Danfoss Solenoid Coil for Control in Potentially Explosive Areas - Type BI
Installation Guide
This guide provides instructions for the installation of the Danfoss Solenoid Coil Type BI, designed for use in potentially explosive areas.
Identification:
- Green/Yellow cord for earthing
- Week and date of manufacturing
- External earth terminal
- Code number
- Voltage
- Approval/Certificate number
- Frequency
- Ambient temperature range
- Country of manufacturing
- Approval logos
EX Certifications:
- Ex mb IIC T4 Gb
- IECEx ULD 21.0024X
- UL 21 ATEX 2606X
- UL21UKEX2374X
Coil Installation Steps:
- Ensure the solenoid coil is protected against impact during use.
- Protect the coil against direct sunlight and other ultraviolet sources.
- Disconnect the power before dismounting the coil.
- Install the coil and cable according to IEC/EN/ EN BS 60079-14.
- The cable supplied with the solenoids must not be handled or flexed, and shall be protected against impact if the ambient temperature is below 0 °C.
- Install the coils in the orientation shown in the diagrams.
- The permitted process medium temperature range is -40 °C to +90 °C.
- The capacitance of exposed, isolated, metallic parts is 7pF.
- The cable is only for fixed installation and the minimum bending diameter for fixed installation: r ≥ 35 mm [arrow].
- The cable jacket material is PVC.
- The cable operating temperature range is -40 – 90 °C.
- The product is provided with a yellow/green PE Conductor as well as an external earth terminal. These shall not be used simultaneously.
- If the external earth connection is connected to earth or bonding system, the PE Conductor must be cut off, isolated and not connected.
- If the PE Conductor is connected to earth, the external earth terminal must be left without any connection.
- For the external earth terminal, the size of the earth core shall be minimum 4 mm² and the installer shall use a suitable method e.g. crimp terminal to ensure secureness of the external earth connection. The screw for external PE shall be mounted with 1.2 Nm ± 0.2. The external earth conductors shall be physically secured close to the coil connection to ensure that the conductors cannot be readily loosened or twisted.
- The end user must ensure the earthing of the coil is maintained.
- Non-detachable cords method Z repairing not allowed. If the coil failed, it must be replaced by a new coil.
Valve Combinations:
Valves works with A:
- EVM-EVRF-EVRP-EVRB
- AKV, AKVA
- EVR 2, 3, 6
- EVRS(T) 3
- EV210BW, EV210B
- ICF
- ICLX
- VDH, VDHT EAM, VDHT
- VPH
- EVRA 3, EVRA(T) 3
Valves works with B:
- EV220B 6, 10, 12, 14, 18, 22
- EV221BW
- EV251B
- EVRS(T) 10-20
- ICF
- EV227B
- EVRA 10, 15, 20 (Before 1996)
- EVRA(T) 10, 15, 20 (Before 1996)
Valves works with both:
- EVR 10, 15, 20, 25, 32, 40
- EV220B, EV220BW
- EV220B 65, 80, 100
- EV250BW, EV250B
- VDH 30 EC
- EV222B
- EV224B
- EVRA 10, 15, 20, 25, 32, 40 (After 1996)
- EVRA(T) 10, 15, 20 (After 1996)
Application and Specification:
Nominal Voltage [V] | Frequency [Hz] | Nominal Current [A] | Code no. with cover and bottom | Code no. with cover and frame | ||
---|---|---|---|---|---|---|
5m cable | 10m cable | 5m cable | 10m cable | |||
24 | DC | 0.46 | 018Z8589 | 018Z8569 | 018Z8596 | 018Z8575 |
24 | 50/60 | 0.48 | 018Z8588 | 018Z8568 | 018Z8595 | 018Z8574 |
110 | 50/60 | 0.102 | 018Z8587 | 018Z8567 | 018Z8593 | 018Z8573 |
230 | 50/60 | 0.053 | 018Z8586 | 018Z8566 | 018Z8592 | 018Z8572 |
240 | 50/60 | 0.047 | 018Z8585 | 018Z8565 | 018Z8591 | 018Z8571 |
Specifications:
- Ambient temp.: -40 °C ≤ Tambient ≤ +40 °C
- Media: -40 °C < Tmedia < +90 °C
- Humidity: 0 - 97%
- Voltage: +6 / -10%
- Connection: 3-Wire cable 3 x 0.75mm²
- Weight: 1.0 kg
- Protection degree: IP67 (Evaluated by Danfoss)
- Pollution degree: 3 (EN60730-1)
- Over voltage category: II (2.5 kV)
- Mode of operation: Type 1 action (EN60730-1)
- Purpose of control: Minimum wire gauge > 4mm²
- External earth wire: incorporated class I control
Safety Instruction:
All national safety regulations must be complied with in connection with installation, start-up and operation of Danfoss solenoid valves. Furthermore, the requirements of the declaration of conformity and national regulations for installation in explosion areas must be followed. Disregarding such regulations involves a risk of serious personal injury or extensive material damage. Work in connection with the solenoid valve must be performed only by suitable qualified persons.
