Comfort-Aire Century MARS

User Manual

VHP-CA Series

Ceiling Cassettes

Models: B-VHP09CA-1, B-VHP12CA-1, B-VHP18CA-1, B-VHP24CA-1

IMPORTANT NOTE: Read this manual carefully before installing or using your new air conditioner. Keep this manual for future reference.

Safety Instructions

It is very important to read the safety instructions before installing and using the appliance. Improper installation due to failure to follow instructions can cause serious damage or injury. The severity of potential damage and injury is categorized as a WARNING or a CAUTION.

Symbol Meanings

⚠️ WARNING: This symbol indicates the risk of bodily injury or loss of life.

❗ CAUTION: This symbol indicates the possibility of material damage or serious consequences.

Warnings Related to Product Use

Electrical Warnings

Warnings Related to Cleaning and Maintenance

ATTENTION

WARNING CONCERNING REFRIGERANT USE

Leak Detection System

The appliance is equipped with a leak detection system. The appliance must be powered on, except during maintenance. For units with a refrigerant sensor, when the sensor detects a refrigerant leak, the indoor unit will display an error code and emit an audible alarm. The outdoor unit's compressor will stop immediately, and the indoor fan will start operating. The lifespan of the refrigerant sensor is 15 years. The indoor unit displays the error code "FHCC" when the refrigerant sensor is not functioning correctly. The refrigerant sensor cannot be repaired and can only be replaced by the manufacturer. It must be replaced only with the sensor specified by the manufacturer (applicable to units with refrigerant sensors only).

Refrigerant Charge Quantity and Minimum Room Surface Area

The machine you purchased may be one of the types indicated in the table below. The indoor and outdoor units are designed to be used together. Please verify your purchased machine. The indoor unit must be installed at least 8.3 ft (2.3 m) from the floor. The room height cannot be less than 7.3 ft (2.2 m), and the minimum operating or storage room surface area must comply with the following table:

Refrigerant Charge and Minimum Room Surface Area Requirements
Model Indoor Unit Outdoor Unit Nominal Indoor Airflow
9K B-VHP09CA-1 A-VHP09SA-1 600m³/h (353CFM)
12K B-VHP12CA-1 A-VHP12SA-1 710m³/h (418CFM)
18K B-VHP18CA-1 A-VHP18SA-1 760m³/h (448CFM)
24K B-VHP24CA-1 A-VHP24SA-1 1300m³/h (765CFM)

For units equipped with refrigerant sensors, the minimum indoor unit airflow is as follows when the unit detects a refrigerant leak:

Refrigerant Charge and Room Surface Area Data
Amin [ft²/m²] me or MREL [oz/kg] hinst [ft/m]
6.0-7.3 / 1.8-2.2 7.6/2.3 8.3/2.5 8.9/2.7 9.9/3.0
<=62.6/1.776 12/1.10
63.4/1.8 60/5.53 55/5.07 51/4.68 47/4.35 44/4.06
70.5/2.0 67/6.15 61/5.64 56/5.20 52/4.83 49/4.51
77.5/2.2 73/6.76 67/6.20 62/5.72 58/5.31 54/4.96
84.6/2.4 80/7.38 73/6.76 68/6.24 63/5.80 59/5.41
91.7/2.6 86/7.99 79/7.32 73/6.76 68/6.28 64/5.86
98.7/2.8 93/8.60 85/7.89 79/7.28 73/6.76 68/6.31
105.8/3.0 100/9.22 91/8.45 84/7.80 78/7.24 73/6.76
112.8/3.2 106/9.83 97/9.01 90/8.32 84/7.73 78/7.21
119.9/3.4 113/10.45 104/9.58 96/8.84 89/8.21 83/7.66
126.9/3.6 120/11.06 110/10.14 101/9.36 94/8.69 88/8.11
134/3.8 126/11.68 116/10.70 107/9.88 99/9.17 93/8.56
141.0/4.0 133/12.29 122/11.27 112/10.40 104/9.66 97/9.01
148.1/4.2 139/12.90 128/11.83 118/10.92 110/10.14 102/9.46
155.1/4.4 146/13.52 134/12.39 124/11.44 115/10.62 107/9.91
162.2/4.6 153/14.13 140/12.96 129/11.96 120/11.11 112/10.37
169.2/4.8 159/14.75 146/13.52 135/12.48 125/11.59 117/10.82
176.3/5.0 166/15.36 152/14.08 140/13.00 130/12.07 122/11.27

