ENG PREMASGARD 211x / 212x / 212x-SD operating manual

Trasmettitore di pressione, pressione differenziale e portata volumetrica con selezione uscita attiva, IP43 - cod. PREMASGARD 212x-SD - ITSensor - ITSensor

Trasmettitore di pressione differenziale e portata volumetrica con uscita analogica - cod. PREMASGARD 212x-SD - ITSensor - ITSensor

PREMASGARD 212x ⁄ 212x - SD


File Info : application/pdf, 11 Pages, 1.52MB

PDF preview unavailable. Download the PDF instead.

File-1632920660
D G F r 6000-3560-0000-1XX 35600-2021 V103 03 / 2021
PREMASGARD®211x PREMASGARD®212x / 212x - SD
D Bedienungs- und Montageanleitung
Druck- und Differenzdruckmessumformer, incl. Anschluss-Set, Kompaktform, einstellbar, kalibrierfähig, mit Mehrbereichsumschaltung und aktivem Ausgang
G Operating Instructions, Mounting & Installation
Pressure and differential pressure measuring transducers, including connection set, compact form, adjustable, calibratable, with multi-range switching and active output
F Notice d'instruction
Convertisseur de pression et de pression différentielle, y compris kit de raccordement, forme compacte, réglable, étalonnable, avec commutation multi-gamme et sortie active
r     
       , .   ,  , , ,        

PREMASGARD® 211x PREMASGARD® 212x PREMASGARD® 212x - SD

S+S REGELTECHNIK GMBH THURN-UND-TAXIS - STR. 22 90411 NÜRNBERG / GERMANY FON +49 (0) 911 / 519 47- 0
mail@SplusS.de www.SplusS.de

CARTONS ET EMBALLAGE PAPIER À TRIER

D G F r
PREMASGARD®211x PREMASGARD®212x / 212x - SD

Maßzeichnung Dimensional drawing Plan coté  

49 ø 4.3

39 12
72 ~107

ø6 15
64

12

12

Maßzeichnung Dimensional drawing Plan coté  

30 ø6

39 72
~107

49 ø 4.3
64
Gerätevariante mit M12-Steckverbinder (optional auf Anfrage) Device version with M12 connector (optional on request) Variante d'appareil avec connecteur M12 (en option et sur demande)     M12 (  )
2

PREMASGARD® 211x

M16x1.5 M16x1.5

14.8 43.3

14.8 37.8

ohne Display without display sin écran  
mit Display with display avec écran  
PREMASGARD® 212x

M16x1.5 M16x1.5

7 14.8
43.3

7 14.8
37.8

ohne Display without display sin écran  
mit Display with display avec écran  

G PREMASGARD® 211x / 212x / 212x - SD

Rev. 2021 - V21

The calibrateable compact pressure sensors of the PREMASGARD® 211x / 212x / 212x - SD series are equipped with 8 switchable measuring ranges, 2 switchable output signals (16 devices in one) and with or without optional display and are used for measuring above-atmospheric, belowatmospheric, or differential pressures and Volume flow in air. The piezo-resistive measuring element is temperature-compensated and guarantees a high degree of reliability and accuracy. These pressure transmitters have a pushbutton for manual zero point calibration and an adjustable offset. Applications of these pressure sensors are in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale catering facilities, for monitoring filters, for level measurement or for triggering frequency converters. Media measured with these pressure transducers are air (non-precipitating), or other gaseous non-aggressive, non-combustible media. The differential pressure sensor is supplied including connection set ASD-06 (2 m connection hose, two pressure connection nipples, screws). You can find further device types under PREMASGARD® 111x / 112x / 112x - SD (l variant with 2-wire connection).

