Pulsar GD400BN 4000 Watt Dual Fuel Inverter Generator Operator's Manual

Introduction

Thank you for choosing Pulsar Products! This manual provides instructions on how to operate and use the generator safely and correctly. It is essential to read and understand this manual before using the generator. For any questions, contact Pulsar Support at 866.591.8921 (M-F) or email support@pulsar-products.com BEFORE using the generator.

All details and images in this Operator's Manual are believed to be accurate at the time of publication. Pulsar Products reserves the right to make updates to this manual at any time. This manual is a permanent part of the generator set and should be included if the generator is resold.

Safety Warnings and Notices

Throughout this manual and on generator decals, various safety notices may appear. These Safety Warnings alert users to potential hazards that could cause death, injury, or property damage. The decals use one of four words: "DANGER", "WARNING", "CAUTION", and "NOTICE". Definitions are as follows:

⚠ DANGER

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

⚠ WARNING

WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

⚠ CAUTION

CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.

NOTICE

Failure to follow the instruction may result in damage to the generator and other property.

Safety Instructions

Before operating the generator, users must read and understand the Operator's Manual and familiarize themselves with safe operation practices.

Names of Components

Familiarize yourself with the generator's parts for safe operation.

(Illustration: Top-down and side views of the generator with labels pointing to each component.)

Control Panel

The control panel features various switches, indicators, and outlets:

To avoid damage, DO NOT connect or disconnect parallel cables while the unit is running.

(Illustration: Detailed diagram of the control panel with all elements labeled.)

Control Functions

Multi-Switch

(Illustration: Diagram of the Multi-Switch knob with OFF, RUN, START/CHOKE positions.)

Overload Indicator (Red)

When the overload indicator illuminates, the generator has detected excess electrical load, and the circuit breaker may open (trip). If the overload indicator illuminates and the generator has no electrical output, perform the following:

  1. Disconnect all electrical loads and shut down the generator.
  2. Reduce total draw of electrical loads connected to less than rated output.
  3. Confirm no debris blocks the air inlet; correct as necessary.
  4. Ensure all circuit breakers are pushed in.
  5. Restart the engine and add electrical load in gradual steps.

Tip: When using electrical equipment with high starting current (e.g., compressors, saws, pumps), the overload indicator may illuminate for a few seconds, which is normal.

Oil Indicator (Red)

When the engine oil level drops too low, the engine automatically shuts down, and the oil alarm indicator illuminates. The engine can be restarted only after the engine oil is filled correctly.

Tip: If the engine will not start, turn the Multi-Switch knob to "RUN" position and pull the recoil handle. If the oil indicator flashes for a few seconds, the oil volume is insufficient; fill oil to the dipstick high mark and restart.

AC Indicator (Green)

The AC indicator illuminates when electrical output is stable.

Energy Saving (Idle) Switch

AC Circuit Breaker

If the total AC load exceeds the rated current, the AC circuit breaker will open (trip) and the button will pop out. In this case, disconnect all loads, restart the generator, and push in the AC circuit breaker(s).

Grounding Terminal

If grounding is required by code or application, follow the guidelines on page 10.

Preparing Your Generator

Engine Oil

The generator ships without engine oil. Do not attempt to start it without sufficient engine oil in the crankcase.

  1. Place the generator on a flat, stable surface.
  2. Unscrew the knob to remove the oil access cover.
  3. Unscrew the oil dipstick.
  4. Use a funnel to add 12 fluid ounces (0.35L) of 10w-30 engine oil to the crankcase. Verify oil level with the dipstick.
  5. Reassemble the oil access cover and tighten the knob.

(Illustration: Sequence showing removing oil access cover, dipstick, and adding oil.)

Pre-use Inspection

NOTICE

Even when not in use, the generator is potentially hazardous. Follow the checklist below before starting. If any problems are found, do not use the generator until repaired by an authorized Pulsar Products Service Center.

Fuel

Check fuel level; add if necessary.

