Annex
Ratings of the test product
Model | GW700-XS-30 | GW1000-XS-30 | GW1500-XS-30 | GW2000-XS-30 | GW2500-XS-30 | GW3000-XS-30 | GW3300-XS-30 |
---|---|---|---|---|---|---|---|
PV input | |||||||
Vmax PV (Vdc) (absolute Max.) | 600 | 600 | 600 | 600 | 600 | 600 | 600 |
Isc PV (absolute Max.) (A) | 25 | 25 | 25 | 25 | 25 | 25 | 25 |
Max. input current (A) | 16 | 16 | 16 | 16 | 16 | 16 | 16 |
MPPT voltage range (Vdc) | 40-450 | 40-450 | 40-450 | 40-450 | 40-550 | 40-550 | 40-550 |
AC Grid (output) | |||||||
Normal Voltage (Vac) | 220/230/400 | ||||||
Frequency (Hz) | 50 / 60 | ||||||
Max. output current (A) | 3.2 | 4.6 | 6.9 | 9.1 | 11.4 | 13.7 | 15 |
Normal Active Power (W) | 700 | 1000 | 1500 | 2000 | 2500 | 3000 | 3300 |
Normal Apparent Power (VA) | 700 | 1000 | 1500 | 2000 | 2500 | 3000 | 3300 |
Max. Apparent Power (VA) | 700 | 1000 | 1500 | 2000 | 2500 | 3000 | 3300 |
Power factor (adjustable) | 1.0 (0.8 leading...0.8 lagging) | ||||||
Others | |||||||
Protective class | Class I | ||||||
Ingress protection (IP) | IP66 | ||||||
Operating Temperature | -25°C to +60°C | ||||||
Inverter Isolation | Non-isolated | ||||||
Overvoltage category | OVC III (AC Main), OVC II (PV) |
G98/1-7 Form C: Type Test Verification Report
Extract form test report number: 6157937.50
1. Operating Range
Status: P
This test should be carried out as specified in A.1.2.10. Pass or failure of the test should be indicated in the fields below (right hand side), for example with the statement “Pass”, “No disconnection occurs”, etc. Graphical evidence is preferred.
Model: GW3000-XS-30
Test | Measured Voltage (V) | Measured Frequency (Hz) | Measured Power (W) | Measured Power factor | Test Time (s) |
---|---|---|---|---|---|
Test 1: | 196.0 | 47.0 | 2677.5 | 1.000 | 24 |
Test 2: | 196.0 | 47.5 | 2684.7 | 1.000 | 5485 |
Test 3: | 253.4 | 51.5 | 2988.7 | 1.000 | 5457 |
Test 4: | 253.4 | 52.0 | 2989.5 | 1.000 | 982 |
Test 5: | 230.5 | 50.0 | 2988.5 | 1.000 | 5406 |
Test 6: | 195.5 | Ramp range: 47.0 Hz to 52.0 Hz | Test frequency ramp: +1 Hzs⁻¹ | Test Duration: 5.05s | Confirm no trip: no trip |
253.0 | Ramp range: 52.0 Hz to 49.0 Hz | Test frequency ramp: -1 Hzs⁻¹ | Test Duration: 3.00s | Confirm no trip: no trip |
2. Power Quality – Harmonics
Status: P
These tests should be carried out as specified in BS EN 61000-3-2. The chosen test should be undertaken with a fixed source of energy at two power levels a) between 45 and 55% and b) at 100% of Registered Capacity. The test requirements are specified in Annex A1 A.1.3.1 (Inverter connected) or Annex A2 A.2.3.1 (Synchronous).