TECHNICAL DATA

Power supply:

24 V AC/DC (± 10 %)

Working resistance: Load resistance: Power consumption:

Ra (Ohm) = 25 ...450 Ohm for I variant RL > 25 kOhm for U variant < 1 W at 24 V DC; < 2 VA at 24 V AC

Current consumption:

< 45 mA

Measuring function:

Differential pressure, volume flow (square root output signal)

Measuring ranges:

multi-range switching with 8 switchable measuring ranges (see table)

Output:

switchable 0 -10 V / 4...20 mA (via DIP switches)

Electrical connection:

3-wire connection

Media temperature:

­20...+50 °C (temperature-compensated 0...+50 °C)

Pressure connection:

with connection nozzles for pressure hose Ø 6 mm

Type of pressure:

differential pressure

Medium:

clean air and other non-aggressive, non-combustible gases

Accuracy:

Type 2110 / 2120 / 2120 - SD (100 Pa): typically ± 3 Pa at +25 °C Type 2111 / 2121 / 2121 - SD (1000 Pa): typically ± 10 Pa at +25 °C Type 2115 / 2125 / 2125 - SD (5000 Pa): typically ± 35 Pa at +25 °C compared to the calibrated reference device

Zero point offset:

± 10 % of final value

Above- / below-atmospheric pressure: ± 50 kPa

Long-term stability:

± 1 % per year

Signal filtering: Hysteresis: Media contacting parts: Temperature drift values: Linearity: Housing:
Housing dimensions:

switchable 1 s / 10 s (via DIP switches)

0.3 % of final value

Brass, Ni, Duroplast, Si, epoxy, RTV, BSG, UV silicone gel

± 0.1 % of final value / °C

< ± 1 % of final value

plastic, UV-resistant, material polyamide, 30 % glass-globe reinforced, colour traffic white (similar to RAL 9016),housing cover for display is transparent!

Type 211x / 212x: with quick-locking screws (slotted/Phillips head combination)

Type 212x - SD:

with snap-on lid

72 x 64 x 37.8 mm (Tyr 1 / Tyr 01 without display) 72 x 64 x 43.3 mm (Tyr 1 / Tyr 01 with display)

Cable connection: Electrical connection: Humidity: Protection class: Protection type:
Standards: Features:

cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or M12 connector according to DIN EN 61076-2-101 (optional on request)

0.14 - 1.5 mm², via terminal screws

< 95 % r. H., non-precipitating air

III (according to EN 60 730)

Type 211x / 212x: Type 212x - SD:

IP 67 (according to EN 60 529)* Housing tested, TÜV SÜD, Report No. 713139052 (Tyr 1)
IP 54 (according to EN 60 529)* Housing tested, TÜV SÜD, Report No. 713160960A (Tyr 01)
* Housing in the built-in state

CE conformity, electromagnetic compatibility according to EN 61 326, EMC directive 2014 / 30 / EU

two-line display with illumination, cutout approx. 36 x 15 mm (W x H), to display ACTUAL pressure

ACCESSORIES

see table

10

G PREMASGARD® 211x / 212x / 212x - SD

Rev. 2021 - V21

PREMASGARD® 212x - SD
Pressure range (Ranges adjustable)
max. ­ 1000...+ 1000 Pa 0... 100 Pa / ­ 100...+ 100 Pa 0... 300 Pa / ­ 300...+ 300 Pa 0... 500 Pa / ­ 500...+ 500 Pa 0... 1000 Pa / ­ 1000...+ 1000 Pa
max. ­ 5000...+ 5000 Pa 0...1000 Pa / ­ 1000...+ 1000 Pa 0...2000 Pa / ­ 2000...+ 2000 Pa 0...3000 Pa / ­ 3000...+ 3000 Pa 0...5000 Pa / ­ 5000...+ 5000 Pa
max. ­ 100...+ 100 Pa 0... 50 Pa / ­ 50...+ 50 Pa 0... 100 Pa / ­ 100...+ 100 Pa

Pressure, differential pressure and volume flow measuring transducers, Standard (Pressure connectors on the bottom side)

Type / WG01B (3-wire connection)
PREMASGARD® 2121 - SD PREMASGARD 2121-SD
PREMASGARD 2121-SD LCD

