CERTIFICATE OF CONFORMITY

Issued to: GoodWe Technologies Co., Ltd.

For the product: Gird-Tied PV Inverter

Trade name: GOODWE

Type/Model: GW700-XS-30; GW1000-XS-30; GW1500-XS-30; GW2000-XS-30; GW2500-XS-30; GW3000-XS-30; GW3300-XS-30

Ratings: See Annex

Manufactured by: GoodWe Technologies Co., Ltd.

Requirements: Engineering Recommendation G98 Issue 1 – Amendment 7: 2022 (G98/1-7)

This Test Certificate is granted on account of an examination by DEKRA, the results of which are laid down in a confidential file no. 6157937.50.

The examination has been carried out on one single specimen of the product. The certificate does not include an assessment of the manufacturer's production. Conformity of his production with the specimen tested by DEKRA is not the responsibility of DEKRA.

This Test Certificate expires at the latest on 2 February 2029 or expires upon withdrawal of one of the above mentioned standards.

Location: Shanghai

Date: 2 February 2024

Certificate Number: 6157937.01COC

Testing Body: DEKRA Testing and Certification (Shanghai) Ltd.

Certification Manager: Cliff Lin

Publication note: Integral publication of this certificate and adjoining reports is allowed.

Accreditation: IAS according to ISO/IEC 17065 for products. Accreditation is valid in the areas of certification mentioned in the certificate.

Annex

Ratings of the test product

ModelGW700-XS-30GW1000-XS-30GW1500-XS-30GW2000-XS-30GW2500-XS-30GW3000-XS-30GW3300-XS-30
PV input
Vmax PV (Vdc) (absolute Max.)600600600600600600600
Isc PV (absolute Max.) (A)25252525252525
Max. input current (A)16161616161616
MPPT voltage range (Vdc)40-45040-45040-45040-45040-55040-55040-550
AC Grid (output)
Normal Voltage (Vac)220/230/400
Frequency (Hz)50 / 60
Max. output current (A)3.24.66.99.111.413.715
Normal Active Power (W)700100015002000250030003300
Normal Apparent Power (VA)700100015002000250030003300
Max. Apparent Power (VA)700100015002000250030003300
Power factor (adjustable)1.0 (0.8 leading...0.8 lagging)
Others
Protective classClass I
Ingress protection (IP)IP66
Operating Temperature-25°C to +60°C
Inverter IsolationNon-isolated
Overvoltage categoryOVC III (AC Main), OVC II (PV)

G98/1-7 Form C: Type Test Verification Report

Extract form test report number: 6157937.50

1. Operating Range

Status: P

This test should be carried out as specified in A.1.2.10. Pass or failure of the test should be indicated in the fields below (right hand side), for example with the statement “Pass”, “No disconnection occurs”, etc. Graphical evidence is preferred.

Model: GW3000-XS-30

TestMeasured Voltage (V)Measured Frequency (Hz)Measured Power (W)Measured Power factorTest Time (s)
Test 1:196.047.02677.51.00024
Test 2:196.047.52684.71.0005485
Test 3:253.451.52988.71.0005457
Test 4:253.452.02989.51.000982
Test 5:230.550.02988.51.0005406
Test 6:195.5Ramp range: 47.0 Hz to 52.0 HzTest frequency ramp: +1 Hzs⁻¹Test Duration: 5.05sConfirm no trip: no trip
253.0Ramp range: 52.0 Hz to 49.0 HzTest frequency ramp: -1 Hzs⁻¹Test Duration: 3.00sConfirm no trip: no trip

2. Power Quality – Harmonics

Status: P

These tests should be carried out as specified in BS EN 61000-3-2. The chosen test should be undertaken with a fixed source of energy at two power levels a) between 45 and 55% and b) at 100% of Registered Capacity. The test requirements are specified in Annex A1 A.1.3.1 (Inverter connected) or Annex A2 A.2.3.1 (Synchronous).