Amin: Minimum required room surface area in ft²/m².

me: Actual refrigerant charge in the system in oz/kg.

MREL: Releaseable refrigerant charge in oz/kg (applicable to units with refrigerant sensors only).

hinst: Height of the appliance bottom from the room floor after installation.

WARNING: The minimum room surface area or conditioned room surface area is based on the releaseable charge and the total system refrigerant charge.

Installation

1. Installation (when refrigerant lines are permitted)

2. When a FLAMMABLE REFRIGERANT is used, installation space or ventilation requirements are determined according to:

3. Worker Qualification

All maintenance, servicing, and repair operations must be performed by qualified personnel. Any procedure affecting safety means must only be performed by competent persons who have undergone training and acquired skills, which should be documented by a certificate. Training for these procedures is provided by national training organizations or accredited manufacturers to teach relevant national competency standards as may be established in legislation. All training must comply with the requirements of ANNEX HH of UL 60335-2-40, 4th edition. Examples of such procedures include:

Maintenance Information

1. Checks Before Starting Work

Before starting repairs on systems containing flammable refrigerants, safety checks are necessary to ensure the risk of ignition is minimal. To perform repairs on the refrigeration system, the following precautions must be observed before working on the system.

2. Work Procedure

Work must be carried out according to a controlled procedure to minimize the risks of flammable gas or vapor presence during the work.

3. General Work Area

All maintenance personnel and any other person working in the local area must be informed of the nature of the work in progress. Confined space work must be avoided.

4. Refrigerant Presence Check

Checks must be carried out in the work area with an appropriate refrigerant detector, before and during the work, to ensure the technician is aware of potentially flammable atmospheres. It is necessary to ensure that the leak detection equipment used is suitable for use with flammable refrigerants, e.g., it does not produce sparks, is sufficiently sealed, and is intrinsically safe.

5. Fire Extinguisher Presence

If hot work operations are to be performed on refrigeration equipment or any associated component, an adequate fire extinguisher must be readily available. A dry powder or CO2 extinguisher must be available near the charging area.

6. Absence of Ignition Sources

No person performing work in relation to a REFRIGERATION SYSTEM shall expose piping to any source of ignition in such a way that it could cause a risk of fire or explosion. All potential ignition sources, including cigarette smoke, must be kept sufficiently distant from the installation, repair, removal, and disposal area of the equipment, stages during which flammable refrigerant may potentially escape and settle in the surrounding space. Before starting work, the area around the equipment must be monitored to ensure there are no risks of flammability or ignition. "No Smoking" signs must be displayed.

7. Ventilated Area

It is necessary to ensure that the area is open to the air or sufficiently ventilated before commencing work on the system or performing hot work operations. Continuous ventilation must be ensured throughout the duration of the work. Ventilation must safely disperse any escaping refrigerant and expel it outdoors into the atmosphere.

8. Refrigerant Material Checks

When electrical components are to be replaced, they must be adapted and compatible with the appropriate recommendations. The manufacturer's maintenance and service guidelines must be followed under all circumstances. If in doubt, contact the manufacturer's technical service for assistance. The following checks must be applied to installations using FLAMMABLE REFRIGERANTS:

9. Electrical Equipment Checks

Repair and maintenance of components must include initial safety verification and component inspection procedures. If a defect exists that could compromise safety, no electrical power must be connected to the circuit until the problem has been resolved satisfactorily. If the defect cannot be resolved immediately, but the ongoing operation must continue, an appropriate temporary solution must be implemented. Any such situation must be reported to the equipment owner so that all parties are aware.

