Instruction Manual for BIOGENESIS models including: 3-6-12 Kg Gas HFC Automatic Device Mare, 3-6-12 Kg, Gas HFC Automatic Device Mare, Automatic Device Mare, Device Mare, Mare

AUTOMATIC DEVICE “MARE SERIES” 3-6-12 Kg Gas HFC

In new installations, the devices for to be operative need at least of this . components: 2164; 2165; 2163

PDF preview unavailable. Download the PDF instead.

BGHFCAUTKG6SIS76
Biogenesis S.r.l. www.bio-genesis.it

AUTOMATIC DEVICE "MARE SERIES" 3-6-12 Kg Gas HFC

In new installations, the devices for to be operative need at least of this
components: 2164; 2165; 2163

· CYLINDER
Alloy steel, epoxypolyestere powder painting, Red Ral 3000.

See example of installation at next page Note: items supplied only on request
Manual actuator

Aluminum

Fitting F 3/8" for

distribution tube distribution tube

· EXTINGUISHING AGENT Gas HFC 227 ea.
· PROPELLANT Nitrogen (N2).
· VALVE Automatic M. 30x1.5, set 93 °C. (with bulb in standard equipment) Supplied with pressure switch set at 11 bar.

· USE
A B fire rating (solid materials, flammable liquids).

Pyrotechnic cartridge for electric Nozzle M 3/8"
activation

· ACTIVATION
- Automatic when bulb temperature is reached. On request (see optional):

- with manual actuator with handle;

- with pyrotechnic cartridge for

electric activation.

Supplied with
Pressure switch

Note for pressure switch: The pressurized device is "normally open". The pressure switch alone, not installed on the device, is "normally closed".

Note: image is for illustrative purpose only, the product purchased can has some differences

· BRACKET Wall-mounted in standard equipment.

Gas HFC Automatic Device, Mare Series, available charge 3, 6, 12 Kg , temperature range from -30°C to +60°C,

certified according to the directive for pressure equipment PED 2014/68/EU. RINA certified, ISO 9094:2015.

Quality Product Suitable for use

certification guaranteed by Bureau on fire involving electrical voltages

uVpertiota1s.0It0a0liaV.,

at

a

distance

of

1

mt.

AVAILABLE VERSIONS

GAS HFC QUANTITY

DIMENSIONS (without bracket) H x L max x Ø cylinder (mm)

C % M3/Kg (concentration
gas in volume)

DISTRIBUTION TUBE LENGTH

Kg 3 440 +/- 5 x 140 +/- 3 x 130 +/- 1 0,1373 7,611 recommended 5 m

Kg 6 490 +/- 5 x 160 +/- 3 x 160 +/- 3 0,1373 7,611 recommended 5 m

Kg 12 590 +/- 5 x 190 +/- 3 x 190 +/- 3 0,1373
APPROVED/CERTIFIED DEVICE:

7,611 recommended 8 m
FIRE RATING :

NUMBER OF NOZZLE
Based on choice of dispensing points of installation
A

DISCHARGE TIME
20 sec. 35 sec.
60 sec.
B

COVERAGE AREA 5 c.m.
10 c.m.
20 c.m.

REPRODUCTION IS PROHIBITED

AUTOMATIC DEVICE "MARE SERIES" 3-6-12 Kg Gas HFC

TECHNICAL SPECIFICATIONS

FIRE RATING EXTINGUISHING AGENT PROPELLANT TEMPERATURE RANGE CYLINDER PRESSURE TEST VALVE TIGHTENING TORQUE CYLINDER MATERIAL EXTERNAL/INTERNAL TREATMENT

A B
Gas HFC 227 ea Nitrogen (N2), 15 Bar at 20 °C
-30°C / +60°C PT 27 bar
Between 40 and 50 Nm Alloy steel
Sandblast and epoxypolyestere powder painting, Red Ral 3000 colour

PACKAGING

STANDARD : single packaging

Note: the packaging quantities and measurements are indicative and can be subject at changes

3 Kg

6 Kg

12 Kg

MAINTENANCE AND INSTALLATION
Install the system in vertical position using the supplied bracket. Place the gas distribution pipe and fix the nozzles. Remove the safety pin to make operating system. Recommended maintenance : every 6 months check pressure; every 72 months replace extinguishing agent; test after 144 months of production date.

EXAMPLE OF AUTOMATIC DEVICE INSTALLATION

4

1

10

L max

9

10

2

9

3

5
8 7

10 8 11

SPARE PARTS

N.

DESCRIPTION

1

Valve M. 30x1.5 with thermosensible bulb for activation at 93°C

2

Valve o-ring

3

Pressure gauge

4 - OPTIONAL Manual actuator in control box(cable 5 m)

Cylinder 3 Kg

5

Cylinder 6 Kg

Cylinder 12 Kg

Iron bracket 3 Kg

6

Iron bracket 6 Kg

Iron bracket 12 Kg

H
7

PVC dip tube 3 Kg PVC dip tube 6 Kg PVC dip tube 12 Kg

8 - OPTIONAL

Brass dispensing nozzle M 3/8"

9 - OPTIONAL Aluminum distribution tube Ø 10, PVC coated

10 - OPTIONAL Fitting F 3/8" for distribution tube

OPTIONAL 11

Pyrotechnic cartridge
Label
Pressure switch 1/8" for valve, set at 11 bar

REPRODUCTION IS PROHIBITED