Oil

Check oil level; add if necessary. Check for any oil leaks.

Gasoline

⚠ DANGER

Gasoline is highly flammable and toxic. Users must read and understand ALL safety instructions before fueling the generator.

Do not overfill the fuel tank! Heat and vibration can cause fuel to leak from an over-filled fuel tank.

After refueling, confirm that the fuel tank cap has been tightened.

NOTICE

Remove the fuel tank cap and add gasoline to the red horizontal line (maximum fuel level indicator inside the tank). After fueling, wipe up any gasoline residue with a soft cloth to prevent damage to the plastic enclosures.

Fuel tank capacity: 1 US gallon.

Propane (LPG)

⚠ DANGER

Propane is highly flammable and potentially explosive. Users must read and understand ALL safety instructions before connecting propane to the generator.

Never bring a propane tank inside the home or any enclosed structure.

After connection, check for leaks: Open the tank supply valve, apply soapy water to the gas fittings, and ensure there are no bubbles.

Propane has an added odorant (sulfur/rotten eggs smell). If this smell is detected, close the propane tank valve at once, then find and correct the problem before attempting to restart the generator.

Starting The Generator

How to Start A Cold Engine with Gasoline

  1. Place generator on a level surface.
  2. Disconnect all electrical loads, including parallel cables, from the generator.
  3. Set the Upper Left "Low Idle" rocker switch to 'OFF'.
  4. Set the Upper Right "Fuel Source" rocker switch to "GASOLINE".
  5. Turn the Multi-Switch to 'START' (choke) to start a cold engine.

Tip: Turn the Multi-Switch to 'RUN' to restart a warm engine.

⚠ CAUTION

To prevent possible injury, follow these steps below for safe recoil engine starting:

  1. Gently pull the recoil handle out until resistance (engine compression) is felt. (Illustration: Person gently pulling recoil handle until resistance is met.)
  2. Let the recoil handle retract completely. (Illustration: Recoil handle retracting.)
  3. Grasp the top handle securely and pull the recoil handle swiftly and completely; the engine should start. (Illustration: Person pulling recoil handle swiftly.)

With the engine started, ensure the Multi-Switch is in the 'RUN' position, then set the "Low Idle" rocker switch to your load-based preference.

How to Start Cold Engine with Propane

  1. Place generator on a level surface.
  2. Disconnect all electrical loads, including parallel cables, from the generator.
  3. Set the Upper Left "Low Idle" rocker switch to 'OFF'.
  4. Set the Upper Right "Fuel Source" rocker switch to "PROPANE".
  5. Connect the propane regulator to the propane tank. (Illustration: Propane tank connected to propane hose.)
  6. Connect the propane hose to the front panel propane inlet; tighten until snug. (Illustration: Propane hose connecting to the LPG INLET on the generator.)
  7. Open the propane tank valve. Be aware of any smell of gas and apply soapy water to the fittings to check for leaks. Only proceed if there are no leaks.
  8. Turn the Multi-Switch to 'START' (choke) to start a cold engine.

Tip: Turn the Multi-Switch to 'RUN' to restart a warm engine.

  1. Follow the three steps below for a safe recoil engine start:
⚠ CAUTION

To prevent possible injury, follow these steps below for safe recoil engine starting:

  1. Gently pull the recoil handle out until resistance (engine compression) is felt. (Illustration: Person gently pulling recoil handle until resistance is met.)

Shutting Down the Generator

  1. Turn the Multi-Switch to "OFF" position. (Illustration: Multi-Switch knob in OFF position.)
  2. After the generator has completely cooled down, remove the propane hose if applicable and store the generator in a cool, dry, sheltered storage area.
  3. Remove or consume all untreated gasoline if planning to store the generator longer than 3 months.

Connecting Loads to the Generator

  1. Start the engine.
  2. Move Energy Saving switch to "OFF".
  3. Insert the plug(s) into AC outlet(s).
  4. Make sure that AC indicator is illuminated.
  5. Switch on electrical equipment.

