User Manual for PROTRONIX models including: NLII-CO2 RH T-5-SX, Combined CO2 Sensor with Sigfox, Combined RH Sensor with Sigfox, Combined T Sensor with Sigfox

User manual for sensor NLII-CO2 RH T-5-SX

Room sensor, CO2, 5000ppm, relative humidity, tepmperature, wireless, Sigfox, power supply24V AC/DC, Design NL

detector, sensor, CO2, carbon dioxide, VOC, humidity, hygrometer, ppm, RH, gas, smoke, temperature, measurement, concentration, ventilation, heat recovery

Protronix s.r.o.

User manual for sensor NLII-CO2 RH T-5-SX

User manual um-nlii-co2 rh t-5-sx-en-v3-201026 Room sensor NLII-CO2 is used to continuously monitor air quality inside buildings and then control ventilation (HVAC) systems according ... SIGFOX wireless communication maintenance during operation is not required Description: 1

SIGFOX wireless communication maintenance during operation is not required Description: 1 The measuring of CO 2 measuring rangeis based on the principle of infrared radiation attenuation dependence on the CO 2 concentration in the air (NDIR). Built-in auto-calibration function ensures very good long term stability. 2

PDF preview unavailable. Download the PDF instead.

um-NLII-CO2-RH-T-5-SX-en
User manual

NLII-CO2+RH+T-5-SX | Combined CO2/RH/T sensor with SIGFOX
Room sensor NLII-CO2 is used to continuously monitor air quality inside buildings and then control ventilation (HVAC) systems according to current levels of air internal air quality. The sensor measures concentration of carbon dioxide (CO2), relative humidity (RH) and temperature (T). It can be effectively used in offices, classrooms, shopping centers, homes, restaurants, fitness centers, commercial buildings, etc.

 measures CO2, RH and temperature  2x analog voltage/current output  SIGFOX wireless communication  maintenance during operation is not
required
Description:
The measuring of CO2 is based on the principle of infrared radiation attenuation dependence on the CO2 concentration in the air (NDIR). Built-in autocalibration function ensures very good long term stability. Measurement of the relative humidity is based on the principle of capacitive polymer sensor. The sensor has built-in two separate analog outputs one for the actual concentration of CO2 and the other for the current relative humidity. Temperature output is available by Sigfox communication. So the sensor efficiently manages ventilation and heat recovery units, based on current room air quality. The current air quality can easily be determined by looking at the three LED indicators. The eco level means good indoor air quality necessary to achieve a sense of well-being and at the same time optimal energy costs for heating, ventilation or air conditioning. For detailed information on the communication protocol, use the document NLII-SigfoxCommunication.
Explanation of abbreviations and technical terms can be found on our website in the Glossary section.

Technical data

Parameter Supply voltage range

Value Unit
12 ­ 35 V DC 12 ­ 24 V AC

Average consumption CO2 measuring range CO2 accuracy CO2 startup CO2 step response RH measuring range RH accuracy 20 ­ 80 % RH accuracy 0 ­ 100 % T measuring range T accuracy Output 1)

0,5 W 400 ­ 5000 ppm ± 35 ppm ±5 % of reading
max 1 min
(90 %) 80 s 0 ­ 100 % RH
± 3 % RH ± 6 % RH 0 ­ 50 °C ± 0,4 °C 0-10 V / 0-20 mA / 4-20 mA

Working humidity non condensing Working temperature
Storage temperature

0 ­ 95 % RH
0 to +50 °C -20 to +60 °C

Expected lifetime

min. 10 years

Ingress protection

IP20

Dimensions

110x158x31 mm

1) It is possible to select the desired type of analog

output by a jumper.

Minimum achievable output value corresponds to

minimum value of the measuring range.

Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic

www.protronix.cz/en/ www.careforair.eu/en/

um-nlii-co2+rh+t-5-sx-en-v3-201026.docx

1/6

User manual

NLII-CO2+RH+T-5-SX | Combined CO2/RH/T sensor with SIGFOX

CO2 sensor autocalibration function

Typical T measurement accuracy

Autocalibration compensates for long-term aging of the key components of the sensor. This function is available only when sensor power supply is continuous and uninterrupted. Calibration during operation is not necessary.

