Instruction Manual for Enginko models including: MCF-LW06424 4 Channel To Lorawan, MCF-LW06424, 4 Channel To Lorawan, To Lorawan, Lorawan

MCF-LW06424 Operating Manual

MCF-LW06424 Operating Manual


File Info : application/pdf, 19 Pages, 1.47MB

PDF preview unavailable. Download the PDF instead.

5098 mcf-lw06424 operating manual
2024/09/05 13:15

1/2

Table of Contents

MCF-LW06424 Operating Manual

MCF-LW06424 Operating Manual ............................................................................................... 1 1. Description ................................................................................................................................ 1 2. Overview .................................................................................................................................... 2
2.1 Technical data ......................................................................................................................... 2 3 Installation .................................................................................................................................. 3
3.1 Connection .............................................................................................................................. 3 3.2 Analog inputs .......................................................................................................................... 4 3.3 Configuration .......................................................................................................................... 6 3.4 System led .............................................................................................................................. 7 3.5 Firmware update ..................................................................................................................... 8 4. Setup .......................................................................................................................................... 8 4.1 Period ...................................................................................................................................... 8 4.2 Thresholds .............................................................................................................................. 9 4.3 Other settings ....................................................................................................................... 10 5. Diagnostic ................................................................................................................................ 11 6 LoRaWAN network ................................................................................................................... 11 6.1 Activation .............................................................................................................................. 12 6.2 Other settings ....................................................................................................................... 13 7 Passwords ................................................................................................................................. 13 8 General configuration file ...................................................................................................... 14 8.1 Multi devices configuration ................................................................................................... 15 9 Payload ...................................................................................................................................... 16 10 Ordering code ........................................................................................................................ 16 11 Declaration of conformity .................................................................................................... 16 12 FCC compliance for MCF-LW06424-US ............................................................................... 16 13 Contacts .................................................................................................................................. 17

e n g i n k o . s u p p o r t . c e n t e r - https://www.enginko.com/support/

Last update: 2023/05/29 07:33

manual_mcf-lw06424 https://www.enginko.com/support/doku.php?id=manual_mcf-lw06424

https://www.enginko.com/support/

Printed on 2024/09/05 13:15

2024/09/05 13:15

1/17

MCF-LW06424 Operating Manual

MCF-LW06424 Operating Manual
Important safety information
Read this manual before attempting to install the device! Failure to observe recommendations included in this manual may be dangerous or cause a violation of the law. The manufacturer will not be held responsible for any loss or damage resulting from not following the instructions of this operating manual.
Do not dismantle or modify in any way. Avoid mechanical stress Do not use any detergent or alcohol to clean the device.
Disposal information for users
Pursuant to and in accordance with Article 14 of the Directive 2012/19/EU of the European Parliament on waste electrical and electronic equipment (WEEE), and pursuant to and in accordance with Article 20 of the Directive 2013/56/EU of the European Parliament on batteries and accumulators and waste batteries.
The barred symbol of the rubbish bin shown on the equipment indicates that, at the end of its useful life, the product must be collected separately from other waste.
Please note that the lithium batteries must be removed from the equipment before it is given as waste and disposed separately. To remove the batteries refer to the specifications in the user manual. For additional information and how to carry out disposal, please contact the certified disposal service providers.
1. Description
MCF-LW06424 is able to read 4 analog inputs 4-20mA with a resolution of 12 bit. The inputs have an insulation of 1000Vdc with respect to the power supply, and are protected against polarity inversion.

e n g i n k o . s u p p o r t . c e n t e r - https://www.enginko.com/support/

Last update: 2023/05/29 07:33

manual_mcf-lw06424 https://www.enginko.com/support/doku.php?id=manual_mcf-lw06424

MCF-LW06424 is available with DIN rail option (MCF-DIN105):

2. Overview
2.1 Technical data
CPU Cortex M4 RTC EEProm 32KB Flash 1MB Encryption AES 128 bit LiPo 800mAh rechargeable battery Class C LoRaWAN® stack EU868, AS923, AU915, US915 1000Vdc isolated analog inputs
https://www.enginko.com/support/

Printed on 2024/09/05 13:15

2024/09/05 13:15

3/17

4 analog current inputs 4-20mA 12bits and disconnect alarm 4 programable thresholds for each channel USB On The Go IoT node setup ad firmware upgrade via USB interface Power supply 10÷36Vdc Storage temperature range -20°C ÷ +80°C Working temperature range -10°C ÷ +70°C Dimensions L x H X P: 81 x 60 x 50mm

3 Installation

3.1 Connection

3.1.1 Power connection as stand-alone device

Please refer to following connections:

MCF-LW06424 Operating Manual

pin Name Description J3.9 GND Negative power supply (BLACK) J3.10 VDD Positive power supply range [10-36Vdc] (RED) Power can also be supplied by USB.
3.1.2 Power connection with DIN rail option
Please refer to following connections:
e n g i n k o . s u p p o r t . c e n t e r - https://www.enginko.com/support/

Last update: 2023/05/29 07:33

manual_mcf-lw06424 https://www.enginko.com/support/doku.php?id=manual_mcf-lw06424

