Gree DC Inverter Multi VRF System
Owner's Manual
Applicable Models: GMV-60WL/C-T(U), GMV-48WL/C-T(U), GMV-36WL/C-T(U)
Preface
For correct installation and operation, please read all instructions carefully. Before reading the instructions, please be aware of the following items:
- The design standard of multi VRF system conforms to related standard of sales countries.
- To ensure safety when operating this system, please strictly follow the instructions in this manual.
- The total capacity of running indoor units must not exceed that of the outdoor units. Otherwise, the cooling (heating) effect of each IDU would be poor.
- Make sure that this manual is kept by direct operators and maintainers.
- If the product needs to be installed, moved or maintained, please contact the designated dealer or local service center for professional support. Users should not disassemble or maintain the unit by themselves, otherwise it may cause relative damage, and the company will bear no responsibilities.
- All the illustrations and information in the instruction manual are only for reference. In order to make the product better, continuous improvement and innovation will be conducted. If there is adjustment in the product, please subject to actual product.
- Under the standby status, the unit will consume a little power for ensuring reliability of the complete unit, maintaining normal communication and preheating refrigerant. When the unit won't be used for a long time, please cut off the power of the complete unit. However, please preheat it when operating the unit next time.
User Notice
DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection of such waste separately for special treatment is necessary.
Exception Clauses
Manufacturer will bear no responsibilities when personal injury or property loss is caused by the following reasons:
- Damage the product due to improper use or misuse of the product.
- Alter, change, maintain or use the product with other equipment without abiding by the instruction manual of manufacturer.
- After verification, the defect of product is directly caused by corrosive gas.
- After verification, defects are due to improper operation during transportation of product.
- Operate, repair, maintain the unit without abiding by instruction manual or related regulations.
- After verification, the problem or dispute is caused by the quality specification or performance of parts and components that produced by other manufacturers.
- The damage is caused by natural calamities, bad using environment or force majeure.
1 Safety Notices
If not abide them strictly, it may cause severe damage to the unit or the people. ⚠️ If not abide them strictly, it may cause slight or medium damage to the unit or the people. ? This sign indicates that the items must be prohibited. Improper operation may cause severe damage or death to people. ❗ This sign indicates that the items must be observed. Improper operation may cause damage to people or property.
- This product can't be installed at corrosive, inflammable or explosive environment or the place with special requirements, such as kitchen. Otherwise, it will affect the normal operation or shorten the service life of the unit, or even cause fire hazard or serious injury. For above special places, please adopt special air conditioner with anti-corrosive or anti-explosion function.
- Follow this instruction to complete the installation work. Please carefully read this manual before unit startup and service.
- Wire size of power cord should be large enough. The damaged power cord and connection wire should be replaced by exclusive cable.
- After connecting the power cord, please fix the electric box cover properly in order to avoid accident.
- Never fail to comply with the nitrogen charge requirements. Charge nitrogen when welding pipes.
- Never short-circuit or cancel the pressure switch to prevent unit damage.
- Please firstly connect the wired controller before energization, otherwise wired controller can not be used.
- Before using the unit, please check if the piping and wiring are correct to avoid water leakage, refrigerant leakage, electric shock, or fire etc.
- Do not insert fingers or objects into air outlet/inlet grille.
- Open the door and window and keep good ventilation in the room to avoid oxygen deficit when the gas/oil supplied heating equipment is used.
- Never start up or shut off the air conditioner by means of directly plug or unplug the power cord.
- Turn off the unit after it runs at least five minutes; otherwise it will influence oil return of the compressor.
- Do not allow children operate this unit.
- Do not operate this unit with wet hands.
- Turn off the unit or cut off the power supply before cleaning the unit, otherwise electric shock or injury may happen.
- Never spray or flush water towards unit, otherwise malfunction or electric shock may happen.
- Do not expose the unit to the moist or corrosive circumstances.
- Under cooling mode, please don't set the room temperature too low and keep the temperature difference between indoor and outdoor unit within 5°C (41°F).
- User is not allowed to repair the unit. Fault service may cause electric shock or fire accidents. Please contact the designated dealer or local service center for help.
- Before installation, please check if the power supply is in accordance with the requirements specified on the nameplate. And also take care of the power safety.
- Installation should be conducted by dealer or qualified personnel. Please do not attempt to install the unit by yourself. Improper handling may result in water leakage, electric shock or fire disaster etc.
- Be sure to use the exclusive accessory and part to prevent the water leakage, electric shock and fire accidents.
- Make sure the unit can be earthed properly and soundly after plugging into the socket so as to avoid electric shock. Please do not connect the ground wire to gas pipe, water pipe, lightning rod or telephone line.
- Electrify the unit 8 hours before operation. Please switch on for 8 hours before operation. Do not cut off the power when 24 hours short-time halting (to protect the compressor).
- If refrigerant leakage happens during installation, please ventilate immediately. Poisonous gas will emerge if the refrigerant gas meets fire.
- Volatile liquid, such as diluent or gas will damage the unit appearance. Only use soft cloth with a little neutral detergent to clean the outer casing of unit.
- If anything abnormal happens (such as burning smell), please power off the unit and cut off the main power supply, and then immediately contact the designated dealer or local service center. If abnormality keeps going, the unit might be damaged and lead to electric shock or fire.
- If the product needs to be installed, moved or maintained, please contact the designated dealer or local service center for professional support, otherwise the company would bear no legal reliability for the related damages arising therefrom.
2 Product Introduction
Gree Multi VRF System adopts inverter compressor technology. By changing the displacement of compressor, step less capacity regulation within range of 15%~100% can be realized. Various product lineups are provided with capacity range from 36000Btu/h to 60000Btu/h, which can be widely used in residential, commercial and working area and especially applicable to places with big load change. Gree residential air conditioner is absolutely your best choice.
2.1 Names of Main Parts
Diagrams showing main parts for GMV-36WL/C-T(U), GMV-48WL/C-T(U), and GMV-60WL/C-T(U) are provided in the original document.
2.2 Combinations of Indoor and Outdoor Units
The number of indoor units that can be connected to the outdoor unit and the total capacity of indoor units should be within 50%~135% of that of the outdoor unit.
Model | Max sets of connectable IDUs |
---|---|
GMV-36WL/C-T(U) | 7 |
GMV-48WL/C-T(U) | 8 |
GMV-60WL/C-T(U) | 10 |
Outdoor units of DC Inverter Multi VRF System can be connected to various indoor units. When any one of the indoor units receives operating command, the outdoor unit will start operation as per required capacity. When all indoor units stop, the outdoor unit will be shut off.