Safety requirements for use in explosive atmospheres are fulfilled through compliance certificates:
- Ex mb IIC T4 Gb
- IECEx ULD 21.0024X
- UL 21 ATEX 2606X
- UL21UKEX2374X
Specific Conditions of Safe Use:
- The solenoid coil shall be protected against impact during use.
- Protect the coil against direct sunlight and other ultraviolet sources.
- Disconnect the power before dismounting the coil.
- Install the coil and cable according to IEC/EN/ EN BS 60079-14.
- The cable supplied with the solenoids must not be handled or flexed, and shall be protected against impact if the ambient temperature is below 0 °C.
- The coils must be installed in the orientation shown in page 1.
- The permitted process medium temperature range is -40 °C to +90 °C.
- The capacitance of exposed, isolated, metallic parts is 7pF.
UK-CA Contact Address:
Danfoss Ltd.
22 Wycombe End,
HP9 1NB, GB
CE Contact Address:
Danfoss A/S
DK-6430 Nordborg
Denmark
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
Related Documents
![]() |
Danfoss Solenoid Valve Manufacturer's Declaration - Conformity and Specifications Official Manufacturer's Declaration from Danfoss A/S for Solenoid Valves (EVR, EVRH, EVRP, etc.), detailing product conformity, technical specifications, and compliance with relevant EU directives and international standards for refrigeration and air conditioning. |
![]() |
Danfoss ICLX 100-150 2-Step Solenoid Valve Installation Guide Comprehensive installation, maintenance, and technical specifications for the Danfoss ICLX 100-150 2-step solenoid valve, covering operation, assembly, and troubleshooting. |
![]() |
Danfoss Industrial Refrigeration Field Service Guide: Installation and Operation Comprehensive installation and operation guide for Danfoss industrial refrigeration components, including valves, regulators, controls, and sensors. Features product details, service procedures, and technical specifications. |
![]() |
Danfoss Valve Station Spare Parts and Accessories: ICF Series Comprehensive list of spare parts and accessories for Danfoss ICF valve stations, including ICF 15, ICF EVRAT, ICF 20, ICF SS 20, ICF 25, ICF SS 25, ICF 50, and ICF 65 models. Find part codes, descriptions, and figure references for various modules, gaskets, and components. |
![]() |
Danfoss EVR 2 - EVR 22 Solenoid Valve Installation Guide Installation guide for Danfoss EVR 2 to EVR 22 solenoid valves, covering NC/NO types, refrigerants, mounting, electrical connections, and coil handling. |
![]() |
Danfoss EVR 2 - EVR 22 Solenoid Valve Installation Guide Comprehensive installation guide for Danfoss EVR 2 to EVR 22 solenoid valves, covering assembly, disassembly, mounting, and operational notes for various refrigerants and system pressures. |
![]() |
Danfoss EVR 2-22 Solenoid Valve Installation Guide Comprehensive installation guide for Danfoss EVR 2 through EVR 22 series solenoid valves (Version 2). Covers refrigerant compatibility, pressure ratings, mounting instructions, disassembly and assembly procedures, and manual operation. |
![]() |
Danfoss Solenoid Valve Types EVR 2 – EVR 22 (Version 2) Installation Guide Installation guide for Danfoss Solenoid Valves, Types EVR 2 through EVR 22 (Version 2). Covers refrigerant compatibility, operating conditions, mounting, identification, and manual operation for refrigeration systems. |