Tip: If total load is less than half rated capacity, move the Energy Saving Switch to 'ON'. If the generator supplies power to multiple devices, plug in those devices from largest to smallest according to rated electrical load.

(Illustration: Sequence showing connecting electrical loads to the generator outlets.)

Using the Generator

Operating Range of the Generator

Ideal Atmospheric Conditions

Standard Deration

Generator Grounding

If grounding is required by code or application, follow the guidelines below. If there is any doubt, contact a licensed electrician.

  1. Use grounding wire of minimum 12 gauge.
  2. Connect one end of grounding wire to the grounding bolt on the control panel.
  3. Connect the other end of the grounding wire to a suitable ground point.

(Illustration: Diagram showing grounding bolt on control panel and connection to a ground point.)

Range of Application

Before using the generator, ensure that the total load is within the rated load range of the generator, otherwise the generator may be damaged.

Service and Maintenance

Good maintenance is essential for safe, economical operation and long service life. The maintenance schedule is below:

Maintenance CycleEach WeekBreak-In Maintenance at 1 Month or 20 Hours UseQuarterly Maintenance is every 90 Days or 50 Hours UseAnnual Maintenance or 100 Hours Use
Engine oil - Check - Fill
Engine oil - Replace
Air Cleaner Element - Inspection
Air Cleaner Element - Clean
Air Cleaner Element - Replace
Carburetor Float Bowl - Clean
Spark Plug - Clean - Adjust
Spark Arrester - Clean
Valve Clearance ** - Check - Adjust
Fuel Tank and Fuel Filter ** - Clean
Fuel Hose - InspectionEvery Two Years
Cylinder Head, Piston - Remove Carbon Deposit **Every 125 hours

** These tasks should be completed by an authorized Pulsar service center.

NOTICE

If the generator is used in high temperature or under high load, change the oil every 25 hours. If the generator is used in a dusty or abrasive environment, service the air filter element every 10 hours; replace it every 25 hours. If a maintenance cycle is missed, perform the maintenance as soon as possible per the table above.

⚠ DANGER

Shut down the engine and allow it to cool before performing any service. Place the generator on a flat, stable surface. Remove the spark plug boot to prevent accidental engine start. NEVER USE ANY GENERATOR INDOORS or in any poorly ventilated area. Engine exhaust contains carbon monoxide which can KILL you and others in the area.

Spark Plug

  1. Remove access cover and spark plug boot.
  2. Use the (included) thin-wall T-socket wrench to remove the spark plug by turning it counter-clockwise. (Illustration: Steps for removing spark plug.)
  3. Inspect spark plug for discoloration and remove carbon deposits; replace if necessary.
  4. Adjust the gap 0.7~0.8mm.

Spark Plug # A5RTC, Gap: 0.7-0.8mm.

  1. Install new or serviced spark plug in reverse order.

Spark Plug torque: 12.5 Nm; 110 in lbs.

Tip: If no torque wrench is available, turn the spark plug 1/4 - 1/2 turn after the gasket contacts the cylinder head.

Adjustment of the Carburetor

This carburetor is not adjustable; only maintenance and cleaning are possible. Pulsar Service Center strongly recommends leaving this work to an authorized service center.

Oil Change

⚠ WARNING

Do not drain the oil immediately after turning off the generator; allow it to cool completely before servicing it.

  1. Raise the generator up on support blocks on a flat, stable surface.
  2. Unscrew the knob to remove oil access cover.
  3. Unscrew oil dipstick.
  4. Place an oil pan under the engine, tilt the generator toward the oil pan until all oil has drained; wipe up any spills. (Illustration: Sequence showing tilting generator to drain oil.)
  5. Refill crankcase with 12 ounces (0.35l) 10w-30 engine oil; check with dipstick.
  6. Tighten oil dipstick, replace oil access cover, and tighten the knob.