Initial safety checks must be performed to ensure that:

10. Sealed electrical components must be replaced if damaged.

11. Intrinsically safe components must be replaced if damaged.

12. Wiring

Verify that the wiring will not be exposed to wear, corrosion, excessive pressure, vibration, sharp edges, or any other detrimental environmental element. The check must also take into account the effects of cable aging or continuous vibrations from sources such as compressors or fans.

13. Flammable Refrigerant Detection

Potential ignition sources must not be used in any way when searching for or detecting refrigerant leaks. A halide lamp (or any other detector using an open flame) must not be used.

The following detection methods are considered acceptable for refrigerant systems. Electronic leak detectors can be used to detect refrigerant leaks, but in the case of FLAMMABLE REFRIGERANTS, the sensitivity may not be sufficient or may require recalibration. (Detection equipment must be calibrated in a non-refrigerant zone.) Ensure the detector is not a potential ignition source and is suitable for use in the presence of refrigerant. Leak detection material must be set to a percentage of the refrigerant's LFL (Lower Flammable Limit) and the leak detection material must be set to a percentage of the refrigerant's LII (Lower Ignition Limit) and calibrated according to the refrigerant used, and the appropriate gas percentage (25% maximum) must be confirmed.

Leak detection fluids are also suitable for use in the presence of most refrigerants, but the use of chlorinated products should be avoided, as chlorine can cause a reaction upon contact with the refrigerant and corrode copper tubing.

NOTE: Examples of leak detection fluids include:

If a leak is suspected, all open flames must be removed/extinguished. If a braze-requiring refrigerant spill is identified, all refrigerant must be removed from the system or isolated (using shut-off valves) in a part of the system located away from the leak. Refer to the following instructions for refrigerant removal.

14. Removal and Evacuation

When repairs are performed, or other actions are initiated in the refrigeration circuit, conventional procedures must be followed. However, for flammable refrigerants, it is important to follow best practices as flammability is a consideration. The following procedure must be followed:

Refrigerant charge must be recovered into suitable recovery cylinders if evacuation is not permitted by local and national codes. For appliances containing flammable refrigerants, the system must be purged with oil-free nitrogen to make the appliance safe for flammable refrigerants. This process may need to be repeated several times. Compressed air or oxygen must not be used to purge refrigerant systems.

For appliances containing flammable refrigerants, refrigerant purging must be carried out by breaking the vacuum in the system with oil-free nitrogen and continuing to fill until service pressure is reached, then venting to the atmosphere and finally re-applying (optional for A2L). This process must be repeated until there is no more refrigerant in the system (optional for A2L). When the last oil-free nitrogen charge is used, the system must return to atmospheric pressure for work to proceed. The suction pump outlet must not be near any potential ignition source, and ventilation must be available.

15. Charging Procedures

In addition to conventional charging procedures, the following requirements must be met:

16. Decommissioning

Before performing this procedure, it is essential that the technician is fully familiar with the equipment and all its specifics. The recommended best practice is to recover all refrigerants safely. Before starting the operation, an oil and refrigerant sample should be taken in case analysis is required before reuse of recovered refrigerant. It is important that electrical power is available before starting the operation.

17. Labeling

The equipment must be labeled to indicate that it has been decommissioned and emptied of its refrigerant. The label must be dated and signed. For appliances containing FLAMMABLE REFRIGERANTS, ensure there are labels on the equipment indicating that the equipment contains FLAMMABLE REFRIGERANT.

18. Recovery

The recommended practice when performing refrigerant recovery, whether for maintenance or decommissioning, is to remove all refrigerants safely. When transferring refrigerant into cylinders, ensure only suitable refrigerant recovery cylinders are used. Ensure an adequate number of cylinders are available to contain the entire system charge. All bottles to be used are designated for refrigerant recovery and labeled for that refrigerant (e.g., cylinders specific for refrigerant recovery). Cylinders must be equipped with a pressure relief valve and shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before starting the recovery process.

