Instruction Manual for VTS models including: RH T-SENS-D-MODRTU Compact Floor-Mounted Air Handling Units, RH T-SENS-D-MODRTU, Compact Floor-Mounted Air Handling Units, Floor-Mounted Air Handling Units, Air Handling Units, Handling Units, Units

Krzysztof Woliński

HUMIDITY TRANSDUCER RH T-SENS-D-MODRTU

Download

Compact Floor-Mounted Air Handling Units | Ventus - VTS Group


File Info : application/pdf, 16 Pages, 1.21MB

PDF preview unavailable. Download the PDF instead.

HUMID EN 2.0
HUMIDITY TRANSDUCER RH+T-SENS-D-MODRTU
VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 1 of 16 ver. 2.0 (11.2021)

1. Introduction
This document describes functionality of air relative humidity and temperature transducer based on integrated Sensirion SHT31-DIS-B sensor, equipped with RS485 interface using MODBUS RTU protocol and 0-5V / 0-10V analogue output.
NOTES:
1) Read this document carefully before attempting to start up the device!
2) The device must be installed by qualified staff only.
1.1. Functions of the device
 relative humidity measurement  0-5V or 0-10V analogue output (hardware selectable range) proportional to
relative humidity  3 status LEDs  RS485 serial interface for remote management (setup and reading of
measurement values)  MODBUS RTU protocol  integrated terminating resistor 120  communication in HALF DUPLEX mode  hardware/software configurable address in the range 1-247  hardware configurable communication baud rate: 19200, 9600, 4800, 2400  software configurable communication baud rate: 115200, 57600, 38400, 19200, 9600, 4800, 2400
1.2. Design Features
The main function of the RH&T transmitter is to measure air relative humidity and temperature using an integrated Sensirion SHT31-DIS-B sensor. The measurement result, as well as the sensor missing/error status, is processed by the built-in microprocessor and then made available on the RS-485 bus via registers of the MODBUS RTU protocol. Additionally, the measurement result air relative humidity is available as analog signal on the 0-5V / 0-10V voltage output.
VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 2 of 16 ver. 2.0 (11.2021)

2. Technical data 2.1. General parameters of the transducer
Power supply
 DC voltage  AC voltage
Current consumption
 typical  max
LED indicators
Signal connection
Housing dimensions  without sampling mast  with sampling mast
Weight Work environment Working temperature
2.2. Parameters of humidity measurement
Sensor model Measurement range Resolution Measurement accuracy (@ T=25ºC)
- in the range 0 ÷ 90% RH - in the remaining measurement range Hysteresis Sampling frequency

DC 20-30 V (nom. DC 24 V) AC 20-28 V (nom. AC 24 V)
TBD TBD See section 3.5 Screw terminals in 5mm pitch (wire diameter  2.5mm)
80x82x55mm 80x82x280mm
230 g Dust-free, air, neutral gases
0ºC ÷ 50ºC
SHT31-DIS-B 0÷ 100% RH
14.5 bit (0.01% RH)
± 2% RH ± 3% RH ± 0.8% RH
1 Hz

VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 3 of 16 ver. 2.0 (11.2021)

Response time 1)

8 s

1) The prerequisite for obtaining the given response times is an air flow > 1m/s; the response time

indicated is equal to one time constant corresponding to 63 % of the steady value

2.3. Parameters of temperatures measurement

Sensor model

SHT31-DIS-B

Measurement range Resolution Measurement accuracy (over entire measuring range) Sampling frequency

0ºC ÷ 90ºC 14.5 bit (0.01ºC)
± 0.25ºC 1 Hz

Response time 1)

2 s

1) The prerequisite for obtaining the given response times is an air flow > 1m/s; the response time

indicated is equal to one time constant corresponding to 63 % of the steady value

2.4. Parameters of analogue output

Output type Output range Resolution
 in [mV] for the range 0-10 V  in [mV] for the range 0-5 V Loading capacity Refreshing period

voltage 0-5 V or 0-10 V
11.5 bit 3.2mV~ 1.6mV~ RL > 1 k
1 s

VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 4 of 16 ver. 2.0 (11.2021)