2.3 Operating Range
Cooling: Outdoor temperature: -5~48°C (23~118°F)
Heating: Outdoor temperature: -20~27°C (-4~81°F)
3 Preparation before Installation
3.1 Standard Parts
Please use the supplied standard parts as required.
No. | Name | Appearance | Qty | Remark |
---|---|---|---|---|
1 | User Manual | [Document Icon] | 1 | -- |
2 | Wiring (match with resistance) | [Wire Icon] | 1 | Must be connected to the last IDU of communication connection |
3 | Corrugated pipe | [Pipe Icon] | 1 | Liquid side connection pipe |
4 | Connection pipe | [Pipe Icon] | 1 | This part is included in the following models: GMV-36WL/C-T(U), GMV-48WL/C-T(U) |
5 | Connection pipe | [Pipe Icon] | 1 | This part is included in the following models: GMV-60WL/C-T(U) |
6 | Chassis gluey plug | [Plug Icon] | 3 | -- |
7 | Drainage joint | [Joint Icon] | 1 | -- |
3.2 Installation Site
Consider the following when selecting the installation site:
- The unit must be installed where strong enough to withstand the weight of the unit and fixed securely, otherwise the unit would topple or fall off.
- Do not install where there is a danger of combustible gas leakage.
- Do not install the unit near heat source, steam, or flammable gas.
- Select a location which is out of children's reach. Keep the unit away from children.
- Make sure the location has space for heat exchange and maintenance so that unit can operate reliably with good ventilation.
- Install the unit where it will not be tilted by more than 5°.
- During installation, if the outdoor unit has to be exposed to strong wind, it must be fixed securely.
- If possible, do not install the unit where it will be exposed to direct sunlight (If necessary, install a blind that does not interfere with the air flow).
- Install ODU in a place where it will be free from getting dirty or getting wet by rain as much as possible.
- Install ODU where it is convenient to connect IDU.
- ODU and IDU should stay as close as possible to shorten the length of refrigerant pipe and reduce bend angles.
- Install ODU where the condensate water can be drained out freely during heating operation. Do not place animals and plants in the path of the warm air.
- Take the air conditioner weight into account and select a place where noise and vibration are small.
If the ODU is totally surrounded by walls, refer to Fig.3.1 for space dimensions (Unit: mm/inch). The diagram shows required clearances around the unit for ventilation and maintenance.
3.3 Piping Work Requirements
Refer to the table below for piping work requirements for R410A Refrigerant System:
Outer diameter (mm/inch) | Wall thickness (mm/inch) |
---|---|
6.35(1/4) | 0.8(1/32) |
9.52(3/8) | 0.8(1/32) |
12.7(1/2) | 0.8(1/32) |
15.9(5/8) | 1.0(1/25) |
19.05(3/4) | 1.0(1/25) |
4 Installation Instruction
4.1 Dimension of Outdoor Unit and Mounting Hole
Unit outline and installation dimensions are provided in Fig.4.1. The table below shows these dimensions:
Model | A (mm/inch) | B (mm/inch) | C (mm/inch) | D (mm/inch) | E (mm/inch) |
---|---|---|---|---|---|
GMV-36WL/C-T(U) GMV-48WL/C-T(U) |
900 (35-3/8) | 340 (13-3/8) | 1345 (53) | 572 (22-1/2) | 378 (15) |
GMV-60WL/C-T(U) | 940 (37) | 320 (12-9/16) | 1430 (56-1/4) | 632 (24-7/8) | 350 (14-7/8) |
4.2 Connection Pipe
4.2.1 Schematic Diagram of Piping Connection
Fig.4.2 illustrates the schematic diagram of piping connections for the VRF system.
4.2.2 Allowable Length and Height Difference of Connection Pipe
Y-type branch joints are used to connect indoor and outdoor units. Fig.4.3 shows the connecting method and allowable lengths/height differences:
Piping parameters | Allowable value (m) | Allowable value (feet) | Fitting pipe |
---|---|---|---|
Total length (actual length) of fitting pipe | 300 | 984 | L1+L2+L3+a+b+c+d |
Length of farthest fitting pipe | 120 | 394 | L1+L2+L3+d |
Actual length | 150 | 492 | L2+L3+d |
Equivalent length of one Y-type branch is 0.5m(1-5/8feet). | -- | -- | -- |
From the 1st branch to the farthest indoor pipe | 40 | 131 | -- |
Height difference between ODU and IDU (ODU at upper side) | 50 | 164 | -- |
Height difference between ODU and IDU (ODU at lower side) | 40 | 131 | -- |
Height difference between IDUs | 15 | 49 | -- |
4.2.3 Dimension of Pipe (Main Pipe) from ODU to the 1st Indoor Branch
The dimension of the pipe from ODU to the 1st indoor branch is determined by the dimension of the outdoor connection pipe, as shown in Fig.4.4:
Basic module | Pipe dimension (Gas pipe) (mm/inch) | Pipe dimension (Liquid pipe) (mm/inch) |
---|---|---|
GMV-36WL/C-T(U) GMV-48WL/C-T(U) |
15.9 (5/8) | 9.52 (3/8) |
GMV-60WL/C-T(U) | 19.05 (3/4) | 9.52 (3/8) |
4.2.4 Selection of Indoor Branches
Select indoor branches according to the total capacity of downstream indoor units (Fig.4.5):
Total capacity of downstream indoor units C (Btu/h) | Model |
---|---|
C<68200 | FQ01A/A |
68200<C<102400 | FQ01B/A |
102400<C<238800 | FQ02/A |
238800<C<460600 | FQ03/A |
460600<C | FQ04/A |
4.2.5 Dimension of Pipe between Indoor Branches
Select pipe between indoor branches according to the capacity of downstream indoor units. If the capacity exceeds that of the outdoor unit, the capacity of the outdoor unit prevails (Fig.4.6):
Total capacity of downstream indoor units C (Btu/h) | Pipe (mm/inch) | Liquid pipe (mm/inch) |
---|---|---|
C19000 | 12.7 (1/2) | 6.35 (1/4) |
19000<C<48500 | 15.9 (5/8) | 9.52 (3/8) |
48500<C<76400 | 19.05 (3/4) | 9.52 (3/8) |
4.2.6 Dimension of Pipe between Indoor Branch and IDU
Dimension of pipe between indoor branch and IDU should be consistent with the dimension of indoor pipe (Fig.4.7):
Rated capacity of IDU C(Btu/h) | Gas pipe (mm/inch) | Liquid pipe (mm/inch) |
---|---|---|
C9600 | 9.52 (3/8) | 6.35 (1/4) |
9600<C<17000 | 12.7 (1/2) | 6.35 (1/4) |
17000<C<48000 | 15.9 (5/8) | 9.52 (3/8) |
48000<C<55000 | 19.05 (3/4) | 9.52 (3/8) |
55000<C<96000 | 22.2 (7/8) | 9.52 (3/8) |
If the distance between IDU and its nearest branch is over 10m (33 feet), then the liquid pipe of IDU (rated capacity 17000Btu/h) shall be enlarged.