Model: GW700-XS-30
Micro-generator tested to BS EN 61000-3-2
Micro-generator rating per phase (rpp): 0.7 kW
For 3-phase Micro-generators, tick this box if harmonic measurements are identical for all three phases. If the harmonics are not identical for each phase, please replicate this section with the results for each phase. Single phase PV inverter
Harmonic c | At 45-55% of Registered Capacity Measured Value MV in Amps | 100% of Registered Capacity Measured Value MV in Amps | Limit in BS EN 61000-3-2 in Amps | Higher limit for odd harmonics 21 and above |
---|---|---|---|---|
2 | 0.020 | 0.034 | 1.080 | |
3 | 0.040 | 0.023 | 2.300 | |
4 | 0.006 | 0.010 | 0.430 | |
5 | 0.042 | 0.028 | 1.140 | |
6 | 0.009 | 0.008 | 0.300 | |
7 | 0.043 | 0.012 | 0.770 | |
8 | 0.011 | 0.007 | 0.230 | |
9 | 0.049 | 0.014 | 0.400 | |
10 | 0.012 | 0.005 | 0.184 | |
11 | 0.115 | 0.045 | 0.330 | |
12 | 0.009 | 0.004 | 0.153 | |
13 | 0.052 | 0.048 | 0.210 | |
14 | 0.008 | 0.005 | 0.131 | |
15 | 0.034 | 0.050 | 0.150 | |
16 | 0.008 | 0.006 | 0.115 | |
17 | 0.027 | 0.047 | 0.132 | |
18 | 0.009 | 0.005 | 0.102 | |
19 | 0.024 | 0.044 | 0.118 | |
20 | 0.009 | 0.005 | 0.092 | |
21 | 0.013 | 0.040 | 0.107 | 0.160 |
22 | 0.009 | 0.005 | 0.084 | |
23 | 0.013 | 0.036 | 0.098 | 0.147 |
24 | 0.009 | 0.005 | 0.077 | |
25 | 0.016 | 0.034 | 0.090 | 0.135 |
26 | 0.009 | 0.004 | 0.071 | |
27 | 0.020 | 0.031 | 0.083 | 0.124 |
28 | 0.009 | 0.004 | 0.066 | |
29 | 0.024 | 0.029 | 0.078 | 0.117 |
30 | 0.009 | 0.004 | 0.061 | |
31 | 0.030 | 0.027 | 0.073 | 0.109 |
32 | 0.008 | 0.004 | 0.058 | |
33 | 0.032 | 0.024 | 0.068 | 0.102 |
34 | 0.008 | 0.004 | 0.054 | |
35 | 0.030 | 0.022 | 0.064 | 0.096 |
36 | 0.007 | 0.004 | 0.051 | |
37 | 0.026 | 0.020 | 0.061 | 0.091 |
38 | 0.006 | 0.003 | 0.048 | |
39 | 0.024 | 0.017 | 0.058 | 0.087 |
40 | 0.006 | 0.003 | 0.046 |
Model: GW3000-XS-30
Micro-generator tested to BS EN 61000-3-2
Micro-generator rating per phase (rpp): 3 kW
For 3-phase Micro-generators, tick this box if harmonic measurements are identical for all three phases. If the harmonics are not identical for each phase, please replicate this section with the results for each phase. Single phase PV inverter
Harmonic c | At 45-55% of Registered Capacity Measured Value MV in Amps | 100% of Registered Capacity Measured Value MV in Amps | Limit in BS EN 61000-3-2 in Amps | Higher limit for odd harmonics 21 and above |
---|---|---|---|---|
2 | 0.017 | 0.019 | 1.080 | |
3 | 0.032 | 0.059 | 2.300 | |
4 | 0.005 | 0.009 | 0.430 | |
5 | 0.036 | 0.043 | 1.140 | |
6 | 0.005 | 0.006 | 0.300 | |
7 | 0.015 | 0.015 | 0.770 | |
8 | 0.004 | 0.004 | 0.230 | |
9 | 0.014 | 0.022 | 0.400 | |
10 | 0.004 | 0.004 | 0.184 | |
11 | 0.035 | 0.056 | 0.330 | |
12 | 0.003 | 0.003 | 0.153 | |
13 | 0.024 | 0.045 | 0.210 | |
14 | 0.003 | 0.003 | 0.131 | |
15 | 0.019 | 0.036 | 0.150 | |
16 | 0.003 | 0.003 | 0.115 | |
17 | 0.014 | 0.022 | 0.132 | |
18 | 0.003 | 0.003 | 0.102 | |
19 | 0.013 | 0.021 | 0.118 | |
20 | 0.003 | 0.003 | 0.092 | |
21 | 0.011 | 0.015 | 0.107 | 0.160 |
22 | 0.003 | 0.003 | 0.084 | |
23 | 0.011 | 0.013 | 0.098 | 0.147 |
24 | 0.002 | 0.003 | 0.077 | |
25 | 0.009 | 0.013 | 0.090 | 0.135 |
26 | 0.002 | 0.003 | 0.071 | |
27 | 0.009 | 0.01 | 0.083 | 0.124 |
28 | 0.002 | 0.002 | 0.066 | |
29 | 0.007 | 0.01 | 0.078 | 0.117 |
30 | 0.002 | 0.002 | 0.061 | |
31 | 0.006 | 0.009 | 0.073 | 0.109 |
32 | 0.002 | 0.002 | 0.058 | |
33 | 0.006 | 0.008 | 0.068 | 0.102 |
34 | 0.002 | 0.002 | 0.054 | |
35 | 0.005 | 0.008 | 0.064 | 0.096 |
36 | 0.002 | 0.002 | 0.051 | |
37 | 0.004 | 0.006 | 0.061 | 0.091 |
38 | 0.001 | 0.002 | 0.048 | |
39 | 0.003 | 0.007 | 0.058 | 0.087 |
40 | 0.001 | 0.002 | 0.046 |
Note: The higher limits for odd harmonics 21 and above are only allowable under certain conditions, if these higher limits are utilised please state the exemption used as detailed in part 6.2.3.4 of BS EN 61000-3-2 in the box below.
