Instructions for nLiGHT models including: NPP16 ER EFP, Relay Pack, NPP16 ER EFP Relay Pack

View

nPP16 ER - Emergency Relay Pack

Download


File Info : application/pdf, 3 Pages, 432.20KB

PDF preview unavailable. Download the PDF instead.

is-npp16er-efp-004
nPP16 ER EFP

UL-924 EMER. RELAY PACK
FAMILY INSTRUCTIONS

SPECIFICATIONS (NPP16 ER EFP)
Electrical Specifications

Input Ratings 120/277VAC, 50/60 Hz 220-240VAC, 50/60Hz (with 230 option) 120/347VAC, 50/60 Hz (with 347 option) 120-277VAC, 50/60 Hz Normal Power Sense 220-240VAC, 50/60Hz Normal Power Sense (with 230 option) 120-347VAC, 50/60 Hz Normal Power Sense (with 347 option)

Output Ratings 120/277VAC, 50/60 Hz 220-240VAC, 50/60Hz (with 230 option) 120/347VAC, 50/60 Hz (with 347 option) 16A - Tungsten, Standard Ballast, Electronic Ballast, General Purpose 120VAC, 50/60 Hz, 1HP - Motor SCCR: 5KA 100mA, 0-10VDC Dimming Sink Current

Relay Type Latching

Low Voltage Output Ratings Self-powering, does not supply nLight bus voltage

Class Rating 0-10V Dimming can be wired Class 1 or 2

Standards/ Ratings Energy Management Equipment, UL916 (E167435) Emergency Lighting and Power Equipment, UL924 (E342232)

Mechanical

Dimensions 3.38" H x 2.53" W x 1.83" D (86mm x 64mm x 47mm) - does not include ½" chase nipple

Mounting 1/2" Knockout (7/8" hole)

Color Red

Connection Type RJ-45 nLight Network Ports (2) Non-Dimming Model: Line Voltage Leads Dimming Model: Line and Low Voltage Leads

Environmental

Warrantied Operating Temperature Standard: 14º to 122º F (-10º to 50º C) LT Option: -4º to 122º F (-20º to 50º C)

Relative Humidity Up to 90%, Non-Condensing

Standards/ Ratings RoHS, Plenum UL2043

C

US LISTED

WARRANTY
5-year limited warranty. Complete warranty terms located at www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx

READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 02/23/2022

1 of 3

IS-NPP16ER-EFP-003

nPP16 ER EFP

UL-924 EMER. RELAY PACK

FAMILY INSTRUCTIONS

INSTALLATION INSTRUCTIONS

· Disconnect or turn off power before installing or servicing the nPP16 ER EFP. · The nPP16 ER EFP includes a factory-installed fuse holder attached to the red wire. For ease of in-
stallation, pass the lead with the fuse holder through the KO and lock nut first, then pass the other leads through the KO and lock nut. Care should be taken not to nick the wires while threading them through the knockout. · Mount through a ½" knockout in a 4" square or larger steel junction box (deep box recommended) or luminaire. Secure with supplied lock nut. · Following the applicable wiring diagram below, connect wires to line voltage feed, neutral, and load. Relay and power supply must be connected to the same input circuit. · Fuse holder must be installed with slack in wire leads at all times. Failure to leave slack in wire leads may cause fuse holder to overheat. · If applicable, connect low voltage violet and gray dimming wires to 0-10 VDC ballast/driver and green wire to an approved ground connection. Note wires have 600V rated insulation. · Interconnect unit (via RJ-45 ports) with other nLight devices in lighting zone using CAT-5e cables. · Test all wiring for shorts prior to powering up the unit from the circuit breaker, and ensure that there are no loose or exposed wires that could short to other wires or components. Once wiring is confirmed, power up the unit from the circuit breaker. · Once low voltage power is received via the CAT-5e connection, all devices in the zone will automatically begin functioning together according to each device's defaults.

BUTTON
RJ-45 PORTS LED

T568B pin/pair assignment is recommended for all CAT-5e cables. Unit powers itself but does not provide any bus power to other connected nLight devices. For Supply Connections, use 14 AWG or larger wires rated for at least 90º C.

NOTE

Normal Diagram for non-dimming units

· Connect to either YEL, or RED|YEL, feed ONLY (sense only)

Emergency

and Cap off unused wire.

DO NOT REMOVE, BYPASS, OR TAMPER WITH FACTORY-INSTALLED

OPTIONAL TEST SWITCH
CAT-5e

nPP16 ER EFP

YEL RED|YEL RED WHT|RED

LEGEND

BASE

230

347

(120/277VAC) (220-240VAC) (120/347VAC)

WHT|RED YEL
RED|YEL
RED BLU BLK WHT

Emer. Neutral

120VAC Emer. Hot

N/A

120VAC Emer. Hot

277VAC Emer. Hot

220-240VAC Emer. Hot

347VAC Emer. Hot

120/277VAC Emer. Hot

220-240VAC Emer. Hot

347VAC Emer. Hot

Emer. Load (Switched Out)

120-277VAC Norm. Hot

120-347VAC Norm. Hot

Norm. Neutral

FUSE HOLDER ATTACHED TO RED

WIRE.