Model: GW700-XS-30

Micro-generator tested to BS EN 61000-3-2

Micro-generator rating per phase (rpp): 0.7 kW

For 3-phase Micro-generators, tick this box if harmonic measurements are identical for all three phases. If the harmonics are not identical for each phase, please replicate this section with the results for each phase. Single phase PV inverter

Harmonic cAt 45-55% of Registered Capacity
Measured Value MV in Amps
100% of Registered Capacity
Measured Value MV in Amps
Limit in BS EN 61000-3-2 in AmpsHigher limit for odd harmonics 21 and above
20.0200.0341.080
30.0400.0232.300
40.0060.0100.430
50.0420.0281.140
60.0090.0080.300
70.0430.0120.770
80.0110.0070.230
90.0490.0140.400
100.0120.0050.184
110.1150.0450.330
120.0090.0040.153
130.0520.0480.210
140.0080.0050.131
150.0340.0500.150
160.0080.0060.115
170.0270.0470.132
180.0090.0050.102
190.0240.0440.118
200.0090.0050.092
210.0130.0400.1070.160
220.0090.0050.084
230.0130.0360.0980.147
240.0090.0050.077
250.0160.0340.0900.135
260.0090.0040.071
270.0200.0310.0830.124
280.0090.0040.066
290.0240.0290.0780.117
300.0090.0040.061
310.0300.0270.0730.109
320.0080.0040.058
330.0320.0240.0680.102
340.0080.0040.054
350.0300.0220.0640.096
360.0070.0040.051
370.0260.0200.0610.091
380.0060.0030.048
390.0240.0170.0580.087
400.0060.0030.046

Model: GW3000-XS-30

Micro-generator tested to BS EN 61000-3-2

Micro-generator rating per phase (rpp): 3 kW

For 3-phase Micro-generators, tick this box if harmonic measurements are identical for all three phases. If the harmonics are not identical for each phase, please replicate this section with the results for each phase. Single phase PV inverter

Harmonic cAt 45-55% of Registered Capacity
Measured Value MV in Amps
100% of Registered Capacity
Measured Value MV in Amps
Limit in BS EN 61000-3-2 in AmpsHigher limit for odd harmonics 21 and above
20.0170.0191.080
30.0320.0592.300
40.0050.0090.430
50.0360.0431.140
60.0050.0060.300
70.0150.0150.770
80.0040.0040.230
90.0140.0220.400
100.0040.0040.184
110.0350.0560.330
120.0030.0030.153
130.0240.0450.210
140.0030.0030.131
150.0190.0360.150
160.0030.0030.115
170.0140.0220.132
180.0030.0030.102
190.0130.0210.118
200.0030.0030.092
210.0110.0150.1070.160
220.0030.0030.084
230.0110.0130.0980.147
240.0020.0030.077
250.0090.0130.0900.135
260.0020.0030.071
270.0090.010.0830.124
280.0020.0020.066
290.0070.010.0780.117
300.0020.0020.061
310.0060.0090.0730.109
320.0020.0020.058
330.0060.0080.0680.102
340.0020.0020.054
350.0050.0080.0640.096
360.0020.0020.051
370.0040.0060.0610.091
380.0010.0020.048
390.0030.0070.0580.087
400.0010.0020.046

Note: The higher limits for odd harmonics 21 and above are only allowable under certain conditions, if these higher limits are utilised please state the exemption used as detailed in part 6.2.3.4 of BS EN 61000-3-2 in the box below.

3. Power Quality – Voltage fluctuations and Flicker

Status: P

These tests should be undertaken in accordance with EREC G98 Annex A1 A.1.3.3 (Inverter connected) or Annex A2 A.2.3.3 (Synchronous). The standard test impedance is 0.4 Ω for a single phase Micro-generating Plant (and for a two phase unit in a three phase system) and 0.24 Ω for a three phase Micro-generating Plant (and for a two phase unit in a split phase system). Please ensure that both test and standard impedance are completed on this form. If the test impedance (or the measured impedance) is different to the standard impedance, it must be normalised to the standard impedance as follows (where the Power Factor of the generation output is 0.98 or above): d max normalised value = (Standard impedance / Measured impedance) x Measured value. Where the Power Factor of the output is under 0.98 then the X to R ratio of the test impedance should be close to that of the standard impedance. The stopping test should be a trip from full load operation. The duration of these tests needs to comply with the particular requirements set out in the testing notes for the technology under test. The test date and location must be declared.