3. Power Quality – Voltage fluctuations and Flicker
Status: P
These tests should be undertaken in accordance with EREC G98 Annex A1 A.1.3.3 (Inverter connected) or Annex A2 A.2.3.3 (Synchronous). The standard test impedance is 0.4 Ω for a single phase Micro-generating Plant (and for a two phase unit in a three phase system) and 0.24 Ω for a three phase Micro-generating Plant (and for a two phase unit in a split phase system). Please ensure that both test and standard impedance are completed on this form. If the test impedance (or the measured impedance) is different to the standard impedance, it must be normalised to the standard impedance as follows (where the Power Factor of the generation output is 0.98 or above): d max normalised value = (Standard impedance / Measured impedance) x Measured value. Where the Power Factor of the output is under 0.98 then the X to R ratio of the test impedance should be close to that of the standard impedance. The stopping test should be a trip from full load operation. The duration of these tests needs to comply with the particular requirements set out in the testing notes for the technology under test. The test date and location must be declared.
Test start date: 2023-11-07
Test end date: 2023-11-07
Test location: No.99, Hongye Road, Suzhou Industrial Park, Suzhou, Jiangsu, P.R. China
Model: GW3000-XS-30
Type: Single Phase
Starting | Stopping | Running | ||||||
---|---|---|---|---|---|---|---|---|
d(max) | d(c) | d(t) | d(max) | d(c) | d(t) | Pst | Plt 2 hours | |
Measured Values at test impedance | 0.145 | 0.077 | 0 | 0.140 | 0.077 | 0 | 0.14 | 0.11 |
Normalised to standard impedance | 0.145 | 0.077 | 0 | 0.140 | 0.077 | 0 | 0.14 | 0.11 |
Normalised to required maximum impedance | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
Limits set under BS EN 61000-3-11 | 4% | 3.3% | 3.3% | 4% | 3.3% | 3.3% | 1.0 | 0.65 |
Test Impedance: R = 0.4 Ω, Xl = 0.25 Ω
Standard Impedance: R = 0.24 * (0.4 ^) Ω, Xl = 0.15 * (0.25 ^) Ω
Maximum Impedance: R = N/A #, Xl = N/A #
*Applies to three phase and split single phase Micro-generators. Delete as appropriate.
^ Applies to single phase Micro-generators and Micro-generators using two phases on a three phase system. Delete as appropriate.
4. Power quality – DC injection
Status: P
This test should be carried out in accordance with A 1.3.4 as applicable. The % DC injection ("as % of rated AC current" below) is calculated as follows: % DC injection = Recorded DC value in Amps / base current where the base current is the Registered Capacity (W) / 230 V. The % DC injection should not be greater than 0.25%.
Model: GW3000-XS-30
Type: Single Phase
Test power level | 20% | 50% | 75% | 100% |
---|---|---|---|---|
Recorded DC injection value in Amps | 27.2mA | 30.2mA | 29.32mA | 27.46mA |
as % of rated AC current | 0.21% | 0.23% | 0.22% | 0.21% |
Limit | 0.25% | 0.25% | 0.25% | 0.25% |
Model: GW700-XS-30
Type: Single Phase
Test power level | 20% | 50% | 75% | 100% |
---|---|---|---|---|
Recorded DC injection value in Amps | 5.11 mA | 7.51 mA | 7.35 mA | 7.53 mA |
as % of rated AC current | 0.17% | 0.247% | 0.242% | 0.247% |
Limit | 0.25% | 0.25% | 0.25% | 0.25% |
5. Power Factor
Status: P
This test shall be carried out in accordance with A.1.3.2 and A.2.3.2 at three voltage levels and at Registered Capacity and the measured Power Factor must be greater than 0.95 to pass. Voltage to be maintained within ±1.5% of the stated level during the test.