Recovery equipment must be in good condition and accompanied by an operating manual that is readily available and suitable for the recovery of flammable refrigerants. If in doubt, the manufacturer must be consulted. Additionally, a set of calibrated scales must be available and in good working order. Hoses must be equipped with leak-proof disconnect fittings.

Recovered refrigerant must be handled in accordance with local legislation in the appropriate recovery bottle, and the appropriate waste transfer note must be arranged. Do not mix refrigerants in recovery equipment, especially in cylinders.

If compressors or oil compressors are to be removed, ensure they have been drained to a sufficient level to guarantee that the oil no longer contains flammable refrigerant. The compressor body must not be heated by an open flame or other ignition sources to accelerate this process. When oil is drained from a system, the operation must be performed safely.

19. Transport, Marking, and Storage of Units

1. Transport of Equipment Containing Flammable Refrigerants

Compliance with transport regulations.

2. Marking of Material with Signs Conforming to Local Regulations.

3. Disposal of Material Using Flammable Refrigerants

In accordance with national regulations.

4. Storage of Material/Appliances

Material storage must be in accordance with the manufacturer's instructions.

5. Storage of Packaged Material (Not Sold)

Protective packaging for storage must be designed so that any mechanical damage to the material inside the packaging does not cause a leak in the refrigerant charge. The maximum number of appliances allowed to be stored together will be determined by local regulations.

Signification of Symbols Displayed on Indoor and Outdoor Units

Operating Instructions

REMARK:

Indoor Unit Display

Display Panel:

DEL Display:

• FORCED COOL Mode: In FORCED COOL mode, the operation indicator flashes. The system will then switch to AUTO after cooling with a high fan speed for 30 minutes. The remote control will be deactivated during this operation.

• OFF Mode: When the display panel is off, the appliance is turned off, and the remote control is reactivated.

Other Functions

REMARK: Each time the air conditioner is turned on, a humming sound will be heard to indicate the product has been powered on normally. If there is no sound, the unit may be abnormal. Please power on again or check the circuit. Actual functions depend on the product purchased; please check the indoor display and your CA remote control. Refer to the <Remote Control Manual> for more features.

• Default Settings

When the air conditioner restarts after a power failure, it will default to factory settings (AUTO Mode, VENT AUTO, 24 °C (76 °F)). This may cause inconsistencies on the remote control and the unit panel. Use your remote control to update the status.

• Automatic Restart

In case of a power failure, the system will shut down immediately. When power is restored, the operation indicator on the indoor unit will flash. To restart the appliance, press the ON/OFF button on the wired remote control. If the system has an automatic restart function, the appliance will restart using the same settings.

• Three-Minute Protection Function

A protection function prevents the air conditioner from being activated for approximately 3 minutes when it restarts immediately after operation.

• Louver Angle Memory Function

For units with a louver angle memory function. When the appliance restarts after a power failure, the horizontal louver angle automatically returns to the previous position. The horizontal louver angle should not be too small, as condensation may form and drip into the unit. To reset the louver, press the manual button, which will reset the horizontal louver setting.

Heat Exchanger Dust Removal Function

This feature helps keep the outdoor coil cleaner and can extend the time between regular maintenance intervals depending on local conditions. When the unit is powered off, a 10-second delay occurs, then the outdoor fan runs in reverse for 70 seconds to blow off accumulated dust and debris.

• Sleep Function (Veille)

The Sleep function is used to reduce energy consumption during sleep (and does not require temperature settings to remain comfortable). This function can only be activated via the remote control. The Sleep (Night) function is not available in FAN or DRY modes. Press the SLEEP (Night) button when you go to bed. In COOL mode, the unit automatically increases the temperature by 1°C (2°F) after 1 hour, and by another 1°C (2°F) after another hour. In HEAT mode, the unit decreases the temperature by 1°C (2°F) after 1 hour, and by another 1°C (2°F) after another hour. The Sleep (Night) function will stop after 8 hours, and the system will continue to operate according to the last settings.