Selected analog output values versus actual CO2 concentration

Selected analog output values versus actual RH Typical RH measurement accuracy at 25 °C

LED indication description
White LED lights: Less than 600 ppm CO2 or less than 40 % RH. (according to the quantity selected for indication)  maintaining low concentrations of CO2 is not cost-effective - slightly increased concentration does not cause any health complications  low concentrations of RH. Too dry air feels cooler as compared to equally hot but more humid air ­ risk of drying of the mucous membranes - respiratory problems
Green LED lights: More than or equal to 600 ppm CO2 or 40 % RH, less than or equal to 1200 ppm CO2 or 60 % RH. (according to the quantity selected for indication)  optimal balance of air quality and energy efficiency of ventilation and air conditioning  optimal relative humidity for humans
Yellow LED lights: More than 1200 ppm CO2 or more than 60 % RH. (according to the quantity selected for indication)  higher concentration of CO2 - further increase of CO2 concentrations above this level can cause fatigue, restlessness, headache  too high humidity - the risk of mold growth and associated health complications

Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic

www.protronix.cz/en/ www.careforair.eu/en/

um-nlii-co2+rh+t-5-sx-en-v3-201026.docx

2/6

User manual

NLII-CO2+RH+T-5-SX | Combined CO2/RH/T sensor with SIGFOX

Sensor start after power on

CAUTION:

All three LEDs flash simultaneously until the first readings are available, but no longer than 10 seconds.
Sensor failure indication
All three LEDs are shining permanently.

Warm-up: operational after 1 minute since power on. The declared accuracy is reached after 4 days of continuous power supply. It is necessary to avoid severe mechanical shock of the sensor.

Electronic board controls and terminals

6 5 4 3 2 1

Terminals

1. ~ + 2. ~ GND 3. OUT1
4. GND 5. OUT2
6. GND

supply AC or DC (+) plus pole supply AC or DC (-) minus pole, GND CO2 sensor analog output, 0-10 V or 0-20 mA or 4-20 mA CO2 sensor output GND RH sensor analog output, 0-10 V or 0-20 mA or 4-20 mA RH sensor output GND

Jumpers
JP1 ­ Current output offset RH JP2 ­ Current output offset CO2 JP3 ­ Voltage/current output CO2 JP4 ­ Voltage/current output RH JP6 ­ LED indication settings

Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic

www.protronix.cz/en/ www.careforair.eu/en/

um-nlii-co2+rh+t-5-sx-en-v3-201026.docx

3/6

User manual

NLII-CO2+RH+T-5-SX | Combined CO2/RH/T sensor with SIGFOX

Jumpers on the electronics board Mark Description JP1 Current output offset RH
- shift quiescent current from 0 mA to 4 mA

Settings Meaning current output RH 0-20 mA current output RH 4-20 mA

JP2 Current output offset CO2 - shift quiescent current from 0 mA to 4 mA

current output CO2 0-20 mA current output CO2 4-20 mA

JP3 Voltage/current output CO2

- select the type of analog output - if the selected voltage output is CO2, JP2 must not be shorted
JP4 Voltage/current output RH

JP6 - 1

- select the type of analog output - if the selected voltage output is RH, JP1 must not be shorted
LED indication

voltage output CO2 current output CO2 voltage output RH current output RH

- LED indication according to ambient light when ambient light is dimmed (at night), LED indicators turn off automatically.

permanent LED indication enabled

JP6 - 4 These positions are not intended for user JP6 - 5 setting.

LED indication according to ambient light

Factory settings
LED indication:
CO2 analog output: RH analog output:

by CO2, indication turns off when ambient light dims voltage output voltage output

Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic

www.protronix.cz/en/ www.careforair.eu/en/

um-nlii-co2+rh+t-5-sx-en-v3-201026.docx

4/6

User manual NLII-CO2+RH+T-5-SX | Combined CO2/RH/T sensor with SIGFOX
Example of CO2 sensor connection for direct EC motor control using 0-10 V signal
If you connect other devices to the same AC power source as the NL sensor, it is necessary to meet GND wiring of all analog inputs and outputs, as well as power wires.

Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic

www.protronix.cz/en/ www.careforair.eu/en/

um-nlii-co2+rh+t-5-sx-en-v3-201026.docx

5/6

User manual

NLII-CO2+RH+T-5-SX | Combined CO2/RH/T sensor with SIGFOX

Sensor assembly

Box color

Front: white - RAL9016 Base: gray - RAL7035

Way to use

The product is intended for indoor use only. You can read the recommendations for sensor placement on our web pages.

End of product life

Discard the product in according to the electronic waste law and the EU directives.

Disassembly
When disassembling, be careful not to rip-out the antenna cable. It connects the antenna in lower part of the sensor with the electronics in the upper part.
Dimensions

The producer reserves the right of technical changes in order to product improvements its properties and functions without previous notice.

Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic

www.protronix.cz/en/ www.careforair.eu/en/

um-nlii-co2+rh+t-5-sx-en-v3-201026.docx