Model: GW3000-XS-30
Voltage | 0.94 pu (216.2 V) | 1 pu (230 V) | 1.1 pu (253 V) |
---|---|---|---|
Measured value | 1.000 | 1.000 | 1.000 |
Power Factor Limit | >0.95 | >0.95 | >0.95 |
Model: GW700-XS-30
Voltage | 0.94 pu (216.2 V) | 1 pu (230 V) | 1.1 pu (253 V) |
---|---|---|---|
Measured value | 0.999 | 0.999 | 0.998 |
Power Factor Limit | >0.95 | >0.95 | >0.95 |
6. Protection – Frequency tests
Status: P
These tests should be carried out in accordance with Annex A1 A.1.2.3 (Inverter connected) or Annex A2 A.2.2.3 (Synchronous). For trip tests, frequency and time delay should be stated. For "no trip tests", "no trip" can be stated.
Model: GW3000-XS-30
Function | Setting | Trip test | "No trip tests" | Confirm no trip | ||
---|---|---|---|---|---|---|
Frequency | Time delay | Frequency / time | ||||
U/F stage 1 | 47.5 Hz | 47.40 | 20.10 s | 47.7 Hz | 30 s | No trip |
U/F stage 2 | 47.0 Hz | 46.90 | 0.548 s | 47.2 Hz | 19.5 s | No trip |
46.8 Hz | 0.45 s | No trip | ||||
O/F | 52.0 Hz | 52.02 | 0.540 s | 51.8 Hz | 120.0 s | No trip |
52.2 Hz | 0.45 s | No trip |
Note: For frequency trip tests the frequency required to trip is the setting ±0.1 Hz. In order to measure the time delay a larger deviation than the minimum required to operate the projection can be used. The "No trip tests" need to be carried out at the setting ±0.2 Hz and for the relevant times as shown in the table above to ensure that the protection will not trip in error.
7. Protection – Voltage tests
Status: P
These tests should be carried out in accordance with Annex A1 A.1.2.2 (Inverter connected) or Annex A2 A.2.2.2 (Synchronous). For trip tests, voltage and time delay should be stated. For "no trip tests", "no trip" can be stated.
Model: GW3000-XS-30
Type: Single Phase
Function | Setting | Trip test | "No trip tests" | Confirm no trip | ||
---|---|---|---|---|---|---|
Voltage | Time delay | Voltage | Time delay | Voltage / time | ||
U/V | 0.8 pu (184 V) | 182.22 V | 2.500 s | 188 V | 5.0 s | No trip |
180 V | 2.45 s | No trip | ||||
O/V stage 1 | 1.14 pu (262.2 V) | 262.21 V | 1.028 s | 258.2 V | 5.0 s | No trip |
O/V stage 2 | 1.19 pu (273.7 V) | 273.69 V | 0.500 s | 269.7 V | 0.95 s | No trip |
277.7 V | 0.45 s | No trip |
Note: For Voltage tests the Voltage required to trip is the setting ±3.45 V. The time delay can be measured at a larger deviation than the minimum required to operate the protection. The No trip tests need to be carried out at the setting ±4 V and for the relevant times as shown in the table above to ensure that the protection will not trip in error.
8. Protection – Loss of Mains test
Status: P
For PV Inverters shall be tested in accordance with BS EN 62116. Other Micro-generators should be tested in accordance with A.2.2.4 at 10%, 55% and 100% of rated power. For test condition A, EUT output = 100 % Pn, test condition B, EUT output = 50 % to 66 % Pn, and test condition C, EUT output = 25 % to 33 % Pn.
Model: GW3000-XS-30
For Inverters tested to BS EN 62116 the following sub set of tests should be recorded in the following table.
The Loss of Mains test section details various test conditions (Balance and Imbalance) performed on the GW3000-XS-30 inverter at different power levels (33%, 66%, 100%). It records parameters such as trip time, PEUT, reactive load, PAC, QAC, run-on time, power output, actual VDC, Qf, and remarks for each test. The limit for trip time is 0.5s.
9. Protection – Frequency change, Vector Shift Stability test
Status: P
This test should be carried out in accordance with EREC G98 Annex A1 A.1.2.6 (Inverter connected) or Annex A2 A.2.2.6 (Synchronous). Confirmation is required that the Micro-generating Plant does not trip under positive / negative vector shift.