2.5. Parameters of serial interface

Transmission Adapter

RS-485

Communication protocol

MODBUS RTU

Transmission type

HALF DUPLEX

Communication baud

2400 / 4800 / 9600 / 19200 / 38400 / 57600 / 115200 Baud/s

Integrated resistor terminating the RS-485 bus

120 

3. Installation 3.1. Safety  The device must be installed by qualified staff only!  All connections must be made in accordance with wiring diagrams
shown in this document!
 Check all electrical connections prior to commissioning! 3.2. Device design

VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 5 of 16 ver. 2.0 (11.2021)

3.3. Description of terminals

OR POWER SUPPLY

Notes: 1. The RXTX+ and RXTX- signals must be connected to the A and B lines of the MODBUS bus respectively. 2. The analogue output returns following voltage values:

Vout



VOLTAGE RANGE 100 %

 Re lative

_

humidity

VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 6 of 16 ver. 2.0 (11.2021)

whereas the concentration value can be calculated basing on the voltage value form using the following formula:

Re lative

_

humidity



100 % VOLTAGE RANGE

 VO U T

where: VOLTAGERANGE = 5V or 10V (0-5V or 0-10V set on the configuration DIP-switch 2 ­ see section 3.4)

Exemplary values are shown in the table below:

Relative humidity [%]

Voltage range = 5 V

0

0.0V~

25

1.0V~

50

2.5V

75

3.75V~

100

5.0V~

Voltage range = 10V
0.0V~ 2.0V~ 5.0V 7.5V~ 10.0V~

3.4. Configuration of MODBUS bus, serial port and analogue output

0 ­ OFF

1 ­ ON

CONFIGURATION

ADDRESS

The purpose of the consecutive switches of the left DIP-switch is as follows (default values are in bold)

VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 7 of 16 ver. 2.0 (11.2021)

1

2 3 4 5 6

Effect

ON

Terminating resistor 120R switched on

OFF

Terminating resistor 120R switched off

ON

Analogue output range 0-5V

OFF

Analogue output range 0-10V

ON ON

Use BAUDRATE and PAR from the software configuration

ON OFF

PAR - parity check (1 STOP bit)

OFF ON

PAR - no parity check (2 STOP bits)

OFF OFF

PAR - no parity check (1 STOP bit)

ON ON

BAUDRATE=2400

ON OFF

BAUDRATE=4800

OFF ON

BAUDRATE=9600

OFF OFF

BAUDRATE=19200

The device address on the MODBUS bus is set using the right DIP-switch:

123 4 5 6 7 8

Effect

ON

Address = address + 1

ON

Address = address + 2

ON

Address = address + 4

ON

Address = address + 8

ON

Address = address + 16

ON

Address = address + 32

ON

Address = address + 64

ON

Address = address + 128

Note: the configuration set by the means of DIP-switches is read once after device restart (after switching on the power or pressing the RESET button). For this reason, if the DIPswitch settings are changed during operation, then after changing the settings, it is

necessary to restart the device by pressing the RESET button or temporarily unplugging the

power supply.

VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 8 of 16 ver. 2.0 (11.2021)

3.5. LED indicators

3.5.1. LED POWER

No.

Description

1

Power supply present

Color / mode of light Red ­ flashing 1000 ms / 1000 ms

3.5.2. LED LINK

No.

Description

1

Data transmission on the bus

2

No transmission

Color / mode of light Green ­ continuous light / irregular flashing
LED off

3.5.3. LED SENSOR

No.

Description

1

0 ­ 19.9% RH

2

20­ 79.0% RH

3

80­ 100% RH

4

Sensor missing or other error

3.6. Recommendations for installation

Color / mode of light
Yellow ­ continuous light Green ­ continuous light Red ­ continuous light Red ­ flashing 100 ms / 600 ms

TRANSDUCER (1)

TRANSDUCER (2)

TRANSDUCER (n)

VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 9 of 16 ver. 2.0 (11.2021)

It is recommended that devices on the MODBUS (RS485) are connected in a daisy-chain configuration, whereby 120R terminating resistors should be connected between A and B lines of the bus at both ends of the chain (close to the outer devices). This resistor is builtin in the RH&T-SENS-D-MODBRTU transducer and can be switched on using the no. 1 switch on the configuration DIP-switch (see section 3.4).
Moreover, shielded cables should be used when the device is operated in high interference environments and the shield should be connected to the nearest PE point on the power supply side.