Test start date: 2023-11-07

Test end date: 2023-11-07

Test location: No.99, Hongye Road, Suzhou Industrial Park, Suzhou, Jiangsu, P.R. China

Model: GW3000-XS-30

Type: Single Phase

StartingStoppingRunning
d(max)d(c)d(t)d(max)d(c)d(t)PstPlt 2 hours
Measured Values at test impedance0.1450.07700.1400.07700.140.11
Normalised to standard impedance0.1450.07700.1400.07700.140.11
Normalised to required maximum impedanceN/AN/AN/AN/AN/AN/AN/AN/A
Limits set under BS EN 61000-3-114%3.3%3.3%4%3.3%3.3%1.00.65

Test Impedance: R = 0.4 Ω, Xl = 0.25 Ω

Standard Impedance: R = 0.24 * (0.4 ^) Ω, Xl = 0.15 * (0.25 ^) Ω

Maximum Impedance: R = N/A #, Xl = N/A #

*Applies to three phase and split single phase Micro-generators. Delete as appropriate.

^ Applies to single phase Micro-generators and Micro-generators using two phases on a three phase system. Delete as appropriate.

4. Power quality – DC injection

Status: P

This test should be carried out in accordance with A 1.3.4 as applicable. The % DC injection ("as % of rated AC current" below) is calculated as follows: % DC injection = Recorded DC value in Amps / base current where the base current is the Registered Capacity (W) / 230 V. The % DC injection should not be greater than 0.25%.

Model: GW3000-XS-30

Type: Single Phase

Test power level20%50%75%100%
Recorded DC injection value in Amps27.2mA30.2mA29.32mA27.46mA
as % of rated AC current0.21%0.23%0.22%0.21%
Limit0.25%0.25%0.25%0.25%

Model: GW700-XS-30

Type: Single Phase

Test power level20%50%75%100%
Recorded DC injection value in Amps5.11 mA7.51 mA7.35 mA7.53 mA
as % of rated AC current0.17%0.247%0.242%0.247%
Limit0.25%0.25%0.25%0.25%

5. Power Factor

Status: P

This test shall be carried out in accordance with A.1.3.2 and A.2.3.2 at three voltage levels and at Registered Capacity and the measured Power Factor must be greater than 0.95 to pass. Voltage to be maintained within ±1.5% of the stated level during the test.

Model: GW3000-XS-30

Voltage0.94 pu (216.2 V)1 pu (230 V)1.1 pu (253 V)
Measured value1.0001.0001.000
Power Factor Limit>0.95>0.95>0.95

Model: GW700-XS-30

Voltage0.94 pu (216.2 V)1 pu (230 V)1.1 pu (253 V)
Measured value0.9990.9990.998
Power Factor Limit>0.95>0.95>0.95

6. Protection – Frequency tests

Status: P

These tests should be carried out in accordance with Annex A1 A.1.2.3 (Inverter connected) or Annex A2 A.2.2.3 (Synchronous). For trip tests, frequency and time delay should be stated. For "no trip tests", "no trip" can be stated.

Model: GW3000-XS-30

FunctionSettingTrip test"No trip tests"Confirm no trip
FrequencyTime delayFrequency / time
U/F stage 147.5 Hz47.4020.10 s47.7 Hz30 sNo trip
U/F stage 247.0 Hz46.900.548 s47.2 Hz19.5 sNo trip
46.8 Hz0.45 sNo trip
O/F52.0 Hz52.020.540 s51.8 Hz120.0 sNo trip
52.2 Hz0.45 sNo trip

Note: For frequency trip tests the frequency required to trip is the setting ±0.1 Hz. In order to measure the time delay a larger deviation than the minimum required to operate the projection can be used. The "No trip tests" need to be carried out at the setting ±0.2 Hz and for the relevant times as shown in the table above to ensure that the protection will not trip in error.