Power supply:
Pin Name Description J2.1 Vdc Positive power supply range [10-36Vdc] J2.2 GND Negative power supply
Power can also be supplied by USB.
3.1.3 Antenna
The magnetic antenna must be positioned on a metal body. It should preferably be vertical and at least 30 cm away from other metal bodies. The installation must take place in a place where the LoRaWAN® signal coverage is good (SF=7 optimal, SF=12 weak). Use the provided clip to hold the antenna connector in place, as in the picture:

3.2 Analog inputs
https://www.enginko.com/support/

Printed on 2024/09/05 13:15

2024/09/05 13:15

5/17

MCF-LW06424 Operating Manual

Pin Name Description Range Resolution J1.1 AI1 Analog input 1 4-20mA 12 bit J1.2 GA Common J1.3 AI2 Analog input 2 4-20mA 12 bit J1.4 GA Common J1.5 AI3 Analog input 3 4-20mA 12 bit J1.6 GA Common J1.7 AI4 Analog input 4 4-20mA 12 bit J1.8 GA Common

Current Loop (4-20mA)

Input resistance

125

Absolute maximum value 24mA

Max error

±0.1%

Insulation

1000Vdc

Current values less than 3mA generate a "disconnected sensor" condition.

Caution: inputs are not galvanically isolated from each other.

3.2.1 Connection examples

1 sensor

e n g i n k o . s u p p o r t . c e n t e r - https://www.enginko.com/support/

Last update: 2023/05/29 07:33

manual_mcf-lw06424 https://www.enginko.com/support/doku.php?id=manual_mcf-lw06424

2 sensors

3.3 Configuration
To deploy the sensor, use LoRaWEB online tool, to setup LoRaWAN® credentials and other preferences (only available for Windows®) : LoRaWEB Tool (iot.mcf88.cloud/LoRaWeb) Before connect the device the first time, please install LoRaBridge applications and drivers: https://iot.mcf88.cloud/LoRaWeb/#/download Validate your settings reading data after the write. enginko provides, upon free registration, user manuals, javascript examples, downlink generator, uplink decoder, firmware updates and different tools :

https://www.enginko.com/support/

Printed on 2024/09/05 13:15

2024/09/05 13:15

7/17

MCF-LW06424 Operating Manual

3.4 System led

LoRaWAN® not configured Joining Sending Receiving

Slow flashing Quick flashing Quick flashing Quick flashing

e n g i n k o . s u p p o r t . c e n t e r - https://www.enginko.com/support/

Last update: 2023/05/29 07:33
Steady state Data error Connection error
3.5 Firmware update

manual_mcf-lw06424 https://www.enginko.com/support/doku.php?id=manual_mcf-lw06424
Fixed Flashing 2 seconds Flashing 1 second

Save the new firmware file (.exe) on the PC, run the file, select the USB FW port and start the update:

and waiting for the end message.
4. Setup

4.1 Period

Period is the interval (in minutes) between one measure and the next one. The sensor sends one measures for every transmission. Value can be between 5 and 65535 minutes (default: 10 minutes).

https://www.enginko.com/support/

Printed on 2024/09/05 13:15

2024/09/05 13:15

9/17

Period interval can be set with LoRaWEB or with downlink command.

4.2 Thresholds

MCF-LW06424 Operating Manual

On the MCF-LW06424 is possible to set 4 thresholds for each channel:
Th+ = Threshold High Rising Th- = Threshold High Falling Tl+ = Threshold Low Rising Tl- = Threshold Low Falling

When target values are rising and exceed the positive thesholds, the device sends an uplink with the
e n g i n k o . s u p p o r t . c e n t e r - https://www.enginko.com/support/

Last update: 2023/05/29 07:33
the latest measure.

manual_mcf-lw06424 https://www.enginko.com/support/doku.php?id=manual_mcf-lw06424

When values are falling below the negative thresholds, the device sends a new uplink with the latest measure.

Thresholds can be enabled, disabled and changed va USB with LoRaWEB or with downlinks:

4.3 Other settings
DST: set to change DST (default: none).
Time sync uplink: set to disable time synchronization request (default: enabled).

Normally sensor asks for a time sync at every power on (uplink starting with 01) or once a week. If no or wrong reply received, it will retry after 1 week.

https://www.enginko.com/support/

Printed on 2024/09/05 13:15

2024/09/05 13:15

11/17

MCF-LW06424 Operating Manual

If not handled in the right way can generate unnecessary traffic on the network.

Please check chapter 2.1 DATA FRAME FORMAT.