Air Filter

A dirty air filter can cause poor performance and engine damage. Perform inspection and cleaning per the maintenance schedule on page 11.

  1. Remove screws to remove air filter housing.
  2. Remove foam filter element.
  3. Clean foam filter element with a mild soap solution, rinse well, and let it dry.
  4. Place a few drops of engine oil on the foam filter element and squeeze gently to distribute the oil film evenly.
  5. Reinstall the air filter element in reverse order. (Illustration: Sequence showing air filter removal, cleaning, oiling, and reinstallation.)

Fuel Filter Screen

⚠ DANGER

NEVER approach the generator while smoking or with any ignition source!

  1. Remove fuel tank cap and fuel tank filter screen.
  2. Clean fuel tank filter screen with mild soap and hot water.
  3. Allow filter screen to dry thoroughly and replace it in the fuel tank.
  4. Replace fuel cap tightly. (Illustration: Sequence showing removal and cleaning of fuel filter screen.)

Storage and Transport

Generator Long Term Storage

  1. Turn the Multi-Switch to "OFF" and allow generator to cool completely.
  2. Remove the spark plug boot to prevent accidental engine start.
  3. Remove bolts and the right service access panel.
  4. Using a Phillips screwdriver, open the fuel drain valve on the carburetor and drain remaining fuel into an approved gasoline container.
  5. Tighten the fuel drain valve.
  6. Change engine oil per page 12.
  7. Remove the spark plug and instill one teaspoon (5ml) of new engine oil into the combustion chamber. Pull the recoil a few times to distribute oil, then reinstall the spark plug.
  8. Replace the right service access panel.
  9. Gently pull the recoil handle until resistance is felt, indicating the intake and exhaust valves are closed.
  10. Store the generator in a clean and dry area.

Generator Transport

Pulsar Products recommends that the generator should be empty of fuel when transported unless it is secured in an open truck bed and secured from tipping. In that case, follow the guidelines below:

Troubleshooting

Engine No-Start

Fuel System

  1. No fuel.
  2. Fuel doesn't reach the combustion chamber.
  3. Contaminated or old fuel.
  4. Debris in the fuel valve.
  5. Carburetor is fouled; service carburetor.

Insufficient Engine Oil

Oil level is too low.

Ignition System

  1. Verify Multi-Switch is at 'RUN' or 'CHOKE'.
  2. No spark from ignition coil failure.
  3. Spark plug is fouled; service it per page 12.

Low Compression

  1. Worn out engine.
  2. Cylinder head bolts have loosened; have an authorized Pulsar Service Center re-torque them properly.
  3. Head gasket leak.

Engine Runs, No Power Output

  1. Ensure all circuit breakers are pushed in.
  2. If generator was exposed to moisture or rain, move it to a dry location for several hours.
  3. Vibration may have caused one or more connectors to loosen over time; check with Pulsar Technical Support for guidance.
  4. Check electrical receptacles for damage.
  5. Generator may be overloaded; remove load, shut down, then restart the engine.

Technical Parameters

ItemParameter (148F/P -2)Parameter (164F/P)
Engine Model148F/P -2164F/P
Engine TypeSingle-cylinder, four-stroke, air-cooled, overhead valve, tilted 25° of the center of gasoline engine cylinder
Bore size x Stroke (mm)48.6×4364×45
Displacement (cc)79.7145
Compression Ratio8.7± 0.28.7± 0.2
Cylinder HeadOHVOHV
Cooling ModeForced AirForced Air
Output Power (kW/r/min)2.1/45003.8/4650
Starting MethodRecoil
Fuel Tank Volume1.1 Gallon1 Gallon
Fuel Type and GradeGasoline or Propane
Lubricating Oil Capacity(0.35L)(0.45L)
Lubricating Oil ModelSAE 10w-30SAE 10w-30
Lubrication ModeSplash LubricationSplash Lubrication
Noise dB (at 7m)6263
Rated Power (kW)1.82.8
Rated Voltage (V)120120
Rated Frequency (Hz)6060
Rated Power Factor11
Phase NumberSingle PhaseSingle Phase
MotorBrushless (Permanent Magnet)
Voltage RegulationInverter Regulation
Frequency RegulationInverter Regulation
Overall Dimension18.9"x11.5"x17"18.9"x11.5"x17"
Net Weight40lbs. (18kg)46lbs. (21kg)

