . . . . . . . . . . . . . . . . . . .Page 52 VIII-Wiring and Operation Sequence . . . . . . . . Page 53 Page 1 WARNING To prevent serious injury or death: 1- Lock-out/tag-out before performing maintenance. 2- If system power is required (e.g., smoke detector maintenance), disable power to blower, remove fan belt where applicable, and ensure all controllers and thermostats are set to the "OFF" position before performing maintenance. 3- Always keep hands, hair, clothing, jewelry, tools, etc., away from moving parts. WARNING Only Manufacturer approved auxiliary devices are permitted to be installed in this unit. CAUTION Any service personnel installing, decommissioning, or performing maintenance on the unit must be properly trained with A2L refrigerants. WARNING Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies. WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier. CAUTION As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing. IMPORTANT The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC's and HCFC's) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non-compliance. WARNING · This appliance must be installed in accordance with local and national wiring regulations. · If the appliance is not fitted with an option for full disconnection from power, a means of disconnection must be incorporated in the fixed wiring in accordance with national and local wiring regulations. Page 2 OPTIONS / ACCESSORIES Item Description COOLING SYSTEM Condensate Drain Trap Drain Pan Overflow Switch Stainless Steel Condensate Drain Pan PVC Copper GAS HEAT Combustion Air Intake Extensions (Order 2 Kits) Gas Heat Input LPG/Propane Conversion Kits (Order 2 Kits) Stainless Steel Heat Exchanger Vertical Vent Extension Standard - 260 kBtuh input Medium - 360 kBtuh input High - 480 kBtuh input Standard Heat Medium Heat High Heat BLOWER - SUPPLY AIR Blower Type Motors Drive Kits See Blower Data Tables for usage and selection MSAV® Multi-Stage Air Volume VAV Variable Air Volume Belt Drive (standard efficiency) - 5 HP Belt Drive (standard efficiency) - 7.5 HP Belt Drive (standard efficiency) - 10 HP Supply VFD Blower Bypass Kit #1 740-895 rpm Kit #2 870-1045 rpm Kit #3 715-880 rpm Kit #4 770-965 rpm Kit #5 660-810 rpm Kit #6 770-965 rpm Kit #7 570-720 rpm Kit #8 480-630 rpm Kit #9 410-535 rpm CABINET Combination Coil/Hail Guards Corrosion Protection Horizontal Return Air Panel Kit NOTE - Order numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed Order Number 22H54 76W27 21Z07 83W42 89L97 Factory Factory Factory 14N28 14N29 14N30 Factory 42W16 Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory 13T16 Factory 38K48 Size 302 360 X X X X OX OX OX OX X X O O O O O O X X X X X X O O X X O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O OX OX O O X X Page 3 OPTIONS / ACCESSORIES Item Description Order Number Size 302 360 INDOOR AIR QUALITY Air Filters Healthy Climate® High Efficiency Air Filters MERV 8 54W21 OX OX 20 x 20 x 2 - order 12 per unit MERV 13 52W39 OX OX MERV 16 21U40 X X Replaceable Media Filter with Metal Mesh Frame (includes Non-Pleated Filter Media) 44N60 X X 20 x 20 x 2- order 12 per unit Indoor Air Quality (CO2) Sensors Sensor - Wall-mount, off-white plastic cover with LCD display 77N39 X X Sensor - Wall-mount, off-white plastic cover, no display 23V86 X X Sensor - Black plastic case, LCD display, rated for plenum mounting 87N52 X X Sensor - Black plastic case, no display, rated for plenum mounting 23V87 X X CO2 Sensor Duct Mounting Kit - for downflow applications 23Y47 X X Aspiration Box - for duct mounting non-plenum rated CO2 sensors (77N39) 90N43 X X Needlepoint Bipolar Ionization (NPBI) Needlepoint Bipolar Ionization (NPBI) Kit TBD X X UVC Germicidal Light Kit 1 Healthy Climate® UVC Light Kit (110/230v-1ph) Step-Down Transformers TBD X X 460V primary, 230V secondary 10H20 X X 575V primary, 230V secondary 10H21 X X ELECTRICAL Voltage 60 Hz 208/230V - 3 phase Factory O O 460V - 3 phase Factory O O 575V - 3 phase Factory O O HACR Circuit Breakers Factory O O ² Short-Circuit Current Rating (SCCR) of 100kA (includes Phase/Voltage Detection) O O ³ Disconnect Switch 80 amp 54W85 OX OX 150 amp 54W86 OX OX 250 amp 54W87 OX OX GFI Service 15 amp non-powered, field-wired (208/230V, 460V only) 74M70 OX OX Outlets , 15 amp factory-wired and powered (208/230V, 460V) Factory O O 20 amp non-powered, field-wired (208/230V, 460V, 575V) 67E01 X X 20 amp non-powered, field-wired (575V) Factory O O Weatherproof Cover for GFI 10C89 X X Phase/Voltage Detection Factory O O ELECTRIC HEAT 30 kW 45 kW 60 kW 90 kW 208/230V-3ph 30U68 OX OX 460V-3ph 30U69 OX OX 575V-3ph 30U70 OX OX 208/230V-3ph 30U74 OX OX 460V-3ph 30U75 OX OX 575V-3ph 30U76 OX OX 208/230V-3ph 30U80 OX OX 460V-3ph 30U81 OX OX 575V-3ph 30U82 OX OX 208/230V-3ph 30U83 OX OX 460V-3ph 30U84 OX OX 575V-3ph 30U85 OX OX Lamps operate on 110-230V single-phase power supply. Step-down transformer may be ordered separately for 460V and 575V units. Alternately, 110V power supply may be used to directly power the UVC ballast(s). 1SCCR option is not available if the MOCP of the configured unit is greater than 200A. 2Disconnect Switch is furnished and factory installed with SCCR option 4If a factory installed disconnect switch is ordered with a factory installed GFI, the default disconnect size is 150 amps. 5Unit powered GFI Service Outlets are not available with SCCR option. Disconnect Switch or Circuit Breaker is required with unit powered GFI Service Outlets. 6Canada requires a minimum 20 amp circuit. Select 20 amp, non-powered, field wired GFI. NOTE - Order numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed Page 4 OPTIONS / ACCESSORIES Item Description 7 HUMIDITROL® CONDENSER REHEAT OPTION Humiditrol® Dehumidification Option Order Number Factory Size 302 360 O O ECONOMIZER High Performance Economizer (Approved for California Title 24 Building Standards / AMCA Class 1A Certified) High Performance Economizer 18X87 OX OX Downflow or Horizontal Applications - Includes Outdoor Air Hood, order Downflow or Horizontal Barometric Relief Dampers separately. Economizer Controls Differential Enthalpy (Not for Title 24) Sensible Control Order 2 21Z09 OX OX Sensor is Furnished Factory O O Single Enthalpy (Not for Title 24) Global 21Z09 OX OX Sensor Field Provided Factory O O Building Pressure Control Differential Sensible 13J77 X X Sensor is Furnished Factory O O Outdoor Air CFM Control Barometric Relief Dampers With Exhaust Hood Downflow Barometric Relief Dampers Horizontal Barometric Relief Dampers 13J76 X X 76W17 OX OX 33K78 OX OX OUTDOOR AIR Outdoor Air Dampers With Outdoor Air Hood Motorized Manual 18X89 OX OX 18X88 X X POWER EXHAUST Standard Static, SCCR Rated High Static with VFD 2 HP (731 - 932 rpm) Power Exhaust Control Pressure Transducer Control Available for 302H and 360H models only with MSAV® Multi-Stage Air Volume option. NOTE - Order numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed 208/230V 74W21 OX OX 460V 74W22 OX OX 575V 74W23 OX OX 208/230V 83M89 X X 460V 83M90 X X 575V 83M91 X X 13J77 X X Page 5 OPTIONS / ACCESSORIES Item Description ROOF CURBS Hybrid Roof Curbs, Downflow 14 in. height 18 in. height 24 in. height Standard Roof Curbs, Horizontal - Requires Horizontal Return Air Panel Kit 30 in. height - slab applications 41 in. height - rooftop applications Horizontal Return Air Panel Kit Required for Horizontal Applications with Roof Curb Insulation Kit For Standard Horizontal Curbs For 30 in. Curb For 41 in. Curb CEILING DIFFUSERS Step-Down - Order one Flush - Order one Transitions (Supply and Return) - Order one NOTE - Order numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed Order Number 11F62 11F63 11F64 11T90 11T97 38K48 73K33 73K35 LARTD30/36S LAFD30/36S LASRT30/36 45K74 45K75 33K80 Size 302 360 X X X X X X X X X X X X X X X X X X X X X X Page 6 SPECIFICATIONS 25 TON Model Nominal Tonnage Efficiency Type Blower Type Cooling Gross Cooling Capacity - Btuh Performance 1 Net Cooling Capacity (Btuh) 1 AHRI Rated Air Flow (cfm) Total Unit Power - kW 1 IEER (Btuh/Watt) 1 EER (Btuh/Watt) Sound Rating Number dBA Refrigerant Refrigerant Type Charge Without Circuit 1 Reheat Circuit 2 Circuit 3 Circuit 4 With Circuit 1 Reheat Circuit 2 Circuit 3 Circuit 4 Electric Heat Available Compressor Type (number) Outdoor Net face area - ft.² (total) Coils Number of rows Fins - in. Outdoor Motor HP (number and type) Coil Fans Rpm Watts (total) Diameter (Number) - in. Blades Total Air volume - cfm Indoor Net face area - ft.² (total) Coils Tube diameter - in. Rows Fins - in. Condensate drain size (NPT) - in. Expansion device type 3 Indoor Nominal motor HP Blower Maximum usable motor output (US Only) and Motor - Drive kit number Kit Selection LCT302H5V LCT302H5M 25 Ton 25 Ton High High VAV MSAV® Variable Air Volume Multi-Stage Air Volume 309,000 309,000 300,000 300,000 8200 8200 26.2 26.2 14.3 15.8 11.4 11.4 95 95 R-454B R-454B 6 lbs. 12 oz. 6 lbs. 12 oz. 6 lbs. 8 oz. 6 lbs. 8 oz. 6 lbs. 11 oz. 6 lbs. 11 oz. 6 lbs. 13 oz. 6 lbs. 13 oz. - - - 6 lbs. 12 oz. - - - 6 lbs. 8 oz. - - - 6 lbs. 11 oz. - - - 6 lbs. 13 oz. See page 18 Scroll (4) Scroll (4) 68.3 68.3 1 1 23 23 1/3 (6 PSC) 1/3 (6 PSC) 1075 1075 2500 2500 (6) 24 (6) 24 3 3 21,500 21,500 31.40 31.40 3/8 3/8 4 4 14 14 (1) 1 in. (1) 1 in. Balanced Port Thermostatic Expansion Valve,removable power head 5, 7.5, 10 5.75, 8.63, 11.5 5 HP Kit 5 660-810 rpm Kit 6 770-965 rpm Kit 7 570-720 rpm Kit 8 480-630 rpm Kit 9 410-535 rpm 7.5 HP Kit 3 715-880 rpm Kit 4 770-965 rpm 10 HP Kit 1 740-895 rpm Kit 2 870-1045 rpm Wheel (Number) diameter x width - in. (2) 18 x 15 Filters Type of filter Fiberglass, disposable Number and size - in. (12) 20 x 20 x 2 Line voltage data (Volts-Phase-Hz) 208/230-3-60, 460-3-60, 575-3-60 NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction. Tested at conditions included in with AHRI Standard 340/360; 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static pressure. Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate. Page 7 SPECIFICATIONS 30 TON Model Nominal Tonnage Efficiency Type Blower Type Cooling Gross Cooling Capacity - Btuh Performance 1 Net Cooling Capacity (Btuh) 1 AHRI Rated Air Flow (cfm) Total Unit Power - kW 1 IEER (Btuh/Watt) 1 EER (Btuh/Watt) Sound Rating Number dBA Refrigerant Refrigerant Type Charge Without Circuit 1 Reheat Circuit 2 Option Circuit 3 Circuit 4 With Circuit 1 Reheat Circuit 2 Option Circuit 3 Circuit 4 Electric Heat Available Compressor Type (number) Outdoor Net face area - ft.² (total) Coils Number of rows Fins - in. Outdoor Motor HP (number and type) Coil Fans Rpm Watts (total) Diameter (Number) - in. Blades Total Air volume - cfm Indoor Net face area - ft.² (total) Coils Tube diameter - in. Rows Fins - in. Condensate drain size (NPT) - in. Expansion device type 3 Indoor Nominal motor HP Blower and Kit Maximum usable motor output (US Only) Motor - Drive kit number Selection LCT360H5V LCT360H5M 30 Ton 30 Ton High High VAV Variable Air Volume MSAV® Multi-Stage Air Volume 360,000 360,000 350,000 350,000 8750 8750 32.5 32.5 13.5 14.2 10.8 10.8 95 95 R-454B R-454B 6 lbs. 6 oz. 6 lbs. 6 oz. 6 lbs. 13 oz. 6 lbs. 13 oz. 6 lbs. 10 oz. 6 lbs. 10 oz. 6 lbs. 6 oz. 6 lbs. 6 oz. - - - 7 lbs. 12 oz. - - - 7 lbs. 8 oz. - - - 6 lbs. 14 oz. - - - 6 lbs. 12 oz. See page 18 Scroll (4) Scroll (4) 68.3 68.3 1 1 23 23 1/3 (6 PSC) 1/3 (6 PSC) 1075 1075 2500 2500 (6) 24 (6) 24 3 3 21,500 21,500 31.40 31.40 3/8 3/8 4 4 14 14 (1) 1 in. (1) 1 in. Balanced Port Thermostatic Expansion Valve,removable power head 5, 7.5, 10 5.75, 8.63, 11.5 5 HP Kit 5 660-810 rpm Kit 6 770-965 rpm Kit 7 570-720 rpm Kit 8 480-630 rpm Kit 9 410-535 rpm 7.5 HP Kit 3 715-880 rpm Kit 4 770-965 rpm 10 HP Kit 1 740-895 rpm Kit 2 870-1045 rpm Wheel (Number) diameter x width - in. (2) 18 x 15 Filters Type of filter Fiberglass, disposable Number and size - in. (12) 20 x 20 x 2 Line voltage data (Volts-Phase-Hz) 208/230-3-60, 460-3-60, 575-3-60 NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction. Tested at conditions included in with AHRI Standard 340/360; 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static pressure. Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate. Page 8 BLOWER DATA BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL & AIR FILTERS IN PLACE FOR ALL UNITS ADD: 1 - Wet indoor coil air resistance of selected unit. 2 - Any factory installed options air resistance (heat section, economizer, etc.) 3 - Any field installed accessories air resistance (duct resistance, diffuser, etc.) Then determine from blower table blower motor output and drive required. See page 10 for wet coil and option/accessory air resistance data. See page 10 for factory installed drive kit specifications. Air Volume cfm 0.20 RPM BHP 0.40 RPM BHP 0.60 RPM BHP 0.80 RPM BHP 1.00 RPM BHP TOTAL STATIC PRESSURE - In. w.g. 1.20 1.40 1.60 RPM BHP RPM BHP RPM BHP 1.80 RPM BHP 2.00 RPM BHP 2.20 RPM BHP 2.40 RPM BHP 2.60 RPM BHP 4000 372 0.26 433 0.65 497 0.99 565 1.27 630 1.54 687 1.79 738 2.04 784 2.30 824 2.56 861 2.82 897 3.10 932 3.40 - - - - - - 4500 382 0.41 441 0.79 506 1.12 574 1.41 638 1.69 694 1.95 744 2.22 790 2.50 831 2.77 868 3.05 903 3.35 938 3.66 974 4.01 5000 392 0.56 451 0.93 516 1.25 584 1.55 646 1.85 702 2.12 751 2.41 796 2.70 837 3.00 874 3.30 909 3.61 944 3.93 980 4.30 5500 402 0.73 462 1.08 527 1.40 594 1.72 655 2.02 710 2.31 758 2.61 802 2.92 843 3.24 880 3.56 916 3.88 951 4.22 987 4.60 6000 414 0.89 473 1.24 539 1.56 605 1.90 665 2.21 718 2.51 766 2.83 809 3.16 850 3.51 887 3.84 922 4.18 957 4.52 994 4.91 Page 9 6500 426 1.07 486 1.41 551 1.74 616 2.10 675 2.42 727 2.73 774 3.07 817 3.43 857 3.80 894 4.15 929 4.49 964 4.85 1001 5.24 7000 439 1.26 499 1.60 565 1.93 628 2.31 685 2.64 737 2.97 782 3.34 825 3.72 864 4.11 901 4.48 937 4.83 971 5.19 1008 5.59 7500 453 1.46 513 1.79 579 2.14 641 2.55 696 2.88 747 3.24 792 3.63 833 4.04 872 4.45 909 4.83 945 5.20 979 5.56 1016 5.97 8000 467 1.66 528 2.00 593 2.38 653 2.81 708 3.15 757 3.53 801 3.95 843 4.39 881 4.82 918 5.22 953 5.59 988 5.96 1025 6.37 8500 483 1.88 544 2.22 608 2.65 667 3.10 720 3.44 768 3.85 812 4.30 852 4.78 890 5.22 927 5.63 962 6.01 997 6.39 1034 6.81 9000 499 2.11 561 2.47 624 2.95 681 3.41 733 3.76 780 4.20 823 4.69 862 5.19 900 5.65 936 6.07 972 6.46 1007 6.85 1044 7.28 9500 516 2.36 578 2.75 640 3.26 696 3.73 746 4.10 792 4.58 834 5.11 873 5.64 910 6.12 946 6.54 982 6.93 1018 7.34 1055 7.78 10,000 534 2.64 596 3.06 657 3.60 711 4.07 760 4.48 805 5.00 845 5.57 884 6.12 921 6.61 957 7.03 992 7.43 1028 7.86 1066 8.32 10,500 553 2.93 615 3.39 674 3.95 727 4.44 775 4.90 817 5.46 857 6.06 895 6.62 932 7.12 967 7.55 1003 7.96 1039 8.40 1077 8.89 11,000 572 3.24 634 3.74 692 4.31 744 4.83 789 5.35 830 5.95 869 6.58 907 7.16 943 7.65 978 8.09 1013 8.51 1050 8.98 1089 9.49 11,500 592 3.58 653 4.12 711 4.70 760 5.27 803 5.85 843 6.49 881 7.13 918 7.71 954 8.21 989 8.65 1025 9.10 1062 9.59 1101 10.12 12,000 613 3.95 674 4.53 729 5.14 776 5.75 818 6.39 857 7.06 894 7.71 930 8.30 965 8.80 1000 9.25 1036 9.71 1073 10.22 - - - - - - 12,500 635 4.37 695 4.98 748 5.62 792 6.29 832 6.98 870 7.67 906 8.33 941 8.91 976 9.42 1011 9.87 1048 10.35 - - - - - - - - - - - - 13,000 657 4.83 715 5.50 766 6.18 808 6.89 847 7.61 883 8.32 918 8.98 953 9.56 988 10.06 - - - - - - - - - - - - - - - - - - - - - - - - 13,500 680 5.35 736 6.06 784 6.78 824 7.53 861 8.29 896 9.00 930 9.66 965 10.24 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 14,000 704 5.92 757 6.67 801 7.44 839 8.23 875 9.00 909 9.72 943 10.38 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 14,500 727 6.55 777 7.34 818 8.16 854 8.97 889 9.75 922 10.48 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15,000 750 7.23 797 8.07 834 8.92 868 9.75 902 10.54 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - BLOWER DATA DRIVE KIT SPECIFICATIONS Motor Efficiency Nominal HP Maximum