4.3 Installation of Connection Pipe
Follow these principles during pipe connection: Connection pipe should be as short as possible, as should be the height difference between indoor and outdoor units. Keep the number of bends as little as possible. Radius of curvature should be as large as possible.
Weld the connection pipe between indoor and outdoor units. Strictly follow the requirements for welding process. Rosin joint or pin hole is not allowed.
When laying the pipe, be careful not to distort it. Radius of bending parts should be over 200mm (8 inches). Note that pipes cannot be repeatedly bent or stretched; otherwise the material will get harder. Do not bend or stretch the pipe for more than 3 times at the same position.
4.3.1 Flaring Process
Steps for flaring:
- Use a pipe cutter to cut the connection pipe if it is unshaped.
- Keep the pipe downward in case cutting scraps get into the pipe. Clear away the burrs after cutting.
- Remove the flared nut connecting the indoor connection pipe and outdoor unit. Then use a flaring tool to fix the flared nut into the pipe (as shown in Fig.4.8).
- Check if the flared part is flaring evenly and if there is any crack.
4.3.2 Pipe Bending
Guidelines for pipe bending:
- Reshape the pipe by hand. Be careful not to damage the pipe.
- Do not bend the pipe over 90°.
- If pipe is repeatedly bent or stretched, it will get hard and difficult to bend and stretch again. Therefore, do not bend or stretch the bend for over 3 times.
- In case that direct bending will open cracks to the pipe, first use a sharp cutter to cut the insulating layer, as shown in Fig.4.10. Do not bend the pipe until it is exposed. When bending is done, wrap the pipe with insulating layer and then secure it with adhesive tape.
4.3.3 Indoor Pipe Connection
Steps for indoor pipe connection:
- Remove pipe cover and pipe plug.
- Direct the flared part of the copper pipe to the center of the screwed joint. Twist on the flared nut tightly by hand, as in Fig.4.11 (Make sure the indoor pipe is correctly connected. Improper location of the center will prevent the flared nut from being securely twisted. Thread of the nut will get damaged if the flared nut is twisted forcibly).
- Use a torque wrench to twist on the flared nut tightly until the wrench gives out a click sound (Hold the handle of the wrench and make it at a right angle to the pipe, as in Fig.4.12).
Tightening torque for pipe diameters:
Pipe diameter | Tightening torque (N·m) |
---|---|
6.35mm | 15~30 |
9.52mm | 35~40 |
12.7mm | 45~50 |
15.9mm | 60~65 |
Additional notes for indoor pipe connection:
- Use sponge to wrap the un-insulated connection pipe and joint. Then tie the sponge tightly with plastic tape.
- Connection pipe should be supported by a bearer rather than the unit.
- The bending angle of piping should not be too small; otherwise the piping might have cracks. Please use a pipe bender to bend the pipe.
- When connecting IDU with connection pipe, do not pull the big and small joints of IDU with force in case the capillary tube or other tubes have cracks and cause leakage.
4.3.4 Outdoor Pipe Connection
Pipe connection for GMV-36WL/C-T(U), GMV-48WL/C-T(U): Twist the flared nut on the connection pipe of outdoor valves. Twisting method is the same as for indoor pipe connection. During engineering installation, the connection pipe inside the unit must be wrapped by insulation sleeve. According to customer requirement or space limit, outlet pipe can be installed from the front, right or rear side (Fig.4.13).
Pipe connection for GMV-60WL/C-T(U): As shown in Fig.4.14 and Fig.4.15, open the outermost soundproof cotton and place a fire barrier between the compressor and straight pipe. Use a soldering gun to unsolder straight pipe 1 and straight pipe 2. Install connection pipe 1 and connection pipe 2 to the corresponding position and then seal the apertures with welding rod. First weld the liquid side connection pipe and then weld the gas side connection pipe. During welding, it's necessary to use wet gauze to wrap up the two cut-off valves. Make sure the flame won't burn the soundproof cotton or other components.
4.3.5 Installation of Y-type Branch
Y-type branches are used for connecting multiple indoor units (Fig.4.16). Use a pipe cutter to cut in the middle of the pipe section that is of proper dimension and remove burrs (Fig.4.17).
Y-type branches must be installed vertically or horizontally. Branches shall be isolated by insulating material that can bear 120°C (248°F) or even higher temperature. The attached foam of the branch cannot be taken as insulating material.
4.3.6 Thermal Insulation for Pipeline
For multi VRF systems, every copper pipe should be labeled to avoid misconnection. At the branch inlet, leave at least 500mm (19-3/4 inches) of straight pipe section.
Thermal insulation for pipeline:
- To avoid condensate or water leakage on the connection pipe, the gas pipe and liquid pipe must be wrapped with thermal insulating material and adhesive tape for insulation from the air.
- Joints of indoor and outdoor units should be wrapped with insulating material and leave no gap between pipe and wall (See Fig.4.18).
- When wrapping the tape, the later circle should cover half of the former one. Do not wrap the tape too tight, otherwise the insulation effect will be weakened.
- After wrapping the pipe, apply sealing material to completely seal the hole on the wall.
Thermal insulating material shall be able to bear the pipe temperature. For heat pump units, the liquid pipe should bear 70°C (158°F) or above and the gas pipe should bear 120°C (248°F) or above. For cooling-only units, both liquid pipe and gas pipe should bear 70°C (158°F) or above. Thermal insulating material of branches should be the same as that of the pipeline. The attached foam of branches cannot be taken as insulating material.
