Raychem JBS-100-L-A

Single Entry Power Connection with Light and Junction Box Installation Instructions

DESCRIPTION

The Raychem JBS-100-L-A is a NEMA 4X-rated power connection kit. It is designed for use with Raychem BTV-CR, BTV-CT, QTVR-CT, XTV(R)-CT, HTV-CT and VPL-CT industrial parallel heating cables. The kit includes a plug-in LED light that indicates when the power is supplied to the heating cable circuit.

These kits may be installed at temperatures as low as -40°F (-40°C), and the maximum ambient temperature is 104°F (40°C). For easier installation, store above freezing until just before installation.

For technical support, call Chemelex at (800) 545-6258.

APPROVALS

Hazardous Locations

*For system Temperature Code, see heating cable or design documentation

(1) Except HTV

(2) For HTV-CT only ** Per CE Code Table 18

KIT CONTENTS

Item Qty Description
A 1 Stand assembly
B 1 Core sealer
C 1 Green/yellow tube
D 1 Cable lubricant
E 1 Cable tie
F 1 Lid
G 1 Box with terminal blocks
H 1 JBL-100-R plug-in light module

TOOLS REQUIRED

ADDITIONAL MATERIALS REQUIRED

OPTIONAL MATERIALS

WARNINGS

WARNING: This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all of the installation instructions.

To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of Chemelex, agency certifications, and national electrical codes, ground-fault equipment protection must be used. Arcing may not be stopped by conventional circuit breakers.

Component approvals and performance are based on the use of Chemelex-specified parts only. Do not use substitute parts or vinyl electrical tape.

The black heating cable core and fibers are conductive and can short. They must be properly insulated and kept dry.

Damaged bus wires can overheat or short. Do not break bus wire strands when scoring the jacket or core.

Keep components and heating cable ends dry before and during installation.

Use only fire-resistant insulation materials, such as fiberglass wrap and flame-retardant foam.

CAUTION: HEALTH HAZARD: Prolonged or repeated contact with the sealant in the core sealer may cause skin irritation. Wash hands thoroughly. Overheating or burning the sealant will produce fumes that may cause polymer fume fever. Avoid contamination of cigarettes or tobacco. Consult MSDS VEN 0033 for further information.

CHEMTREC 24-hour emergency telephone: (800) 424-9300

Non-emergency health and safety information: Tel: (800) 545-6258.

AVERTISSEMENT : Ce composant électrique doit être installé correctement pour éviter les risques d'incendie ou de chocs électriques. Lire ces avertissements importants et suivre attentivement toutes les instructions d'installation.

Pour réduire le danger d'incendie causé par un arc électrique entretenu, si le câble chauffant est endommagé ou mal installé, et pour respecter les exigences de Chemelex et celles des codes applicables, il est impératif d'utiliser une protection par disjoncteur différentiel. Les disjoncteurs ordinaires ne sont pas toujours capables de supprimer les arcs électriques.

Les approbations et les performances des composants sont basées sur l'utilisation des pièces Chemelex spécifiées seulement. N'utilisez pas de pièces de rechange ou de ruban isolant en vinyle.

Le noyau et les fibres du câble chauffant noir sont conducteurs et peuvent provoquer un court-circuit. Ils doivent être correctement isolés et gardés à sec.

Les fils omnibus endommagés peuvent surchauffer ou subir un court-circuit. Ne brisez jamais les fils omnibus lorsque vous incisez la gaine ou le noyau.

Maintenez les composants et les extrémités des câbles chauffants secs avant et pendant l'installation.

Les fils omnibus peuvent provoquer un court-circuit s'ils se touchent. Les garder à l'écart les uns des autres.

N'utilisez que des matériaux isolants ininflammables, par exemple une gaine de fibre de verre ou de la mousse ignifuge.

Laissez ces instructions d'installation à l'utilisateur pour qu'il puisse les consulter.

MISE EN GARDE : DANGER POUR LA SANTÉ : Le contact prolongé ou répété avec le produit d'étanchéité du noyau peut provoquer une irritation de la peau. Lavez-vous les mains soigneusement. La surchauffe et la combustion du produit d'étanchéité produira des vapeurs qui peuvent causer la fièvre des vapeurs de polymères. Évitez la contamination des cigarettes ou du tabac. Consultez la fiche technique santé-sécurité (FTSS) VEN 0033 pour obtenir de plus amples informations.

Téléphone en cas d'urgence 24 heures sur 24 de CHEMTREC : (800) 424-9300

Renseignements non urgents en matière de santé et de sécurité : (800) 545-6258.