Diagram: Sleep Function (Nuit) showing temperature adjustments over time for COOL and HEAT modes.

Refrigerant Leak Detection

Note: Error codes "EH CI", "EHC2", "EHC3", and "ECCI" are only applicable to units with a refrigerant sensor.

Maintenance and Care

ATTENTION: The cooling efficiency of your unit and your health would be compromised for the concealed air conditioner; ensure the filter is cleaned every two weeks.

Cleaning Your Indoor Unit (Air Filter)

⚠️ WARNING: Removing and cleaning the filter can be dangerous. Removal and maintenance must be performed by an authorized technician.

Step 1: Remove the air filter.

Diagram: Shows opening the cover, unscrewing, and pressing buttons to remove the air inlet frame.

Separate the frame from the filter assembly.

Remove the clean air filter. (Optional) Please note that the clean air filter cannot be washed with water. It is recommended to replace it regularly.

Step 2: Clean the air filter.

Clean the air filter by vacuuming the surface or washing it with lukewarm water and mild detergent.

Diagram: Shows cleaning the filter with a vacuum or washing it. If using water, the inlet side should face downwards away from the water stream. If using a vacuum, the inlet side should face the vacuum.

Step 3: Rinse and dry the filter.

Rinse the filter with clean water and let it air dry. DO NOT let the filter dry in direct sunlight.

Reinstall the filter.

❗ CAUTION

Air Conditioning Maintenance

Maintenance - Long Periods of Non-Use

If you plan not to use your air conditioner for an extended period, follow these steps:

Maintenance - Pre-Season Check

After long periods of non-use, or before periods of frequent use, follow these recommendations:

Troubleshooting

❗ CAUTION: If any of the following conditions occur, turn off your appliance immediately!

DO NOT TRY TO REPAIR THEM YOURSELF! CONTACT AN AUTHORIZED SERVICE PROVIDER IMMEDIATELY.

Common Problems

The following problems are not malfunctions and, in most cases, do not require any repair.

Troubleshooting Table
Problem Possible Causes Solution
The unit does not turn on when the ON/OFF button is pressed. The unit has a 3-minute protection function to prevent overload. The unit cannot be restarted within three minutes of being turned off. Wait for power to be restored.
The unit switches from COOL/HEAT Mode to FAN Mode. Cooling and Heating Models: If the operation indicator and PRE DEF (preheating/defrosting) indicators are lit, the outdoor temperature is too cold, and the unit's anti-cold wind is activated for defrosting.
Cooling-only Models: If the "Fan Only" indicator is lit, the outdoor temperature is too cold, and the unit's anti-freeze protection is activated for defrosting.
Turn on the power.
The indoor unit emits white mist. The unit may adjust its setting to prevent frost formation on the unit. Once the temperature rises, the unit will start operating in the previously selected mode. Replace the fuse.
The indoor element emits noises. The set temperature has been reached, causing the unit to turn off the compressor. The unit continues to operate as the temperature fluctuates again. Replace the batteries.
The indoor element emits noises. In humid conditions, a large distance between the room air and the conditioned air can cause mist. Both the indoor unit and when the unit remains in HEAT mode after defrosting, the outdoor units themselves emit white mist due to humidity generated by the defrosting process. Wait three minutes after restarting the unit.
The two indoor units and the outdoor unit emit noises. You hear a grinding noise when the system is off or in COOL mode. The noise is also heard when the drain pump (optional) is running. A grinding noise may occur after using the unit in HEAT mode due to the expansion and contraction of the unit's plastic parts. A faint whistling noise during operation is normal and caused by refrigerant gas circulating through the indoor and outdoor units. A faint whistling noise when the system starts, stops, or is defrosting is normal and caused by the stop, change of direction, or refrigerant gas noise. Grinding: Normal expansion and contraction of plastic and metal parts caused by temperature changes during operation may cause grinding noises. Turn on the timer.
The outdoor unit makes noises. The unit will emit different sounds depending on its current operating mode. Check for leaks and recharge the system with refrigerant.
The outdoor unit / The appliance emits a bad odor. Dust emitted by the unit may accumulate over time during prolonged periods of non-use, which may be emitted when the unit is turned on. This can be mitigated by covering the outdoor unit during long periods of inactivity. The unit may absorb odors from the environment (e.g., furniture, kitchen, cigarettes, etc.) which will be emitted during operations. The unit filters may have mold and need cleaning. The outdoor fan, during operation, controls fan speed to optimize product performance. Evacuate and recharge the system with refrigerant.
The appliance emits a bad odor. The filters of the unit have mold and need to be cleaned. Determine which system circuit is blocked and replace the defective equipment part.
The unit does not start. The outdoor fan, during operation, controls fan speed to optimize product performance. Replace the compressor.
The unit does not start. The outdoor fan, during operation, controls fan speed to optimize product performance. Install a pressure switch to regulate voltage.
The unit does not start. The outdoor fan, during operation, controls fan speed to optimize product performance. Use an auxiliary heating device.
The unit does not start. The outdoor fan, during operation, controls fan speed to optimize product performance. Ensure all doors and windows are closed during use.
The unit does not start. The outdoor fan, during operation, controls fan speed to optimize product performance. Check for leaks, repair if necessary, and refill refrigerant.