4.3.7 Support and Protection of Pipeline
Supports should be made for hanging connection pipes. The distance between each support cannot be over 1m (3-1/4 feet). Protection against accidental damage should be made for outdoor pipelines. When a pipeline exceeds 1m (3-1/4 feet), a pinch board should be added for protection.
4.4 Disassembly of Compressor Feet
To prevent unit damage during transportation, 2 metal pieces are fitted to the outdoor unit's compressor feet before the unit leaves the factory (See Fig.4.19). When installing the unit, these metal pieces for transportation must be removed (except for GMV-60WL/C-T(U)). Then fasten the binding nuts again and wrap back soundproofing cotton. If the unit runs with metal pieces fitted on, the compressor will shake abnormally and the unit's operating life will be shortened.
4.5 Vacuum Pumping, Refrigerant Adding
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation! There is no extra refrigerant in the outdoor unit for air purging!
4.5.1 Vacuum Pumping
The outdoor unit has been charged with refrigerant before delivery. Field-installed connection pipes need to be charged with additional refrigerant.
- Confirm whether outdoor liquid and gas valves are closed.
- Use a vacuum pump to withdraw the air inside the indoor unit and connection pipe from the outdoor valve, as shown in Fig.4.20.
4.5.2 Refrigerant Adding
Refrigerant quantity of outdoor unit before delivery:
Model | Refrigerant Qty (kg/oz) |
---|---|
GMV-36WL/C-T(U) | 3.3 (116) |
GMV-48WL/C-T(U) | 3.3 (116) |
GMV-60WL/C-T(U) | 4.6 (162) |
The refrigerant amount charged before delivery does not include the amount that needs to be added to indoor units and the connection pipeline. The length of the connection pipe is decided on site. Therefore, the amount of additional refrigerant shall be decided on site according to the dimension and length of the field-installed liquid pipe. Record the amount of additional refrigerant for convenience of after-sales service.
Calculation of the amount of additional refrigerant:
Adding refrigerant method includes 2 steps:
- Amount of additional refrigerant depending on the pipe size (X).
- Amount of additional refrigerant depending on Quantity of IDU (Y).
Total charging amount = X + Y. Detail calculation is as follows:
- X = (Liquid pipe length × amount of additional refrigerant per 1m)
Diameter of liquid pipe (mm/inch) | kg/m | oz/inch |
---|---|---|
19.05 (3/4) | 0.25 | 0.224 |
15.9 (5/8) | 0.17 | 0.152 |
12.7 (1/2) | 0.11 | 0.099 |
9.52 (3/8) | 0.054 | 0.048 |
6.35 (1/4) | 0.022 | 0.020 |
- Y = (Quantity of IDU - 2) × 0.3 kg (10.58 oz)
First, confirm that there is no leakage from the system. When the compressor is not working, charge additional R410A with the specific amount to the unit through the filling opening of the liquid pipe valve of the outdoor unit. If the required amount cannot be quickly filled due to pressure increase of the pipe, then set the unit in cooling startup and fill refrigerant from the low pressure check valve of the outdoor unit.
Example:
IDUs:
- Duct type GMV-N18G/A3A-D(U)
- Duct type GMV-N12G/A3A-D(U)
- Duct type GMV-ND09PLS/A-T(U)
- Duct type GMV-ND09PLS/A-T(U)
Liquid pipe:
- 9.52mm (3/8inch): A=10m (32-3/4 feet), B=5m (16-3/8 feet), C=4m (13-1/8 feet), a=3m (9-3/4 feet)
- 6.35mm (1/4inch): D=5m (16-3/8 feet), b=3m (9-3/4 feet), c=2m (6-3/4 feet), d=1m (3-1/4 feet)
1) Amount of additional refrigerant depending on the pipe size (X):
Total length of each liquid pipe:
- 9.52: A+B+C+a = 10+5+4+3 = 22m (72-3/16 feet)
- 6.35: D+b+c+d = 5+3+2+1 = 11m (36-1/16 feet)
2) Amount of additional refrigerant depending on Quantity of IDU (Y):
Quantity of indoor units: 4 sets.
Therefore, the total charging amount = (22 × 0.054) + (11 × 0.022) + (4 - 2) × 0.3 = 1.188 + 0.242 + 0.6 = 2.03 kg (71-3/5 oz).
4.6 Electric Wiring
All electrical installation must be performed by qualified technicians in accordance with local laws, regulations, and this user manual.
- Use air conditioner specialized power supply and make sure that it is consistent with the system's rated voltage.
- Do not pull the power cord with force.
- Caliber of the power cord must be large enough. A damaged power cord or connection wire must be replaced by specialized electrical cords.
- Connect the unit to a specialized grounding device and make sure it is securely grounded. It's a must to install an air switch and current circuit breaker that can cut off the power of the entire system. The air switch should include magnetic trip function and thermal trip function so that the system can be protected from short circuit and overload.
- Air conditioners belong to class I electrical appliances, so they must be securely grounded.
- The yellow-green wire inside the unit is a ground wire. Do not cut it off or secure it with tapping screws, otherwise it will lead to electric shock.
- Power supply must include a secure grounding terminal. Do not connect the ground wire to: Water pipe; Gas pipe; Drain pipe; Other places that are deemed as not secure by professional technicians.
4.6.1 Electrical Wiring
Instructions for wiring:
- For solid core wiring (Fig.4.22): Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation about 25mm (15/16 inch). Using a screwdriver, remove the terminal screw(s) on the terminal board. Using pliers, bend the solid wire to form a loop suitable for the terminal screw. Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw using a screwdriver.
- For strand wiring (Fig.4.23): Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation about 10mm (3/8 inch). Using a screwdriver, remove the terminal screw(s) on the terminal board. Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end. Position the round terminal wire, and replace and tighten the terminal screw with a screwdriver (Fig.4.23).
- How to fix connection cord and power cord by cord clamp: After passing the connection cord and power cord through the insulation tube, fasten it with the cord clamp (Fig.4.24).
Important notes before starting work:
- Before starting work, check that power is not being supplied to the indoor unit and outdoor unit.
- Match the terminal block numbers and connection cord colors with those of the indoor unit side. Erroneous wiring may cause burning of the electric parts.
- Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.
- Always fasten the outside covering of the connection cord with cord clamps (If the insulator is not clamped, electric leakage may occur).
- Always connect the ground wire.
4.6.2 Wiring Diagram
Connection of power cord and communication wire: Separate power supply for IDU and ODU (Fig.4.25).