Model: GW3000-XS-30
Start Frequency | Change | Confirm no trip | |
---|---|---|---|
Positive Vector Shift | 49.0 Hz | +50 degrees | No trip |
Negative Vector Shift | 50.0 Hz | -50 degrees | No trip |
10. Protection – Frequency change, RoCoF Stability test
Status: P
The requirement is specified in section 11.3, test procedure in Annex A.1.2.6 (Inverter connected) or Annex A2 A.2.2.6 (Synchronous). Confirmation is required that the Micro-generating Plant does not trip for the duration of the ramp up and ramp down test.
Model: GW3000-XS-30
Ramp range | Test frequency ramp: | Test Duration | Confirm no trip |
---|---|---|---|
49.0 Hz to 51.0 Hz | +0.95 Hzs⁻¹ | 2.15 s | No trip |
51.0 Hz to 49.0 Hz | -0.95 Hzs⁻¹ | 2.10 s | No trip |
11. Limited Frequency Sensitive Mode – Over frequency test
Status: P
This test should be carried out in accordance with A.1.2.9. The test should be carried out using the specific threshold frequency of 50.4 Hz and Droop of 10%. The measurement tolerances are contained in A.1.2.9.
Model: GW3000-XS-30
Alternatively, simulation results should be noted below:
Test sequence at Registered Capacity >80%
Test sequence | Measured Active Power Output (W) | Frequency (Hz) | Calculated droop (%) | Primary Power Source | Active Power Gradient |
---|---|---|---|---|---|
Step a) 50.00 Hz ±0.01 Hz | 2988.49 | 50.00 | -- | Photovoltaic | - |
Step b) 50.45 Hz ±0.05 Hz | 2956.20 | 50.45 | 9.18 | array | - |
Step c) 50.70 Hz ±0.10 Hz | 2799.75 | 50.70 | 9.52 | simulator | - |
Step d) 51.15 Hz ±0.05 Hz | 2529.41 | 51.15 | 9.79 | - | |
Step e) 50.70 Hz ±0.10 Hz | 2799.16 | 50.70 | 9.49 | - | |
Step f) 50.45 Hz ±0.05 Hz | 2955.70 | 50.45 | 9.03 | - | |
Step g) 50.00 Hz ±0.01 Hz | 2986.62 | 50.00 | -- | - |
Test sequence at Registered Capacity 40-60%
Test sequence | Measured Active Power Output (W) | Frequency (Hz) | Calculated droop (%) | Primary Power Source | Active Power Gradient |
---|---|---|---|---|---|
Step a) 50.00 Hz ±0.01 Hz | 1499.22 | 50.00 | -- | Photovoltaic | - |
Step b) 50.45 Hz ±0.05 Hz | 1466.50 | 50.45 | 9.05 | array | - |
Step c) 50.70 Hz ±0.10 Hz | 1310.66 | 50.70 | 9.52 | simulator | - |
Step d) 51.15 Hz ±0.05 Hz | 1039.56 | 51.15 | 9.78 | - | |
Step e) 50.70 Hz ±0.10 Hz | 1310.57 | 50.70 | 9.52 | - | |
Step f) 50.45 Hz ±0.05 Hz | 1466.87 | 50.45 | 9.15 | - | |
Step g) 50.00 Hz ±0.01 Hz | 1499.93 | 50.00 | -- | - |
The frequency at each step should be maintained for at least one minute and the Active Power reduction in the form of a gradient determined and assessed for compliance with paragraph 11.2.3. The Droop should be determined from the measurements between 50.4 Hz and 51.15 Hz. The allowed tolerance for the frequency measurement shall be ± 0.05 Hz. The allowed tolerance for Active Power output measurement shall be ±10% of the required change in Active Power. The resulting overall tolerance range for a nominal 10% Droop is +2.8% and – 1.5%.
12. Power output with falling frequency test (For PV Inverter)
Status: P
This test should be carried out in accordance with A.1.2.7.
Model: GW3000-XS-30
Test sequence | Measured Active Power Output (W) | Frequency (Hz) | Primary power source |
---|---|---|---|
Test a) 50 Hz ± 0.01 Hz | 2989.31 | 50.00 | Photovoltaic array simulator |
Test b) Point between 49.5 Hz and 49.6 Hz | 2987.71 | 49.60 | Photovoltaic array simulator |
Test c) Point between 47.5 Hz and 47.6 Hz | 2988.26 | 47.60 | Photovoltaic array simulator |
13. Re-connection timer
Status: P
Model: GW3000-XS-30
Test should prove that the reconnection sequence starts after a minimum delay of 20 s for restoration of voltage and frequency to within the stage 1 settings of Table 2. Both the time delay setting and the measured delay should be provided in this form; both should be greater than 20 s to pass. Confirmation should be provided that the Micro-generating Plant does not reconnect at the voltage and frequency settings below; a statement of “no reconnection” can be made.