Poor Cooling Performance

Problem Possible Causes Solution
Poor cooling performance. The temperature setting may be too high / lower than the ambient temperature. The indoor or outdoor unit heat exchanger is dirty. The air filter is dirty. Air entering or exiting the unit is blocked. Doors and windows are open. Excessive heat is generated. Close windows and curtains during periods of strong sunlight or bright sun. Too many heat sources in the room (people, computers, reduced amount of heat from electronics, etc.). Low refrigerant level due to a leak or long-term use. Remove and clean the filter according to instructions. Remove and clean the filter according to instructions. Remove and clean the filter according to instructions. Ensure all doors and windows are closed during appliance operation. Check for leaks, repair if necessary, or use long-term refrigerant that has been discharged. Remove and clean the filter according to instructions. Remove and clean the filter according to instructions.

Unit Does Not Function

Problem Possible Causes Solution
The unit does not function. Power failure. Power is cut off. Fuse is blown. Remote control batteries are low. The unit's 3-minute protection has been activated. Timer is activated. Too much or too little refrigerant in the system. Incompressible gas or moisture in the system. System circuit is blocked. Compressor is broken. Voltage is too high or too low. Outdoor temperature is extremely low. Cold air enters through doors and windows. Low refrigerant level due to a leak or long-term use. Wait for power to be restored. Turn on the power. Replace the fuse. Replace the batteries. Wait three minutes after restarting the unit. Turn off the timer. Check for leaks and recharge the system with refrigerant. Evacuate and recharge the system with refrigerant. Determine which circuit is blocked and replace the defective equipment part. Replace the compressor. Install a pressure switch to regulate voltage. Use an auxiliary heating device. Ensure all doors and windows are closed during use. Check for leaks, repair if necessary, and refill refrigerant.

Indicator Lights Continuously Blinking

The appliance may stop functioning or continue to operate safely. If the indicator lights continue to blink or error codes appear, wait approximately 10 minutes. The problem may resolve itself.

If not, turn off the power, then reconnect the power cord. Turn on the unit.

If the problem persists, turn off the power and contact the nearest customer service center.

REMARK: If your problem persists after performing the checks and diagnostics explained above, immediately turn off your appliance and contact an authorized after-sales service.

Design and specifications are subject to change without notice for product improvement. Consult the sales agency or manufacturer for details. All manual updates will be downloaded from the service website. Please check the latest version.