Output (switchable)
0 -10 V / 4...20 mA 0 -10 V / 4...20 mA

Display 

Item No. (with snap-on lid)
IP 54 1301-11B7-0010-000
1301-11B7-2010-000

PREMASGARD® 2125 - SD PREMASGARD 2125-SD PREMASGARD 2125-SD LCD

0 -10 V / 4...20 mA 0 -10 V / 4...20 mA

IP 54 1301-11B7-0050-000  1301-11B7-2050-000

PREMASGARD® 2120 - SD PREMASGARD 2120-SD PREMASGARD 2120-SD LCD

0 -10 V / 4...20 mA 0 -10 V / 4...20 mA

IP 54 1301-11B7-0110-000  1301-11B7-2110-000

PREMASGARD® 212x
Pressure range (Ranges adjustable)
max. ­ 1000...+ 1000 Pa 0... 100 Pa / ­ 100...+ 100 Pa 0... 300 Pa / ­ 300...+ 300 Pa 0... 500 Pa / ­ 500...+ 500 Pa 0... 1000 Pa / ­ 1000...+ 1000 Pa
max. ­ 5000...+ 5000 Pa 0...1000 Pa / ­ 1000...+ 1000 Pa 0...2000 Pa / ­ 2000...+ 2000 Pa 0...3000 Pa / ­ 3000...+ 3000 Pa 0...5000 Pa / ­ 5000...+ 5000 Pa
max. ­ 100...+ 100 Pa 0... 50 Pa / ­ 50...+ 50 Pa 0... 100 Pa / ­ 100...+ 100 Pa

Pressure, differential pressure and volume flow measuring transducers, Premium (Pressure connectors on the bottom side)

Type / WG01 (3-wire connection)
PREMASGARD® 2121 PREMASGARD 2121
PREMASGARD 2121 LCD

Output (switchable)
0 -10 V / 4...20 mA 0 -10 V / 4...20 mA

Display 

Item No. (with quick-locking screws)
IP 67 1301-11A7-0010-000
1301-11A7-2010-000

PREMASGARD® 2125 PREMASGARD 2125 PREMASGARD 2125 LCD

0 -10 V / 4...20 mA 0 -10 V / 4...20 mA

IP 67 1301-11A7-0050-000  1301-11A7-2050-000

PREMASGARD® 2120 PREMASGARD 2120 PREMASGARD 2120 LCD

0 -10 V / 4...20 mA 0 -10 V / 4...20 mA

IP 67 1301-11A7-0110-000  1301-11A7-2110-000

PREMASGARD® 211x
Pressure range (Ranges adjustable)
max. ­ 1000...+ 1000 Pa 0... 100 Pa / ­ 100...+ 100 Pa 0... 300 Pa / ­ 300...+ 300 Pa 0... 500 Pa / ­ 500...+ 500 Pa 0... 1000 Pa / ­ 1000...+ 1000 Pa
max. ­ 5000...+ 5000 Pa 0...1000 Pa / ­ 1000...+ 1000 Pa 0...2000 Pa / ­ 2000...+ 2000 Pa 0...3000 Pa / ­ 3000...+ 3000 Pa 0...5000 Pa / ­ 5000...+ 5000 Pa
max. ­ 100...+ 100 Pa 0... 50 Pa / ­ 50...+ 50 Pa 0... 100 Pa / ­ 100...+ 100 Pa
Multi-range switching: Output: Optional:

Pressure, differential pressure and volume flow measuring transducers, Premium (Pressure connectors on the top side)

Type / WG01 (3-wire connection)
PREMASGARD® 2111 PREMASGARD 2111
PREMASGARD 2111 LCD

Output (switchable)
0 -10 V / 4...20 mA 0 -10 V / 4...20 mA

Display 

Item No. (with quick-locking screws)
IP 67 1301-1197-0010-000
1301-1197-2010-000

PREMASGARD® 2115 PREMASGARD 2115 PREMASGARD 2115 LCD

0 -10 V / 4...20 mA 0 -10 V / 4...20 mA

IP 67 1301-1197-0050-000  1301-1197-2050-000

PREMASGARD® 2110

IP 67

PREMASGARD 2110

0 -10 V / 4...20 mA

1301-1197-0110-000

PREMASGARD 2110 LCD

0 -10 V / 4...20 mA

 1301-1197-2110-000

The pressure ranges depend on the device type and can be set via DIP switches. 0 -10 V or 4...20 mA (selectable via DIP switches) Cable connection with M12 connector according to DIN EN 61076-2-101 (on request)