4. MODBUS protocol

4.1. Register map

Register R/W no.
0x0000 R 0x0001 R 0x0002 R

Name
RH_REG TEMP_REG TEST_VAL_REG

0x0003 RW 0x0004 RW
0x0005 RW
0x0006 R 0x0007 R 0x0008 R 0x0009 R 0x000A R
0x000B R 0x000C R

PASS_REG COMMAND_REG
PARAM_REG
----STATUS_REG
DEV_ID_REG SOFT_VER_REG

Values

Notes

0 ÷ 1000 -4000 ÷ 12380 1000 (0x3E8)

Relative humidity (1=0.1%; 1000=100%)
Temperature [ºC] (1=0.01ºC) with sing Test value ­ to verify the correctness of
register readings

1234 (0x04D2)

password register

1 / 2 / 3 / 4 / 5 /

command register

6

Refer to

parameter register

command table

0

reserved

0

reserved

0

reserved

0

reserved

0 / 1 / 2 Status register (0: NO SENSOR; 1: SENSOR OK,

2: ERROR)

0xC100

Device identification

0 ­ 0x9999

Software version

(e.g. 0x3210 means software 3.21a)

VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 10 of 16 ver. 2.0 (11.2021)

Command table:

Command no. 1 2

Function Set device address Set the baud rate

3
4 6 Notes:

Set parity bits Set stop bits Device reset

Parameters
1-247 (1 ­ default value)
24 ­ 2400 bit/s 48 ­ 4800 bit/s 96 ­ 9600 bit/s 192 ­ 19200 bit/s = default value 384 ­ 38400 bit/s 576 ­ 57600 bit/s 1152 ­ 115200 bit/s
0 ­ NO PARITY, no parity bit (default value) 1 ­ EVEN PARITY, even parity bit 2 ­ ODD PARITY, odd parity bit
1 ­ 1x STOP, 1 stop bit (default value) 2 ­ 2x STOP, 2 stop bits
1 ­ software reset of the device 2 ­ software reset of sensor module

 Reading registers from addresses not listed in this table results in 0x02 exception.

 Specifying an incorrect or out-of-range parameter value results in entering the value 0xEEEE into the command register.

 The device is configured by writing three registers (password / command / parameter) at the same time using the 0x10 function with the corresponding values ­ according to the command table, or by writing single registers (using 0x06 or 0x10 function) with the latter writing of a (valid) password causing the execution of the command.

 During a single password entry (both with function 0x06 and 0x10) in case of a password match, the correctness of information in command and parameter registers is checked and if correct, the command is executed.

4.1.1. DEV_ID_REG (addr=11=0x000B) ­ read only

Bit no. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

name

DEV[4..0]

HV[1..0]

OPTIONS[4..0]

0 0 T[1..0]

This register is used to store device ID. Meaning of bits:
DEV[4..0] = b11000 ­ fixed value meaning "air parameter sensors" HV[1..0] ­ value 0..3 ­ hardware version OPTIONS[4..0] ­ values 0..31 ­ device type

VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 11 of 16 ver. 2.0 (11.2021)

b01000 ­ RH&T transducer with SHT31-DIS-B sensor T[1..0] ­ value 0..3 ­ type
0 ­ duct type 1 ­ room type 2, 3 - reserved
RH&T duct sensor in basic hardware version returns the value b1100000010000000=0xC080.

4.1.2. SOFT_VER_REG (addr=12=0x000C) ­ read only

Bit no. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

name

N[3..0]

A[3..0]

B[3..0]

REV[3..0]

Software version is represented as a sting of 4 characters: N.ABrev where N, A, B are digits in the the 0..9 range rev (with values 0..9) is a letter in the range `a'...'j'. Examples: 0x0000 represents software version: 0.00a; 0x4321  4.32b ; 0x2345  2.34f

4.2. Protocol functions
CODE 0x03 (dec 3) 0x06 (dec 6) 0x10 (dec 16)

Name Reading N x 16-bit registers Writing single 16-bit registers Writing N x 16-bit registers

4.2.1. Reading the contents of a group of output registers (0x03)

Command format:

Description Address
Function code Data block address Number of registers (N)
Check sum CRC

Size [Bytes] 1 1 2 2 2

Values
1 ­ 247 0x03
0x0000 ­ 0xFFFF 1 ­ 125
0x0000 ­ 0xFFFF

Notes See section 4.4

VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 12 of 16 ver. 2.0 (11.2021)