Limited Express Warranty

Congratulations on your purchase of your new HVAC equipment. It has been designed for a long service life and reliable operation, and is backed by one of the industry's strongest warranties. Your appliance is automatically eligible for the warranty coverage indicated below, provided you retain your proof of purchase (receipt) for the equipment and meet the warranty conditions.

TEN (10) YEAR LIMITED EXPRESS WARRANTY

MARS warrants that all parts, including the compressor of the VHP-SA series ductless mini-split, shall be free from defects in workmanship and materials for normal use and service for ten (10) years from the original customer's purchase date for the original installation. This limited express warranty applies only when the ductless mini-split is installed as a complete matched system: outdoor unit and indoor unit, and only when the system is installed according to MARS installation instructions and in compliance with all local, state, and national codes for normal use.

EXCEPTIONS

The limited express warranty does not cover routine maintenance. MARS recommends performing an inspection/maintenance at least once per season, and proof of maintenance must be kept. Furthermore, labor costs, transportation costs for replacement parts, refrigerant or filter replacement, any other service or repair are not covered by this limited warranty. It also does not cover any part or component of the system that is not supplied by MARS, regardless of the cause of failure of that portion or component.

CONDITIONS OF WARRANTY APPLICATION

WARRANTY PERIOD AND REGISTRATION

The warranty begins on the date of purchase by the original consumer. The customer must keep a sales contract with a receipt as proof of the warranty period. Without this proof, the express warranty begins on the date of factory shipment.

REMEDIES PROVIDED BY THE LIMITED EXPRESS WARRANTY

The sole remedy available under the limited warranty is the replacement of the defective part. If replacement parts are required during the term of this warranty, MARS replacement parts must be used; no warranty on the replacement part(s) will extend the original applicable warranty of the unit. Ready for use, the owner is responsible for unit maintenance. Labor required for diagnosis and replacement of the defective part is not covered by this limited express warranty. If, for any reason, the replacement part or product is no longer available during the warranty period, MARS shall have the right to provide credit for the current suggested retail price of the part or product in lieu of providing repair or replacement.

LIMITATION OF LIABILITY

  1. No other express or implied warranty applies. MARS does not warrant merchantability. We do not warrant that the appliance is suitable for any use or can be used in buildings or rooms of any size or condition, except as specifically stated in this document. No other warranty, express or implied, whose scope exceeds the conditions presented in this document, applies.
  2. All implied warranties by law are limited to the seven-year parts warranty period. Your exclusive remedy is limited to the replacement of defective parts. We shall not be liable under any circumstances for consequential or incidental damages caused by a defect in this appliance.
  3. This warranty gives you specific legal rights. You may also have other rights that vary from state to state. Some states do not allow limitations on the duration of an implied warranty or do not allow the exclusion or limitation of indirect or consequential damages, so the above limitations or exclusions may not apply to you.
  4. No warranty is provided for units sold outside the continental United States and Canada. Your distributor or final seller may provide a warranty for units sold outside these areas.
  5. MARS shall not be liable for damages if our warranty resolution performance is delayed by events beyond our control, including accidents, alterations, abuse, war, government restrictions, strikes, fire, flood, or other acts of God.

HOW TO OBTAIN WARRANTY SERVICE OR PARTS

If you have a warranty claim, promptly notify your installer. If the installer does not wish to address your claim, send a letter to MARS, 1900 Wellworth Ave., Jackson MI 49203. Attach an inspection report from your installer or service technician. Indicate the model number, serial number, and date of purchase.

Owner's responsibilities are outlined in the instruction manual. Read it carefully.

Please visit www.marsdelivers.com to register your new product.