Diagram for units with a dimming option (-D or -DS suffix)

Normal (sense only)

Emergency

LEGEND

BASE

230

347

(120/277VAC) (220-240VAC) (120/347VAC)

For further troubleshooting guidance, please contact the Controls Technical Support Team
1(800)-535-2465
TROUBLESHOOTING (NPP16 ER EFP)

OPTIONAL TEST SWITCH
CAT-5e

nPP16 ER EFP

YEL RED|YEL RED WHT|RED

GRN

VIO PNK

GRY PNK*
*0-10V Dimming Common from luminaire may be pink or as otherwise indicated per section 410.69 of the 2020 NEC

WHT|RED YEL
RED|YEL
RED BLU BLK WHT VIO PNK* GRN

Emer. Neutral

120VAC Emer. Hot

N/A

120VAC Emer. Hot

277VAC Emer. Hot

220-240VAC Emer. Hot

347VAC Emer. Hot

120/277VAC Emer. Hot

220-240VAC Emer. Hot

347VAC Emer. Hot

Emer. Load (Switched Out)

120-277VAC Norm. Hot

120-347VAC Norm. Hot

Norm. Neutral

0-10V Dim (+)

0-10V Com (­)

Earth Ground

Additional nLight devices do not show power from nPP16 ER EFP device

· Confirm there is a device that provides bus power in the daisy-chain. Note that "ER" devices to not supply bus power.
· Confirm line voltage power is present to the nPP16 ER EFP unit · Confirm line voltage power is connected to the correct line voltage input wire, as identified in the wiring diagram · Confirm all line voltage wiring connections · Confirm RJ45 pinout connections

RJ45 LEDs are showing rapid flash for 1 second, followed by two blinks

· Confirm there is no debris or bent pins within the RJ45 connections on all devices in the daisy-chain, and that all connectors are properly snapped into the RJ45 port
· Use a CAT5 cable tester to confirm all cables are properly terminated · Confirm no CAT5 cables are kinked or held with cable ties that are overtightened

Restore Factory Defaults

1. Press and hold button until LED flashes rapidly 2. Press button 9 times 3. During LED flash back (3 individual flashes), press the button twice 4. LED will flash twice to confirm reset, press and hold button until LED flashed rapidly 5. Press button 9 times. LED wil blink twice to show successful factory reset

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 02/23/2022

2 of 3

IS-NPP16ER-EFP-003

nPP16 ER EFP
UL-924 EMER. RELAY PACK
FAMILY INSTRUCTIONS

Operational settings can be changed via the push-button sequence outlined below and right. Addtional settings can also be configured via SensorView software.

A-LEVEL PROGRAMMING INSTRUCTIONS Please read all 3 steps before programming
1. Enter a specific programming function by pressing button the number of times as the desired function number from the A-Level Detailed Function Tables (e.g., press 23 times for function 23, Occupied Bright Level).

2. LED will flash back the selected function's current setting (e.g., 11 times for 100%). To change setting, proceed to step 3 before flash back sequence repeats 3 times. To exit the current function or to change to a different function, wait for sequence to repeat 3 times then return to step 1.
3. Press button the number of times indicated in the particular function's detailed table for the NEW desired setting. As confirmation of setting change, LED flashes back the NEW setting 3 times before exiting.
A-LEVEL DETAILED FUNCTION TABLES

17 = Secondary Zone Dimming Offset Percentage voltage difference of unit's dimming output from primary dimming output (Function 26, Follow Photocell Mode, must be enabled)

1 - 100% 2 - 90% 3 - 80% 4 - 70% 5 -60% 6 -50% 7 -40%

8 -30% 9 -20% 10 -10% 11 0%* 12 10% 13 20% 14 30%

15 40% 16 50% 17 60% 18 70% 19 80% 20 90% 21 100%

23 = Occupied Bright Level

The percentage of the controllable dimming range that the dimming

output rises to when occupancy is detected. Setting is not applicable

if Follow Photocell Mode is enabled. Note: Adjusting the dim level

using a WallPod changes this setting when Follow Photocell Mode

is disabled.

1 1%

5 40%

9 80%

2 10%

6 50%

10 90%

3 20%

7 60%

11 100%*

4 30%

8 70%

24 = Unoccupied Dim Level

The percentage of the controllable dimming range that a dimming

output drops the lights to after the Idle Time Until Dim timer expires

1 1%*

5 40%

9 80%

2 10%

6 50%

10 90%

3 20%

7 60%

11 100%

4 30%

8 70%

26 = Follow Photocell Mode Directs how a device's dimming output reacts relative to a photocell
(ADC)

1 Disable* 2 Enabled (- only) 3 Enabled +/-

NOTE
* indicates default setting for base nPP16 (D) ER EFP models.