HP Drive Kit Number RPM Range Standard 5 5.75 5 660 - 810 Standard 5 5.75 6 770 - 965 Standard 5 5.75 7 570 - 720 Standard 5 5.75 8 480 - 630 Standard 5 5.75 9 410 - 535 Standard 7.5 8.63 3 715 - 880 Standard 7.5 8.63 4 770 - 965 Standard 10 11.50 1 740 - 895 Standard 10 11.50 2 870 - 1045 NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate. For VFD applications, nominal motor output is also maximum usable motor output. FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE Air Volume cfm Wet Indoor Coil in. w.g. Reheat Coil in. w.g. Gas Heat Exchanger Standard Medium Heat Heat High Heat in. w.g. in. w.g. in. w.g. Filters Economizer Horizontal MERV 8 MERV 13 MERV 16 Roof Curb in. w.g. in. w.g. in. w.g. in. w.g. in. w.g. 4000 0.04 0.04 0.08 0.08 0.11 0.00 0.00 0.00 0.06 0.04 4500 0.04 0.04 0.09 0.10 0.13 0.00 0.00 0.00 0.07 0.05 5000 0.05 0.04 0.10 0.12 0.15 0.00 0.00 0.00 0.08 0.06 5500 0.06 0.06 0.11 0.14 0.17 0.01 0.00 0.01 0.09 0.07 6000 0.07 0.06 0.12 0.16 0.19 0.01 0.00 0.02 0.10 0.08 6500 0.08 0.08 0.13 0.18 0.21 0.01 0.01 0.02 0.11 0.09 7000 0.09 0.08 0.14 0.20 0.24 0.02 0.01 0.03 0.12 0.10 7500 0.10 0.10 0.15 0.21 0.25 0.02 0.01 0.04 0.13 0.11 8000 0.11 0.10 0.17 0.24 0.28 0.02 0.01 0.04 0.14 0.13 8500 0.12 0.10 0.20 0.27 0.31 0.03 0.01 0.04 0.15 0.15 9000 0.13 0.12 0.22 0.29 0.34 0.04 0.01 0.04 0.16 0.17 9500 0.14 0.14 0.24 0.32 0.38 0.04 0.02 0.06 0.17 0.19 10,000 0.15 0.16 0.27 0.36 0.42 0.05 0.02 0.06 0.18 0.21 10,500 0.16 0.17 0.30 0.40 0.46 0.06 0.02 0.06 0.19 0.24 11,000 0.18 0.18 0.33 0.43 0.50 0.07 0.02 0.07 0.20 0.27 11,500 0.19 0.19 0.37 0.48 0.55 0.08 0.02 0.08 0.22 0.30 12,000 0.20 0.20 0.40 0.52 0.60 0.10 0.02 0.08 0.23 0.33 12,500 0.21 0.22 0.44 0.57 0.65 0.11 0.03 0.10 0.24 0.37 13,000 0.23 0.23 0.48 0.61 0.70 0.13 0.03 0.10 0.25 0.40 13,500 0.24 0.25 0.53 0.67 0.76 0.14 0.03 0.11 0.26 0.44 14,000 0.26 0.26 0.57 0.72 0.82 0.16 0.03 0.12 0.27 0.49 14,500 0.27 0.27 0.62 0.78 0.89 0.18 0.04 0.13 0.28 0.53 15,000 0.29 0.29 0.68 0.84 0.95 0.21 0.04 0.13 0.29 0.58 Page 10 BLOWER DATA POWER EXHAUST PERFORMANCE - STANDARD STATIC Return Duct Negative Static Pressure Air Volume Exhausted in. w.g. cfm 0.00 12,800 0.05 12,200 0.10 11,500 0.15 10,800 0.20 9900 0.25 9000 0.30 7900 0.35 6750 0.40 5450 0.45 4150 0.50 2900 POWER EXHAUST - HIGH STATIC Air Volume cfm 8500 Return Duct Negative Static Pressure - In. w.g. 0 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 487 0.43 501 0.44 521 0.46 548 0.49 584 0.53 625 0.58 667 0.64 708 0.70 746 0.75 783 0.81 818 0.87 9000 9500 10,000 10,500 11,000 11,500 12,000 515 0.51 528 0.52 547 0.54 570 0.57 601 0.61 638 0.66 678 0.71 717 0.77 755 0.83 791 0.90 826 0.96 544 0.60 556 0.61 573 0.63 594 0.66 620 0.69 652 0.74 689 0.80 727 0.86 765 0.93 800 0.99 834 1.05 572 0.70 584 0.71 599 0.73 618 0.76 641 0.79 669 0.83 702 0.89 738 0.95 774 1.02 810 1.09 843 1.15 601 0.81 612 0.82 626 0.84 643 0.87 663 0.90 688 0.94 718 0.99 750 1.05 785 1.12 819 1.19 853 1.27 629 0.93 640 0.95 653 0.97 668 0.99 687 1.02 709 1.06 735 1.11 764 1.16 796 1.23 830 1.31 862 1.38 658 1.06 668 1.08 680 1.10 694 1.12 711 1.15 731 1.19 754 1.24 780 1.29 810 1.36 841 1.43 872 1.50 686 1.21 696 1.22 707 1.24 721 1.27 736 1.30 754 1.34 774 1.38 798 1.43 825 1.49 853 1.56 883 1.64 Page 11 BLOWER DATA CEILING DIFFUSER AIR RESISTANCE - in. w.g. Air Volume cfm 2 Ends Open Step-Down Diffuser LARTD30/36S 1 Side/2 Ends Open 7500 0.37 0.31 8000 0.42 0.36 8500 0.48 0.41 9000 0.55 0.47 9500 0.62 0.53 10,000 0.70 0.60 10,500 0.78 0.68 11,000 0.87 0.76 11,500 0.97 0.85 12,000 1.08 0.94 12,500 1.19 1.04 13,000 1.30 1.15 13,500 1.43 1.26 14,000 1.56 1.38 14,500 1.69 1.50 15,000 1.84 1.63 All Ends & Sides Open 0.25 0.29 0.34 0.39 0.45 0.51 0.58 0.65 0.73 0.82 0.91 1.00 1.10 1.20 1.31 1.43 Flush Diffuser LAFD30/36S 0.29 0.34 0.39 0.44 0.51 0.57 0.65 0.72 0.81 0.9 0.99 1.10 1.20 1.31 1.43 1.56 CEILING DIFFUSER AIR THROW DATA - ft. Air Volume cfm 1 Effective Throw Range - ft. Step-Down Flush 9000 40 - 47 29 - 35 9500 43 - 50 33 - 41 10,000 46 - 54 37 - 46 10,500 50 - 58 42 - 51 11,000 53 - 61 46 - 56 11,500 55 - 64 50 - 61 12,000 58 - 67 54 - 66 12,500 61 - 71 58 - 71 13,000 64 - 74 62 - 75 13,500 67 - 77 66 - 79 0 ft. per minute. Four sides open. Throw is the horizontal or vertical distance an airstream travels on leaving the outlet or diffuser before the maximum velocity is reduced to 5 Page 12 MINIMUM R454B SPACE AND CFM REQUIREMENTS Unit LCT/LGT302 Minimum Airflow Qmin(CFM) 178 Qmin(m³h) 303 LCT/LGT360 169 286 ¹ NOTE - The minimum airflow is the lowest CFM allowed during venting operation (leak mitigation). Minimum Room Area of Conditioned Space Unit LCT/LGT302 TAmin(ft²) 99 TAmin(m²) 9.19 LCT/LGT360 94 8.68 ² NOTE - The minimum room area of conditioned space is the smallest area the unit can service. Refrigerant Charge R-454B Unit LGT/LCT302 Stage 1 Mc(lbs) 6.75 LGT/LCT302 Stage 2 6.50 LGT/LCT302 Stage 3 6.69 LGT/LCT302 Stage 4 6.81 LGT/LCT360 Stage 1 6.38 LGT/LCT360 Stage 2 6.81 LGT/LCT360 Stage 3 6.63 LGT/LCT360 Stage 4 6.38 Mc(kg) 3.06 2.95 3.03 3.09 2.89 3.09 3.01 2.89 Altitude Adjustment Factor Halt 0 200 400 600 800 1000 1200 1400 1600 AF 1 1 1 1 1.02 1.05 1.04 1.1 1.12 Halt 1600 1800 2000 2200 2400 2600 2800 3000 3200 AF 1.12 1.15 1.18 1.21 1.25 1.28 1.32 1.36 1.4 ³ NOTE - Use the Altitude Adjustment Factor to adjust the values in the tables above to different altitudes. Find the relevant altitude above sea level in the two "Halt" rows and then multiply the value needed from the tables above by the altitude factor number. Example: For the minimum airflow in CFM for an LCT/LGT302 at 1000 ft. above see level, multiply 178 by 1.05 to get 186.9 CFM as the new Qmin. Page 13 ELECTRICAL DATA Model 1 Voltage - 60Hz 208/230V - 3 Ph Compressor 1 Rated Load Amps 22.4 Locked Rotor Amps 166.2 Compressor 2 Rated Load Amps 22.4 Locked Rotor Amps 166.2 Compressor 3 Rated Load Amps 22.4 Locked Rotor Amps 166.2 Compressor 4 Rated Load Amps 22.4 Locked Rotor Amps 166.2 Outdoor Fan Full Load Amps (6 Non-ECM) 2.4 Motors (6) Total 14.4 Standard Power Exhaust (3) 0.33 HP Full Load Amps 2.4 Total 7.2 High Static Power Exhaust (3) 2 HP Full Load Amps 7.5 Total 22.5 Service Outlet 115V GFI (amps) 15 Indoor Blower Motor HP 5 7.5 10 Full Load Amps 16.7 24.2 30.8 2 Maximum Overcurrent Protection (MOCP) Unit Only 150 150 150 With (3) 0.33 HP 150 150 175 Standard Power Exhaust With High Static 150 175 175 Power Exhaust (3) 2 HP 3 Minimum Circuit Ampacity (MCA) Unit Only 127 135 143 With (3) 0.33 HP 134 142 150 Standard Power Exhaust With High Static 149 157 165 Power Exhaust (3) 2 HP NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. Extremes of operating range are 0% plus and minus 1 of line voltage. HACR type breaker or fuse. Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. LCT302H5M, LCT302H5V 460V - 3 Ph 9.1 74.6 9.1 74.6 9.1 74.6 9.1 74.6 1.3 7.8 1.3 3.9 3.4 10.2 15 5 7.5 10 7.6 11 14 60 60 70 60 70 70 70 70 80 55 58 62 58 62 66 65 69 72 25 TON 575V - 3 Ph 7.2 54 7.2 54 7.2 54 7.2 54 1 6 1 3 2.7 8.1 20 5 7.5 10 6.1 9 11 45 50 50 50 50 60 60 60 60 43 47 49 46 50 52 51 55 57 Page 14 ELECTRIC HEAT DATA Model LCT302H5M, LCT302H5V 25 TON 1 Voltage - 60Hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph Indoor Blower Motor - HP 5 7.5 10 5 7.5 10 5 7.5 10 Electric Heat Voltage 208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V 2 Maximum Unit+ 30 kW 150 150 150 150 150 150 60 60 70 45 50 50 Overcurrent Electric Heat Protection 45 kW 4 150 175 4 150 175 175 175 80 90 90 70 70 70 (MOCP) 60 kW 4 150 175 175 175 4 175 200 90 90 90 70 70 80 90 kW 4 225 250 4 225 250 4 250 4 300 125 125 150 100 100 110 3 Minimum Circuit Ampacity (MCA) Unit+ 30 kW 127 127 135 135 143 143 55 59 63 44 48 50 Electric Heat 45 kW 139 157 148 166 156 174 78 82 86 62 66 68 60 kW 146 166 156 175 164 183 82 86 90 66 69 72 90 kW 209 238 218 247 227 256 118 123 126 95 98 101 2 Maximum Unit+ 30 kW 150 150 150 150 175 175 60 70 70 50 60 60 Overcurrent Electric Heat Protection and Standard 45 kW 4 150 175 175 175 4 175 200 90 90 100 70 70 80 (MOCP) Power Exhaust (3) 0.33 HP 60 kW 175 175 4 175 200 4 175 200 90 100 100 70 80 80 90 kW 4 225 250 4 250 4 300 4 250 4 300 125 150 150 100 110 110 3 Minimum Unit+ 30 kW 134 134 142 142 150 150 60 64 68 48 52 54 Circuit Electric Heat Ampacity and Standard 45 kW 148 166 157 175 165 183 83 87 91 66 70 72 (MCA) Power Exhaust (3) 0.33 HP 60 kW 155 175 165 184 173 192 87 91 95 70 73 76 90 kW 218 247 227 256 236 265 123 127 131 98 102 105 2 Maximum Unit+ 30 kW 150 150 175 175 175 175 70 80 80 60 60 60 Overcurrent Electric Heat Protection and High Static 45 kW 4 175 200 200 200 4 200 225 90 100 100 80 80 80 (MOCP) Power Exhaust (3) 2 HP 60 kW 4 175 200 4 200 225 4 200 225 100 100 110 80 80 90 90 kW 4 250 4 300 4 250 4 300 300 4 300 150 150 150 110 110 125 3 Minimum Circuit Ampacity (MCA) Unit+ 30 kW 149 149 157 157 165 165 68 72 76 54 58 60 Electric Heat and High Static 45 kW 167 185 176 194 184 202 90 95 98 72 76 79 Power Exhaust (3) 2 HP 60 kW 175 194 184 203 192 211 95 99 103 76 80 82 90 kW 237 266 247 275 255 284 131 135 139 105 108 111 Extremes of operating range are plus 0% and minus 1 of line voltage. HACR type breaker or fuse. Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Factory installed circuit breaker not available. Page 15 ELECTRICAL DATA Model LCT360H5M, LCT360H5V 1 Voltage - 60Hz 208/230V - 3 Ph 460V - 3 Ph Compressor 1 Rated Load Amps 30.9 12.8 Locked Rotor Amps 178.5 103 Compressor 2 Rated Load Amps 30.9 12.8 Locked Rotor Amps 178.5 103 Compressor 3 Rated Load Amps 30.9 12.8 Locked Rotor Amps 178.5 103 Compressor 4 Rated Load Amps 30.9 12.8 Locked Rotor Amps 178.5 103 Outdoor Fan Full Load Amps (6 Non-ECM) 2.4 1.3 Motors (6) Total 14.4 7.8 Standard Full Load Amps 2.4 1.3 Power Exhaust (3) 0.33 HP Total 7.2 3.9 High Static Full Load Amps 7.5 3.4 Power Exhaust (3) 2 HP Total 22.5 10.2 Service Outlet 115V GFI (amps) 15 15 Indoor Blower Motor HP 5 7.5 10 5 7.5 10 Full Load Amps 16.7 24.2 30.8 7.6 11 14 2 Maximum Overcurrent Protection (MOCP) Unit Only 175 200 200 80 80 90 With (3) 0.33 HP 200 200 200 80 80 90 Standard Power Exhaust With High Static 200 200 225 90 Power Exhaust (3) 2 HP 90 100 3 Minimum Circuit Ampacity (MCA) Unit Only 163 170 177 70 74 77 With (3) 0.33 HP 170 178 184 74 78 81 Standard Power Exhaust With High Static 185 193 200 80 84 87 Power Exhaust (3) 2 HP NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. Extremes of operating range are 0% plus and minus 1 of line voltage. HACR type breaker or fuse. Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 30 TON 575V - 3 Ph 10.1 78 10.1 78 10.1 78 10.1 78 1 6 1 3 2.7 8.1 20 5 7.5 10 6.1 9 11 60 60 70 60 70 70 70 70 70 56 58 61 59 61 64 64 67 69 Page 16 ELECTRIC HEAT DATA Model LCT360H5M, LCT360H5V 30 TON 1 Voltage - 60Hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph Indoor Blower Motor - HP 5 7.5 10 5 7.5 10 5 7.5 10 Electric Heat Voltage 208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V 2 Maximum Unit+ 30 kW 175 175 200 200 200 200 80 80 90 60 60 70 Overcurrent Electric Heat Protection 45 kW 175 175 200 200 200 200 80 90 90 70 70 70 (MOCP) 60 kW 175 175 200 200 200 200 90 90 90 70 70 80 90 kW 4 225 250 4 225 250 4 250 4 300 125 125 150 100 100 110 3 Minimum Circuit Ampacity (MCA) Unit+ 30 kW 163 163 170 170 177 177 70 74 77 56 58 61 Electric Heat 45 kW 163 163 170 170 177 177 78 82 86 62 66 68 60 kW 163 166 170 175 177 183 82 86 90 66 69 72 90 kW 209 238 218 247 227 256 118 123 126 95 98 101 2 Maximum Unit+ 30 kW 200 200 200 200 200 200 80 80 90 60 70 70 Overcurrent Electric Heat Protection and Standard 45 kW 200 200 200 200 200 200 90 90 100 70 70 80 (MOCP) Power Exhaust (3) 0.33 HP 60 kW 200 200 200 200 200 200 90 100 100 70 80 80 90 kW 4 225 250 4 250 4 300 4 250 4 300 125 150 150 100 110 110 3 Minimum Circuit Ampacity (MCA) Unit+ 30 kW 170 170 178 178 184 184 74 78 81 59 61 64 Electric Heat and Standard 45 kW 170 170 178 178 184 184 83 87 91 66 70 72 Power Exhaust (3) 0.33 HP 60 kW 170 175 178 184 184 192 87 91 95 70 73 76 90 kW 218 247 227 256 236 265 123 127 131 98 102 105 2 Maximum Unit+ 30 kW 200 200 200 200 225 225 90 90 100 70 70 70 Overcurrent Electric Heat Protection and High Static 45 kW 200 200 200 200 225 225 90 100 100 80 80 80 (MOCP) Power Exhaust (3) 2 HP 60 kW 200 200 4 200 225 225 225 100 100 110 80 80 90 90 kW 4 250 4 300 4 250 4 300 300 4 300 150 150 150 110 110 125 3 Minimum Circuit Ampacity (MCA) Unit+ 30 kW 185 185 193 193 200 200 80 84 87 64 67 69 Electric Heat and High Static 45 kW 185 185 193 194 200 202 90 95 98 72 76 79 Power Exhaust (3) 2 HP 60 kW 185 194 193 203 200 211 95 99 103 76 80 82 90 kW 237 266 247 275 255 284 131 135 139 105 108 111 Extremes of operating range are plus 0% and minus 1 of line voltage. HACR type breaker or fuse. Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Factory installed circuit breaker not available. Page 17 ELECTRIC HEAT CAPACITIES Volts Input 30 kW kW Input Btuh Output 45 kW Stages kW Input Btuh Output 208 22.5 76,800 1 33.8 115,300 220 25.2 86,000 1 37.8 129,000 230 27.5 93,900 1 41.3 141,000 240 30.0 102,400 1 45.0 153,600 440 25.2 86,000 1 37.8 129,000 460 27.5 93,900 1 41.3 141,000 480 30.0 102,400 1 45.0 153,600 550 25.2 86,000 1 37.8 129,000 575 27.5 93,900 1 41.3 141,000 600 30.0 102,400 1 45.0 153,600 60 kW Stages kW Input Btuh Output 2 45.0 153,600 2 50.4 172,000 2 55.1 188,000 2 60.0 204,800 2 50.4 172,000 2 55.1 188,000 2 60.0 204,800 2 50.4 172,000 2 55.1 188,000 2 60.0 204,800 90 kW Stages kW Input Btuh Output 2 67.6 230,700 2 75.6 258,000 2 82.7 282,200 2 90.0 307,100 2 75.6 258,000 2 82.7 282,200 2 90.0 307,100 2 75.6 258,000 2 82.7 282,200 2 90.0 307,100 Stages 2 2 2 2 2 2 2 2 2 2 Page 18 PARTS ARRANGEMENT BLOWERS FILTERS EVAPORATOR (TWELVE - 20 X 20 X 2") COIL ECONOMIZER DAMPERS (OPTIONAL) BLOWER MOTOR REHEAT COIL BLOWER INVERTER UNIT CONTROLLER 4 8.8.8.8 3 1 2 CONDENSATE DRAIN DISCONNECT (FACTORY-INSTALLED OPTION) ELECTRIC HEAT FIGURE 1 CONDENSER FANS (6) CONDENSER COILS COMPRESSORS Page 19 CONTROL BOX TB13 K203 F10 K2 K146 C20 K150 A55 A178 T1 T18 A96 K202 K3 S42 K1 K14 K65 C19 K152 K10 T3 A173 A3 K262 TB25 T13 T49 A12 K9 or K125 LGT ONLY A3 CONTROL, BURNER 1 LGT ONLY A12 CONTROL, BURNER 2 A55 CONTROL, M4 A178 CONTROL, C4 A96 CONTROL INVERTER, BLOWER A173 CONTROL, SMOKE DETECTOR C1 CAPACITOR, OUTDOOR FAN 1 C2 CAPACITOR, OUTDOOR FAN 2 C18 CAPACITOR, OUTDOOR FAN 3 C19 CAPACITOR, OUTDOOR FAN 4 C20 CAPACITOR, OUTDOOR FAN 5 C21 CAPACITOR, OUTDOOR FAN 6 F6 FUSE, EXHAUST FAN F10 FUSE, COMPONENT K1 K2 K14 K146 CONTACTOR, COMPRESSOR 1 CONTACTOR, COMPRESSOR 2 CONTACTOR, COMPRESSOR 3 CONTACTOR, COMPRESSOR 4 FIGURE 2 Page 20 C1 C2 C18 K231 F6 C21 K153 K149 K68 K3 CONTACTOR, BLOWER LCT ONLY K9 RELAY, ELECTRIC HEAT K10 K68 K149 K150 K252 K153 RELAY, OUTDOOR FAN 1 RELAY, OUTDOOR FAN 2 RELAY, OUTDOOR FAN 3 RELAY, OUTDOOR FAN 4 RELAY, OUTDOOR FAN 5 RELAY, OUTDOOR FAN 6 K65 RELAY, EXHAUST FAN K231 RELAY, EXHAUST FAN 2 LGT FIELD INSTALLED K125 RELAY, LO W TEMP VEST HEATER 1 LGT FIELD INSTALLED K262 RELAY, LOW TEMP VEST HEATER 2 K202 CONTACTOR, INVERTER K203 RELAY, INVERTER CONTROL S42 OVERLOAD PROTECTOR, BLOWER MOTOR T1 LGT ONLY T3 LGT ONLY T13 T18 TRANSFORMER, CONTROL TRANSFORMER, COMBUSTION AIR BLOWER 1 TRANSFORMER, COMBUSTION AIR BLOWER 2 TRANSFORMER, CONTACTOR T49 TRANSFORMER, UV TB13 TERMINAL STRIP, POWER DISTRIBUTION TB25 TERMINAL STRIP,BLOWER I-UNIT COMPONENTS ELECTROSTATIC DISCHARGE (ESD) Precautions and Procedures CAUTION Electrostatic discharge can affect electronic components. Take precautions to neutralize electrostatic charge by touching your hand and tools to metal prior to handling the control. Units are configure to order units (CTO). Unit components are shown in .FIGURE 1. All units come standard with hinged unit panels. The unit panels may be held open with the door rod located inside the unit. All L1, L2, and L3 wiring is color coded; L1 is red, L2 is yellow, and L3 is blue. A-Control Box Components Control box components are shown in FIGURE 2, The control box is located in the upper left portion of the compressor compartment. 