nVent CADDY CSBQIKCL0100EG Installation Manual
INSTRUCTION SHEET



Step 1

***(XX) = Finish Specifier

Step 2

Step 3

Step 4

Sway brace assemblies are intended to be installed in accordance with NFPA-13 and the manufacturer's installation instructions.

WARNING: 1. nVent products shall be installed and used only as indicated in nVent product instruction sheets and training materials. Instruction sheets are available at
www.nVent.com and from your nVent customer service representative. 2. nVent products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings. 3. All instructions must be completely followed to ensure proper and safe installation and performance. 4. Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property
damage, serious bodily injury and/or death, and void your warranty. 5. Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment. 6. All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any
other purpose.

NOTE: All load ratings are for static conditions and do not account for dynamic loading such as wind, water or seismic loads, unless otherwise noted.

The customer is responsible for: a. Conformance to all governing codes. b. The integrity of structures to which the products are attached, including their capability of safely accepting the loads imposed, as evaluated by a qualified engineer. c. Using appropriate industry standard hardware as noted above.

SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.

Dyna-Flow is a registered trademark of Allied Tube and Conduit Corporation. FM is a registered certification mark of FM Approvals LLC, LTD. NFPA is a registered trademark of National Fire Protection Association, Inc. UL is a registered trademark of UL LLC.

nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS399_K

1 OF 10

© 2008-2018 nVent All Rights Reserved

INSTRUCTION SHEET



(1) Load ratings for Schedule 40 above may also be applied to GB/T 3091, EN 10255 (Heavy), and JIS G3454 pipe. (2) Load ratings for Schedule 10 above may also be applied to GB/T 3091, EN 10255 (Medium or Heavy), JIS G3452, FM approved Thinwall,
and Schedule 40 pipes unless otherwise indicated. (3) Load ratings for LW above refers to FM Approved Lightwall Pipe, commonly referred to as "Schedule 7". These ratings may also be
applied to EN 10220, and GB/T 8163 pipe unless otherwise specified.

Part Number CSBQIKCL0100XX CSBQIKCL0125XX CSBQIKCL0150XX CSBQIKCL0200XX

UL® Loads (Listed for Restraints)

Service Pipe Schedule

Lateral 1" Brace Pipe

Dyna-Flow®

N/A

10

655 lb (2,914 N)

40

655 lb (2,914 N)

Dyna-Flow®

655 lb (2,914 N)

10

655 lb (2,914 N)

40

655 lb (2,914 N)

Dyna-Flow®

750 lb (3,337 N)

10

750 lb (3,337 N)

40

750 lb (3,337 N)

Dyna-Flow®

750 lb (3,337 N)

10

750 lb (3,337 N)

40

750 lb (3,337 N)

1 1/4" Brace Pipe N/A
655 lb (2,914 N) 655 lb (2,914 N) 540 lb (2,402 N) 540 lb (2,402 N) 540 lb (2,402 N) 655 lb (2,914 N) 655 lb (2,914 N) 655 lb (2,914 N) 540 lb (2,402 N) 540 lb (2,402 N) 540 lb (2,402 N)

nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS399_K

2 OF 10

© 2008-2018 nVent All Rights Reserved

INSTRUCTION SHEET



nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS399_K

3 OF 10

© 2008-2018 nVent All Rights Reserved

INSTRUCTION SHEET


Concrete anchor could be cast in place, wedge, pre-set or a concrete anchor screw.

Concrete anchor could be cast in place, wedge, pre-set or a concrete anchor screw.

nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS399_K

4 OF 10

© 2008-2018 nVent All Rights Reserved

INSTRUCTION SHEET


Concrete anchor could be cast in place, wedge, pre-set or a concrete anchor screw.

Concrete anchor could be cast in place, wedge, pre-set or a concrete anchor screw.

nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS399_K

5 OF 10

© 2008-2018 nVent All Rights Reserved

INSTRUCTION SHEET



The CSBBARJ can be installed as shown on the top flange of an I-Beam with tapered and non-tapered flanges.

nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS399_K

6 OF 10

© 2008-2018 nVent All Rights Reserved

INSTRUCTION SHEET



nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS399_K

7 OF 10

© 2008-2018 nVent All Rights Reserved

INSTRUCTION SHEET



nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS399_K

8 OF 10

© 2008-2018 nVent All Rights Reserved

INSTRUCTION SHEET


Concrete anchor could be cast in place, wedge, pre-set or a concrete anchor screw.

nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS399_K

9 OF 10

© 2008-2018 nVent All Rights Reserved

INSTRUCTION SHEET


Through bolt shown. A lag screw may also be used.

Through bolt shown. A lag screw may also be used.

nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

TECHNICAL SUPPORT: www.nVent.com

CFS399_K

10 OF 10

© 2008-2018 nVent All Rights Reserved