WARNING: Explosion Hazard- Substitution of Components May Impair Suitablity for Class I Division 2 (Zone 2)

AVERTISSEMENT: Risque d'explosion. La substitution de composants peut rendre ce matériel inacceptable pour les emplacements de Classe I, Division 2 (Zone 2).

WARNING: Explosion Harzard- Do Not Disconnect Equipment Unless Power has been Switched Off or The Area is Known to be Non-Hazardous.

AVERTISSEMENT: Risque d'explosion. Ne pas débrancher l'appareil à moins d'avoir coupé l'alimentation électrique ou à moins qu'il ne s'agisse d'un emplacement non dangereux

Heating Cable Types

BTV-CR, BTV-CT, QTVR-CT: Consists of Outer jacket, Braid, Inner jacket, Conductive core, Bus wire.

XTV(R)-CT: Consists of Outer jacket, Braid, Inner jacket, Conductive fiber, Spacer, Bus wire.

VPL-CT: Consists of Outer jacket, Braid, Inner jacket, Heating element, Bus wire connection, Clear jacket, Insulated bus wire.

HTV-CT: Consists of Outer jacket, Braid, Inner jacket, Conductive Core + Electrical Insulation, Bus Wire.

Installation Instructions

Step 1

Step 2

Step 3

Step 4

Step 5A (BTV and QTVR)

Step 5B (XTV(R)-CT)

Step 5C (VPL)

Step 5D (HTV)

Step 6

Step 7

Step 8

Step 9

Step 10

Step 11

Step 12

Step 12A

Step 13

Step 14 (Optional) To change direction of box opening:

Step 15

Step 16

Step 17

Step 18

Step 19

Models: JBS-100-L-A Single Entry Power Connection, JBS-100-L-A, Single Entry Power Connection, Entry Power Connection, Power Connection

File Info : application/pdf, 16 Pages, 3.47MB

PDF preview unavailable. Download the PDF instead.

RAYCHEM-IM-H59057-JBS100LA-EN ?srsltid=AfmBOoqo BWeLAUoO9n6eU8wS75lzLE9grFZEOARqsSOkLYW-h174JVe

References

Adobe PDF Library 17.0 Adobe InDesign 20.3 (Windows)

Related Documents

Preview Raychem JBS-100-STB Single Entry Power Connection with Junction Box Installation Instructions
Installation instructions for the Raychem JBS-100-STB, a NEMA 4X rated power connection kit designed for use with various Raychem industrial parallel heating cables. This guide details the necessary tools, additional materials, and step-by-step procedures for safe and effective installation, including hazardous location approvals and important safety warnings.
Preview Raychem JBM-100-L-A Installation Instructions
Installation instructions for the Raychem JBM-100-L-A NEMA 4X-rated connection kit, designed for use with various Raychem industrial parallel heating cables. Includes safety warnings, approvals, kit contents, required tools, and step-by-step installation guidance.
Preview Raychem CS-100 Core Sealer Installation Instructions
Installation instructions for the Raychem CS-100 core sealer, a fluoroether-sealant-filled insulator designed for use with various Raychem industrial parallel heating cables. Includes safety warnings and step-by-step guidance.
Preview Raychem JBM-100-A/A6 Installation Instructions: Electric Heat Tracing Connection Kits
Comprehensive installation guide for Raychem JBM-100-A and JBM-100-A6 NEMA 4X-rated connection kits, detailing procedures for various heating cables, wiring configurations, and safety precautions.
Preview Raychem E-100-A High-Profile End Seal Installation Instructions
Detailed installation instructions for the Raychem E-100-A High-Profile End Seal, designed for use with various Raychem industrial parallel heating cables. Includes safety warnings, required tools, and step-by-step guidance for installation and re-entry.
Preview Industrial Electrical Heat Tracing Systems Engineering Specification
This engineering specification details requirements for Raychem's advanced industrial electrical heat-management and heat tracing systems, covering design, materials, installation, and testing.
Preview Raychem SES-CONT Smart End Seal Continuity Monitoring Transmitter Installation Instructions
Detailed installation instructions for the Raychem SES-CONT smart end seal continuity monitoring transmitter, covering preparation, assembly, and final setup for various Raychem heating cables.
Preview Raychem PMKG-LS Low-Profile Splice Connection Kit Installation Guide
Installation instructions for the Raychem PMKG-LS Low-Profile Splice Connection Kit, designed for use with Raychem parallel heating cables in various hazardous and nonhazardous locations. Includes detailed steps, required tools, and materials.