1-Disconnect Switch S48 (Optional all units) All units may be equipped with an optional disconnect switch S48. Other factory or field installed optional circuit breakers may be used, such as CB10. S48 and CB10 are toggle or twist-style switches, which can be used by the service technician to disconnect power to the unit. 2-Transformer T1 (all units) All units use a single line voltage to 24VAC transformer mounted in the control box. Transformer supplies power to control circuits in the unit. The transformer is rated at 70VA and is protected by a 3.5 amp circuit breaker (CB8). The 208/230 (Y) voltage transformers use two primary voltage taps as shown in figure 3, while 460 (G) and 575 (J) voltage transformers use a single primary voltage tap. 208/230V TRANSFORMER BLUE YELLOW SECONDARY 208 VOLTS RED 230 VOLTS ORANGE PRIMARY BLACK FIGURE 3 3-Transformer T18 T18 is a single line voltage to 24VAC transformer used in all units. Transformer T18 is protected by a 3.5 amp circuit breaker (CB18). T18 is identical to transformer T1. The transformer supplies 24VAC power to the contactors. 4-C. A. B. Transformers T3 & T13 (575V) All LCT 575 (J) voltage units use transformer T3 and T13. The auto voltage to 230VAC transformers are located in the control box. The transformers have an output rating of 0.75A. T3 transformer supplies 230VAC power to combustion air blower motor (B6) while T13 transformer supplies power to combustion air blower motor (B15) in all units. T3 and T13 also provide 230VAC to optional ultraviolet germicidal (UVC) lamps. 5-Terminal Block TB13 TB13 terminal block distributes line voltage power to the line voltage items in the unit. 6-Terminal Block TB2 When unit is not equipped with an optional S48 disconnect switch, supply power is connected to TB2. 7-Outdoor Fan Motor Fuse Block & Fuses F10 and Power Exhaust Fan Motor Fuse Block and Fuses F6 (240 & 300 Y Volt Only) Three line voltage fuses, F10, provide overcurrent protection to all condenser fans. Two line voltage fuses, F6, provide overcurrent protection to the two optional power exhaust fans. The fuses are rated at 30A in 208/230V units. 8-Fuses F4 Fuse F4 is used only with single point power supply. F4 provides overcurrent protection to the compressor and other cooling components. Note - F4, S48 and TB2 are located inside a sheet metal enclosure in the unit front left corner mullion. 9-Outdoor Fan Capacitors C1, C2, C18, C19,C20, C21 Fan capacitors C1, C2, C18, C19, C20 and C21 are 370V / 10 MFD capacitors used to assist in the start up of condenser fans B4, B5, B21, B22, B23 and B24. respectively. 10-Compressor Contactors K1, K2, K14, K146 All compressor contactors are three pole double break contactors with a 24VAC coil. In all units, K1, K2, K14 and K146 energize compressors B1, B2, B13, and B20 respectively. ELECTRIC HEAT CONTROL SECTION (30 - 90 kW electric heat only) 11-Electric Heat Relay K9 All unit equipped with optional electric heat use an electric heat relay K9. K9 is a N.O. SPST pilot relay intended to electrically interlock operation of left and right side electric heat sections. K9 is energized by the A55 Unit Controller. Page 21 12-Blower Contactor K3 Blower contactor K3, is a three-pole-double-break contactor with a 24VAC coil used to energize the indoor blower motor B3 in response to blower demand. 13-Outdoor Fan Relay K10, K68, K149, K150, K152, K153 Outdoor fan relays K10, K68, K149, K150, K152 and K153 used in all units, are DPDT relays with a 24VAC coil. In all units, K10 energizes fan 1 (B4), K68 energizes fan 2 (B5), K149 energizes fan 3 (B21), K150 energizes fan 4 (B22), K152 energizes fan 5 (B23) and K153 energizes fan 6 (B24). 14-Power Exhaust Relay K65 (PEF units) Power exhaust relay K65 is a N.O. DPDT relay with a 24VAC coil. K65 is used in all units equipped with optional power exhaust fans. K65 is energized by the Unit Controller (A55). 15-Blower Motor Overload Relay S42 The blower motor overload relay is used in all units equipped with M-volt unit blower motors manufactured before Dec. 19, 2010 as well as units with standard efficiency motors of 10 HP. The relay (S42) is connected in line with the blower motor to monitor the current flow to the motor. When the relay senses an overload condition, a set of normally closed contacts open to de-energize pin #4 in plug P299 of the A55 Unit Controller. A55 de-energizes all outputs. Units will be equipped with a relay manufactured by Telemecanique figure 4 or Siemens figure 5. 16-Ultraviolet Germicidal Lamp (UVC) and Transformer T49 UVC transformer T49 is used by units of all voltages except 208/230V. 575V LCT which are equipped with a UVC. The auto voltage to 230VAC transformer is installed in the control box. The transformer has an output rating of 0.75 amps. T49 transformer supplies 230VAC power to the UVC lamp. 17-Unit Controller A55 (all units) The Unit Controller provides all unit control functions, unit status information, unit diagnostics, programmable parameters and USB verification and profile sharing. Refer to the Unit Controller guide provided with the unit. Thermostat wires are connected to J297 on the Unit Controller . TRIP INDICATION WINDOW AMP SETTING POINTER AMP SETTING CONTROL (BLUE DIAL) LINE VOLTAGE IN TELEMECANIQUE OVERLOAD RELAY CLEAR COVER (SHOWN CLOSED) STOP BUTTON (RED) DETAIL SHOWING RESET BUTTON ADJUSTED TO MANUAL POSITION Lift clear cover and turn adjustment screw counterclockwise. Reset screw will pop out when pointer is in M (manual position). Close cover to lock reset screw into position. RED TEST BUTTON (Push To Test) BLUE RESET SCREW (Shown in AUTO position as LOAD VOLTAGE shipped from the factory) OUT Lift clear cover to adjust relay amp setting according to value given on the blower motor nameplate. Proper relay amp setting equals motor nameplate FLA X service factor of 1.15 X .95. Cover must also be lifted to adjust control mode from automatic reset to manual reset (see detail above) and to test the control. ton. A yellow marker should appear in the trip indication window to the right of the amp setting control. Press the blue reset screw to reset the relay. The red STOP button opens the normally closed contacts which power the blower motor. This button stops blower motor operation as long as it is pressed in. FIGURE 4 SIEMENS OVERLOAD RELAY BLUE RESET BUTTON IN FACTORY-SET AUTO MODE (Turn clockwise to H for manual reset) GREEN TRIP INDICATOR (Flush with surface -- not tripped; Above surface -- tripped) TON AMP ADJUSTMENT DIAL Adjust relay amp setting according to value given on the blower motor nameplate. Proper relay amp setting equals motor nameplate FLA X service factor of 1.15 X .95. Use small slotted screwdriver to adjust control mode from automatic reset (A) to manual reset (H). Control must be in the manual reset mode (H) to perform a test. Press the red test button. Green trip indicator should pop out. Press the blue reset screw to reset the relay. FIGURE 5 18-Compressor 3 & 4 Control Module A178 (all units) The compressor 3 & 4 control module A178 controls two additional compressor stages. A178 includes all inputs and outputs required for compressor and fan control, compressor stage diagnostics, and low ambient control. Page 22 Relative Humidity Sensor - Optional Economizer Differential Pressure Sensor - Optional The indoor relative humidity sensor (A91) is an analog sensor with a 0-10VDC output over a relative humidity range of 0-100% relative humidity. The sensor is powered with 24VAC. Enthalpy Sensor - Optional Rooftop units installed with Smart AirflowTM will have a Pressure Transducer (PT5) present in the economizer. PT5 requires 5VDC power supply (P266-5 and {P2666) and gives 0.25 VDC to 4 VDC output (P266-4) corresponding to 0" water column and 2" water column respectively. For all practical purposes the output should be less The optional enthalpy sensors (A7 and A63) used with the economizer have an output of 4-20mA. The sensor is powered with 18VAC provided by M3 unit control. than 1.2" water column if not an error code is stored and service alarm output is turned on. Temperature Sensors The return air (RT16) and discharge air (RT6) duct probes and the outdoor air (RT17) are all two wire thermistors. The resistance vs. temperature table is shown below: TABLE 1 Resistance vs. Temperature Temp. °F (°C) Resistance +/-2% Temperature °F (°C) Resistance +/-2% Temp. °F (°C) Resistance +/-2% -40 (-40) 335,671 40 (4.4) 26,106 90 (32.2) 7,332 -20 (-28.9) 164,959 50 (10) 19,904 100 (37.8) 5,826 0 (-17.8) 85,323 60 (15.6) 15,313 120 (48.9) 3,756 20 (-6.7) 46,218 70 (21.1) 11,884 130 (54.4) 3,047 30 (-1.1) 34,566 80 (26.7) 9,298 Room Sensors Room sensor (A2) is a two-wire thermistor with 1k series resistor. Temp. °F (°C) 40 (4.4) 45 (7.2) 50 (10) 55 (12.8) Resistance +/-2% 27,102 23,764 20,898 18,433 TABLE 2 Two-Wire Thermistor Temperature °F (°C) Resistance +/-2% 60 (15.6) 16,313 65 (18.3) 14,474 70 (21.1) 12,882 75 (23.9) 11,498 Temp. °F (°C) 80 (26.7) 85 (29.4) 90 (32.2) Resistance +/-2% 10,299 9,249 8,529 Carbon Dioxide Sensor The indoor carbon dioxide sensor (A63) is an analog sensor with a 0-10VDC output over a carbon dioxide range of 0-2000 ppm as shown in the following table. The sensor is powered with 24VAC. Carbon Dioxide PPM 0 200 400 DC Voltage 0 1 2 Carbon Dioxide PPM 600 800 1000 TABLE 3 Carbon Dioxide Range DC Voltage Carbon Dioxide PPM 3 1200 4 1400 5 1600 DC Voltage 6 7 8 Carbon Dioxide PPM 1800 2000 DC Voltage 9 10 VAV Supply Static Sensor The supply duct differential static pressure sensor (A30) is an analog sensor with a 0-10VDC output over a range of 0-5"w.c as shown in the following table. The sensor is powered with 24VAC. Pressure "w.c. 0 0.5 1 DC Voltage 0 1 2 Pressure "w.c. 1.5 2 2.5 TABLE 4 Carbon Dioxide Range DC Voltage Pressure "w.c. 3 3 4 3.5 5 4 DC Voltage 6 7 8 Pressure "w.c. 4.5 5 DC Voltage 9 10 Page 23 LIQUID LINES (4) CIRCUIT 4 (S96) CIRCUIT 2 (S88) CIRCUIT 3 (S98) CIRCUIT 4 (S97) CIRCUIT 3 (S28) CIRCUIT 2 (S7) CIRCUIT 1 (S4) CIRCUIT 1 DISCHARGE LINE DISCHARGE PRESSURE TAP LOW PRESSURE SWITCH (S87) SUCTION PRESSURE TAP SUCTION LINE FIGURE 6 Page 24 B-Cooling Components FIGURE 6 All units use independent cooling circuits consisting of separate compressors, condenser coils and evaporator coils. Six draw-through type condenser fans are used in all units. All units are equipped with belt-drive blowers which draw air across the evaporator during unit operation. Cooling may be supplemented by a factory- or field-installed economizer. The evaporators are slab type and are stacked. Each evaporator uses a thermostatic expansion valve as the primary expansion device. Each evaporator is also equipped with enhanced fins and rifled tubing. In all units each compressor is protected by a crankcase heater, high pressure switch and low pressure switch. Additional protection is provided by low ambient switches and freezestats (on each evaporator). 1-Compressors B1, B2, B13, B20 WARNING Electrical shock hazard. Compressor must be grounded. Do not operate without protective coverover terminals. Disconnect power before removing protective cover. Discharge capacitors before servicing unit. Failure to follow these precautions could cause electrical shock resulting in injury or death. All units use four scroll compressors. Compressor capacity may vary from stage to stage. In all cases, the capacity of each compressor is added to reach the tota capacity of the unit. Compressor electrical specifications can be found in the SPECIFICATIONS section in this manual. Each compressor is energized by a corresponding compressor contactor. NOTE-Refer to the wiring diagram section for specific unit operation. If a compressor replacement is necessary, call 1-800-4536669. IMPORTANT Some scroll compressors have an internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system rises above 40 psig. DO NOT REPLACE COMPRESSOR. 2-Crankcase Heaters HR1, HR2, HR5, HR11 All units use bellyband-type crankcase heaters. Heater HR1 is installed around compressor B1, heater HR2 compressor B2, HR5 compressor B13, and HR11 compressor B20. Crankcase heater wattage varies by compressor size. 3-High Pressure Switches S4, S7, S28, S96 The high pressure switch is an auto-reset SPST N.C. switch which opens on a pressure rise. All units are equipped with this switch. The switch is located in the liquid line and is wired in series with the compressor contactor coil through A55 Unit Controller or A178 Compressor 3 and 4 Controller. S4 (first circuit), S7 (second circuit), S28 (third circuit), and S96 (fourth circuit) are wired in series with the respective compressor contactor coils. When liquid pressure rises to 610 ± 15 psig (4206 ± 103 kPa) (indicating a problem in the system) the switch opens and the respective compressor is de-energized (the economizer can continue to operate). When liquid pressure drops to 475 ± 15 psig (3275 ± 103 kPa) the pressure switch will close. Unit Controller A55 has a three-strike counter before locking out the particular compressor circuit. This means the control allows three high pressure trips per one thermostat demand. The control can be reset by breaking and remaking the thermostat demand or manually resetting the control. Page 25 5-Low Pressure Switches S87, S88, S98, S97 The low pressure switch is an auto-reset SPST N.O. switch (held N.C. by refrigerant pressure) which opens on a pressure drop. All units are equipped with this switch. The switch is located in the compressor suction line. S87 (compressor one), S88 (compressor two), S98 (compressor three), and S97 (compressor four) are wired in series with the contactor coils through the A55 Unit Controller. The Unit Controller A55 governs the low pressure switches by shunting the switches during start up until pressure is stabilized. After the shunt period, the control has a threestrike counter, during first thermostat demand, before the compressor is locked out. The control is reset by breaking and remaking the thermostat demand or manually resetting the control. When suction pressure drops to 40 + 5 psig (276 ± 34 kPa) (indicating low pressure), the switch opens and the compressor is de-energized. The switch automatically resets when pressure in the suction line rises to 90 + 5 psig (620 ± 34 kPa), due to many causes such as refrigerant being added. 6-Filter Drier (all units) All units have a filter drier located in the liquid line of each refrigerant circuit at the exit of each condenser coil. The drier removes contaminants and moisture from the system. 