7. Protection – Voltage tests

Status: P

These tests should be carried out in accordance with Annex A1 A.1.2.2 (Inverter connected) or Annex A2 A.2.2.2 (Synchronous). For trip tests, voltage and time delay should be stated. For "no trip tests", "no trip" can be stated.

Model: GW3000-XS-30

Type: Single Phase

FunctionSettingTrip test"No trip tests"Confirm no trip
VoltageTime delayVoltageTime delayVoltage / time
U/V0.8 pu (184 V)182.22 V2.500 s188 V5.0 sNo trip
180 V2.45 sNo trip
O/V stage 11.14 pu (262.2 V)262.21 V1.028 s258.2 V5.0 sNo trip
O/V stage 21.19 pu (273.7 V)273.69 V0.500 s269.7 V0.95 sNo trip
277.7 V0.45 sNo trip

Note: For Voltage tests the Voltage required to trip is the setting ±3.45 V. The time delay can be measured at a larger deviation than the minimum required to operate the protection. The No trip tests need to be carried out at the setting ±4 V and for the relevant times as shown in the table above to ensure that the protection will not trip in error.

8. Protection – Loss of Mains test

Status: P

For PV Inverters shall be tested in accordance with BS EN 62116. Other Micro-generators should be tested in accordance with A.2.2.4 at 10%, 55% and 100% of rated power. For test condition A, EUT output = 100 % Pn, test condition B, EUT output = 50 % to 66 % Pn, and test condition C, EUT output = 25 % to 33 % Pn.

Model: GW3000-XS-30

For Inverters tested to BS EN 62116 the following sub set of tests should be recorded in the following table.

The Loss of Mains test section details various test conditions (Balance and Imbalance) performed on the GW3000-XS-30 inverter at different power levels (33%, 66%, 100%). It records parameters such as trip time, PEUT, reactive load, PAC, QAC, run-on time, power output, actual VDC, Qf, and remarks for each test. The limit for trip time is 0.5s.

9. Protection – Frequency change, Vector Shift Stability test

Status: P

This test should be carried out in accordance with EREC G98 Annex A1 A.1.2.6 (Inverter connected) or Annex A2 A.2.2.6 (Synchronous). Confirmation is required that the Micro-generating Plant does not trip under positive / negative vector shift.

Model: GW3000-XS-30

Start FrequencyChangeConfirm no trip
Positive Vector Shift49.0 Hz+50 degreesNo trip
Negative Vector Shift50.0 Hz-50 degreesNo trip

10. Protection – Frequency change, RoCoF Stability test

Status: P

The requirement is specified in section 11.3, test procedure in Annex A.1.2.6 (Inverter connected) or Annex A2 A.2.2.6 (Synchronous). Confirmation is required that the Micro-generating Plant does not trip for the duration of the ramp up and ramp down test.

Model: GW3000-XS-30

Ramp rangeTest frequency ramp:Test DurationConfirm no trip
49.0 Hz to 51.0 Hz+0.95 Hzs⁻¹2.15 sNo trip
51.0 Hz to 49.0 Hz-0.95 Hzs⁻¹2.10 sNo trip

11. Limited Frequency Sensitive Mode – Over frequency test

Status: P

This test should be carried out in accordance with A.1.2.9. The test should be carried out using the specific threshold frequency of 50.4 Hz and Droop of 10%. The measurement tolerances are contained in A.1.2.9.