Selection of air switch and power cord:
Model | Power supply | Max Fuse Size/Fusible (A) | Max Ckt, Bkr Size/Disjoncteur Max. (A) | Min. Circuit Ampacity (A) |
---|---|---|---|---|
GMV-36WL/C-T(U) | 208/230V~ 60Hz | 35 | 35 | 28.5 |
GMV-48WL/C-T(U) | 208/230V~ 60Hz | 40 | 40 | 33 |
GMV-60WL/C-T(U) | 208/230V~ 60Hz | 40 | 40 | 34.5 |
Notes on selection:
- Selection of circuit breaker and power cord in the above table is based upon the unit's maximum power (maximum current).
- Specification of power cord is based on the working condition where ambient temperature is 40°C (104°F) and multi-core copper cable (working temperature is 90°C (194°F), e.g., power cable with YJV cross-linked copper, insulated PE and PVC sheath) is lying on the surface of a slot. If the working condition changes, please adjust the specification according to national standards.
- Specification of circuit breaker is based on the working condition where the ambient temperature of the circuit breaker is 40°C (104°F). If the working condition changes, please adjust the specification according to national standards.
4.6.3 Engineering Wiring of Power Supply and Communication Cable
Please refer to Fig.4.26 & Fig.4.27 for engineering wiring. If there is a hole for a cable tie in the wiring route, please fix the wire with a cable tie. Connect the power cord and communication cable to the corresponding terminal board and grounding screw according to the wiring diagram.
Please be noted that engineering wiring cannot touch the pipe and appliance. This figure is only applicable for engineering wiring reference of power supply and communication cable. If there are differences between the figure structure and the actual unit, please refer to the actual unit. For engineering wiring, please refer to the wiring diagram provided with the unit.
5 Check Items after Installation and Test Operation
5.1 Check Items after Installation
Check items | Possible conditions due to improper installation | Remark |
---|---|---|
Each part of the unit is installed securely? | Unit may drop, shake or emit noise. | |
Gas leakage test is taken or not? | Insufficient cooling (heating) capacity. | |
Unit gets proper thermal insulation or not? | There may be condensation and dripping. | |
Drainage is smooth or not? | There may be condensation and dripping. | |
Is the voltage in accordance with the rated voltage specified on the nameplate? | Unit may have malfunction or components may get damaged. | |
Is the electric wiring and pipe connection installed correctly? | Unit may have malfunction or components may get damaged. | |
Unit is securely grounded or not? | Electrical leakage. | |
Power cord meets the required specification? | Unit may have malfunction or components may get damaged. | |
Is the air inlet/outlet blocked? | Insufficient cooling (heating) capacity. | |
Length of refrigerant pipe and the charging amount of refrigerant are recorded or not? | The refrigerant charging amount is not accurate. | |
Binding pieces on compressor feet are removed or not? | Compressor may get damaged. |
5.2 Test Operation and Debugging
(1) Test operation and debugging must be performed after finishing the first installation or replacing the main board of the outdoor unit. Otherwise, the unit won't be able to work.
(2) Test operation and debugging must be performed by professional technicians or under the guidance of professional technicians.
5.2.1 Prepare the Test Operation and Debugging
- Do not connect power until all installation work is finished.
- All control circuits and wires are correctly and securely connected.
- Check whether the fixing loops for compressor foots are removed.
- All small pieces, especially metal chips, thread ends, and forceps holders, must be removed from the unit.
- Check whether the unit's appearance and pipeline system has been damaged during transportation.
- Calculate the quantity of refrigerant that needs to be added according to the pipe length. Pre-charge the refrigerant. In case that the required charging quantity is not reached while refrigerant can't be added, record the quantity of refrigerant that still needs to add and complement the quantity during test operation. For details of adding refrigerant during test operation, see below.
- After refrigerant is added, make sure valves of the outdoor unit are completely open.
- For convenience of troubleshooting during debugging, the unit shall be connected to a PC with applicable debugging software. Make sure the unit's real-time data can be checked through this computer. The installation and connection of debugging software can be found in the Service Manual.
- Before test operation, make sure the unit is powered on and the compressor has been preheated for more than 8 hours. Touch the unit to check whether it's normally preheated. If yes, start test operation. Otherwise, the compressor might be damaged.
5.2.2 Test Operation and Debugging
Description of test operation procedures and main board display of ODU:
Progress | Description of each stage of debugging progress | Debugging code | LED | Code meaning and operation method |
---|---|---|---|---|
01_Set master unit | System is not debugged. | A0 | ON | Hold main board's SW3 button for 5s to start debugging. |
2s later, next step starts. | 01 | ON | ||
02_ Allocate addresses | System is allocating addresses. | 02/Ad | Display circularly | 10s later, display as below: |
No master indoor unit. Display will be on for 1min, during which master IDU can be set manually. If not, system will set the unit with minimum IP address as the master IDU. | 02/L7 | Display circularly | ||
Allocation is finished. | 02/oC | Display circularly | 2s later, next step starts. | |
03_ Confirm the quantity of ODU | System is confirming. | 03/01 | Display circularly | 1s later, next step starts. |
04_ Confirm the quantity of IDU | "00~16" displays the quantity of indoor unit. Confirm the number manually. If the number is not consistent with the display one, cut off power of IDU and ODU and check whether the communication wire of IDU is correctly connected. After the check, connect power and start debugging from progress 01. If the number is then correct, press main board's SW3 button to confirm. | 04/00~16 | Display circularly | |
System has confirmed the quantity. | 04/oC | Display circularly | 2s later, next step starts. | |
05_ Detect ODU's internal communication and capacity ratio | Communication between master ODU and driver has error. Check the communication connection of ODU's main board and drive board. When the error is eliminated, start next step. If power is off during troubleshooting, then restart debugging from progress 01 after power is on. | 05/C2 | Display circularly | |
Communication of master ODU and driver is normal. Unit will display as in the left for 2s and detect the capacity ratio of IDU and ODU. If the ratio is within range, then next step will start 2s later. If the ratio is out of range, unit will display as below. | 05/oC | Display circularly | ||
Rated capacity ratio of IDU is too high. Change the combination way of IDU and ODU to make the ratio within range. And restart debugging from progress 01. | 05/CH | Display circularly | ||