7-Condenser Fans B4, B5, B21, B22, B23, B24 See Specifications section in this manual for specifications of condenser fans. All condenser fans used have singlephase motors. All units are equipped with six condenser fans. The complete fan assembly may be removed for servicing and cleaning by removing the fan grill and turning the complete assembly until the motor brackets line up with the notches in the top panel. Lift the fan assembly out of the unit and disconnect the jack plug located on the motor. VARIABLE AND STAGED SUPPLY AIR UNIT REFRIGERANT CIRCUITS CIRCUIT 4 CIRCUIT 3 EVAPORATOR COIL EVAPORATOR COIL FIGURE 7 CONDENSER COIL CONDENSER COIL Page 26 8-Diagnostic Sensors Units are equipped with factory-installed thermistors located on different points on the refrigerant circuit. The thermistors provide the Unit Controller with constant temperature readings of two specific locations on the refrigeration circuit. These temperatures are used as feedback in certain modes of unit operation. In addition, the Unit Controller uses these temperatures to initiate alarms such as loss of condenser or evaporator airflow and loss of charge. Each thermistor must be specifically placed for proper unit operation and to initiate valid alarms. See FIGURE 8 (RT46, RT47, RT50, RT51) and FIGURE 9 (RT48, RT49, RT52, RT53) for proper locations. LGT/LCT302, 360 EVAPORATOR COIL (RT46, 47, 50, 51) LGT/LCT302, 360 CONDENSER COIL RT48, 49, 52, 53 22J06 BLUE RT47 22J06 GREEN RT51 22J06 YELLOW RT46 22J06 RED RT50 FIGURE 8 23V50 BLUE RT49 SEE DETAIL F 23V50 YELLOW RT48 SEE DETAIL G (Rear View) 23V50 GREEN RT53 SEE DETAIL I 23V50 RED RT52 SEE DETAIL H DETAILS NOT TO SCALE FIGURE 9 Page 27 9-RDS Sensors Units are equipped with factory-installed RDS Sensors located on different points on the unit. The RDS sensors provide the Unit Controller with continuous readings for leaked refrigerant concentration levels and sensor health status (Good or Fault). These readings are used to modify unit operation to disperse the leaked refrigerant and to remove possible ignition sources. In addition, the Unit Controller uses these readings to initiate alarms to alert the operator of a refrigerant leak or faulty sensor(s). Each sensor must be specifically placed for proper unit operation and to initiate valid alarms. See FIGURE 10 and FIGURE 11 for sensor locations. LGT/LCT302-360 INDOOR COMPARTMENT RDS SENSOR FIGURE 10 LGT/LCT 302-360 COMPRESSOR RDS SENSOR FIGURE 11 Page 28 C-Bower Compartment The blower compartment in all units is located between the evaporator coil and the compressor / control section on the opposite side of the condenser coil. The blower assembly is accessed by disconnecting the blower motor wiring (and all other plugs) and removing the screws on either side of the sliding base. The base pulls out as shown in FIGURE 12. 1-Blower Wheels (all units) All units have two 18 in. x 15 in. (457 mm x 381 mm) blower wheels. Both wheels are driven by one motor. 2-Indoor Blower Motor B3 (all units) All units use three-phase single-speed blower motors. CFM adjustments are made by adjusting the motor pulley (sheave). Motors are equipped with sealed ball bearings. All motor specifications are listed in the SPECIFICATIONS section in this manual. Units may be equipped with motors manufactured by various manufacturers, therefore electrical FLA and LRA specifications will vary. See unit rating plate for information specific to your unit. A-Blower Operation NOTE-The following is a generalized procedure and does not apply to all thermostat control systems. 1 - Blower operation is dependent on the thermostat control system option that has been installed in the units. Refer to operation sequence of the control system installed for detailed descriptions of blower operation. 2 - Generally, blower operation is set at the thermostat fan switch. With the fan switch in "ON" position and the OCP input is "ON", the blower operates continuously. With the fan switch in "AUTO" position, the blower cycles with demand. 3 - In most cases, the blower and entire unit will be off when the system switch is in the "OFF" position. The only exception is immediately after a heating demand when the blower control keeps the blower on until all heat is extracted from the heat exchanger. B-Blower Access 1 - Disconnect wiring connected to heating limit switches and mixed air sensor in units with an economizer. Disconnect blower harness at K3 contactor (CAV) or A96 inverter (VAV/Staged). Failure to do so could damage harness or components. 2 - Remove screws on either side of blower assembly sliding base. See FIGURE 12. 3 - Pull base toward outside of unit C-Determining Unit CFM IMPORTANT - Multi-staged supply air units are factoryset to run the blower at full speed when there is a blower (G) demand without a heating or cooling demand. Refer to the field-provided, design specified CFM for all modes of operation. Use the following procedure to adjust motor pulley to deliver the highest CFM called for in the design spec. See Inverter Start-Up section to set blower CFM for all modes once the motor pulley is set. Variable Air Volume Units - Refer to the Variable Air Volume Start-Up section. 1 - The following measurements must be made with a dry indoor coil. Run blower (G demand) without a cooling demand. Measure the indoor blower shaft RPM. Air filters must be in place when measurements are taken. 2 - With all access panels in place, measure static pressure external to unit (from supply to return). Blower performance data is based on static pressure readings taken in locations shown in FIGURE 13. NOTE - Static pressure readings can vary if not taken where shown. 3 - See "BLOWER DATA" section (table of contents) to use static pressure and RPM readings to determine unit CFM, and when installing units with any of the optional accessories listed. 4 - The blower RPM can be adjusted at the motor pulley. Loosen Allen screw and turn adjustable pulley clockwise to increase CFM. Turn counterclockwise to decrease CFM. See FIGURE 12 . Do not exceed minimum and maximum number of pulley turns as shown in TABLE 5. TABLE 5 Belt Min. Turns Open Max. Turns Open A Section No minimum 5 B Section 1* 6 *No minimum number of turns open when B belt is used on pulleys 6" O.D. or larger. Page 29 TO INCREASE CFM LOOSEN ALLEN SCREW & TURN PULLEY CLOCKWISE TO DECREASE CFM TURN PULLEY COUNTERCLOCKWISE BLOWER ASSEMBLY SLIDING BASE LOOSEN (4) SCREWS TO ADJUST BELT TENSION SIDE VIEW BLOWER ASSEMBLY BELT TENSION ADJUSTING SCREW BLOWER MOTOR TO INCREASE BELT TENSION 1-Loosen four screws securing blower motor to sliding base. clockwise, to move the motor downward and tighten the belt. 3-Tighten four screws. BLOWER WHEEL PULLEY MOTOR ALLEN SCREW PULLEY FIGURE 12 REMOVE SCREWS TO SLIDE BLOWER ASSEMBLY OUT OF UNIT LOCATION OF STATIC PRESSURE READINGS INSTALLATIONS WITH DUCTWORK INSTALLATIONS WITH CEILING DIFFUSERS ROOFTOP UNIT ROOFTOP UNIT SUPPLY TURN MAIN DUCT RUN RETURN AIR READING LOCATION FIRST BRANCH OFF OF MAIN RUN SUPPLY AIR READING LOCATION SUPPLY AIR READING LOCATION SUPPLY TURN RETURN AIR READING LOCATION DIFFUSER FIGURE 13 Page 30 D-Blower Belt Adjustment Maximum life and wear can be obtained from belts only if proper pulley alignment and belt tension are maintained. Tension new belts after a 24-48 hour period of operation. This will allow belt to stretch and seat into pulley grooves. Make sure blower and motor pulley are aligned. See FIGURE 14. 1 - Loosen four screws securing blower motor to sliding base. See FIGURE 12. 2 - To increase belt tension - Turn belt tension adjusting screw to the left, or counterclockwise, to tighten the belt. This increases the distance between the blower motor and the blower housing. To loosen belt tension Turn the adjusting screw to the right, or clockwise to loosen belt tension. 3 - Tighten four screws securing blower motor to sliding base once adjustments have been made. PULLEY ALIGNMENT ALIGNED E-Check Belt Tension Overtensioning belts shortens belt and bearing life. Check belt tension as follows: 1 - Measure span length X. See FIGURE 15. 2 - Apply perpendicular force to center of span (X) with enough pressure to deflect belt 1/64" for every inch of span length or 1.5mm per 100mm of span length. Example: Deflection distance of a 40" span would be 40/64" or 5/8". Example: Deflection distance of a 400mm span would be 6mm. 3 - Measure belt deflection force. For a used belt, the deflection force should be 5 lbs. (35kPa) . A new belt deflection force should be 7 lbs. (48kPa). A force below these values indicates and undertensioned belt. A force above these values indicates an overtensioned belt. MEASURE BELT TENSION MOTOR PULLEY BELT BLOWER PULLEY NOT ALIGNED FIGURE 14 FORCE DEFLECTION 1/64" PER INCH OF SPAN OR 1.5mm PER 100mm OF SPAN FIGURE 15 F-Field-Furnished Blower Drives For field furnished blower drives, see BLOWER DATA (table of contents) for CFM and RPM. The BLOWER DATA section also has tables for drive numbers and manufacturer's model numbers. Reference the manufacturer's model numbers in the table below.. Drive No. 1 2 3 4 5 6 7 8 9 ADJUSTABLE SHEAVE Supplier No. OEM Part No. 1VP71x1-3/8 100239-06 1VP71x1-1/8 100239-06 1VP65x1-3/8 78M7101 1VP60x1-3/8 78L5501 1VP56x1-1/8 P-8-1492 1VP60x1-1/8 41C1301 1VP50x1-1/8 P-8-1977 1VP44x1-1/8 36C0701 1VP44x1-1/8 36C0701 MANUFACTURER'S NUMBERS (60 HZ) DRIVE COMPONENTS FIXED SHEAVE BELTS Supplier No. OEM Part No. Supplier No. OEM Part No. BK140H 100788-13 BX78 100245-44 BK120H 100788-07 BX75 31K9801 BK130H 100788-08 BX75 31K9801 BK110H 100788-06 BX71 31K9701 BK120H 100788-07 BX71 31K9701 BK110H 100788-06 BX70 31K9601 BK120H 100788-07 BX70 31K9601 BK120H 100788-07 BX70 31K9601 BK140H 100788-13 BX73 100245-41 SPLIT BUSHING Supplier No. OEM Part No. H - 1-3/16 105616-02 H - 1-3/16 105616-02 H - 1-3/16 105616-02 H - 1-3/16 105616-02 H - 1-3/16 105616-02 H - 1-3/16 105616-02 H - 1-3/16 105616-02 H - 1-3/16 105616-02 H - 1-3/16 105616-02 Page 31 E-Optional Electric Heat Components See ELECTRICAL/ELECTRIC HEAT DATA tables for possible LCT match-ups and electrical ratings. EHA parts arrangement is shown in figures 27 and 28. All electric heat sections consist of electric heating elements exposed directly to the air stream. Two electric heat sections (first section and second section) are used in all 30kW through 120kW heaters. See figure 29. Multiple-stage elements are sequenced on and off in response to thermostat demand. 1-Main Control Box Components A55, K9, A178 The main control box (see figure 2) houses the A55, A178 Unit Controller and the K9 electric heat relay. For a description of the components see section I-A. 2-Terminal Block TB3 Electric heat line voltage connections are made to terminal block TB3 (or a fuse block on some models) located in the upper left corner of the electric heat vestibule. 3-Contactors K15, K16, K17 and K18 Contactors K15, K16, K17 and K18 are all three-pole double-break contactors located on the electric heat vestibule. K15 and K16 are located on the first electric heat section, while K17 and K18 are located on the second electric heat section. However, in the 30kW heaters, the first section houses all contactors and fuses. All contactors are equipped with a 24VAC coil. Contactors K15 and K17 energize the first stage heating elements, while K16 and K18 energize the second stage heating elements. 4-High Temperature Limits S15 and S107 (Primary) S15 and S107 are SPST N.C. auto-reset thermostats located on the back panel of the electric heat section below the heating elements. S15 is the high temperature limit for the first electric heat section, while S107 is the high temperature limit for the second electric heat section. Both thermostats are identical and are wired to the A55 Unit Controller. When either S15 or S107 opens, indicating a problem in the system, contactor K15 is de-energized. When K15 is de-energized, first stage and all subsequent stages of heat are de-energized. The thermostats used on EHA360-45-2 Y/G/J volt are factory set to open at 200F + 5F (93.3 C + 2.8C) on a temperature rise and automatically reset at 160F + 6F (71.14C + 3.3C) on a temperature fall. All other electric heat sections thermostats are factory-set to open at 170F + 5F (76.7C + 2.8C) on a temperature rise and automatically reset at 13F + 6F (54.4C + 3.3C) on a temperature fall. The thermostats are not adjustable. 5-Heating Elements HE1 through HE14 Heating elements are composed of helix wound bare nichrome wire exposed directly to the air stream. Three elements are connected in a three-phase arrangement. The elements in 208/230V units are connected in a "Delta" arrangement. Elements in 460 and 575V units are connected in "Wye" arrangement. See EHA wiring diagram in WIRING DIAGRAM AND OPERATION SEQUENCE section in back of this manual. Each stage is energized independently by the corresponding contactors located on the electric heat vestibule panel. Once energized, heat transfer is instantaneous. High temperature protection is provided by primary and redundant high temperature limits and overcurrent protection is provided by fuses. 6-Fuse F3 Fuse F3 are housed in a fuse block which holds three fuses. Each F3 fuse is connected in series with each leg of electric heat. Figure 28 and table 7 show the fuses used with each electric heat section. For simplicity, the service manual labels the fuses F3 - 1 through F3 - 8. ELECTRIC HEAT SECTION PARTS ARRANGEMENT HEATING ELEMENTS HE1 - HE14 ELECTRIC HEAT VESTIBULE CONTROL WIRE HARNESS TRIC HEAT LIMIT S15(1ST SECTION) S107(2nd SECTION) FIGURE 16 Page 32 TERMINAL STRIP (TB3) ELECTRIC HEAT VESTIBULE PARTS ARRANGEMENT FIRST HEAT SECTION (LEFT SIDE) ACCESS DOOR FUSE F3 F3 - 1 FUSE F3 F3 - 2 FIRST STAGE ELECTRIC HEAT CONTACTOR K15 SECOND STAGE ELECTRIC HEAT CONTACTOR K16 FUSE F3 F3 - 3 FUSE F3 F3 - 4 TERMINAL STRIP (TB3) SECOND HEAT SECTION (RIGHT SIDE) ACCESS DOOR FUSE F3 F3 - 5 FUSE F3 F3 - 6 FIRST STAGE ELECTRIC HEAT CONTACTOR K17 SECOND STAGE ELECTRIC HEAT CONTACTOR K18 FIGURE 17 FUSE F3 F3 - 7 FUSE F3 F3 - 8 Page 33 HEAT SECTION PLACEMENT COMPRESSOR COMPARTMENT SECOND ELECTRIC HEAT SECTION (RIGHT SIDE) FIRST ELECTRIC HEAT SECTION (LEFT SIDE) FIGURE 18 EHA QUANTITY & SIZE (1) EHA360-15 & (1) EHA360S-15 (30 kW Total) or (1) EHA156-15 & (1) EHA156S-15 (2) EHA360-22.5 (45 kW Total) or (2) EHA156-22.5 (2) EHA150-30 (60 kW Total) or (2) EHA156-30 (2) EHA360-45 (90 kW Total) TABLE 6 LCH ELECTRIC HEAT SECTION FUSE RATING VOLTAGES F3 - 1 F3 - 2 F3 - 3 FUSE (3 each) F3 - 4 F3 - 5 208/230V 60 Amp 250V 60 Amp 250V ----- ----- ----- 460V 50 Amp 600V ----- ----- ----- ----- 575V 40 Amp 600V ----- ----- ----- ----- 208/230V 50 Amp 250V ----- ----- 25 Amp 250V 50 Amp 250V 460V 25 Amp 600V ----- ----- 15 Amp 600V 25 Amp 600V 575V 20 Amp 600V ----- ----- 10 Amp 600V 20 Amp 600V 208/230V 50 Amp 250V ----- ----- 50 Amp 250V 50 Amp 250V 460V 25 Amp 600V ----- ----- 25 Amp 600V 25 Amp 600V 575V 20 Amp 600V ----- ----- 20 Amp 600V 20 Amp 600V 208/230V 50 Amp 250V ----- 60 Amp 250V 60 Amp 250V 50 Amp 250V 460V 25 Amp 600V ----- ----- 50 Amp 600V 25 Amp 600V 575V 20 Amp 600V ----- ----- 40 Amp 600V 20 Amp 600V F3 - 6 ------------------------------------------------- F3 - 7 ------------------------------------60 Amp 250V --------- F3 - 8 ----- ----- ----- 25 Amp 250V 15 Amp 600V 10 Amp 600V 50 Amp 250V 25 Amp 600V 20 Amp 600V 60 Amp 250V 50 Amp 600V 40 Amp 600V Page 34 II-PLACEMENT AND INSTALLATION Make sure the unit is installed in accordance with the installation instructions and all applicable codes. See accessories section for conditions requiring use of the optional roof mounting frame (LARMF18/36 or LARMFH30/36). III-STARTUP - OPERATION - CHARGING Refrigerant Charge R-454B Unit LGT/LCT302 Stage 1 Mc(lbs) 6.75 LGT/LCT302 Stage 2 6.50 LGT/LCT302 Stage 3 6.69 LGT/LCT302 Stage 4 6.81 LGT/LCT360 Stage 1 6.38 LGT/LCT360 Stage 2 6.81 LGT/LCT360 Stage 3 6.63 LGT/LCT360 Stage 4 6.38 Mc(kg) 3.06 2.95 3.03 3.09 2.89 3.09 3.01 2.89 WARNING - Do not exceed nameplate charge under any condition. This unit is factory charged and should require no further adjustment. If the system requires additional refrigerant, reclaim the charge, evacuate the system, and add required nameplate charge. When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used. However, for flammable refrigerants it is important that best practice be followed and, since flammability is a consideration, the following procedure shall be adhered to: · Safely remove refrigerant following local and na- tional regulations, · Evacuate the circuit, · Purge the circuit with inert gas, · Evacuate, · Purge with inert gas, · Open the circuit The refrigerant charge shall be recovered into the correct recovery cylinders if venting is not allowed by local and national codes. For appliances containing flammable refrigerants, the system shall be purged with oxygenfree nitrogen to render the appliance safe for flammable refrigerants. This process might need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems. Refrigerant purging shall be achieved by breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final oxygen-free nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and that ventilation is available. In addition to conventional charging procedures, the following requirements shall be followed. · Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them. · Cylinders shall be kept in an appropriate position according to the instructions. · Ensure that the refrigerating unit is earthed prior to charging the system with refrigerant. · Label the system when charging is complete (if not already). · Extreme care shall be taken not to overfill the refrigerating unit. Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site. · When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i. e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure- relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. · The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants includ-ing, when applicable, flammable refrigerants. In ad-dition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manu-facturer if in doubt Page 35 · The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. · If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely. Prior to recharging the system, it shall be pressuretested with the appropriate purging gas. The system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site NOTE - System charging is not recommended below 60F (15C). In temperatures below 60F (15C), the charge must be weighed into the system. If weighing facilities are not available, or to check the charge, use the following procedure: 1 - Make sure outdoor coil is clean. Attach gauge manifolds and operate unit at full CFM in cooling mode with economizer disabled until system stabilizes (approximately five minutes). Make sure all outdoor air dampers are closed. 2 - Compare the normal operating pressures to the pressures obtained from the gauges. Check unit components if there are significant differences. 3 - Measure the outdoor ambient temperature and the suction pressure. Refer to the charging curve to determine a target liquid temperature. Note - Pressures are listed for sea level applications. 4 - Use the same thermometer to accurately measure the liquid temperature (in the outdoor section). · If measured liquid temperature is higher than the target liquid temperature, add refrigerant to the system. · If measured liquid temperature is lower than the target liquid temperature, recover some refrigerant from the system. · When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i. e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure- relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. · When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i. e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. · The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants including, when applicable, flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. · The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. · If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely. 5 - Add or remove charge in increments. Allow the system to stabilize each time refrigerant is added or removed. 6 - Continue the process until measured liquid temperature agrees with the target liquid temperature. Do not go below the target liquid temperature when adjusting charge. Note that suction pressure can change as charge is adjusted. 7 - Example LGT/LCT302H Circuit 1: At 95°F outdoor ambient and a measured suction pressure of 128 psig, the target liquid temperature is 100°F. For a measured liquid temperature of 106°F, add charge in increments until measured liquid temperature agrees with the target liquid temperature. Page 36 Circuit 1 Circuit 2 Circuit 3 Circuit 4 65°F Suct (psig) Disc (Psig) 87 227 94 229 110 235 131 244 97 220 103 221 119 227 138 237 105 238 113 241 130 249 151 259 110 237 117 240 134 247 154 257 TABLE 7 LGT/LCT302H Normal Operating Pressures Outdoor Coil Entering Air Temperature 75°F 85°F 95°F Suct (psig) Disc (Psig) Suct (psig) Disc (Psig) Suct (psig) Disc (Psig) 90 264 93 306 97 352 97 266 100 308 104 355 113 272 117 314 120 360 134 280 137 322 141 368 98 256 100 297 102 345 105 256 107 298 109 345 121 261 123 302 126 348 141 271 143 310 146 355 107 276 110 319 113 366 115 279 118 321 120 368 133 286 135 327 138 374 153 295 156 336 159 382 111 275 113 319 115 369 119 277 121 320 123 370 136 283 138 325 140 373 156 292 158 332 161 379 105°F Suct (psig) Disc (Psig) 100 404 107 406 124 412 145 419 104 398 112 398 129 400 149 406 116 418 123 420 141 425 162 432 117 425 125 425 143 427 163 432 115°F Suct (psig) Disc (Psig) 104 459 111 462 128 467 149 475 107 458 114 457 131 458 152 463 119 475 127 477 145 481 166 488 120 488 128 487 146 487 167 491 Liquid Temperature (°F) 130 120 110 100 90 80 70 60 90 Circuit 1 - LGT/LCT302 - No Reheat & Reheat OD Temp (°F) 115 105 95 85 75 65 100 110 120 130 140 150 Suction Pressure (psig) Page 37 Liquid Temperature (°F) 130 120 110 100 90 80 70 60 95 135 125 115 105 95 85 75 65 100 Circuit 2 - LGT/LCT302 - No Reheat & Reheat OD Temp (°F) 115 105 95 85 75 65 105 115 125 135 145 Suction Pressure (psig) Circuit 3 - LGT/LCT302 - No Reheat & Reheat 155 OD Temp (°F) 115 105 95 85 75 65 110 120 130 140 150 160 170 Suction Pressure (psig) Liquid Temperature (°F) Page 38 Liquid Temperature (°F) 130 120 110 100 90 80 70 60 105 Circuit 1 Circuit 2 Circuit 3 Circuit 4 65°F Suct (psig) Disc (Psig) 82 232 90 237 107 247 121 254 91 228 98 232 114 240 130 247 99 254 108 258 126 268 144 280 105 245 113 248 128 256 144 269 Circuit 4 - LGT/LCT302 - No Reheat & Reheat OD Temp (°F) 115 105 95 85 75 65 115 125 135 145 155 165 Suction Pressure (psig) TABLE 8 LGT/LCT360H Normal Operating Pressures Outdoor Coil Entering Air Temperature 75°F 85°F 95°F Suct (psig) Disc (Psig) Suct (psig) Disc (Psig) Suct (psig) Disc (Psig) 85 269 89 309 92 355 94 274 97 315 101 360 110 284 114 325 118 370 125 291 129 333 133 378 93 265 94 307 96 354 100 269 103 311 105 358 117 276 119 318 122 364 133 282 136 323 139 369 101 293 103 337 105 386 111 297 113 341 115 389 129 306 131 350 134 398 147 318 150 361 152 409 106 283 107 325 109 372 114 285 116 327 118 374 131 293 134 334 136 381 148 305 151 346 154 392 105°F Suct (psig) Disc (Psig) 95 404 104 410 121 420 137 428 98 406 106 410 124 415 142 420 107 439 117 442 136 450 155 461 110 425 119 426 138 432 157 443 115°F Suct (psig) Disc (Psig) 98 457 107 463 125 473 141 481 99 463 108 467 126 472 145 476 109 497 119 500 138 508 157 518 111 482 121 483 141 489 160 499 Page 39 Liq. Temp. (F) 140 130 120 110 100 90 80 70 60 90 130 120 110 100 90 80 70 60 90 Circuit 1 - LGT/LCT360 - No Reheat OD Temp (°F) 85 75 65 115 105 95 100 110 120 130 140 150 Suction Pressure (psig) Circuit 2 - LGT/LCT360 - No Reheat OD Temp (°F) 115 105 95 85 75 65 100 110 120 130 140 150 Suction Pressure (psig) Liq. Temp. (F) Page 40 Liq. Temp. (F) 130 120 110 100 90 80 70 60 95 140 130 120 110 100 90 80 70 100 Circuit 3 - LGT/LCT360 - No Reheat OD Temp (°F) 115 105 95 85 75 65 105 115 125 135 145 155 165 Suction Pressure (psig) Circuit 4 - LGT/LCT360 - No Reheat OD Temp (°F) 115 105 95 85 75 65 110 120 130 140 150 160 170 Suction Pressure (psig) Liq. Temp. (F) Page 41 IV- SYSTEMS SERVICE CHECKS A-Cooling System Service Checks All units are factory charged and require no further adjustment; however, charge should be checked periodically using the normal operating pressure method. 1-Gauge Manifold Attachment Attach high pressure line to discharge line Schrader port and the low pressure line to the suction line Schrader port. NOTE-When unit is properly charged discharge line pressures should approximate those in Refrigerant Check and Charge section. V-MAINTENANCE The unit should be inspected once a year by a qualified service technician. WARNING Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies. WARNING Any service personnel installing, decommissioning, or performing maintenance on the unit must be properly trained with A2L refrigerants Prior to beginning work on systems containing refigerant to ensure the risk of ignition is minimized: · All work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed. · The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants, i. e. non-sparking, adequately sealed or intrinsically safe. · If any hot work is to be conducted on the refrigerating equipment or any associated parts, the appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area. · No person carrying out work in relation to a refrigerating system which involves exposing any pipe work shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. "No Smoking" signs shall be displayed. · Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. · Where electrical components are being changed, service technicians shall be fit for the purpose and to the correct specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer's technical department for assistance. The following checks shall be applied to installations using flameable refrigerants as applicable: 1 - The actual refrigerant charge is in accordance with the room size within which the refrigerant containing parts are installed. 2 - The ventilation machinery and outlets are operating adequately and are not obstructed. 3 - If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant. 4 - Markings on the equipment should be visible and legible. Markings and signs that are illegible shall be corrected. 5 - Refrigerating pipes or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded. · For systems containing refigerant all repair and maintenance to electrical components shall include initial safety checks and component inspection procedures such as that capacitors are discharged in a safe manner to avoid possibility of sparking, that no live electrical components and wiring are exposed while charging, recovering, or purging the system, and that there is continuity of earth bonding. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used that is reported to the owner of the equipment, so all parties are advised. NOTE - Sealed electrical components shall be replaced, not repaired. NOTE - Intrinsically safe components must be replaced, not repaired. Page 42 · Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used. Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable refrigerants, the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed, and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are also suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. · When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used. However, for flammable refrigerants it is important that best practice be followed, since flammability is a consideration. The following procedure shall be adhered to: a. Safely remove refrigerant following local and national regulations, b. Evacuate the circuit, c. Purge the circuit with inert gas, d. Evacuate, e. Purge with inert gas, f. Open the circuit. · The refrigerant charge shall be recovered into the correct recovery cylinders if venting is not allowed by local and national codes. For appliances containing flammable refrigerants, the system shall be purged with oxygen-free nitrogen to render the appliance safe for flammable refrigerants. This process might need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems. Refrigerant purging shall be achieved by breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final oxygen-free nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and that ventilation is available. A-Filters All units are equipped with twelve 20" x 20" x 2" (508mm x 508mm x 51mm) pleated throw-away type filters. Filters may be accessed through the economizer / filter access door (left of the blower door). All filters are removed by pulling on the pull tab, located on the bottom of each row of filters. Filters should be checked monthly (or more frequently in severe use) and cleaned or replaced regularly. Take note of the "AIR FLOW DIRECTION" marking on the filter frame when re-installing. NOTE-Filters must be U.L.C. certified or equivalent for use in Canada. CAUTION Be careful when servicing unit to avoid accidental contact with sharp metallic edges which may cause personal injury. B-Lubrication All motors and blower wheels used are prelubricated; no further lubrication is required. C-Supply Air Blower Wheel Annually inspect supply air blower wheel for accumulated dirt or dust. Turn off power before attempting to remove access panel or to clean blower wheel. If balancing clips are removed, make sure they are reinstalled in the same location when cleaning is completed. NOTE-Do not lose balancing clips. D-Evaporator Coil Inspect and clean coil at beginning of each season. Clean using mild detergent or commercial coil cleanser. Check condensate drain pan and line, if necessary. Flush coil and condensate drain with water taking care not to get insulation, filters and return air ducts wet. Check connecting lines and coil for evidence of oil and refrigerant leaks. E-Condenser Coil Clean condenser coil annually with water and inspect monthly during the cooling season. Access panels are provided on front and back of condenser section. Clean the all-aluminum coil by spraying the coil steadily and uniformly from top to bottom. Do not exceed 900 psi or a 45 angle; nozzle must be at least 12 inches from the coil face. Take care not to fracture the braze between the fins and refrigerant tubes. Reduce pressure and work cautiously to prevent damage. NOTE-If owner complains of insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to Gauge Manifold Attachment and Charging sections in this manual. F-Electrical 1- Check all wiring for loose connections. 2- Check for correct voltage at unit (unit operating). 