Installation Guide for PHILIPS models including: DDBC320-DALI, 2 Driver Controller

DDBC320-DALI

This Class B digital apparatus complies with Canadian ICES-003: CAN ICES-3(B)/NMB-3(B). Cet appareil numerique de la classe B est conforme a la norme NMB-003 du...

PDF preview unavailable. Download the PDF instead.

DYN DDBC320-DALI II-R02
DDBC320-DALI
DALI-2 Driver Controller

Installation Instructions
Instructions d'installation Installationsanweisungen Instrucciones de instalación Istruzioni per l'installazione Installatie-instructies  

Devices must be installed in an approved enclosure by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.
Les appareils doivent être installés dans un lieu jugé apte, par un électricien qualifié et conformément aux règles et normes locales et nationales en matière d'électricité et de construction.
Die Geräte müssen von einem geprüften Elektriker entsprechend allen nationalen und lokalen Elektro ­ und Bauvorschriften in einem zugelassenen Gehäuse installiert werden.

Los dispositivos se deben instalar en un recinto aprobado por un electricista cualificado de acuerdo a todos los reglamentos eléctricos y de construcción locales y nacionales pertinentes
I dispositivi devono essere installati da un elettricista qualificato in un luogo approvato, in conformità a tutti gli standard e le norme nazionali e locali vigenti in materia di impianti elettrici e costruzioni edilizie.
Apparaten moeten door een erkende elektricien worden geïnstalleerd in een goedgekeurde behuizing in overeenstemming met alle nationale en lokale elektriciteits ­ en bouwvoorschriften en wetgeving.

  
/ 

104 mm (4.09 in) 95 mm (3.74 in)

1A IEC Pollution Degree II

216 mm (8.50 in)

64 mm (2.52 in)

45 mm (1.80 in)

50° C (122° F) 0° C (32° F)

90%

45 mm (1.80 in)

1B

45 mm (1.80 in)

68 mm (2.68 in)

160 mm (6.30 in)

45 mm (1.80 in)

2

Output Ratings/Channel (CH)

Load Type

CH1-CH3

Electronic Ballast Pilot Duty Inrush Current

16 A, 277 V 20 A, 240 V
6 A, 120 V 3 A, 240 V 2.6 A, 277 V
500 A

(UL) (CE)

Output Ratings/Group
CH-CH < 500 V DDBC320-DALI  60A

0.2-5 mm2 24-10 AWG

0.6 Nm 5.5 Lb-in

L

Control Channel Ratings

DALI

 64/Universe

Address- Guaranteed 220 mA

able

Maximum 250 mA

Insulation: basic

 192

x10-16

DALI
L N

DUS...
x34-64

DPMI...

NL SUPPLY

IN OUT CH 1

IN OUT CH 2

IN OUT CH 3

DA- DA+ DA- DA+ DA- DA+ DALI 1 DALI 2 DALI 3

ON

1

2

3

OFF

10

64

11

59

12

54

13

49

14

44

15

39

16

34

3
100-277 V 0.5 A

NL

FELV / Class 2, suitable for Class 1 wiring (UL)

CH1 IN OUT

CH2 IN OUT

CH3 IN OUT

DALI 1 DALI 2 DALI 3 DA- DA+ DA- DA+ DA- DA+

DALI

DALI

DALI

µP

DALI 1 DALI 2 DALI 3

SHLD GND
D+ D+12 V AUX/UL924

IEC Overvoltage Category III 4

1 push ­ On/Off Push and hold 4 secs ­ DALI test Push to cancel test
Link

DALI 1 DALI 2 DALI 3 Ethernet

12 V 300 mA

RJ45

RS-485 DyNet/DMX Rx Ethernet SELV/Class 2 (UL)

Service Switch:
1 push ­ Network ID Push and hold 4 sec ­ Device reset
Service and DALI LED modes
OK OK, Network busy
Fault

5

6

SHLD GND D+ D+12 V AUX/UL924

GND

AUX / UL924

< 20 m

0.3-2.5 mm2  2 A RS-485 DyNet 22-12 AWG

0.4 Nm 3.5 Lb-in

RJ45 Ethernet

7A
Ethernet 7

7B DALI DALI DALI

RS-485 DyNet

Ethernet

DALI DALI DALI RS-485 DyNet

Caution ­ DALI wires are NOT SELV and should never be considered touch safe. Basic insulation or higher is required between DALI wires and mains cabling.
Caution ­ Any modifications not approved by the manufacturer of this device could void the user's authority to operate this device.
FCC and RSS-210 of IC (Industry Canada) Rules ­ This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules and pursuant to RSS210 of the IC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help. Any modifications not approved by the manufacturer of this device could void the user's authority to operate this device.
This Class B digital apparatus complies with Canadian ICES-003: CAN ICES-3(B)/NMB-3(B). Cet appareil numerique de la classe B est conforme a la norme NMB003 du Canada: CAN ICES-3(B)/NMB-3(B).
Installation of a home and building automation and control system shall comply with HD 60364-4-41. The temperature limits and current-carrying capacities for the communication wires specified in HD 384.5.523 shall not be exceeded.

© 2021 Signify Holding. All rights reserved. Specifications are subject to change without notice. No representation or warranty as to the accuracy or completeness of the information included herein is given and any liability for any action in reliance thereon is disclaimed. Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V. All other trademarks are owned by Signify Holding or their respective owners.

www.lighting.philips.com/dynalite
AZZ 531 0821 R02


Adobe PDF Library 15.0 Adobe InDesign 16.3 (Macintosh)