Rated capacity ratio of IDU is too low. Change the combination way of IDU and ODU to make the ratio within range. And restart debugging from progress 01. | 05/CL | Display circularly | ||
06_ Detect outdoor components | Outdoor component's error. Besides "06", the other blinking will display the related error code. After errors are eliminated, system will start next step automatically. If power is off during troubleshooting, then restart debugging from progress 01 after power is on. | 06/error code | Display circularly | |
System detects no error on outdoor components. | 06/oC | Display circularly | 10s later, next step starts. | |
07_ Detect indoor components | System detects error on indoor components. XX means the project code of IDU with error, e.g., no.1 IDU has d5 and d6 errors, meanwhile no.3 IDU displays error d6 and d7, then the nixie tube will display "07", "01", "d5", "d6" and "03" circularly. After errors are eliminated, system will start next step automatically. If power is off during troubleshooting, then restart debugging from progress 01 after power is on. If errors occur in IDU which the project code is a 3-digit number, then it will display the 2 big digits of project code first, then the 2 small digits, finally the error code, e.g: L1 error occurs in no.101 IDU, then the nixie tube will display "01", "01" and "L1" circularly. Display method is the same for several IDUs with multiple errors. | 07/XX/error code 07/XXXX/error code |
Display circularly | |
No error on components of IDU. | 07/oC | Display circularly | 5s later, next step starts. | |
08_ Confirm preheated compressor | Preheat time for compressor is less than 8 hours. Display will be as in the left until the preheat time reaches 8 hours. Press main board's SW3 button to confirm manually that the preheat time has reached 8 hours. Then start next step. (NOTE: Compressor may get damaged if it is started without 8 hours of preheat time) | 08/U0 | Display circularly | |
Compressor has been preheated for 8 hours. | 08/oC | Display circularly | 2s later, next step starts. | |
09_ Refrigerant judgments before startup | System is lack of refrigerant and display will be as in the left. Please cut off power of IDU and ODU and check if there is leakage on the pipeline. Solve the leakage problem and complement refrigerant into the unit. Then connect power and restart debugging from progress 01. (Note: Before re-charging refrigerant, unit must be powered off in case system starts progress 10 automatically). | 09/U4 | Display circularly | |
Refrigerant is normal and unit will display as in the left for 2s. Then next step starts. | 09/oC | Display circularly | ||
10_ Status judgments of outdoor valves before startup | Valves of ODU are being inspected. Compressor will start operation for 2min or so and then stop. The opening and closing status of outdoor valves are as below. | 10/on | Display circularly | |
Outdoor valves are not fully turned on. Press main board's SW4 button and display shows "09/OC". Then check if the gas and liquid valves of ODU are completely open. After confirmation, press the SW4 button again. Then compressor will start running for about 2min to inspect the status of valves. | 10/U6 | Display circularly | ||
Valves status is normal. Unit will display as in the left for 2s and then start next step. | 10/oC | Display circularly | ||
12_ Confirm debugging startup | Ready for units to start debugging. Press main board's SW3 button to confirm startup of debugging. 2s later, main board will display as below. | 12/AP | Display circularly | |
Startup is confirmed. After displaying for 2s, system will choose "15_Cooling debugging" or "16_Heating debugging" according to ambient temperature. If the project requests to add refrigerant but it is not complemented before debugging, then refrigerant can be added in this process through the L-VALVE. | 12/AE | Display circularly | ||
15_ Cooling debugging | Debugging for cooling mode. If no malfunction occurs for 50min when compressor is running, then the system is certified as normal. After shutting down the unit for 5s, the system will enter normal standby status. | 15/AC | Display circularly | |
Malfunction occurs when debugging for cooling mode. | 15/error code | Display circularly | ||
16_ Heating debugging (For heat pump units only) | Debugging for heating mode. If no malfunction occurs for 50min when compressor is running, then the system is certified as normal. After shutting down the unit for 5s, the system will enter normal standby status. | 16/AH | Display circularly | |
Malfunction occurs when debugging for heating mode. | 16/error code | Display circularly | ||
17_ Debugging finished | The entire unit has finished debugging and is under standby condition. | oF | ON |
5.2.3 Appendix: Reference of Normal Operation Parameters
Reference parameters for normal operation:
No. | Debug item | Parameter name | Unit | Reference |
---|---|---|---|---|
1 | Outdoor temperature | -- | °C (°F) | -- |
2 | Compressor discharge temp | -- | °C (°F) | When compressor starts, discharge temp in cool mode is within 70~105°C (158~221°F) and at least 10°C (50°F) higher than the high pressure saturation temp. As for temp in heat mode, it is within 65~90°C (149~194°F) and at least 10°C (50°F) higher than the high pressure saturation temp. |
3 | Defrosting temp | -- | °C (°F) | In cool mode, defrosting temp is 4~10°C (39~50°F) lower than system's high pressure value. In heat mode, defrosting temp is about 2°C (36°F) different from system's low pressure value. |
4 | System high pressure | -- | °C (°F) | In cool mode, the normal high pressure value is within 20~55°C (68~131°F). According to the change of ambient temp and system's operating capacity, the high pressure value will be 10~30°C (50~86°F) higher than ambient temp. The higher ambient temp is, the smaller temp difference is. If ambient temp is 25~35°C (77~95°F) in cool mode, system's high pressure value will be within 44~53°C (111~127°F). In heat mode, if ambient temp is above -5°C (23°F), system's high pressure value is within 40~52°C (104~126°F). If ambient temp is low and many IDUs are turned on, the high pressure will be lower. |
5 | System low pressure | -- | °C (°F) | When ambient temp in cool mode is 25~35°C (77~95°F), the low pressure value is 0~8°C (32~46°F). When ambient temp in heat mode is above -5°C (23°F), the low pressure value is -15~8°C (5~46°F). |
6 | Opening degree of thermal EXV | PLS | PLS | In cool mode, the thermal electronic expansion valve remains 480PLS. In heat mode, the adjustable opening degree of EXV is 60~480PLS. |
7 | Compressor's operating freq | Hz | Changes in 10Hz~80Hz (GMV-36WL/C-T(U), GMV-48WL/C-T(U)) Changes in 16Hz~80Hz (GMV-60WL/C-T(U)) | |
8 | Compressor's operating current | A | When compressor works normally, the current is no more than 22.6A. | |
9 | Compressor's IPM temp | °C (°F) | When ambient temp is below 35°C (95°F), IPM temp is lower than 80°C (176°F) and the highest temp won't be above 95°C (203°F). | |
10 | Fan motor's operating freq | Hz | Changes in 0~49Hz (GMV-36WL/C-T(U), GMV-48WL/C-T(U)) according to system's pressure. Changes in 0~40Hz (GMV-60WL/C-T(U)) according to system's pressure. | |