3- Check amp-draw on both condenser fan motor and blower motor. Fan Motor Rating Plate ____ Actual ________ Indoor Blower Motor Rating Plate____ Actual____ Page 43 VI-ACCESSORIES The accessories section describes the application of most of the optional accessories which can be factory- or field-installed. A-LARMF18/36-14, 24 or LARMFH30/36-30, 41 Mounting Frames When installing the LCT units on a combustible surface for downflow discharge applications, the Lennox LARMF18/36 14-inch or 24-inch (356 mm or 610mm) height roof mounting frame is used. For horizontal discharge applications, use LARMFH30/36 30-inch or 41inch (762mm or 1041mm) height roof mounting frame. This frame converts unit from down-flow to horizontal air flow. The 14 and 24 inch (356 and 610mm) downflow and 41 inch (1041mm) horizontal frame meets National Roof ing Code requirements. The roof mounting frames are recommended in all other applications but not required. If the units are not mounted on a flat (roof) surface, they MUST be supported under all edges and under the middle of the unit to prevent sagging. The units MUST be mounted level within 1/16" per linear foot or 5mm per meter in any direction. The assembled LARMF18/36 mounting frame is shown in FIGURE 19. Refer to the roof mounting frame installation instructions for details of proper assembly and mounting. The roof mounting frame MUST be squared to the roof and level before mounting. Plenum system MUST be installed before the unit is set on the mounting frame. Typical roof curbing and flashing is shown in FIGURE 20. Refer to the roof mounting frame installation instructions for proper plenum construction and attachment. B-Control Systems The A55 Unit Controller provides all control function for the rooftop unit. Default operation requires a standard room thermostat or direct digital controller (DDC). The A55 can also control the unit from a zone temperature sensor. The A55 Unit Controller is a network controller when daisychained to the L Connection® Network Control System. For ease of configuration, the A55 can be connected to a PC with Unit Controller PC software installed. C-Transitions Optional supply/return transitions LASRT30/36 are available for use with LCT series units utilizing optional LARMF18/36 roof mounting frame. Transition must be installed in the LARMF18/36 mounting frame before mounting the unit to the frame. Refer to the manufacturer's instructions included with the transition for detailed installation procedures. ASSEMBLED ROOF MOUNTING FRAME END BACK FRONT END CENTER SUPPORTS (TWO PIECES EACH) FIGURE 19 TYPICAL FLASHING DETAIL UNIT BASE BOTTOM FIBERGLASS INSULATION (Furnished) UNIT BASE RAIL NAILER STRIP (Furnished) RIGID INSULATION (Field Supplied) COUNTER FLASHING (Field Supplied) CANT STRIP (Field Supplied) ROOF MOUNTING FRAME (Extends around entire perimeter of unit) ROOFING MATERIAL FIGURE 20 Page 44 D-Supply and Return Diffusers Optional flush mount diffuser/return FD11 and extended mount diffuser/return RTD11 are available for use with the LGT units. Refer to manufacturer's instructions included with transition for detailed installation procedures. E-E1DAMP25D-1 & E1DAMO15D-1 Outdoor Air Dampers E1DAMP25D-1- & E1DAMO15D-1 consists of a set of dampers which may be manually or motor operated to allow up to 25 percent outside air into the system at all times (FIGURE 21). Either air damper can be installed in LGT units. Washable filter supplied with the outdoor air dampers can be cleaned with water and a mild detergent. It should be sprayed with Filter Handicoater when dry prior to reinstallation. Filter Handicoater is R.P. Products coating no. 418 and is available as Lennox Part No. P-8-5069. F-E1ECON15D-1 Economizer (Field or Factory Installed) The optional economizer can be used with LGT units in downflow and horizontal air discharge applications. The economizer uses outdoor air for free cooling when temperature and/or humidity is suitable. An economizer hood is furnished with the economizer. NOTE - Gravity exhaust dampers are required with power exhaust. The economizer is controlled by the A55 Unit Controller. The economizer will operate in one of four modes.These settings are available through the main menu at SETUP > TEST & BALANCE > DAMPER Each mode also requires different sensors. MANUAL OUTDOOR AIR DAMPER MOTORIZED OUTDOOR AIR DAMPER FILTER BRACKET SIDE VIEW HOOD TOP SEAL HOOD TOP FILTER FIGURE 21 Page 45 1-"TMP" MODE (SENSIBLE TEMPERATURE) In the "TMP" mode, the A55 Unit Controller uses input from the factory installed RT6 Supply Air Sensor, RT16 Return Air Sensor, and RT17 Outdoor Air Sensor to determine suitability of outside air and economizer damper operation. When outdoor sensible temperature is less than return air sensible temperature, outdoor air is used for cooling. This may be supplemented by mechanical cooling to meet comfort demands. This application does not require additional optional sensors. 2-"ODE" MODE (OUTDOOR ENTHALPY) The "ODE" or outdoor enthalpy mode requires a factory or field-provided and -installed Honeywell C7400 enthalpy sensor (53W64). The sensor monitors outdoor air temperature and humidity (enthalpy). When outdoor air enthalpy is below the enthalpy control setpoint, the economizer modulates to allow outdoor air for free cooling. 3-"DIF" MODE (DIFFERENTIAL ENTHALPY) The "DIF" or differential enthalpy mode requires two factory or field-provided and -installed Honeywell C7400 enthalpy sensors (53W64). One sensor is installed in the outside air opening and the other sensor is installed in the return air opening. When the outdoor air enthalpy is below the return air enthalpy, the economizer opens to bring in outdoor air for free cooling. 4-"GLO" MODE (GLOBAL) Global Mode - The "GLO" or global mode is used with an energy management system which includes a global control feature. Global control is used when multiple units (in one location) respond to a single outdoor air sensor. Each energy management system uses a specific type of outdoor sensor which is installed and wired by the controls contractor. Motorized Outdoor Air Damper - The "GLO" mode is also used when a motorized outdoor air damper is installed in the system. NOTE - All economizer modes of operation will modulate dampers to 55F (13C) supply air. G-Gravity Exhaust Dampers E1DAMP60D-1 dampers are used in downflow and LAGEDH30/ 36 are used in horizontal air discharge applications. E1DAMP60D-1 dampers are installed in the return air compartment of the unit (FIGURE 22). LAGEDH30/ 36 gravity exhaust dampers are installed in the return air plenum. The dampers must be used any time an economizer or power exhaust fans are applied to LGT series units. An exhaust hood is furnished with any type of gravity exhaust damper. Gravity exhaust dampers allow exhaust air to be discharged from the system when an economizer and/or power exhaust is operating. Gravity exhaust dampers also prevent outdoor air infiltration during unit off cycle. See installation instructions for more detail. LAGED(H)30/36 dampers are used with LGT series units. See installation instructions for more detail. E1DAMP60D-1 AND LAPEF INSTALLATION ECONOMIZER FRESH AIR HOOD LAPEF POWER EXHAUST FAN ASSEMBLY LAGED GRAVITY EXHAUST DAMPERS FIGURE 22 H- E1PWRE40D-1 Power Exhaust Fans Power exhaust fans are used with LGT in downflow applications only. E1PWRE40D-1 power exhaust fans require optional E1DAMP60D-1 downflow gravity exhaust dampers and E1ECON15D-1 economizer. Power exhaust fans provide exhaust air pressure relief and run when return air dampers are closed and supply air blowers are operating. FIGURE 22 shows location of the power exhaust fans. See installation instructions for more detail. I-Smoke Detectors A171, A172, A173 Photoelectric smoke detectors are a factory installed option. The smoke detectors can be installed in the supply air section (A172), return air section (A171), or in both the supply and return air section. Smoke detection control module (A173) is located below the control panel. Wiring for the smoke detectors are shown on the temperature control section (C) wiring diagram in back of this manual. Page 46 J-Blower Proving Switch S52 The blower proving switch monitors blower operation and locks out the unit in case of blower failure. The switch is N.O. and closes at 0.15" W.C. (37.4 Pa) The switch is mounted on the middle left corner of the blower support panel. Wiring for the blower proving switch is shown on the temperature control section (C) wiring diagram in back of this manual. K-Dirty Filter Switch S27 The dirty filter switch senses static pressure increase indicating a dirty filter condition. The switch is N.O. and closes at 0.85" W.C. (211.7 Pa). The switch is mounted on the top corner of the economizer. Wiring for the dirty filter switch is shown on the temperature control section (C) wiring diagram in back of this manual. Actuation of this switch does not affect unit operation. .L-Indoor Air Quality (CO2) Sensor A63 The indoor air quality sensor monitors CO2 levels and reports the levels to the Unit Controller A55. The board adjusts the economizer dampers according to the CO2 levels. The sensor is mounted next to the indoor thermostat or in the return air duct. Refer to the indoor air quality sensor installation instructions for proper adjustment. Wiring for the indoor air quality switch is shown on the temperature control section (C) wiring diagram in back of this manual. M-Supply Air Variable Frequency Drive VAV units only NOTE - Units equipped a Variable Frequency Drive (VFD) are designed to operate on balanced, three-phase power. Operating units on unbalanced three-phase power will reduce the reliability of all electrical components in the unit. Unbalanced power is a result of the power delivery system supplied by the local utility company. Factory-installed inverters are sized to drive blower motors with an equivalent current rating using balanced three-phase power. If unbalanced three-phase power is supplied; the installer must replace the existing factory-installed inverter with an inverter that has a higher current rating to allow for the imbalance. Refer to the installation instructions for additional information and available replacements. VAV units contain a supply air blower equipped with a variable frequency drive A96 (VFD) which varies supply air CFM. As duct static increases, the supply air volume will decrease. As duct static decreases, the supply air volume will increase. In VAV units, the Unit Controller uses input from a field-installed pressure transducer (A30) to maintain a 1.0" w.c. (default) static pressure. Refer to the Unit Controller manual parameter 388 and 389 to adjust the static pressure setpoint. The pressure transducer is shipped in a box in the blower compartment. Install the transducer according to manufacturer's instructions. Note -Make sure the transducer is installed in the main duct at least 2/3 of the distance away from the unit. The supply air VFD (A96) is located near the compressors. The Unit Controller will lock-out the unit for 5 minutes(default) if static pressure exceeds 2.0"w.c. for 20 seconds. The Unit Controller will permanently shut down the unit after three occurrences. Use the following parameters to adjust the default values: Parameter 110; Error time off delay. Parameter 42; Air Supply Static Shutdown Set Point. Parameter 43; Static Pressure Lockout Counter Set Point. Page 47 VAV By-Pass Operation (Optional) IMPORTANT - All dampers must be open to prevent damage to duct work and dampers. 1 - Turn off all power to unit. 2- Locate K3, K203, J248 and J249 connectors near the VFD. See FIGURE 26. 3- Disconnect J248 from P248 and connect connect P248 jumper plug to J248. P248 jumper plug is attached to the J248 wire harness near the J248 jack connector. See FIGURE 24. 4- Disconnect P247 from J247 and connect J249 to P247. See FIGURE 25. 5 - L ocate VFD control relay K203 on the lower control panel. See FIGURE 26. 6- Disconnect wires marked K203-A and K203-B 7- Connect K3-A (female terminal) to K203-A (male terminal) and K3-B (female terminal) to K3-B (male terminal) 8- Restore power to unit. Blower will operate in constant air volume (CAV) mode. 9- Check the indoor blower motor nameplate for full load amperage (FLA) value. Measure the amp readings from the indoor blower motor operating in bypass mode. If measured amps are higher than nameplate FLA value, decrease the CFM by opening (turning counterclockwise) the motor pulley. Refer to the Indoor Blower Motor section. Do not exceed minimum and maximum number of pulley turns as shown in table 1. VAV BY-PASS CONNECTOR From Relay Connect From Contactor K203-A K203-B Disconnect K3-A K3-B K203-A K203-B K203-A K203-B From A55 FIGURE 23 From A55 VAV BY-PASS CONNECTOR Disconnect P248 Connect J248 P248 Jumper Plug J248 FIGURE 24 BY-PASS CONNECTOR Disconnect Connect P247 P247 J249 J247 FIGURE 25 SUPPLY AIR VARIABLE FREQUENCY DRIVE A55 A96 K202 S42 UNIT CONTROLLER A178 K3 TB25 FIGURE 26 Page 48 N-Drain Pan Overflow Switch S149 (optional) The overflow switch is used to interrupt cooling operation when excessive condensate collects in the drain pan. The N.O. overflow switch is controlled by K220 and DL46 relays, located in the unit control panel. When the overflow switch closes, 24VAC power is interrupted and after a fivesecond delay the unit compressors are de-energized. Once the condensate level drops below the set level, the switch will open. After a five-minute delay the compressor will be energized. O-Hot Gas Reheat Start-Up and Operation General Hot gas reheat units provide a dehumidifying mode of operation. These units contain a reheat coil adjacent to and downstream of the evaporator coil. Reheat coil solenoid valves, L14 and L30, route hot discharge gas from the compressor to the reheat coil. Return air pulled across the evaporator coil is cooled and dehumidified; the reheat coil adds heat to supply air. See FIGURE 27 for reheat refrigerant routing. See FIGURE 28 for cooling only refrigerant routing. L14/L30 Reheat Coil Solenoid Valve When Unit Controller input (Unit Controller J298-5 or J299-8) indicates room conditions require dehumidification, L14/L30 reheat valve is energized (Unit Controller P269-3 or P269-4) and refrigerant is routed to the reheat coil. Reheat Setpoint Reheat is factory-set to energize when indoor relative humidity rises above 60% (default). The reheat setpoint can be adjusted by changing Unit Controller Settings - Control menu. A setting of 100% will operate reheat from an energy management system digital output Reheat will terminate when the indoor relative humidity falls 3% (57% default) or the digital output de-energizes. The reheat deadband can be adjusted at Settings - Control menu. A91 Humidity Sensor Relative humidity should correspond to the sensor (A91) output voltage listed in the table below. For example: if indoor air relative humidity is 80% + 3%, the humidity sensor output should read 8.00VDC. Check the sensor output annually for accuracy. Keep the air intake openings on the sensor clean and free of obstructions and debris Relative Humidity (%RH + 3%) Sensor Output (VDC) 20 2.00 30 3.00 40 4.00 50 5.00 60 6.00 70 7.00 80 8.00 90 9.00 Check-Out Test reheat operation using the following procedure. 1 - Make sure reheat is wired as shown in wiring section. Make sure unit is in local thermostat mode. Use the Unit Controller key pad to elect SERVICE TEST DEHUMIDIFIER 300, 360 - The blower, compressor 1, and compressor 2 (reheat) should be operating. L14 and L30 LEDs on the Unit Controller should also be ON, indicating the reheat valves are energized, REHEAT MODE will be appear on the Unit Controller display. Press BACK on the Unit Controller display to stop the testing mode. Default Reheat Operation Reheat will operate as shown inTABLE 9 once three conditions are met. 1 - Blower must be operating. System must be in occupied mode. System must NOT be operating in heating mode. IMPORTANT - Free cooling does not operate during reheat. For other reheat control options, refer to the Unit Controller manual. Additional Cooling Stages (3-Stage) Units are shipped from the factory to provide two stages of cooling. Three stages of cooling is available in zone sensor mode. Three stages of cooling is also available by installing a transfer relay and a three-stage thermostat. Refer to the Main Control Operation section in the Unit Controller manual when using the transfer relay. Additional Cooling Stages (4-Stage) Four stages of cooling is available in zone sensor mode on units with four compressors. Compressors are not de-energized when unit operation changes from cooling to reheat or from reheat to cooling. Instead, L14 and L30 reheat valves are energized (reheat) or de-energized (cooling). NOTE - Another thermostat staging option is available which allows both compressors to be energized during free cooling. See Unit Controller manual for details. Page 49 "NEUTRAL" DEHUMIDIFIED AIR REHEAT MODE REFRIGERANT ROUTING 300, 360H4M EVAPORATOR COIL NOTE:Refrigerant circuits one and two operate during reheat. MIXED INDOOR/OUTDOOR AIR REHEAT COIL CONDENSER COIL REHEAT COIL "NEUTRAL" DEHUMIDIFIED AIR FIGURE 27 COOLING MODE REFRIGERANT ROUTING 300, 360H4M EVAPORATOR COIL MIXED INDOOR/OUTDOOR AIR REHEAT COIL REHEAT COIL CONDENSER COIL OUTDOOR AIR REFRIGERANT CIRCUIT 1 REFRIGERANT CIRCUIT 2 REFRIGERANT CIRCUIT 3 REFRIGERANT CIRCUIT 4 REHEAT VALVE CHECK VALVE THERMAL EXPANSION VALVES FIGURE 28 Page 50 OUTDOOR AIR REFRIGERANT CIRCUIT 1 REFRIGERANT CIRCUIT 2 REFRIGERANT CIRCUIT 3 REFRIGERANT CIRCUIT 4 REHEAT VALVE CHECK VALVE THERMAL EXPANSION VALVES TABLE 9 REHEAT OPERATION Two-Stage Thermostat - Default T'stat and Humidity Demands Operation 300, 360 (4-Compressors) Reheat Only Compressor 1 & 2 Reheat Reheat & Y1 Compressor 1 & 2 Reheat Compressor 3 Cooling¹ Reheat & Y1 & Y2 Compressor 1, 2, 3, & 4 Cooling³ Three-Stage Thermostat (Transfer relay required) T'stat and Humidity Demands Operation 300, 360 (4-Compressors) Reheat Only Compressor 1 & 2 Reheat Reheat & Y1 Compressor 1 & 2 Reheat Compressor 3 Cooling¹ Reheat & Y1 & Y2 Compressor 1 & 2 Reheat Compressor 3 & 4 Cooling³ Reheat & Y1 & Y2 & Y3 Compressor 1, 2, 3, & 4 Cooling Four-Stage Zone Sensor Mode Cooling* and Humidity** Demands Operation 300, 360 (4-Compressors) Reheat Only Compressor 1 & 2 Reheat Reheat & Y1 Compressor 1 & 2 Reheat Compressor 3 Cooling¹ Reheat & Y1 & Y2 Compressor 1 & 2 Reheat Compressor 3 & 4 Cooling² Reheat & Y1 & Y2 & Y3 Compressor 1 Reheat, Compressor 2, 3, & 4 Cooling³ Reheat & Y1 & Y2 & Y3 & Y4 Compressor 1, 2, 3, & 4 Cooling *Cooling stage is initiated when zone temperature is higher than the cooling setpoint plus the appropriate stage differential. **Reheat demand is initiated when relative humidity is higher than relative humidity setpoint. ¹If there is no reheat demand and outdoor air is suitable, free cooling will operate. ²If there is no reheat demand and outdoor air is suitable, free cooling and compressor 1 will operate. ³If there is no reheat demand and outdoor air is suitable, free cooling and compressor 1 and 2 will operate. If there is no reheat demand and outdoor air is suitable, free cooling and compressor 1, 2, and 3 will operate. If there is no reheat demand and outdoor air is suitable, free cooling and compressor 1, 2, 3, and 4 will operate. The following conditions must be met before reheat will be energized: (factory-default; see Unit Controller manual for other options) 1 - Blower must be operation. System must be in occupied mode. System must NOT be operating in heating mode. Page 51 VII-Decommissioning Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that electrical power is available befor the task is commenced. Steps to ensure this are: · Become familiar with the equipment and its operation, · Isolate the system electrically, · Ensure that before attempting the procedure that mechanical handling equipment is available, if required, for handling refrigerant cylinders, and that all personal protective equipment is available and being used correctly while the recovery process is supervised at all times by a competent person and that the recovery equipment and cylinders conform to the appropriate standards. Additionally, pump down refrigerant system, if possible, and if a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. Make sure that cylinders are situated on the scales before recovery takes place. Start the recovery machine and operate in accordance with instructions. Do not overfill cylinders (no more than 80 % volume liquid charge). Do not exceed the maximum working pressure of the cylinder, even temporarily. When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. Recovered refrigerant shall not be charged into another refrigerating system unless it has been cleaned and checked. Equipment shall be labeled stating that it has been decommissioned and emptied of refrigerant. The label shall be dated and signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used. Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable refrigerants, the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed, and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are also suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used. However, for flammable refrigerants it is important that best practice be followed, since flammability is a consideration. The following procedure shall be adhered to: · Safely remove refrigerant following local and national regulations, · Evacuate the circuit, · Purge the circuit with inert gas, · Evacuate, · Purge with inert gas, · Open the circuit. The refrigerant charge shall be recovered into the correct recovery cylinders if venting is not allowed by local and national codes. For appliances containing flammable refrigerants, the system shall be purged with oxygenfree nitrogen to render the appliance safe for flammable refrigerants. This process might need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems. Refrigerant purging shall be achieved by breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final oxygen-free nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and that ventilation is available. Page 52 VIII-WIRING DIAGRAMS AND OPERATION SEQUENCE Page 53 Page 54 SEQUENCE OF OPERATION EHA 15 - 90 Y & G The Y voltage diagram use elements configured in a Wye. The G and J voltage diagram use elements configured in a Delta. Both diagrams follow the following sequence of operation: NOTE:Two electric heat sections are used in all 15kW through 90kW heaters. The heat sections are labelled first electric heat section (left side) and second electric heat section (right side). See FIGURE 18. NOTE: In the case of EHA 15 and 30kW, the second heat section (right side) is a slave (only has electric heat elements and a limit). Line voltage is supplied to elements in both heat section one (left side) and two (right side) by the contactors in heat section one (left side). HEATING ELEMENTS: 1 - Terminal strip TB3 is energized when the unit disconnect closes. TB3 supplies line voltage to electric heat elements HE1 through HE14. Each heating element is protected by fuse F3. FIRST STAGE HEAT: 2 - Heating demand initiates at W1 in thermostat. 3 - 24VAC is routed to the main control module A55. After A55 proves N.C. primary limits S15 (heat section one, left side), S107 (heat section two, right side), the electric heat contactor K15 and heat relay K9 are energized. 4 - N.O. contact K15-1 closes allowing the first bank of elements in heat section one (left side) to be energized. 5 - At the same time, N.O. contacts K9-1 close. A N.O. contact in A55 closes, energizing electric heat relay K17. 6 - N.O. contacts K17-1 close allowing the first set of elements in heat section two (right side) to be energized. SECOND STAGE HEAT: 7 - With the first stage heat operating, an additional heating demand initiates at W2 in the thermostat. 8 - 24VAC is routed through the main control module A55, which in turn energizes the electric heat contactor K16. 9 - N.O. contacts K16-1 close allowing the second set of elements in heat section one (left side) to be energized. 10 - Simultaneous with step eight, a N.O. contact in the A55 Unit controller closes, allowing 24VAC to energize electric heat contactor K18. 11 - N.O. contacts K18-1 close allowing the second set of elements in heat section two (right side) to be energized. END OF SECOND STAGE HEAT: 12 - Heating demand is satisfied. Terminal W2 in the thermostat is de-energized. 13 - Electric heat contactors K16 and K18 are deenergized. 14 - The second set of electric heat elements in heat sections one (left side) and two (right side) are deenergized. END OF FIRST STAGE HEAT: 15 - Heating demand is satisfied. Terminal W1 in the thermostat is de-energized. 16 - Electric heat contactors K15 and K17 are deenergized. 17 - The first set of electric heat elements in heat sections one (left side) and two (right side) are deenergized. Page 55 THERMOSTAT P255 P255 BL U RED WHT WHT RE D PNK GRY GRY S E NS OR 1 J 261 YEL YEL PNK GRY 123 6 A1 7 3 CT RL S MOKE DE T E CT J 250 P250 YEL Y 1 YEL YEL Y 2 YEL RED R 3 PNK BLK B 4 GRY S E NS OR 2 J 252 P252 YEL Y YEL 1 YEL Y YEL 2 PNK R RED 3 GRY B BLK 4 4 P251 J 251 YEL 1 YEL 2 RED 3 BLK 4 P253 J 253 1 YEL 2 YEL 3 RED 4 BLK 15 16 17 1 2 1, 5 YEL 4 361 2 RED RED F I RE AL ARM CONT ACT S UPPL I E D BY OT HE RS 5 1 2 DI - 1 R 9 5 F ROM I AQ WI RI NG DI AGRAM 8 R E D 1 2 A55. J 299 RE D- BL K GRY RE D- BL K GRY RED RED ORN P424 YEL WB- 031 WB- 030 P299 1 2 P387 J 299 J 387 123 4 5 6 7 8 9 10 38 49 10 5 2 7 1 6 R DI - 1 C R G C W1 W2 DI - 2 Y1 Y2 R DI - 3 OCP GL O R DI - 4 DO- 1 C FREE R C S52 AI - 1 GND GND S27 HUM GND GND 2 4 VAC T E MP S149 AI - 2 I ON C GND R FREE GND A5 5 MAI N CT RL 1234 5678 J 297 P297 9 10 123456 J 298 P298 7 8 9 10 A55. J 298 3 C Y1 2 6 Y2 7 R C I AQ+ 123 A55. J 298 A55. J 297 RCG Y1 123 6 2 B A T O PROVI DE T HRE E COMPRE S S OR S T AGE S . RE QUI RE S 3 HE AT , 3 COOL T HE RMOS T AT AND K27 RE L AY 4 3 S T AGE COOL I NG/ 3 S T AGE HE AT I NG A55. J 298 7 R I AQ+ I AQ134 7 187 R C I AQ+ 123 PUR WB- 044 GRY 7 WB- 045 WHT WB- 046 TO B5- SECT L OC CC03 APPL I E S ONL Y T O D- BOX J 387 C 2 A5 5 J 298 J 297 J 299 2 L ONT a l k MODUL E T O M4 T HE RMOS T AT I NPUT AL L OT HE R T HE RMOS T AT S I GNAL S RE MAI N CONNE CT E D AS S HOWN ON T HE T OP T O PROVI DE S UPE RMARKE T RE HE AT S CHE ME US E S 86 DE HUMI DI S T AT AND K55 S UPE RMARKE T RE HE AT DE NOT E S OPT I ONAL COMPONE NT S AND WI RI NG CL AS S 2 F I E L D WI RI NG Model: Voltage: Supersedes: LC, LG, LH, LD Series RTU Thermostat All Voltages 538078-01 Form No: 5 3 8 0 7 8 - 0 2 Rev: 0 H E AT ING COOLING COOLING ACCS ACCS S E C T ION A S E C T ION B SECTION SECTION SECTION B 3 /5 C D WIR ING DIAGRAM FLOW A55. J 297 Page 56 GATEWAY THERMOSTAT J 255 P255 BL U RED YEL WHT WHT RE D PNK GRY GRY RED RED A55. J 299 RE D- BL K GRY RE D- BL K GRY RED RED ORN P424 YE L WB- 031 WB- 030 S E NS OR 1 J 261 YEL YEL PNK GRY 123 4 A1 7 3 CT RL S MOKE DE T E CT J 250 P250 YEL Y 1 YEL YEL Y 2 YEL RED R 3 PNK BLK B 4 GRY S E NS OR 2 J 252 P252 YEL Y YEL 1 YEL Y YEL 2 PNK R RED 3 GRY B BLK 4 4 P251 J 251 YEL 1 YEL 2 RED 3 BLK 4 P253 J 253 1 YEL 2 YEL 3 RED 4 BLK 15 16 17 1 2 F I RE AL ARM CONT ACT S UPPL I E D BY OT HE RS 3 4 361 2 P299 1 A5 5 J 299 123 4 MAI N CT RL 1, 3 1 2 DI - 1 R 9 2 5 6 7 8 9 10 P387 J 387 38 3 F ROM I AQ WI RI NG DI AGRAM RED 7 1 2 49 10 5 2 7 1 6 R C DI - 1 G R W1 C W2 Y1 DI - 2 Y2 OCP R GL O DI - 3 R DO- 1 DI - 4 C R FREE C AI - 1 GND S 52 HUM GND GND S 27 T E MP GND AI - 2 2 4 VAC C S149 R I ON GND FREE S GND + 12345678 J 297 P297 9 10 1 2 3 4 5 6 7 8 9 10 123 J 298 J 304 P298 P304 82 A55. J 298 A55. J 298 BL K RED R C I AQ+ 123 WB- 046 WB- 045 WB- 044 R C I AQ+ 123 WHT GRY PUR S HI E L D TO B5- SECT L OC CC03 APPL I E S ONL Y T O D- BOX 5 US E D ONL Y I N NOVAR L S E GAT E WAY R I AQ+ I AQ- C 134 2 5 187 2 1 2 A55. J 298 DE NOT E S OPT I ONAL COMPONE NT S AND WI RI NG CL AS S 2 F I E L D WI RI NG J 387 A5 5 J 298 J 297 J 299 J 304 L ONT a l k MODUL E Model: Voltage: Supersedes: LC, LG, LH, LD Series RTU Thermostat- GATEWAY Controls All Voltages 538079-01 Form No: 5 3 8 0 7 9 - 0 2 Rev: 0 HE AT ING COOLING COOLING ACCS ACCS S E C T ION A S E C T ION B SECTION SECTION SECTION B 3 /5 C D WIR ING DIAGRAM FLOW Page 57 ECONOMIZER MS 7110K RANGE 2- 10 VDC RED BL K BRN WHT NF 24- S R AF 24- S R RANGE 2- 10 VDC P3 3 7 9 8 RED GRY RE D- BL K RE D- BL K 1 1, 2 RE D- BL K BLK RT16 1 P104 4 J 104 1 2 P105 J 105 1 2 3 RE D- BL K BLK RE D- BL K BLK GRY RE D- BL K 2 4 VAC GND GND DP OS GND VOT GND RT16 1 8 VDC A7- S GND GND 1 8 VDC A62- S P384 J 384 8 1 10 3 9 2 A5 5 MAI N CT RL 11 4 12 5 13 6 14 7 RE D- BL K BLK Model: Voltage: Supersedes: LC,LG,LH,LD,SC,SG Series Economizer & Motorized OAD HTG CLG CLG ACCS ACCS SEC SEC SEC SEC SEC A B B3 C D All Voltages WIR ING DIAGRAM FLOW N/A Form No: 5 3 8 0 7 2 - 0 1 Rev: 2 Page 58 WB- 012 WB- 011 WB- 010 L C/ L H UNI T S ONL Y WB- 012 WB- 011 WB- 010 L C/ L H UNI T S ONL Y WB- 012 WB- 011 WB- 010 L C/ L H UNI T S ONL Y POWER ENTRY T E RMI NAL BL OCK ( UNI T POWE RE D GF I OUT L E T NOT OF F E RE D) T O T B13 L I NE B- SECT L OC AA07 DI S CONNE CT S WI T CH ( UNI T POWE RE D GF I OUT L E T OPT I ONAL ) T O T B13 L I NE B- SECT L OC AA07 CI RCUI T BRE AKE R ( UNI T POWE RE D GF I OUT L E T OPT I ONAL ) T O T B13 L I NE B- SECT L OC AA07 L1 L2 L3 WI RI NG F ROM E L E CT RI C HE AT AS S E MBL I E S I F APPL I CABL E L1 L2 L3 WI RI NG F ROM E L E CT RI C HE AT AS S E MBL I E S I F APPL I CABL E L1 L2 L3 WI RI NG F ROM E L E CT RI C HE AT AS S E MBL I E S I F APPL I CABL E L C/ L H UNI T S IW T H 80 AMP DI S CONNE CT S IW T CH ONL Y. ( NOT PRE S E NT WHE N OPT I ONAL UNI T POWE RE D GF I OUT L E T I S I NS T AL L E D) L1 L2 L3 L1 L2 L3 BL U BL U PNK PNK L1 L2 L3 L I NE VOL T AGE F I E L D I NS T AL L E D F ROM S 117 I F OPT I ONAL UNI T POWE RE D GF I OUT L E T I S I NS T AL L E D. L1 L2 L3 L I NE VOL T AGE F I E L D I NS T AL L E D F ROM S 117 I F OPT I ONAL UNI T POWE RE D GF I OUT L E T I S I NS T AL L E D. OPT I ONAL UNI T POWE RE D GF I OUT L E T S HOWN NOT E : 120V F I E L D PROVI DE D POWE R S UPPL Y I S RE QUI RE D WHE N UNI T I S E QUI PPE D WI T H OPT I ONAL F I E L D WI RE D GF I OUT L E T ONL Y. L1 L2 L3 L I NE VOL T AGE F I E L D I NS T AL L E D L1 T1 Model: Voltage: Supersedes: L2 WHT GRN- YE L BLU PNK T2 BL K BL K GRN- YE L BRAS S S CRE W GRN DE NOT E S OPT I ONAL COMPONE NT S AND WI RI NG SI L VER SCREW LC, LG, LH, LD Series RTU Power Entry Options 156 - 360 All Voltages 538103-01 Form No: 5 3 8 1 0 3 - 0 2 Rev: 2 Page 59 WB- 012 WB- 011 WB- 010 POWER ENTRY T O T B13 L I NE B- SECT L OC AA07 L1 L2 L3 L1 L2 L3 L I NE VOL T AGE F I E L D I NS T AL L E D OPT I ONAL GF I OUT L E T 120V F I E L D PROVI DE D POWE R S UPPL Y I S RE QUI RE D. DE NOT E S OPT I ONAL COMPONE NT S AND WI RI NG Model: Voltage: Supersedes: LG, LD Series RTU with SCCR Power Entry Options 156 - 360 All Voltages 538104-01 Form No: 5 3 8 1 0 4 - 0 2 Rev: 2 538104-02 Rev 2 Page 60 POWER ENTRY WB- 012 WB- 011 WB- 010 WB- 012 WB- 011 WB- 010 UNI T S W/ E L E CT RI C HE AT T O T B13 L I NE B- SECT L OC AA07 UNI T S W/ O E L E CT RI C HE AT T O T B13 L I NE B- SECT L OC AA07 L1 L2 L3 WI RI NG F ROM E L E CT RI C HE AT AS S E MBL I E S L1 L2 L3 L I NE VOL T AGE F I E L D I NS T AL L E D L1 L2 L3 L I NE VOL T AGE F I E L D I NS T AL L E D OPT I ONAL GF I OUT L E T 120V F I E L D PROVI DE D POWE R S UPPL Y I S RE QUI RE D. DE NOT E S OPT I ONAL COMPONE NT S AND WI RI NG Model: Voltage: Supersedes: LC, LH Series RTU with SCCR Power Entry Options 156 - 360 All Voltages 538105-01 Form No: 5 3 8 1 0 5 - 0 2 Rev: 2 Page 61 G / J VOLT WITH BY-PASS K10 K68 GND K149 GND ORN GRY 1 A5 5 P394 1 4 3 6 J 394 MAI N CT RL ORN 1 YEL 2 YEL 1 YEL- BLK YEL- BLK 2 1 YEL YEL 2 1 YEL- BLK YEL- BLK 2 5 24VAC 1 HPS W1 6 24VAC 2 HPS W2 7 24VAC 3 L PS W1 8 24VAC 4 L PS W2 P388 J 388 P385 J 385 J 382 P382 1 RE D- BL K GRY 2 1 RE D- BL K GRY 2 1 RE D- BL K GRY 2 1 RT17 RT6 1 4 GND GND 4 2 RT48 RT46 2 5 GND GND 5 3 RT49 RT47 3 6 GND GND 6 1 RE D- BL K 2 GRY 3 4 RE D- BL K 1 GRY 2 RE D- BL K 1 GRY 2 RE D- BL K 1 21 2 2 3 GRY 3 4 4 1 BL U- BL K BL U- BL K 2 1 BLU BLU 2 1 BL U- BL K BL U- BL K 2 1 BLU BLU 2 P399 J 399 8 24VAC 4 HPS W4 7 24VAC 3 HPS W3 6 24VAC 2 L PS W4 5 24VAC 1 L PS W3 1 RE D- BL K GRY 2 1 RE D- BL K GRY 2 P404 J 404 J 401 P401 A1 7 8 AUX CT RL 1 RT52 3 GND RT50 1 GND 3 2 RT53 4 GND RT51 2 GND 4 RE D- BL K 1 GRY 2 RE D- BL K 1 GRY 2 ORN GRY ORN GRY A5 5 MAI N CTRL J 390 1 4 P390 2 5 ORN GRY GND GRY GRY GND GND L30 GND GND K152 K153 BYPS ORN K150 GRY GND GND 2 4 VAC GND COMP 4 BL U COMP 3 P NK GRY GND BL U BL WR/ I ON GND COMP 1 GND COMP 2 GND 2 4 VAC GND MPE / ZBPD 0- 10VDC GND I DB RPM GND 2 4 VAC GND L 14 2 4 VAC J 395 1 P395 WB- 008 TO P400 ON A178 WB- 009 RED GRY RE D GRY RED GRY RE D- BL K GRY 2 3 4 J 394 2 5 P394 3 8 2 7 J 381 P381 WB- 038 L OC BB08 RED GRY RED GRY ZONE BYPAS S DAMPE R CONNE CT I ON, 0- 10VDC ONL Y. 24V PWR S UPPL Y T O BE F I E L D PROVI DE D. P431 1 4 PL UG P431 L OCATE D NE AR CONT ROL BOARD A178. WB- 039 L OC BB08 MODBUS CABL E W/ RJ - 45 YEL RED GRN P415 213 J 392 4 2 1 3 J 389 1 3 2 4 J 398 1 3 2 P392 P389 P398 F ROM L OC MM0 5 BL U- BL K YEL GRY YEL- BLK GRY WB- 014 GRY WB- 013 F ROM L OC MM0 5 GRN GRY TO K202 A1 WB- 002 GRN GRY OPT I ONAL UVC- L I GHT CONNE CT I ONS F ROM T 49, S E E I AQ DI AGRAM GRN GRN GRY GRN WB- 003 TO K202 A2 OPT I ONAL POWE R E XHAUS T F AN S UPPL Y VOL TAGE TO F6- L1/ L2 B5- S E CT L OC AA04 WB- 040 WB- 041 RED WB- 016 WHT WB- 015 WHT WB- 034 US E J UMPE R PROVI DE D I N UVC KI T T O CONNE CT T O L 2 BL K WHT WB- 033 F ROM K203 B GRY WB- 003 F ROM K203 A GRN WB- 002 WB- 021 BRN BL K WB- 022 BL K WB- 023 DRNWR DRNWR P NK BL U P NK RE AR MI DDL E F RONT YEL L1 L2 L3 BLU F ROM A12 MODBUS A- S E CT L OC F F 02 - OR- A55 HE ADE R 413 PNK ( NOT