ACCESSORIES

ASD-06

Connection set (included in the scope of delivery), consisting of 2 connection nipples (straight) made of ABS,
2 m PVC hose (soft, UV-resistant) and 4 screws

ASD-07 DAL-01 WS-04

2 connection nipples (at 90 degree angle) made of plastic, ABS Pressure outlet for ceiling or in-wall installation (e.g. in clean rooms) Weather and sun protection hood, 130 x 180 x 135 mm, stainless steel V2A (1.4301)

11

Item No. 7100-0060-3000-000
7100-0060-7000-000 7300-0060-3000-001 7100-0040-7000-000

G PREMASGARD® 211x / 212x / 212x - SD
Mounting diagram

Rev. 2021 - V21 PREMASGARD® 211x

110 Pa
(A) Mounting diagram
110 Pa

110 Pa
(B)
110 Pa

110 Pa
(C)
110 Pa

110 Pa
(D) PREMASGARD® 212x
PREMASGARD® 212x - SD
110 Pa

(A)

(B)

TYPES OF MONITORING: Pressure connections at the pressure switch are marked with P1 (+) for higher pressure and P2 (­) for lower pressure.
(A) Below-atmospheric pressure P1 (+) is not connected, but open to the atmosphere P2 (­) connected to inside of duct
(B) Filter P1 (+) connected upstream of filter P2 (­) connected downstream of filter
(C) Ventilator P1 (+) connected downstream of ventilator P2 (­) connected upstream of ventilator
(D) Volume flow P1 (+) dynamic pressure, connected in flow direction P2 (­) static pressure, connected free of dynamic pressure components
V = k ·  p
V = Volume flow k = K factor p = Differential pressure [Pa]
12

(C)

(D)

Load resistance diagram PREMASGARD® 211x

4...20 mA

PREMASGARD® 212x

PREMASGARD® 212x - SD

500 450 400

Working resistance (Ohm)

300 Admissible range
200
100
25 10 15 20 25 30 35 36 40 Operating voltage (V DC)

G PREMASGARD® 211x / 212x / 212x - SD

Schematic diagram

PREMASGARD® 211x PREMASGARD® 212x PREMASGARD® 212x - SD

Connecting diagram

Rev. 2021 - V21
PREMASGARD® 211x PREMASGARD® 212x PREMASGARD® 212x - SD

min. max. LED

key offset Plug for display

ON
123456 DIP
switches

123

Status LED (DIP 6) I Output (ON) = orange U Output (OFF) = green

Pushbutton Zero point setting key (auto zero)

offset

Offset correction see graph ca. ± 10% of final value

Plug for display contact is on the right side

- 230V AC
+ 24V AC/DC

-+ PLC PC

123

+UB 24V AC/DC Output pressure [Pa]
­UB GND
+UB 24 V AC/DC Output pressure [Pa]
-UB AC/DC GND

Conversion table for pressure values:

Unit = 1 Pa 1 kPa 1 bar 1 mbar 1 mH2O

bar 0.00001 bar
0.01 bar 1 bar
0.001 bar 0.0980665 bar

mbar 0.01 mbar
10 mbar 1000 mbar
1 mbar 98.0665 mbar

Pa 1 Pa 1000 Pa 100000 Pa 100 Pa 9806.65 Pa

kPa 0.001 kPa
1 kPa 100 kPa 0.1 kPa 9.80665 kPa

mH2O 0.000101971 mH2O
0.101971 mH2O 10.1971 mH2O
0.0101971 mH2O 1 mH2O

DIP switches for pressure range setting, output attenuation and zero compensation:

Pressure range

DIP DIP

Output characteristic line

DIP

(selectable) ­ max. measuring range (default) is depending to the type of device

1 2

(Mode selectable)

4

0...50 Pa 0...100 Pa 0...1000 Pa ­50...+50 Pa ­100...+100 Pa ­1000...+1000 Pa OFF OFF

­ 0...300 Pa 0...2000 Pa

­ ­300...+300 Pa ­2000...+2000 Pa O N OFF

Linear (default) (for pressure detection)