B-LEVEL PROGRAMMING INSTRUCTIONS Please read all 4 steps before programming
1. Enter B-Level programming mode by holding down button until LED flashes rapidly, release, hold down until rapid flash again, release, then immediately enter programming function as described in step 2.
2. Enter a programming function by pressing button the number of times as the desired function number from the table labeled B-Level Functions (e.g., 12 times for function 12, Occupancy Tracking Channel).

3. LED will flash back the selected function's current setting (e.g., 1 flash for channel 1). To change setting, proceed to step 4 before flash back sequence repeats 3 times. To exit the current function or to change to a different function, wait for sequence to repeat 3 times then return to step 1.
4. Press button the number of times indicated in the particular function's detailed table for the NEW desired setting (e.g., press 2 times for channel 2). As confirmation of setting change, LED flashes back the NEW setting 3 times before exiting.
B-LEVEL DETAILED FUNCTION TABLES

12 = Occupancy Tracking Channel The local channel on which a device's relay and/or dimming output receives occupancy information
1 - 16 (e.g., 1 = Channel 1*, 2 = Channel 2; etc.)

14 = Photocell Tracking Channel The local channel on which a device's relay and/or dimming output receives photocell information
1 - 16 (e.g., 1 = Channel 1*, 2 = Channel 2; etc.)

16 = Switch Tracking Channel The local channel on which a device's relay and/or dimming output receives switch information.
1 - 16 (e.g., 1 = Channel 1*, 2 = Channel 2; etc.)
Note: Normal default is channel 1, units with SW2 and SA2 options are
defaulted to channel 2

17 = Override (Relay / Dimming) Indicates whether a device's relay is forced on/off and/or dimming output is forced to max/min
1 Not forced* 2 Override On 3 Override Off

18 = Special Operating Mode

Unique defined behaviors of relays and/or dimming outputs, see right

for function definitions

1 Normal*

5 Predictive Off

2 Manual On

6 Manual to Override On

3 Auto to Override On

7 Manual to Normal

4 Manual to Full Auto On

19 = Invert Relay Logic Reverses functionality of relays
1 Normal Logic* 2 Inverse Logic

21 = WallPod Dimming Adjustments

Defines whether user dimming adjustments are maintained after

lights are cycled, whether they revert to default levels, or whether they

temporarily disable a connected dimming photocell (until lights cycle)

1 Permanent* 2 Temporary 3 Photocell Temp

Override

22 = Maintain Dim Level when Vacant

Prevents lights from turning fully off once in unoccupied state

1 No*

2 Yes

23 = Special Switch Tracking Mode

Defines unique behavior related to how relays respond to particular

switch information

1 Disable*

3 Ignore Ons

2 Ignore Offs

4 Ignore Ons & Offs

27 = Relay Always On

Forces relay to stay closed even in off state

1 No*

2 Yes

28 = Dimming Always On

Maintains unoccupied dim level when in off state. Does not affect relay.

1 No*

2 Yes

29 = Occupancy Expiration of Manual Off

When enabled, operation of device will revert from a push-button

triggered override off state to Normal mode once the Occupancy Time Delay

(adjustable via SensorView or push-button) expires. Not used with Manual

On operating modes.

1 Disable*

2 Enable

31 = High End Trim**

Maximum voltage level of the device's dimming output. Commonly used for

task tuning where absolute light level is not to be increased via a Wallpod

or scene. When output is at high end trim, the reported control percentage

will be 100%. Corresponding lumen output % is dependent on ballast/

driver capabilities.

1 0.7 V

4 3V

7 6V

10 9V

2 1V

5 4V

8 7V

11 10V

3 2V

6 5V

9 8V

32 = Low End Trim**

Minimum voltage level of the device's active dimming range. Level can not

be reduced via a WallPod or scene. When output is at low end trim, the

reported control percentage will be 1%. Corresponding lumen output % is

dependent on ballast/driver capabilities.

1 0.7 V

4 3V

7 6V

10 9V

2 1V

5 4V

8 7V

11 10V

3 2V

6 5V

9 8V

** Setting precision of 0.1V is available via SensorView. Device status LED

blinks out current value rounded to nearest selection above.

FUNCTION 18 DEFINITIONS
NORMAL Operating Mode where occupancy sensors are capable of turning lights both on/off
AUTO TO OVERRIDE ON Special Mode where lights are turned on initially by occupant detection but then left in the Override On state
MANUAL ON TO FULL AUTO Special Mode that initially requires the occupant to manually turn on the lights, after which the sensor assumes full on/off control
MANUAL ON Special Mode that always requires the occupant to manually turn the lights on, while having them turn off automatically by a sensor (default on models with SA and SA2 options)
PREDICTIVE OFF When lights are switched off, this Special Mode determines whether occupants remained or left the room, so as to leave the lights in either the Override Off or Auto On state
MANUAL TO TIMED OVERRIDE ON Special Mode where lights are initially turned on manually but remain in the Override On state for a pre-determined period (Timed Override Delay)
MANUAL TO NORMAL Special Mode where lights are initially turned on manually but remain in the Normal State (enabling auto-dimming) for a pre-determined period (Timed Override Delay)

For further troubleshooting guidance, please contact the Controls Technical Support Team