Electrical Schematic

This section provides an electrical schematic for the 120V, 60Hz Electrical System. It illustrates the connections between the GENERATOR BLOCK and the CONTROL PANEL BLOCK, detailing components such as the Main Winding, Stepping Motor, Inverter, AC receptacles (125V 20A, 125V 30A), Circuit Breakers (20A, 30A), Paralleling Receptacle, ECO switch, Overload Recovery switch, various indicator lights (AC pilot, Overload, Oil warning), Engine Switch, CO actuators, CO module, Igniter, Spark Plug, Trigger Coil, Oil Sensor, and CO alarm lamp. The schematic includes wire color codes for identification (B: Black, R: Red, Y: Yellow, W: White, Bu: Blue, Br: Brown, G: Green, Gr: Grey, P: Pink, O: Orange).

Models: GD400BN 4000 Watt Dual Fuel Inverter Generator, GD400BN, 4000 Watt Dual Fuel Inverter Generator, Dual Fuel Inverter Generator, Inverter Generator, Generator

File Info : application/pdf, 17 Pages, 5.62MB

PDF preview unavailable. Download the PDF instead.

GD400BN manual 07282022

References

Adobe Illustrator CS5.1 Adobe PDF library 9.90

Related Documents

Preview Pulsar PG4500BiSRCO Inverter Generator Operator's Manual
Operator's manual for the Pulsar PG4500BiSRCO Inverter Generator, covering safety, features, operation, maintenance, and troubleshooting for gasoline and LPG dual-fuel use.
Preview Pulsar 10000 Watt Dual Fuel Generator Owner's Manual PG10000B
Comprehensive owner's manual for the Pulsar 10000 Watt Dual Fuel Generator (Model PG10000B), covering safety, operation, maintenance, troubleshooting, and specifications for both gasoline and LPG use.
Preview Pulsar 9500 Watt Dual Fuel Inverter Generator Operator's Manual
This operator's manual provides comprehensive instructions for the Pulsar PGD95BiSCO 9500 Watt Dual Fuel Inverter Generator, covering safety precautions, operation, maintenance, and troubleshooting.
Preview Pulsar PG4500iSR Inverter Generator Operator's Manual
Comprehensive operator's manual for the Pulsar PG4500iSR gasoline inverter generator, covering safety, features, operation, maintenance, and troubleshooting.
Preview Pulsar PGD40iSCO 4000 Watt Inverter Generator Operator's Manual
Comprehensive operator's manual for the Pulsar PGD40iSCO 4000 Watt Inverter Generator, covering safety instructions, component identification, control functions, preparation, operation, maintenance, troubleshooting, and technical specifications.
Preview Pulsar PG4500iSR Inverter Generator Operator's Manual
This operator's manual provides comprehensive instructions for the Pulsar PG4500iSR Inverter Generator, a portable gasoline-powered unit designed for tools, appliances, camping, lighting, and backup power. Learn about its features, safe operation, maintenance, and troubleshooting for reliable service.
Preview Pulsar PG6580BCO Generator Operator's Manual
Comprehensive operator's manual for the Pulsar PG6580BCO portable generator, covering safety, assembly, operation, maintenance, troubleshooting, and specifications for both gasoline and LPG fuel.
Preview Pulsar PG3500MR Generator Operator's Manual: Safety, Operation, and Maintenance Guide
Comprehensive operator's manual for the Pulsar PG3500MR portable gasoline generator. Covers safety instructions, assembly, operation, maintenance, troubleshooting, and warranty information.