11 | IDU ambient temp | -- | °C (°F) | According to ambient temp. |
12 | Indoor heat exchanger's inlet temp | -- | °C (°F) | For a same IDU in cool mode, the inlet temp will be 1~7°C (34~45°F) lower than the outlet temp, and 4~9°C (39~48°F) higher than the low pressure value. For a same IDU in heat mode, the inlet temp will be 10~20°C (50~68°F) lower than the outlet temp. |
13 | Opening degree of indoor EXV | PLS | In cool mode, the opening degree of indoor EXV varies within 70~480PLS. In heat mode, the opening degree of indoor EXV varies within 70~480PLS (GMV-36WL/C-T(U), GMV-48WL/C-T(U)). In cool mode, the opening angle of indoor EXV varies within 70~480PLS. In heat mode, the opening angle of indoor EXV varies within 40~480PLS (GMV-60WL/C-T(U)). | |
14 | Communication parameters | Communication data | -- | Number of IDUs detected by software is the same with the actual number. No communication error. |
15 | Drainage system | -- | -- | Indoor unit can drain water out completely and smoothly. Condensate pipe has no backward slope of water; Water of outdoor unit can be drained completely through the drainage pipe. No water drop from unit base. |
16 | Others | -- | -- | Compressor and indoor/outdoor fan motors do not have strange noise. Unit can operate normally. |
6 Common Malfunctions and Troubleshooting
If an abnormal situation (such as peculiar smell) occurs, please stop the operation immediately and turn off the main power supply, and then contact a Gree authorized maintenance center. If the unit continues to operate under abnormal situation, the air conditioner will be damaged and an electric shock or fire accident may result. Do not maintain the air conditioner by yourself; misoperation may cause electric shock or fire hazard. Please contact professional personnel of a Gree authorized maintenance center to maintain.
Before asking for maintenance, please check the following issues first:
Phenomenon | Causes | Troubleshooting |
---|---|---|
Air conditioner can't operate | Fuse is broken or circuit breaker is open Power failure Power supply is not connected The power for batteries of remote controller is insufficient Remote controller is not within the remote control range |
Replace fuse or close the circuit breaker Restart up the unit and then the unit will operate Connect the power supply Replace the batteries Remote control range is within 8m |
Air conditioner operates, while it stops operation immediately | Air inlet or air outlet of indoor unit/outdoor unit is blocked | Eliminate the obstacles |
Cooling or heating is abnormal | Air inlet or air outlet of indoor unit/outdoor unit is blocked Temperature setting is improper Fan speed is set too low Fan direction is not correct Door or window is open Direct sunshine Too many persons in the room Too many thermal sources in the room The filter is dirty and blocked |
Eliminate the obstacles Adjust temperature setting by remote controller or wired controller Adjust fan speed setting by remote controller or wired controller Adjust fan direction setting by remote controller or wired controller Close door and window Hang curtains or window shade at the window Reduce the thermal source Clean the filter |
If the problem cannot be solved after checking the above items, please contact the Gree service center and describe the cases and models.
Following circumstances are not malfunctions:
Phenomenon | Causes |
---|---|
When unit is started immediately after it is just turned off | Overload protection switch makes it run after 3 minutes delay |
When power is turned on | Standby operating for about 1 minute |
Mist comes from the unit | Under cooling: Indoor high humidity air is cooled rapidly |
Noise is emitted | When the power supply is connected, there is a small "dada" sound. This is the sound of startup action of electronic expansion valve. When the system is conducting cooling or defrosting, there is a continuous "sa----" sound. This is the sound of refrigerant flowing inside the unit. When the system is switching cooling and heating modes; during heating operation, the unit enters or quits defrosting operation or oil return operation, there is "chi----" sound. This is the sound for direction reversal of 4-way valve. When the system is started or stopped for a short time, you can hear the sound of "sa----"; you can also hear this sound for a short time after the start or stop of the defrosting operation. This is the sound produced when the refrigerant stops or changes the flow. When the system is in cooling operation or after it stops running, a continuous "sa ----" sound can be heard. This is the operation sound of the drain system. When the system is running or after it stops running, a "creaking" sound can be heard. This is the sound produced when plastic parts such as panel expand and contract due to temperature changes. When the system is in heating operation, after the indoor unit stops running, the sound like running water can be heard. The unit is melting the frost on the outdoor unit, please wait about 10 minutes (due to different unit models, the waiting time will vary). When the indoor unit stops running, a faint "sa----" sound or "gurgling" sound can be heard. This sound can be heard when other indoor units are running. This is to prevent oil and refrigerant from staying in the indoor unit, and to keep a small amount of refrigerant flowing. When the unit is running, the operating sound of the compressor changes. This is caused by changes in compressor operating frequency. During the operation of the unit or after the operation is started or stopped, a continuous "sa ----" sound can be heard. This is the sound produced when the refrigerant bypass valve operates. When the operating mode of the unit changes, the indoor unit and outdoor unit will produce "sa ----" and "gurgling" sounds. This is the sound produced when the refrigerant stops or changes flow. |
The sound from the outdoor unit can be heard indoors | This is because the outdoor unit is installed close to the window or wall, and the sound insulation is poor, and the external noise is transmitted in. |
There is dust blowing out from the unit | Dust in indoor unit is blown out. |
The unit emits odor | The odor of the air conditioner is sucked into the room and then blown out. |
Operating: The indoor unit is still running after shutting down | The fan of indoor unit will continue to work for 20 to 70 seconds to fully use the residual cooling or heat of the heat exchanger, and to prepare for the next use. |
Mode conflict | When the selected operation mode of the indoor unit conflicts with the operation mode of the outdoor unit, after five seconds, the indoor unit error indicator flashes or the remote controller displays the operation conflict, and the indoor unit shuts down. At this time, the indoor unit can be converted to run with the outdoor unit. The mode can be restored to normal without conflict. The cooling mode and dry mode do not conflict, and the air supply does not conflict with any mode. |
Cooling or heating mode cannot start up |
7 Error Indication
Inquiry method of error indication: combine division symbol and content symbol to check the corresponding error.