OFF

­ 0...500 Pa 0...3000 Pa

­ ­500...+500 Pa ­3000...+3000 Pa OFF O N

0...100 Pa 0...1000 Pa 0...5000 Pa ­100...+100 Pa ­1000...+1000 Pa ­5000...+5000 Pa O N O N

Square root extracting (to determine the volume flow)

O N

Measuring range mode

DIP

Measurement signal filtering

DIP

Output

DIP

(Mode selectable)

3

(Time interval selectable)

5

(selectable)

6

Unidirectional ( 0 ...+MR ) (default)

OFF

10 s (default)

OFF

Voltage 0 -10 V (default)

OFF

Bidirectional (­MR ...+MR )

O N

1 s

O N

Current 4... 20 mA

O N

13

G PREMASGARD® 211x / 212x / 212x - SD | Configuration and zero point calibration

The following configurations can be preset via DIP switches. The DIP switch sliding blocks can be moved without using tools. DIP switch 6 is not assigned.
Pressure ranges In each case four different pressure ranges depending on the type of device can be preset via DIP switches DIP 1 and DIP 2.
Measuring range mode The measuring range is configured via DIP switch DIP 3, either into the unidirectional range or into the bidirectional range. Therefore altogether eight pressure measuring ranges are configurable.
Characteristic line ­ analog output The output characteristic line can be defined via DIP switch DIP 4. Here is distinguished between a linear and a square root extracting output characteristic line. When square root extracting output characteristic line is selected, the measuring range setting at DIP switches DIP 1 and DIP 2 is without function. In that case the maximum pressure range is used for computation.

Offset adjustment is done at a potentiometer on the circuit board within an adjustment range of ± 10 % of the device's pressure range. Ex-factory this potentiometer is in center position and is lacquer sealed. All settings and adjustments that are made before must be done in this configuration. Offset adjustment is carried out using a tool called "screwdriver 2.5" (blade with in mm).
Automatic offset setting 1. Before setting the zero point, the device must be in operation
for at least 60 minutes. 2. Connect pressure inputs P (+) and P (­) by means of a hose
(pressure difference between both inputs = 0 Pa). 3. For zero point setting press "key" (auto zero) pushbutton
uninterruptedly for 5 seconds.
A LED signalises prompting the calibration by short flashing, and after a short countdown the measured (current) offset value is added to the measurand and zero voltage safe stored.
Correct calibration is confirmed by steady light of the LED for 3 seconds respectively indicated in the display (optional) by switching from "AUTO 0" to "PROG 0".
Note: By releasing the button during the countdown (counter > 0), zero point setting is immediately terminated!

Measurement signal filtering
In order to stabilize the pressure measurement signal and the output voltage, the measurement signal is filtered.
The time interval for such averaging can be preset via DIP switch DIP 5 to 1 or 10 seconds.
By a longer filtering interval, the settling time of the sensor is automatically extended.

Manual offset adjustment At the potentiometer OFFSET P can be balanced. The adjustment range is ca. ± 10 % of the pressure range. Here another reference point different from zero point can be used.
Readout in the display In the 1st line of the display, the ACTUAL pressure up to the measuring range limit is displayed. Switching between the units Pa and hPa (100 Pa = 1 hP) happens automatically. Pa = Pascal hP = Hektopascal

14

G PREMASGARD® 211x / 212x / 212x - SD | Configuration and zero point calibration

U - variant (Range: 0...+ xx Pa)
After successful zero point calibration, the output voltage is 0 V at 0 Pa pressure difference (with the offset knob in central position)!
Output voltage 0...10 V for pressure difference from 0 Pa to final value

I - variant (Range: 0...+ xx Pa)
After successful zero point calibration, the output current is 4 mA at 0 Pa pressure difference (with the offset knob in central position)!
Output current 4...20 mA for pressure difference from 0 Pa to final value

10 V

20 mA

Displacement of characteristic line by control knob (right stop) Offset = +10%

Displacement of characteristic line(+) by control knob (right stop) ca. +10%

I output in mA

0 V (zero point offset)

Original characteristic line Offset = 0
Control knob in central position = default
Displacement of characteristic line by control knob (left stop) Offset = ­10%
100% of measuring range