Time delay setting | Measured delay | Checks on no reconnection when voltage or frequency is brought to just outside stage 1 limits of Table 10.1. | ||||
---|---|---|---|---|---|---|
At 1.16 pu (266.2 V) | At 0.78 pu (180.0 V) | At 47.4 Hz | At 52.1 Hz | |||
Confirmation that the Micro-generator does not re-connect. | 40 s | 42 s | No Reconnection | No Reconnection | No Reconnection | No Reconnection |
Recover to normal operation range after confirmation of no connection | Yes | Yes | Yes | Yes | ||
Confirmation that the Power Generating Module shall reconnect | Reconnection after 42 s | Reconnection after 42 s | Reconnection after 42 s | Reconnection after 42 s |
14. Fault level contribution
Status: P
These tests shall be carried out in accordance with EREC G98 Annex A1 A.1.3.5 (Inverter connected) and Annex A2 A.2.3.4 (Synchronous). Please complete each entry, even if the fault contribution is zero.
Model: GW3000-XS-30
For machines with electro-magnetic output
Parameter | Symbol | Value | Time after fault | Volts | Amps |
---|---|---|---|---|---|
Peak Short Circuit current | ip | N/A | 20ms | 56.0V | 0.8A |
Initial Value of aperiodic current | A | N/A | 100ms | 52.4V | 3.61A |
Initial symmetrical short-circuit current* | Ik | N/A | 250ms | 51.3V | 10.84A |
Decaying (aperiodic) | iDC | N/A | 500ms | 51.0V | 12.29A |
Parameter | Symbol | Value | Time to trip | In seconds |
---|---|---|---|---|
component of short circuit current* | X/R | N/A | 0.791S | |
Reactance/Resistance Ratio of source* |
For rotating machines and linear piston machines the test should produce a 0 s – 2 s plot of the short circuit current as seen at the Micro-generator terminals.
* Values for these parameters should be provided where the short circuit duration is sufficiently long to enable interpolation of the plot.
15. Logic interface (input port)
Status: P
Confirm that an input port is provided and can be used to reduce the Active Power output to zero | Yes |
Provide high level description of logic interface, e.g. details in 9.4.3 such as AC or DC signal (the additional comments box below can be used) | Yes |
16. Self-Monitoring solid state switching
Status: P
No specified test requirements. Refer to EREC G98 Annex A1 A.1.3.6 (Inverter connected).
It has been verified that in the event of the solid state switching device failing to disconnect the Micro-generator, the voltage on the output side of the switching device is reduced to a value below 50 V within 0.5 s.
Confirmation: Yes
17. Cyber security
Status: P
Confirm that the Manufacturer or Installer of the Micro-generator has provided a statement describing how the Micro-generator has been designed to comply with cyber security requirements, as detailed in 9.7.
Confirmation: Yes, Manufacturer's declaration provided.
Additional comments
The inverter provides a logical interface that can be operated via an external switch or contactor to reduce the active power output to zero. Users can install the switch connected to port 7 and port 8 of the inverter and just need control the switch signal causing the switch to open or short. When the switch is closed, the inverter will operate normally. When the switch is opened, the inverter will cease to export active power within 5 seconds.
Port Diagram Description: The diagram shows various ports on the inverter. Key ports include:
- CT (Current Transformer): Ports 1 (CT+) and 2 (CT-).
- RS485 Communication: Ports 3 (RS485 A1), 4 (RS485 B1), 5 (RS485 A2), 6 (RS485 B2).
- Remote Shutdown/Emergency Power Off: Ports 7 (RM-SHUTDOWN2) and 8 (RM-SHUTDOWN1).
- Dry Contact: Port 9 (Relay-OUT+), Port 10 (Relay-OUT-).
- DRED or RCR: Ports 11 (COM/DRMO or REF_1), 12 (REFGEN or REF 2).
- Other Interface/Control: Ports 13 (DRM4/8 or DI 4), 14 (DRM3/7 or DI 3), 15 (DRM2/6 or DI_2), 16 (DRM1/5 or DI_1).