Indoor Errors
Note: The following is a summary of common indoor error codes. For a complete list, please refer to the original manual.
Error Code | Content |
---|---|
L0 | Malfunction of IDU (uniform) |
L1 | Protection of indoor fan |
L2 | Auxiliary heating protection |
L3 | Water-full protection |
L4 | Abnormal power supply for wired controller |
L5 | Freeze prevention protection |
L6 | Mode shock |
L7 | No main IDU |
L8 | Power supply is insufficient |
L9 | For single control over multiple units, number of IDU is inconsistent |
LA | For single control over multiple units, IDU series is inconsistent |
LH | Alarm due to bad air quality |
LC | IDU is not matching with outdoor unit |
LL | Malfunction of water flow switch |
LE | Rotation speed of EC DC water pump is abnormal |
LF | Malfunction of shunt valve setting |
LJ | Setting of functional DIP switch code is wrong |
LP | Zero-crossing malfunction of PG motor |
LU | Indoor unit's branch is not inconsistent for one-to-more unit of heat recovery system |
Lb | Inconsistent IDU of group-controlled reheat and dehumidification system |
y1 | Malfunction of inlet tube temperature sensor 2 |
y2 | Malfunction of outlet tube temperature sensor 2 |
y7 | Malfunction of fresh air intake temperature sensor |
yA | IFD malfunction |
d1 | Indoor PCB is poor |
d2 | Malfunction of lower water temperature sensor of water tank |
d3 | Malfunction of ambient temperature sensor |
d4 | Malfunction of entry-tube temperature sensor |
d5 | Malfunction of middle temperature sensor |
d6 | Malfunction of exit-tube temperature sensor |
d7 | Malfunction of humidity sensor |
d8 | Malfunction of water temperature sensor |
d9 | Malfunction of jumper cap |
dA | Web address of IDU is abnormal |
dH | PCB of wired controller is abnormal |
dC | Abnormal setting for capacity button |
dL | Malfunction of air outlet temperature sensor |
dE | Malfunction of indoor CO2 sensor |
dF | Malfunction of upper water temperature sensor of water tank |
dJ | Malfunction of backwater temperature sensor |
dP | Malfunction of inlet tube temperature sensor of generator |
dU | Malfunction of drainage pipe temperature sensor of generator |
db | Debugging status |
dd | Malfunction of solar power temperature sensor |
dn | Malfunction of swing parts |
dy | Malfunction of water temperature sensor |
y8 | Main error of indoor air box sensor |
Outdoor Errors
Note: The following is a summary of common outdoor error codes. For a complete list, please refer to the original manual.
Error Code | Content |
---|---|
F0 | Main board of ODU is poor |
F1 | Malfunction of high-pressure sensor |
F3 | Malfunction of low-pressure sensor |
F5 | Malfunction of discharge temperature sensor of compressor 1 |
F6 | Malfunction of exit-tube temperature sensor |
F7 | Malfunction of humidity sensor |
F8 | Malfunction of water temperature sensor |
F9 | Malfunction of jumper cap |
E0 | Malfunction of ODU (uniform) |
E1 | High-pressure protection |
E2 | Discharge low-temperature protection |
E3 | Low-pressure protection |
E4 | High discharge temperature protection of compressor |
Ed | Drive module low temperature protection |
J0 | Protection for other modules |
J1 | Over-current protection of compressor 1 |
Debugging Errors
Note: The following is a summary of common debugging error codes. For a complete list, please refer to the original manual.
Error Code | Content |
---|---|
U0 | Preheat time of compressor is insufficient |
U2 | Wrong setting of ODU's capacity code/jumper cap |
U3 | Power supply phase sequence protection |
U4 | Refrigerant-lacking protection |
U5 | Wrong address for driving board of compressor |
U6 | Alarm because valve is abnormal |
U7 | Power grid DRED0 response protection |
U8 | Short-circuit malfunction of IDU |
U9 | Malfunction of pipe-line for ODU |
UA | DC bus overvoltage protection at power grid side |
UH | DC bus undervoltage protection at power grid side |
UC | Setting of main IDU is successful |
UL | Emergency operation DIP switch code of compressor is wrong |
UE | Charging of refrigerant is invalid |
UF | Identification malfunction of IDU of mode exchanger |
UJ | FO protection for PV module |
Ud | Grid-connected driver board error |
Un | Communication malfunction between main control and inverter |
Uy | Over-temperature protection for PV module |
8 Maintenance and Care
Regular check, maintenance, and care can extend the unit's service life. Please have a specialized person in charge of the management of air conditioners.
8.1 Outdoor Heat Exchanger
The outdoor heat exchanger shall be cleaned regularly, at least once every two months. You can use a dust catcher with a nylon brush to clean away the dust on the heat exchanger. If a compressed air source is available, it can also be used to clean the heat exchanger. Do not clean it with water.
8.2 Drain Pipe
Please check regularly whether the drain pipe is blocked or not. Make sure condensate can be drained out smoothly.
8.3 Notice before Seasonal Use
- Check whether air inlets and air outlets of indoor and outdoor units are blocked.
- Check whether ground connection is reliable or not.
- Check whether batteries in the remote controller are replaced or not.
- Check whether the air filter is properly installed.
- If the unit starts up after not operating for a long time, it should be powered on 8 hours before operation starts to preheat the outdoor compressor.
- Check whether the outdoor unit is securely installed. If there is any problem, please contact a Gree authorized service center.
8.4 Maintenance after Seasonal Use
- Disconnect power of the entire system.
- Clean the air filter and outer case of indoor and outdoor units.
- Clean away the dust and obstacles on indoor and outdoor units.
- If the outdoor unit has rust, please apply some paint to it so as to prevent the rust from growing.
8.5 Parts Replacement
Parts and components can be obtained from a nearby Gree office or Gree distributor.
When conducting air tightness test and leakage test, do not mix oxygen, C2H2, or other dangerous gas into the refrigerant circuit. Otherwise, it may lead to danger. Use nitrogen or refrigerant to conduct the tests.
9 After-sales Service
If there is a quality defect or other problems with the product, please contact the Gree local after-sales service department for help.
Warranty must be based on the following conditions:
- Product's initial startup must be performed by professional technicians from Gree service center or persons assigned by Gree.
- Only Gree spare parts are used.
- All instructions of unit operation and maintenance in this manual must be strictly followed according to the set period and set frequency.
- Any breach of the above conditions will disable the warranty.