4 mA 0 Pa

Original characteristic line Offset = 0 (potentiometer in central position = factory setting)
Displacement of characteristic line(­) by control knob (left stop) ca. ­10% Pressure difference in Pa
+ Pa

U - variant (Range: ­ xx ... + xx Pa) After successful zero point calibration, the output voltage is 5 V at 0 Pa pressure difference (with the offset knob in central position)!
Output voltage 0...10 V for pressure difference ­ P ... +P
10 V Pressure at input (P+)> pressure at input (P­)

U output in V

Displacement of characteristic line(+) by control knob (right stop) ca. +10%

­ Pa

0 Pa

Pressure at input (P­)> Pressure at input (P+)

Pressure difference in Pa
+ Pa 5 V
Original characteristic line Offset = 0 (potentiometer in central position = factory setting)
Displacement of characteristic line(­) by control knob (left stop) ca. ­10%

I - variant (Range: ­ xx ... + xx Pa)
After successful zero point calibration, the output current is 12 mA at 0 Pa pressure difference (with the offset knob in central position)!
Output current 4... 20 mA for pressure difference ­ P ... +P

20 mA

Pressure at input (P+)> pressure at input (P­)

Displacement of characteristic line(+) by control knob (right stop) ca. +10%

­ Pa

0 Pa

Pressure at input (P­)> Pressure at input (P+)

Pressure difference in Pa
+ Pa 12 mA
Original characteristic line Offset = 0 (potentiometer in central position = factory setting)
Displacement of characteristic line(­) by control knob (left stop) ca. ­10%

15

G General notes
This device can be mounted in any position. The voltage output is short-circuit proof. Applying overvoltage at the voltage output will destroy this device. Pressure ranges are indicated on the device label. Applying measuring pressures beyond that range will cause mismeasurements and increased deviations or may destroy the device.
­ Attention! When leading in cables, make sure, they do not go under the board. This might buckle or damage hose connections! ­ The voltage output is short-circuit proof. Applying overvoltage at the voltage output will destroy this device. ­ Pressure inputs are "poled" i.e. the above-atmospheric pressure line must be connected at input P+
and the below-atmospheric pressure line must be connected at input P­. ­ At an adjusting element, the output signal can be offset by ± 10 % of the final value of the measuring range.
In this way, possible ageing or drift effects can be compensated. ­ Adjustment may only be made at the presence of differential pressure (ca. 90 % of final value). ­ By changing the offset at the adjusting element, factory-calibration is lost! ­ If this device is operated beyond the specified range, all warranty claims are forfeited.
Our "General Terms and Conditions for Business" together with the "General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry" (ZVEI conditions) including supplementary clause "Extended Retention of Title" apply as the exclusive terms and conditions. In addition, the following points are to be observed: ­ These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded! ­ A suitable weather and sun protection hood must be used when installed outdoors. ­ Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage
induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed. ­ This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and
the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind. ­ No warranties or liabilities will be assumed for defects and damages arising from improper use of this device. ­ Consequential damages caused by a fault in this device are excluded from warranty or liability. ­ These devices must be installed and commissioned by authorised specialists. ­ The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations
from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products. ­ In case of any modifications made by the user, all warranty claims are forfeited. ­ This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.
Direct sun irradiation or heat irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided. ­ Operating this device close to other devices that do not comply with EMC directives may influence functionality. ­ This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,
or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes. ­ Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions. ­ Modifications of these records are not permitted. ­ In case of a complaint, only complete devices returned in original packing will be accepted.
Notes on commissioning: This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an initial manual adjustment on-site during commissioning and subsequently at regular intervals.
Commissioning is mandatory and may only be performed by qualified personnel! These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

SUPPLY VOLTAGE :
For operating voltage reverse polarity protection, a one-way rectifier or reverse polarity protection diode is integrated in this device variant. This internal one-way rectifier also allows operating devices on AC supply voltage.
The output signal is to be tapped by a measuring instrument. Output voltage is measured her against zero potential (O V) of the input voltage!