Response format:
Description Address
Function code Byte counter Register values Check sum CRC

Size [Bytes] 1 1 1
2 * N 2

Values 1 ­ 247 0x03 2 * N Acc. to register map 0x0000 ­ 0xFFFF

Error format:
Description Address
Function code Error code
Check sum CRC

Size [Bytes] 1 1 1 2

Values 1 ­ 247 0x83 1 ­ 4 0x0000 ­ 0xFFFF

4.2.2. Writing single 16-bit registers (0x06)

Command format:

Description Address
Function code Register address Value to be stored Check sum CRC

Size [Bytes] 1 1 2 2 2

Values
1 ­ 247 0x06
0x0000 ­ 0xFFFF 0x0000 ­ 0xFFFF 0x0000 ­ 0xFFFF

Response format:
Description Address
Function code Register address Value to be stored Check sum CRC
Error format:
Description Address
Function code Error code
CRC check sum

Size [Bytes] 1 1 2 2 2
Size [Bytes] 1 1 1 2

Values 1 ­ 247 0x06 0x0000 ­ 0xFFFF 0x0000 ­ 0xFFFF 0x0000 ­ 0xFFFF
Values 1 ­ 247 0x86 1 ­ 4 0x0000 ­ 0xFFFF

Notes
See section 4.4 Notes
See section 4.2.4 See section 4.4
Notes
See section 4.4
Notes
See section 4.4 Notes
See section 4.2.4 See section 4.4

VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 13 of 16 ver. 2.0 (11.2021)

4.2.3. Writing a group of output registers (0x10)

Command format:

Description Address
Function code Data block address Liczba rejestrów (N)
Byte counter Values to be stored
CRC check sum

Size [Bytes] 1 1 2 2 1
2 * N 2

Values
1 ­ 247 0x10 0x0000 ­ 0xFFFF 1 ­ 123 2 * N 0x0000 ­ 0xFFFF 0x0000 ­ 0xFFFF

Notes See section 4.4

Response format:

Description Address
Function code Data block address Number of registers (N)
CRC check sum

Size [Bytes] 1 1 2 2 2

Values
1 ­ 247 0x10
0x0000 ­ 0xFFFF 1 ­ 123
0x0000 ­ 0xFFFF

Notes See section 4.4

Error format:
Description Address
Function code Error code
CRC check sum

Size [Bytes] 1 1 1 2

Values 1 ­ 247 0x90 1 ­ 4 0x0000 ­ 0xFFFF

Notes
See section 4.2.4 See section 4.4

4.2.4.
CODE 0x01 0x02 0x03 0x04

Description of errors
Name Invalid function Invalid data range / address Invalid data value SLAVE device error

4.3. Data format
4.3.1. Character / byte format
The following figure shows the format of a byte transmitted in the MODBUS RTU protocol. Each transmitted character has 10 or 11 bits, which are sent in order from the least significant to the most significant.

VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 14 of 16 ver. 2.0 (11.2021)

With even / odd parity check START 1 2 3 4 5 6 7 8 PAR STOP
Without parity check (1 or 2 stop bits): START 1 2 3 4 5 6 7 8 STOP (STOP)

4.3.2. Order of bytes in 16-bit data fields in a transmission frame

The following figure shows the byte order of the 16-bit data fields. For 16-bit data fields, the correct byte order is that the older byte is transmitted first, then the younger byte (HILO - BIG ENDIAN), while for the CRC field the younger byte is transmitted first, then the older byte (LO HI - LITTLE ENDIAN).

REG-0 (16bit)

HI

LO

DATA

REG-1 (16 bit)

REG-N (16bit)

...

HI

LO

HI

LO

CHECK SUM

CRC (16bit)