Confirmed Uplinks: set for unconfirmed uplinks (default: confirmed uplink).
Single join/day: set for to allow only one join per day (default: multiple join allowed).
LED working: Set OFF to turn off the diagnostic led.
USB: Internal use.
5. Diagnostic

Press Check to see the analog values.
6 LoRaWAN network
The sensor is compliant with LoRaWAN® specification 1.0.2, regional 1.0.2b.
e n g i n k o . s u p p o r t . c e n t e r - https://www.enginko.com/support/

Last update: 2023/05/29 07:33

manual_mcf-lw06424 https://www.enginko.com/support/doku.php?id=manual_mcf-lw06424

6.1 Activation
The device supports the following activations on a LoRaWAN® network:
1. NONE: sensor not activated 2. OTAA: the JoinEUI and the AppKey not setted, must be written to the device; 3. OTAA MCF88: Over the air activation, fixed keys: JoinEUI = 904e915000000002, AppKey on
request; 4. OTAA ENGINKO: Over the air activation, fixed keys: JoinEUI = 904e915000000002, AppKey on
request; 5. ABP: requires writing to the device of NwkSkey, AppSkey, DevAddr.

https://www.enginko.com/support/

Printed on 2024/09/05 13:15

2024/09/05 13:15

13/17

MCF-LW06424 Operating Manual

The device exits factory activated with NONE mode. On request devices can be shipped already activated. Note: in OTAA AppKey is write only, in reading the field will always be empty, even if set.
6.2 Other settings
Network settings: please keep "Any" settings. Change it only if Objenious network is used (default_ any). Network type: LoRa syncword can be setted as "private"(0x12) instead "public" (0x34), but the NS must be setted accordingly (default: public). Band: select the right LoRaWAN ® band settings accodingly to country requirements.
7 Passwords
The device can be protected by passwords, to avoid unauthorized persons to read data or modify parameters. As default passwords are equal to 0. Allowed values range from 0 to 999999999 (only numbers). To change the passwords, set the new values with LoRaWEB:
e n g i n k o . s u p p o r t . c e n t e r - https://www.enginko.com/support/

Last update: 2023/05/29 07:33

manual_mcf-lw06424 https://www.enginko.com/support/doku.php?id=manual_mcf-lw06424

Once the passwords are setted, to gain access from LoRaWEB to the sensor, set the right values before reading from the device:
To bring back the sensor to factory default and reset the passwords, a reset code must be requested to enginko (please provide the DevEUI of the sensor when you ask for that code).
8 General configuration file
WIth LoRaWEB is possible to configure the device using an XML file, instead to manually adjust the parameters (for details about the file format please ask to enginko). This is very useful especially in case of multiple devices configuration. With "Save" button an XML file with the actual configuration of the sensor will be generated. This is useful to store or clone the configuration, or to send it to enginko's support if needed.

https://www.enginko.com/support/

Printed on 2024/09/05 13:15

2024/09/05 13:15

15/17

8.1 Multi devices configuration

MCF-LW06424 Operating Manual

WIth LoRaWEB is possible to configure many devices in an easy way.
For multi-configuration is needed at least one XML file with the parameters to set.
Settings on this file will be applied to all the sensors.
With an additional XLS file is possible to load different LoRa configuration parameters (Activation Type, AppKey, AppEUI, NetKey, DevAddress, Band, Private option) for each sensor, based on DevEUI.
XLS is prevailing on the XML, so if both files are enabled, if the DevEUI of the device matches one of the DevEUIs in the XLS file, LoRa parameters will be setted from this one.
These configuration can be done in the in the Settings:
Use of the general configuration by file; Use of the specific configuration by file.

For details on files format please ask to enginko.
e n g i n k o . s u p p o r t . c e n t e r - https://www.enginko.com/support/

Last update: 2023/05/29 07:33
9 Payload

manual_mcf-lw06424 https://www.enginko.com/support/doku.php?id=manual_mcf-lw06424

For payload descriptions, uplinks and downlinks format and available commands please refer to this document:
DATA FRAME FORMAT

10 Ordering code

Code

Description

MCF-LW06424 4-20mA to LoRaWAN® interface EU863-870

MCF-LW06424-AS 4-20mA to LoRaWAN® interface AS920-925

MCF-LW06424-US 4-20mA to LoRaWAN® interface US902-928

MCF-LW06424-AU 4-20mA to LoRaWAN® interface AU915-928

For payload descriptions, uplinks and downlinks format and available commands please refer to this document:
DATA FRAME FORMAT

11 Declaration of conformity

Hereby, enginko Srl declares that MCF-LW06424 complies with the essential requirements and other relevant provisions of Directive 2014/53/EU.

12 FCC compliance for MCF-LW06424-US

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

https://www.enginko.com/support/

Printed on 2024/09/05 13:15

2024/09/05 13:15

17/17

Consult the dealer or an experienced radio/TV technician for help.

MCF-LW06424 Operating Manual

Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this equipment.

Contains FCC ID: 2AWAL409810

13 Contacts

enginko Srl Via Roma 3 I-28060 Sozzago (NO) T : +39 0321 15 93 088
E : info@enginko.com PEC: enginkosrl@legalmail.it W: enginko.com

rev.0

From: https://www.enginko.com/support/ - e n g i n k o . s u p p o r t . c e n t e r Permanent link: https://www.enginko.com/support/doku.php?id=manual_mcf-lw06424 Last update: 2023/05/29 07:33

e n g i n k o . s u p p o r t . c e n t e r - https://www.enginko.com/support/



References