Model: GW3000-XS-30

Alternatively, simulation results should be noted below:

Test sequence at Registered Capacity >80%

Test sequenceMeasured Active Power Output (W)Frequency (Hz)Calculated droop (%)Primary Power SourceActive Power Gradient
Step a) 50.00 Hz ±0.01 Hz2988.4950.00--Photovoltaic-
Step b) 50.45 Hz ±0.05 Hz2956.2050.459.18array-
Step c) 50.70 Hz ±0.10 Hz2799.7550.709.52simulator-
Step d) 51.15 Hz ±0.05 Hz2529.4151.159.79-
Step e) 50.70 Hz ±0.10 Hz2799.1650.709.49-
Step f) 50.45 Hz ±0.05 Hz2955.7050.459.03-
Step g) 50.00 Hz ±0.01 Hz2986.6250.00---

Test sequence at Registered Capacity 40-60%

Test sequenceMeasured Active Power Output (W)Frequency (Hz)Calculated droop (%)Primary Power SourceActive Power Gradient
Step a) 50.00 Hz ±0.01 Hz1499.2250.00--Photovoltaic-
Step b) 50.45 Hz ±0.05 Hz1466.5050.459.05array-
Step c) 50.70 Hz ±0.10 Hz1310.6650.709.52simulator-
Step d) 51.15 Hz ±0.05 Hz1039.5651.159.78-
Step e) 50.70 Hz ±0.10 Hz1310.5750.709.52-
Step f) 50.45 Hz ±0.05 Hz1466.8750.459.15-
Step g) 50.00 Hz ±0.01 Hz1499.9350.00---

The frequency at each step should be maintained for at least one minute and the Active Power reduction in the form of a gradient determined and assessed for compliance with paragraph 11.2.3. The Droop should be determined from the measurements between 50.4 Hz and 51.15 Hz. The allowed tolerance for the frequency measurement shall be ± 0.05 Hz. The allowed tolerance for Active Power output measurement shall be ±10% of the required change in Active Power. The resulting overall tolerance range for a nominal 10% Droop is +2.8% and – 1.5%.

12. Power output with falling frequency test (For PV Inverter)

Status: P

This test should be carried out in accordance with A.1.2.7.

Model: GW3000-XS-30

Test sequenceMeasured Active Power Output (W)Frequency (Hz)Primary power source
Test a) 50 Hz ± 0.01 Hz2989.3150.00Photovoltaic array simulator
Test b) Point between 49.5 Hz and 49.6 Hz2987.7149.60Photovoltaic array simulator
Test c) Point between 47.5 Hz and 47.6 Hz2988.2647.60Photovoltaic array simulator

13. Re-connection timer

Status: P

Model: GW3000-XS-30

Test should prove that the reconnection sequence starts after a minimum delay of 20 s for restoration of voltage and frequency to within the stage 1 settings of Table 2. Both the time delay setting and the measured delay should be provided in this form; both should be greater than 20 s to pass. Confirmation should be provided that the Micro-generating Plant does not reconnect at the voltage and frequency settings below; a statement of “no reconnection” can be made.

Time delay settingMeasured delayChecks on no reconnection when voltage or frequency is brought to just outside stage 1 limits of Table 10.1.
At 1.16 pu (266.2 V)At 0.78 pu (180.0 V)At 47.4 HzAt 52.1 Hz
Confirmation that the Micro-generator does not re-connect.40 s42 sNo ReconnectionNo ReconnectionNo ReconnectionNo Reconnection
Recover to normal operation range after confirmation of no connectionYesYesYesYes
Confirmation that the Power Generating Module shall reconnectReconnection after 42 sReconnection after 42 sReconnection after 42 sReconnection after 42 s

14. Fault level contribution

Status: P

These tests shall be carried out in accordance with EREC G98 Annex A1 A.1.3.5 (Inverter connected) and Annex A2 A.2.3.4 (Synchronous). Please complete each entry, even if the fault contribution is zero.

Model: GW3000-XS-30

For machines with electro-magnetic output

ParameterSymbolValueTime after faultVoltsAmps
Peak Short Circuit currentipN/A20ms56.0V0.8A
Initial Value of aperiodic currentAN/A100ms52.4V3.61A
Initial symmetrical short-circuit current*IkN/A250ms51.3V10.84A
Decaying (aperiodic)iDCN/A500ms51.0V12.29A
ParameterSymbolValueTime to tripIn seconds
component of short circuit current*X/RN/A0.791S
Reactance/Resistance Ratio of source*

For rotating machines and linear piston machines the test should produce a 0 s – 2 s plot of the short circuit current as seen at the Micro-generator terminals.