LO

HI

4.4. CRC check sum
WORD CRC16 (const BYTE *nData, WORD wLength)
{ static const WORD wCRCTable[] = { 0x0000, 0xC0C1, 0xC181, 0x0140, 0xC301, 0x03C0, 0x0280, 0xC241, 0xC601, 0x06C0, 0x0780, 0xC741, 0x0500, 0xC5C1, 0xC481, 0x0440, 0xCC01, 0x0CC0, 0x0D80, 0xCD41, 0x0F00, 0xCFC1, 0xCE81, 0x0E40, 0x0A00, 0xCAC1, 0xCB81, 0x0B40, 0xC901, 0x09C0, 0x0880, 0xC841, 0xD801, 0x18C0, 0x1980, 0xD941, 0x1B00, 0xDBC1, 0xDA81, 0x1A40, 0x1E00, 0xDEC1, 0xDF81, 0x1F40, 0xDD01, 0x1DC0, 0x1C80, 0xDC41, 0x1400, 0xD4C1, 0xD581, 0x1540, 0xD701, 0x17C0, 0x1680, 0xD641, 0xD201, 0x12C0, 0x1380, 0xD341, 0x1100, 0xD1C1, 0xD081, 0x1040, 0xF001, 0x30C0, 0x3180, 0xF141, 0x3300, 0xF3C1, 0xF281, 0x3240, 0x3600, 0xF6C1, 0xF781, 0x3740, 0xF501, 0x35C0, 0x3480, 0xF441, 0x3C00, 0xFCC1, 0xFD81, 0x3D40, 0xFF01, 0x3FC0, 0x3E80, 0xFE41, 0xFA01, 0x3AC0, 0x3B80, 0xFB41, 0x3900, 0xF9C1, 0xF881, 0x3840, 0x2800, 0xE8C1, 0xE981, 0x2940, 0xEB01, 0x2BC0, 0x2A80, 0xEA41, 0xEE01, 0x2EC0, 0x2F80, 0xEF41, 0x2D00, 0xEDC1, 0xEC81, 0x2C40, 0xE401, 0x24C0, 0x2580, 0xE541, 0x2700, 0xE7C1, 0xE681, 0x2640, 0x2200, 0xE2C1, 0xE381, 0x2340, 0xE101, 0x21C0, 0x2080, 0xE041, 0xA001, 0x60C0, 0x6180, 0xA141, 0x6300, 0xA3C1, 0xA281, 0x6240, 0x6600, 0xA6C1, 0xA781, 0x6740, 0xA501, 0x65C0, 0x6480, 0xA441, 0x6C00, 0xACC1, 0xAD81, 0x6D40, 0xAF01, 0x6FC0, 0x6E80, 0xAE41, 0xAA01, 0x6AC0, 0x6B80, 0xAB41, 0x6900, 0xA9C1, 0xA881, 0x6840, 0x7800, 0xB8C1, 0xB981, 0x7940, 0xBB01, 0x7BC0, 0x7A80, 0xBA41, 0xBE01, 0x7EC0, 0x7F80, 0xBF41, 0x7D00, 0xBDC1, 0xBC81, 0x7C40, 0xB401, 0x74C0, 0x7580, 0xB541, 0x7700, 0xB7C1, 0xB681, 0x7640, 0x7200, 0xB2C1, 0xB381, 0x7340, 0xB101, 0x71C0, 0x7080, 0xB041, 0x5000, 0x90C1, 0x9181, 0x5140, 0x9301, 0x53C0, 0x5280, 0x9241, 0x9601, 0x56C0, 0x5780, 0x9741, 0x5500, 0x95C1, 0x9481, 0x5440, 0x9C01, 0x5CC0, 0x5D80, 0x9D41, 0x5F00, 0x9FC1, 0x9E81, 0x5E40, 0x5A00, 0x9AC1, 0x9B81, 0x5B40, 0x9901, 0x59C0, 0x5880, 0x9841, 0x8801, 0x48C0, 0x4980, 0x8941, 0x4B00, 0x8BC1, 0x8A81, 0x4A40, 0x4E00, 0x8EC1, 0x8F81, 0x4F40, 0x8D01, 0x4DC0, 0x4C80, 0x8C41, 0x4400, 0x84C1, 0x8581, 0x4540, 0x8701, 0x47C0, 0x4680, 0x8641, 0x8201, 0x42C0, 0x4380, 0x8341, 0x4100, 0x81C1, 0x8081, 0x4040};
BYTE nTemp; WORD wCRCWord = 0xFFFF;
while (wLength--)
VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 15 of 16 ver. 2.0 (11.2021)

{ nTemp = *nData++ ^ wCRCWord; wCRCWord >>= 8; wCRCWord ^= wCRCTable[nTemp];
} return wCRCWord; }
VTS reserves the right to implement changes without prior notice. www.vtsgroup.com Page 16 of 16 ver. 2.0 (11.2021)



References

Microsoft Word 2016 Microsoft Word 2016