RECORD THIS INFORMATION AS PROOF OF YOUR PURCHASE

Outdoor Unit: Model No. _______________ Serial No. _______________

Indoor Unit 1: Model No. _______________ Serial No. _______________

Indoor Unit 2: Model No. _______________ Serial No. _______________

Indoor Unit 3: Model No. _______________ Serial No. _______________

Indoor Unit 4: Model No. _______________ Serial No. _______________

Indoor Unit 5: Model No. _______________ Serial No. _______________

Date of Purchase: __________________________________________________________________________

VHP-SA_WARRANTY_3/2025

Due to continuous product improvements, technical specifications and dimensions are subject to change and correction without prior notice or obligation. Determination of the application and suitability for use of any product rests with the installer. Furthermore, the installer is responsible for verifying product dimensional data before commencing any installation preparation. Incentive and rebate programs have specific performance and product certification requirements. All products comply with regulations in effect at the date of manufacture; however, certifications are not necessarily granted for the life of a product. Therefore, it is the applicant's responsibility to determine if a specific model is eligible for these rebate and incentive programs.

1900 Wellworth Ave., Jackson, MI 49203 • Ph. 517-787-2100 • www.marsdelivers.com

9/2025

PDF preview unavailable. Download the PDF instead.

VHP-CA OwnerManual FR 9-9-25 Microsoft Word for Microsoft 365 Microsoft Word for Microsoft 365

Related Documents

Preview MARS Ceiling Cassette Replacement Parts List and Exploded View
Comprehensive replacement parts list and exploded view diagrams for MARS Comfort Aire Century Ceiling Cassette air conditioning units, including models B-VHP09CA-1, B-VHP12CA-1, B-VHP18CA-1, and B-VHP24CA-1.
Preview Manual de Instrucciones Comfort-Aire Century Serie VHP-CA
Descubra cómo instalar, operar y mantener su unidad de aire acondicionado de casete para techo Comfort-Aire Century Serie VHP-CA con este manual detallado. Incluye guías de seguridad, solución de problemas y especificaciones.
Preview Comfort-Aire & Century Ducted Indoor Unit Replacement Parts List
Official replacement parts list and exploded views for Comfort-Aire and Century ducted indoor units. Includes detailed part numbers and diagrams for models B-VHP09DA-1, B-VHP12DA-1, B-VHP18DA-1, B-VHP24DA-1, and B-VHP36DA-1, provided by MARS. Note: Specifications are subject to change; installer is responsible for verifying dimensional data and program qualification.
Preview Manuel d'installation - Climatiseurs MARS Série VHP-WA
Guide complet pour l'installation des climatiseurs consoles au sol MARS Série VHP-WA (modèles B-VHP09WA-1, B-VHP12WA-1, B-VHP18WA-1), incluant consignes de sécurité, procédures de câblage, raccordement et tests.
Preview MARS VHP-UA Series Split Air Conditioner Installation Manual
This document provides comprehensive installation instructions for the MARS VHP-UA Series split air conditioner modules (floor and ceiling types). It covers safety precautions, product overview, installation procedures for indoor and outdoor units, refrigerant piping, electrical wiring, air evacuation, testing, packaging, and warranty information.
Preview Manuel d'utilisation Climatiseur Cassette Plafond MARS VHP-1A
Guide complet pour l'installation, l'utilisation et l'entretien du climatiseur cassette au plafond MARS Série VHP-1A. Inclut les mesures de sécurité, les caractéristiques, le dépannage et les spécifications.
Preview Comfort-Aire/Century Floor Mount Indoor Unit Replacement Parts List
Comprehensive replacement parts list and exploded view descriptions for Comfort-Aire and Century floor mount indoor units, including models B-VHP09WA-1, B-VHP12WA-1, and B-VHP18WA-1. Features part numbers, quantities, and location identifiers for HVAC technicians.
Preview Mars Multi-Position Air Handler Replacement Parts List and Diagrams
Comprehensive replacement parts list and exploded view diagrams for Mars Multi-Position Air Handlers, including models B-VHP18AA-1, B-VHP24AA-1, B-VHP30AA-1, and B-VHP36AA-1. Features part names, quantities, part numbers, and contact information.