* Values for these parameters should be provided where the short circuit duration is sufficiently long to enable interpolation of the plot.

15. Logic interface (input port)

Status: P

Confirm that an input port is provided and can be used to reduce the Active Power output to zeroYes
Provide high level description of logic interface, e.g. details in 9.4.3 such as AC or DC signal (the additional comments box below can be used)Yes

16. Self-Monitoring solid state switching

Status: P

No specified test requirements. Refer to EREC G98 Annex A1 A.1.3.6 (Inverter connected).

It has been verified that in the event of the solid state switching device failing to disconnect the Micro-generator, the voltage on the output side of the switching device is reduced to a value below 50 V within 0.5 s.

Confirmation: Yes

17. Cyber security

Status: P

Confirm that the Manufacturer or Installer of the Micro-generator has provided a statement describing how the Micro-generator has been designed to comply with cyber security requirements, as detailed in 9.7.

Confirmation: Yes, Manufacturer's declaration provided.

Additional comments

The inverter provides a logical interface that can be operated via an external switch or contactor to reduce the active power output to zero. Users can install the switch connected to port 7 and port 8 of the inverter and just need control the switch signal causing the switch to open or short. When the switch is closed, the inverter will operate normally. When the switch is opened, the inverter will cease to export active power within 5 seconds.

Port Diagram Description: The diagram shows various ports on the inverter. Key ports include:

PDF preview unavailable. Download the PDF instead.

GW XS-G3 Certificate-G98 Microsoft Word 适用于 Microsoft 365

Related Documents

Preview GoodWe XS Series G3 Grid-Tied PV Inverter User Manual
Comprehensive user manual for the GoodWe XS Series G3 Grid-Tied PV Inverter (0.7-3.3kW). Covers installation, electrical connection, commissioning, troubleshooting, and maintenance for trained professionals.
Preview GoodWe XS G3 Series Solar Inverter Technical Specifications
Comprehensive technical specifications for the GoodWe XS G3 Series solar inverters, covering models from GW700-XS-30 to GW3300-XS-30. Details include input voltage, output power, efficiency ratings, protection features, and general operating data.
Preview GoodWe XS G3 Grid-Tie Inverter User Manual
User manual for the GoodWe XS G3 series Grid-Tie photovoltaic inverter, covering installation, electrical connection, commissioning, troubleshooting, and maintenance. Includes safety precautions, product overview, and technical specifications.
Preview GoodWe XS G3 Series Solar Inverters: High Efficiency and Compact Design
Explore the GoodWe XS G3 Series of single-phase solar inverters, offering high efficiency, compact design, and advanced features for residential solar energy generation. Available in models from 0.7kW to 3.3kW.
Preview GoodWe EU Declaration of Conformity for Grid-Tied PV Inverters
This document is the EU Declaration of Conformity for GoodWe's GW700-XS through GW3000N-XS series of grid-tied PV inverters. It confirms compliance with relevant Union harmonization legislation and directives, including those related to radio equipment, hazardous substances, electromagnetic compatibility, and low voltage.
Preview GoodWe Grid-tied PV Inverter EU Declaration of Conformity
This document contains the EU Declaration of Conformity for GoodWe Technologies Co., Ltd. Grid-tied PV Inverters, including models GW700-XS through GW3000-XS series, confirming compliance with relevant EU harmonisation legislation and directives such as RED, RoHS, EMC, and LVD.
Preview GoodWe XS G3 Series Solar Inverters - High Efficiency and Reliability
Discover the GoodWe XS G3 series of solar inverters, offering high efficiency, intelligent monitoring, and robust safety features. These compact and lightweight inverters are ideal for residential solar systems, providing reliable power generation and advanced protection.
Preview GoodWe Inverters Product Certificate - Lenor Colombia S.A.S.
Official product certificate issued by Lenor Colombia S.A.S. for GoodWe Inverters, detailing product references, manufacturer information, and compliance with Colombian regulations (RETIE).