Connecting scheme Individual operation

Power supply

AC 24V~ DC 24V =

0V GND

Circuitry V

0...10V 0V/GND

When several devices are supplied by one 24 V AC voltage supply, it is to be ensured that all "positive" operating voltage input terminals (+) of the field devices are connected with each other and all "negative" operating voltage input terminals (­) (= reference potential) are connected together (in-phase connection of field devices). All outputs of field devices must be referenced to the same potential!
In case of reversed polarity at one field device, a supply voltage shortcircuit would be caused by that device. The consequential short-circuit current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!

Connecting scheme Parallel operation

Power supply

AC 24V~ DC 24V =

0V GND

16

Circuitry

Circuitry

0...10V 0V/GND 0...10V 0V/GND

D G F r
PREMASGARD®211x PREMASGARD®212x / 212x - SD

Maßzeichnung Dimensional drawing Plan coté  

30 ø6

39 72
~107

49 ø 4.3
64

PREMASGARD® 212x - SD
mit Schnappdeckel with snap-on lid
avec couvercle emboîté   

M16x1.5 M16x1.5

7 14.8
43.3

7 14.8
37.8

ohne Display without display sin écran  
mit Display with display avec écran  

© Copyright by S+S Regeltechnik GmbH
Nachdruck, auch auszugsweise, nur mit Genehmigung der S+S Regeltechnik GmbH. Reprint in full or in parts requires permission from S+S Regeltechnik GmbH. La reproduction des textes même partielle est uniquement autorisée après accord de la société S+S Regeltechnik GmbH. ,      ,     S+S Regeltechnik GmbH.
Irrtümer und technische Änderungen vorbehalten. Alle Angaben entsprechen unserem Kenntnisstand bei Veröffentlichung. Sie dienen nur zur Information über unsere Produkte und deren Anwendungsmöglichkeiten, bieten jedoch keine Gewähr für bestimmte Produkteigenschaften. Da die Geräte unter verschiedensten Bedingungen und Belastungen eingesetzt werden, die sich unserer Kontrolle entziehen, muss ihre spezifische Eignung vom jeweiligen Käufer bzw. Anwender selbst geprüft werden. Bestehende Schutzrechte sind zu berücksichtigen. Einwandfreie Qualität gewährleisten wir im Rahmen unserer Allgemeinen Lieferbedingungen.
Subject to errors and technical changes. All statements and data herein represent our best knowledge at date of publication. They are only meant to inform about our products and their application potential, but do not imply any warranty as to certain product characteristics. Since the devices are used under a wide range of different conditions and loads beyond our control, their particular suitability must be verified by each customer and/or end user themselves. Existing property rights must be observed. We warrant the faultless quality of our products as stated in our General Terms and Conditions.
Sous réserve d'erreurs et de modifications techniques. Toutes les informations correspondent à l'état de nos connaissances au moment de la publication. Elles servent uniquement à informer sur nos produits et leurs possibilités d'application, mais n'offrent aucune garantie pour certaines caractéristiques du produit. Etant donné que les appareils sont soumis à des conditions et des sollicitations diverses qui sont hors de notre contrôle, leur adéquation spécifique doit être vérifiée par l'acheteur ou l'utilisateur respectif. Tenir compte des droits de propriété existants. Nous garantissons une qualité parfaite dans le cadre de nos conditions générales de livraison.
    .         .           ,       .         ,     ,        .      .        «  ».
31

15

D G F r
Zubehör Accessories Accessoires 

Maßzeichnung Dimensional drawing Plan coté  

ASD - 06

Maßzeichnung Dimensional drawing Plan coté  
45 35

ø 3.5 ø 16 ø 25
ø 6.0

ø5 ø6

ø 22

17

ASD - 07

Maßzeichnung Dimensional drawing Plan coté  

29

Federn Springs

DAL - 01

3.5

78 81

70

60

ø 6.5
ASD - 06 Anschluss-Set Connection set Kit de raccordement   

ø6
ASD - 07 Anschlussnippel Connection nipple Embouts de raccordement  

ø 29 ø 35
DAL -01 Druckauslass Pressure outlet Sortie pression   

WS-04 Wetter- und Sonnenschutz (optional) Weather and sun protection (optional) Protection contre les intempéries et le soleil (en option)         ()
32



References

PDFium PDFium