S HOWN) YEL BLU BL U YEL P NK F ROM T 18 L OC BB04/ 05 123 P246 WB- 032 P NK 12 P422 OPT I ONAL I ONI ZE R WI RI NG. S E E I AQ WI RI NG DI AGRAM. YEL BL U BL U YEL YEL P NK BL U YEL P NK BL U YEL YEL P NK YEL WB- 012 WB- 011 WB- 010 P NK P NK P NK WB- 039 WB- 038 S E E POWE R E NT RY DI AGRAM I N DI S CONNE CT BOX F OR DE T AI L S YEL YEL RED P NK GRY RED BL U YEL RED BL U YEL RED BL U BL U YEL P NK P NK RED GRY RED YEL BL U 123 123 P NK P NK YEL YEL BL U BL U 1 2 3 J 247 P249 PNK YEL BL U YEL P NK J 249 1 2 BLU 3 P247 BL U YEL P NK 3 YEL P NK YEL BL U YEL GRY WB- 008 RED GRY WB- 009 4 J 400 1 2 P400 F ROM T 18 J 397 1 6 P397 4 9 2 7 GRY ORN GRN ORN GRY WB- 013 WB- 014 T O L OC E E 04/ 05 DE NOT E S OPT I ONAL COMPONE NT S AND WI RI NG GRY ORN PNK YEL BLU F ROM F 10 1 PNK PNK PNK YEL YEL 3 BLU YEL 2 WB- 001 T O K10, K68, K152, K153, L OC KK08 WB- 004 T O K125/ K262, A- S E CT L OC BB07 WB- 005 T O A3/ A12, A- S E CT L OC BB07 WB- 006 T O B6/ B15, A- S E CT L OC BB07 WB- 007 T O HR6/ HR16, A- S E CT L OC BB07 WB- 037 T O K149, K150, K152, K153, L OC MM09 WB- 030 T O K10, K68, K149, K150, L OC KK08 F ROM F 10 YEL WB- 037 YEL P UR WB- 030 P UR WB- 001 YEL P NK PNK YEL ORN 1 P NK YEL YEL BL U ORN 1 BLU ORN 1 YEL BL U ORN 1 P NK BL U ORN 1 P NK BL U ORN 1 2 2 2 2 2 2 P UR P UR P UR ORN ORN ORN ORN ORN ORN BL K P UR BL K BL K BL K BL K BL K 12 P86 3 P47 3 2 1 J 47 45 P86 6 P52 3 2 1 J 52 78 P86 9 P106 3 2 1 J 106 12 P87 3 P107 3 2 1 J 107 45 P87 6 P108 3 2 1 J 108 78 P87 9 P109 3 2 1 J 109 BL U YEL P NK RED YEL P NK YEL P NK YEL P NK Model: LGT, LCT 302, 360 - G, J-VOLT COOLING - MSAV - WITH BYPASS Voltage: Supersedes: 460V/3~/60Hz (G), 575V/3~/60Hz (J) N/A Form No: 5 3 8 3 3 9 -0 1 Rev: 0 W IR IN G HE ATING DIAG R AM SECTION FLOW A COOLING S E C T IO N B COOLING ACCS ACCS SECTION SECTION SECTION B 3 /5 C D Page 62 G / J VOLT NO BY-PASS PNK YEL BL U ORN GRY 1 A5 5 P394 1 4 3 6 J 394 MAI N CT RL ORN 1 YEL 2 YEL 1 YEL- BLK YEL- BLK 2 1 YEL YEL 2 1 YEL- BLK YEL- BLK 2 5 24VAC 1 HPS W1 6 24VAC 2 HPS W2 7 24VAC 3 L PS W1 8 24VAC 4 L PS W2 P388 J 388 P385 J 385 J 382 P382 1 RE D- BL K GRY 2 1 RE D- BL K GRY 2 1 RE D- BL K GRY 2 1 RT17 RT6 1 4 GND GND 4 2 RT48 RT46 2 5 GND GND 5 3 RT49 RT47 3 6 GND GND 6 1 RE D- BL K 2 GRY 3 4 RE D- BL K 1 GRY 2 RE D- BL K 1 GRY 2 RE D- BL K 1 21 2 2 3 GRY 3 4 4 1 BL U- BL K BL U- BL K 2 1 BLU BL U 2 1 BL U- BL K BL U- BL K 2 1 BLU BL U 2 P399 J 399 8 24VAC 4 HPS W4 7 24VAC 3 HPS W3 6 24VAC 2 L PS W4 5 24VAC 1 L PS W3 1 RE D- BL K GRY 2 1 RE D- BL K GRY 2 GRY GND GND GRY L30 GND L14 COMP 4 BL U COMP3 GRY GND GRY GND COMP2 BL WR/ I ON GND COMP1 GND MPE / ZBPD 0- 10VDC GND I DB RPM GND RED 2 4 VAC GRY GND 2 4 VAC GND 2 4 VAC J 395 1 2 3 P395 4 J 394 2 5 P394 J 381 3 8 2 7 P381 J 392 4 2 1 3 J 389 1 3 2 4 J 398 1 3 2 P392 P389 P398 BL U- BL K WB- 008 TO P400 ON A178 WB- 009 RED GRY RED WB- 038 L OC BB08 RED GRY RED GRY RE D- BL K GRY 3 P431 1 1 2 WB- 039 L OC BB08 MODBUS CABL E W/ RJ - 45 5 PL UG P431 L OCAT E D NE AR CONT ROL BOARD A178. WB- 043 GRY RE D- BL K 4 WB- 042 TO B5- SECT L OC AA01 VF D POWE R E XHAUS T WB- 032 2 1 WB- 033 P422 OPT I ONAL I ONI ZE R WI RI NG. S E E I AQ WI RI NG DI AGRAM. OPT I ONAL UVC- L I GHT CONNE CT I ONS F ROM T 49, S E E I AQ DI AGRAM BL K WHT YEL GRY YEL- BLK OPT I ONAL POWE R E XHAUS T F AN S UPPL Y VOL T AGE TO F6- L1/ L2 B5- S E CT L OC AA04 WB- 040 WB- 041 YEL RED GRN P415 213 US E J UMPE R PROVI DE D I N UVC KI T T O CONNE CT T O L 2 WB- 021 BRN BL K WB- 022 BL K WB- 023 DRNWR DRNWR PNK BL U PNK RE AR MI DDL E F RONT YEL L1 L2 L3 BL U F ROM A12 MODBUS A- S E CT L OC F F 02 - OR- A55 HE ADE R 413 PNK ( NOT S HOWN) YEL BL U BL U YEL PNK F ROM T 18 L OC BB04/ 05 123 P246 PNK PNK PNK WB- 039 WB- 038 S E E POWE R E NT RY DI AGRAM I N DI S CONNE CT BOX F OR DE T AI L S BL U YEL YEL PNK BL U YEL PNK BL U YEL YEL PNK YEL WB- 012 WB- 011 WB- 010 YEL YEL RED PNK GRY RED BL U YEL RED BL U YEL RED BL U RED GR Y RED 123 123 PNK YEL BL U 123 123 P247 P423 RED WB- 016 WHT WB- 015 WHT WB- 034 PNK BL U PNK YEL BL U YEL PNK YEL BL U YEL P404 J 404 J 401 P401 GRY ORN K149 GRY GND ORN GRY GND A1 7 8 AUX CT RL 1 RT52 3 GND RT50 1 GND 3 2 RT53 4 GND RT51 2 GND 4 RE D- BL K 1 GRY 2 RE D- BL K 1 GRY 2 ORN A5 5 MAI N CTRL K68 K10 J 390 1 4 P390 2 5 GND 2 4 VAC GND GRY WB- 008 RED GRY WB- 009 GND GRY GND ORN K150 4 J 400 1 2 P400 GND A3 0 2 4 VAC A5 5 MAI N CT RL J 378 3 1 2 P378 K152 K153 A1 7 8 AUX CT RL J 397 1 6 2 7 P397 GRY ORN FI ELD PROVI DE D WI RI NG F ROM T 18 7 OPT I ONAL POWE R E XHAUS T BL OWE R S UPPL Y VOL T AGE 1234 P69 6 GRN- YE L PNK YEL BL U F ROM F 10 ORN 1 PNK PNK PNK YEL YEL 3 BLU YEL YEL 2 WB- 001 T O K10, K68, K152, K153, L OC KK08 WB- 004 T O K125/ K262, A- S E CT L OC BB07 WB- 005 T O A3/ A12, A- S E CT L OC BB07 WB- 006 T O B6/ B15, A- S E CT L OC BB07 WB- 007 T O HR6/ HR16, A- S E CT L OC BB07 WB- 037 T O K149, K150, K152, K153, L OC MM09 WB- 030 T O K10, K68, K149, K150, L OC KK08 F ROM F 10 ORN GRY GRY DE NOT E S OPT I ONAL COMPONE NT S AND WI RI NG WB- 037 YEL PUR WB- 030 PUR WB- 001 YEL PNK PNK YEL ORN 1 PNK YEL YEL BL U ORN 1 BLU ORN 1 YEL BL U ORN 1 PNK BL U ORN 1 PNK BL U ORN 1 2 2 2 2 2 2 PUR PUR PUR ORN ORN ORN ORN ORN ORN BL K PUR BL K BL K BL K BL K BL K 12 P86 3 P47 3 2 1 J 47 45 P86 6 P52 3 2 1 J 52 78 P86 9 P106 3 2 1 J 106 12 P87 3 P107 3 2 1 J 107 45 P87 6 P108 3 2 1 J 108 78 P87 9 P109 3 2 1 J 109 BL U YEL PNK RED YEL PNK YEL PNK YEL PNK Model: LGT, LCT 302, 360 - G, J-VOLT COOLING - MSAV NO BYPASS -OR- VAV Voltage: Supersedes: 460V/3~/60Hz (G), 575V/3~/60Hz (J) N/A Form No: 5 3 8 3 4 0 -0 1 Rev: 0 W IR IN G HE ATING DIAG R AM SECTION FLOW A COOLING S E C T IO N B COOLING ACCS ACCS SECTION SECTION SECTION B 3 /5 C D Page 63 Y VOLT WITH BY-PASS K10 K68 GND K149 GND ORN GRY 1 A5 5 P394 1 4 3 6 J 394 MAI N CT RL ORN 1 YEL 2 YEL 1 YEL- BLK YEL- BLK 2 1 YEL YEL 2 1 YEL- BLK YEL- BLK 2 5 24VAC 1 HPS W1 6 24VAC 2 HPS W2 7 24VAC 3 L PS W1 8 24VAC 4 L PS W2 P388 J 388 P385 J 385 J 382 P382 1 RE D- BL K GRY 2 1 RE D- BL K GRY 2 1 RE D- BL K GRY 2 1 RT17 RT6 1 4 GND GND 4 2 RT48 RT46 2 5 GND GND 5 3 RT49 RT47 3 6 GND GND 6 1 RE D- BL K 2 GRY 3 4 RE D- BL K 1 GRY 2 RE D- BL K 1 GRY 2 RE D- BL K 1 21 2 2 3 GRY 3 4 4 1 BL U- BL K BL U- BL K 2 1 BLU BLU 2 1 BL U- BL K BL U- BL K 2 1 BLU BLU 2 P399 J 399 8 24VAC 4 HPS W4 7 24VAC 3 HPS W3 6 24VAC 2 L PS W4 5 24VAC 1 L PS W3 1 RE D- BL K GRY 2 1 RE D- BL K GRY 2 P404 J 404 J 401 P401 A1 7 8 AUX CT RL 1 RT52 3 GND RT50 1 GND 3 2 RT53 4 GND RT51 2 GND 4 RE D- BL K 1 GRY 2 RE D- BL K 1 GRY 2 ORN GRY ORN GRY A5 5 MAI N CTRL J 390 1 4 P390 2 5 ORN GRY GND GRY GRY GND GND L30 GND GND K152 K153 BYPS ORN K150 GRY GND GND 2 4 VAC GND COMP 4 BLU COMP 3 PNK GRY GND BLU GRY GND COMP 2 BL WR/ I ON GND COMP 1 GND 2 4 VAC GND MPE / ZBPD 0- 10VDC GND I DB RPM GND 2 4 VAC L14 GND 2 4 VAC J 395 1 P395 WB- 008 TO P400 ON A178 WB- 009 RED GRY RE D GRY RED GRY RE D- BL K GRY 2 3 4 J 394 2 5 P394 3 8 2 7 J 381 P381 WB- 038 L OC BB08 RED GRY RED GRY ZONE BYPAS S DAMPE R CONNE CT I ON, 0- 10VDC ONL Y. 24V PWR S UPPL Y T O BE F I E L D PROVI DE D. P431 1 4 PL UG P431 L OCAT E D NE AR CONT ROL BOARD A178. WB- 039 L OC BB08 MODBUS CABL E W/ RJ - 45 F ROM K203 A YEL RED GRN GRN WB- 002 WB- 021 BRN BLK WB- 023 DRNWR DRNWR UVC- L I GHT POWE R: US E DUAL CONNE CT OR PROVI DE D I N KI T. S E E I AQ DI AGRAM. L1 L2 L3 BL U YEL RE AR PNK MI DDL E F RONT 5 PNK YEL BL U BLU PNK WB- 022 BL K P415 5 213 F ROM A12 MODBUS A- S E CT L OC F F 02 - ORA55 HE ADE R 413 ( NOT S HOWN) BLU YEL PNK F ROM T 18 L OC BB04/ 05 123 P246 PNK YEL WB- 012 WB- 011 WB- 010 PNK PNK PNK WB- 039 WB- 038 S E E POWE R E NT RY DI AGRAM I N DI S CONNE CT BOX F OR DE T AI L S F ROM K203 B GRY WB- 003 WB- 033 WB- 032 PNK YEL J 392 4 2 1 3 P392 F ROM L OC MM0 5 J 389 1 3 P389 YEL GRY WB- 014 GRY GRN MM0 5 WB- 013 F ROM L OC GRY TO K202 A1 WB- 002 GRN GRY GRN WB- 003 TO K202 A2 GRY GRN GRN WHT BLK 12 P422 OPT I ONAL I ONI ZE R WI RI NG. S E E I AQ WI RI NG DI AGRAM. BLU PNK PNK YEL RED BLU YEL RE D PNK YEL BL U YEL BL U RED 123 123 RED PNK PNK YEL YEL BLU BLU 123 J 247 P249 PNK YEL BL U 3 PNK PNK L1 L2 L3 Model: LGT, LCT 302, 360 - Y-VOLT COOLING - MSAV WITH BYPASS YEL BL U YEL BLU YEL YEL- BLK PNK RED 2 4 J 398 1 3 P398 2 4 J 400 1 2 P400 BL U- BL K OPT I ONAL POWE R E XHAUS T F AN S UPPL Y VOL T AGE TO F6- L1/ L2 B5- S E CT L OC AA04 WB- 040 WB- 041 F ROM T 18 GRY WB- 008 RED GRY WB- 009 J 397 1 6 P397 4 9 2 7 GRY ORN GRN ORN GRY WB- 013 WB- 014 T O L OC E E 04/ 05 DE NOT E S OPT I ONAL COMPONE NT S AND WI RI NG GRY ORN YEL PNK PNK YEL BLU YEL BLU YEL YEL PNK BLU YEL PNK YEL BLU F ROM F 10 1 PNK PNK PNK YEL YEL 3 BLU YEL YEL 2 WB- 001 T O K10, K68, K152, K153, L OC KK08 WB- 004 T O K125/ K262, A- S E CT L OC BB07 WB- 005 T O A3/ A12, A- S E CT L OC BB07 WB- 006 T O B6/ B15, A- S E CT L OC BB07 WB- 007 T O HR6/ HR16, A- S E CT L OC BB07 WB- 037 T O K149, K150, K152, K153, L OC MM09 WB- 030 T O K10, K68, K149, K150, L OC KK08 F ROM F 10 WB- 037 YEL PUR WB- 030 PUR WB- 001 YE L PNK PNK YEL ORN 1 PNK YEL YEL BL U ORN 1 BLU ORN 1 YEL BLU ORN 1 PNK BLU ORN 1 PNK BLU ORN 1 2 2 2 2 2 2 PUR PUR PUR ORN ORN ORN ORN ORN ORN BLK PUR BLK BLK BLK BLK BLK 12 P86 3 P47 3 2 1 J 47 45 P86 6 P52 3 2 1 J 52 78 P86 9 P106 3 2 1 J 106 12 P87 3 P107 3 2 1 J 107 45 P87 6 P108 3 2 1 J 108 78 P87 9 P109 3 2 1 J 109 BLU YEL YEL PNK RED BLU YEL RED BLU YEL PNK YEL Voltage: Supersedes: 208-240V/3~/60Hz (Y) N/A Form No: 5 3 8 3 3 4 -0 1 Rev: 0 W IR IN G HE ATING DIAG R AM SECTION FLOW A COOLING S E C T IO N B COOLING ACCS ACCS SECTION SECTION SECTION B 3 /5 C D YEL Page 64 Y VOLT NO BYPASS ORN GRY P394 J 394 1 4 3 6 ORN P388 J 388 1 YEL 2 YEL 1 BLU BL U 2 1 YEL YEL 2 1 BLU BL U 2 A5 5 MAI N CT RL 5 24VAC 1 HPS W1 6 24VAC 2 HPS W2 7 24VAC 3 L PS W1 1 RE D- BL K GRY 2 1 RE D- BL K GRY 2 1 RE D- BL K GRY 2 8 24VAC 4 L PS W2 DE F ROS T CONT ROL RT 48- S E NS OR, COND COI L 1 RT 49- S E NS OR, COND COI L 2 1 RT17 RT6 1 4 GND GND 4 2 RT48 RT46 2 5 GND GND 5 3 RT49 RT47 3 6 GND GND 6 GRY GND GND GRY MPE / ZBPD 0- 10VDC GND I DB RPM GND L2 GND L1 RE D 2 4 VAC GRY GND 2 4 VAC GND 2 4 VAC J 395 1 2 3 P395 4 J 394 2 5 J 381 3 8 2 7 J 392 4 2 1 3 P394 P381 P392 J 391 1 2 P391 RE D- BL K GRY WB- 008 TO P400 ON A178 WB- 009 RED GRY RED WB- 038 L OC BB08 RED GRY RED GRY 3 1 2 P431 WB- 039 L OC BB08 MODBUS CABL E W/ RJ - 45 5 PL UG P431 L OCAT E D NE AR CONT ROL BOARD A178. WB- 043 2 GRY RE D- BL K TO B5- SECT L OC AA01 VF D POWE R E XHAUS T WB- 042 4 WB- 032 BLK WB- 033 WH T 1 P422 OPT I ONAL I ONI ZE R WI RI NG. S E E I AQ WI RI NG DI AGRAM. YEL RED GRN WB- 021 BRN BLK WB- 023 DRNWR DRNWR UVC- L I GHT POWE R: US E DUAL CONNE CT OR PROVI DE D I N KI T. S E E I AQ DI AGRAM. L1 L2 L3 BL U YEL RE AR PNK MI DDL E F RONT 2 PNK YEL BL U BLU PNK P415 213 2 F ROM A12 MODBUS A- S E CT L OC F F 02 - ORA55 HE ADE R 413 ( NOT S HOWN) WB- 022 BL K BLU YEL PNK F ROM T 18 L OC BB04/ 05 123 P246 12 ORN GRY PNK BLU PNK YEL BL U BL WR/ I ON GND L34 S OL E NOI D, 2- S T G COMPR 1 GND COMP1 GND COMP2 GND K10 K68 GND K149 GND P385 J 385 J 382 P382 1 RE D- BL K 2 GRY 3 4 RE D- BL K 1 GRY 2 RE D- BL K 1 GRY 2 RE D- BL K 1 11 2 2 3 GRY 3 4 4 CONT ROL BOARD ARRANGE ME NT E VAPORAT OR COI L F RE E ZE PROT E CT I ON RT 46- S E NS OR, E VAP COI L 1 RT 47- S E NS OR, E VAP COI L 2 J 389 1 3 2 4 J 390 1 4 P389 P390 2 5 A1 7 8 AUX CT RL J 397 1 6 P397 ORN K150 YEL GRY BLU GRY ORN ORN GRY GRY ORN GR Y OPT I ONAL POWE R E XHAUS T F AN S UPPL Y VOL T AGE TO F6- L1/ L2 B- 5 S E CT L OC AA04 WB- 040 WB- 041 1234 OPT I ONAL POWE R E XHAUS T BL OWE R S UPPL Y VOL T AGE P69 GRN- YE L PNK PNK 6 PNK YEL YEL BLU YEL PNK YEL 1 23 PNK YEL BLU YEL PNK YEL BLU YEL GRY GND ORN ORN K152 K153 GRY WB- 008 RED 2 4 VAC GRY GND WB- 009 DE NOT E S OPT I ONAL COMPONE NT S AND WI RI NG GND 2 7 J 400 1 2 P400 GRY GRY F ROM T 18 L OC BB05 ORN WB- 005 DUAL F UE L UNI T S ONL Y: T O A3/ A12, A- S E CT L OC BB07 WB- 004 DUAL F UE L UNI T S ONL Y: OPT I ONAL L OW AMBI E NT VE S T I BUL E HE AT E R KI T . T O K125/ K262, A- S E CT L OC BB07 WB- 006 DUAL F UE L UNI T S ONL Y: T O B6/ B15, A- S E CT L OC BB07 WB- 007 DUAL F UE L UNI T S ONL Y: OPT I ONAL L OW AMBI E NT VE S T I BUL E HE AT E R KI T HR6/ HR16, A- S E CT L OC BB07 PNK YEL WB- 012 WB- 011 WB- 010 BL U YEL PNK PNK PNK PNK WB- 039 WB- 038 BLU BLU PNK PNK YEL BL U PNK YEL BL U S E E POWE R E NT RY DI AGRAM I N DI S CONNE CT BOX F OR DE T AI L S GRY RED RED GRY RED 123 123 PNK YEL BLU 123 123 P247 P423 PNK YEL BLU YEL PNK YEL BL K PUR BL K PUR BL K PUR BL K PUR BL K PUR BL K PUR PNK YEL PNK YEL YEL BL U ORN 1 ORN 1 ORN 1 ORN 1 ORN 1 ORN 1 2 2 2 2 2 2 ORN ORN ORN ORN ORN ORN 12 P86 3 P47 3 2 1 J 47 45 P86 6 P52 3 2 1 J 52 78 P86 9 P106 3 2 1 J 106 12 P87 3 P107 3 2 1 J 107 45 P87 6 P108 3 2 1 J 108 78 P87 9 P109 3 2 1 J 109 YEL BL U PNK BL U PNK BL U BAS I C RT U L AYOUT B22 B4 B3 B23 B5 B1 B2 B24 B21 Model: LHT, LDT 302 - Y-VOLT COOLING - MSAV- NO BYPASS Voltage: Supersedes: 208-240V/3~/60Hz (Y) N/A Form No: 5 3 8 3 5 4 -0 1 Rev: 0 W IR IN G HE ATING DIAG R AM SECTION FLOW A COOLING S E C T IO N B COOLING ACCS ACCS SECTION SECTION SECTION B3 C D Page 65 SEQUNCE OF OPERATION LCT302 - 360 POWER: 1- Line voltage from TB2, unit disconnect S48, or other factory or field installed optional power disconnects, such as CB10, energizes transformer T1 and T18. Transformer T1 provides 24VAC power to the A55 Unit Controller and T18 provides 24VAC power to A178 Compressor 3 and 4 Controller. The two controllers provide 24VAC power to the unit cooling, heating and blower controls and thermostat. 2- Terminal block TB13 is also energized when the unit disconnect closes. TB13 supplies line voltage to compressor crankcase heaters, compressors, blower motors and fan motors. BLOWER OPERATION (OCP INPUT MUST BE ON): 3- The A55 Unit Controller receives a demand from thermostat terminal G. A55 energizes blower contactor K3 with 24VAC. On VFD units, A55 energizes relay K203. 4- N.O. K3-1 closes, energizing blower B3. On VFD units, N.O. K203-2 closes, sending a signal to the inverter, A96, to start forward rotation. P259 pin #4 sends a 0 -10VDC signal to A96 to control blower B3 speed. POWER EXHAUST FANS/BLOWERS: 5- The A55 Unit Controller receives a demand and energizes exhaust fan relay K65 OR exhaust blower contactor K205 or exhaust blower relay K207. 1ST STAGE COOLING (B1 AND B2 ARE ENERGIZED): 6- First stage cooling demand energizes Y1 and G in the thermostat. G energizes blower, if blower is not already running (see step 3). 7- 24VAC is routed to the A55 Unit Controller. After A55 proves N.C. low pressure switch S87 and S88, N.C. freezestat S49 and S50 and N.C. high pressure switch S4 and S7, compressor contactors K1 and K2 are energized. 8- N.O. contacts K1-1 and K2-1 close energizing compressor B1 and B2. 9- A55 Unit Controller and A178 Controller energize fan contactor K10, K68, and K149 based on low ambient switch S11 and S84 inputs and predefined control logic. 10-N.O. contact K10-1, K68-1, K149-1 close energizing fan B4, B5 and B21 respectively. 11- N.C. Contacts K1-2 and K2-2 open de-energizing compressor 1 and 2 crankcase heater HR1 and HR2. 2ND STAGE COOLING: 12- Second stage cooling demand energizes Y2. 13-24VAC is routed to A178 Compressor 3 and 4 Controller. After A178 proves N.C. low pressure switches S98 and S97, N.C. freezestats S53 and S95 and N.C. high pressure switches S28 and S96, compressor contactors K14 and K146 are energized. 14- N.O. contacts K14-1 close energizing compressor B13. 15- N.O. contacts K146-1 close energizing compressor B20. 16- A178 Controller energizes fan contactor K150, K152, K153 based on low ambient switch S85 and S94 inputs and predefined control logic. 17-N.O. contacts K150-1, K152-1 and K153-1 close energizing condenser fan B22, B23 and B24 respectively. 18-N.C contacts K14-2 and K146-2 open de-energizing compressor 3 and 4 crankcase heater HR5 and HR11. Page 66Adobe PDF Library 17.0 Adobe InDesign 20.0 (Windows)