STEINEL IR Quattro HD-2 DALI-2 Input Device
Brand: STEINEL
1. About This Document
Please read and keep this document safe. It is protected by copyright. Reproduction, even in part, requires STEINEL's permission. Changes for technical progress are reserved.
Symbols
- ⚠️ Hazard warning!
- ? Reference to text passages in the document.
2. General Safety Precautions
⚠️ Before any work on the sensor, disconnect the power supply!
- The electrical cable to be connected must be de-energized during installation. First, switch off the power and check for absence of voltage using a voltage tester.
- Installing the sensor involves working on the mains power supply. This work must be carried out professionally according to national installation regulations and connection conditions.
- Use only original spare parts.
- Repairs must only be carried out by specialist workshops.
3. IR Quattro HD-2 DALI-2 IPD
Proper Use
Sensor for ceiling mounting indoors. Connection to a DALI bus system.
The IR Quattro HD-2 DALI-2 IPD offers high-resolution, highly sensitive motion detection. The square detection zone can be precisely adjusted. The sensor is particularly suitable for offices, classrooms, and large industrial spaces.
UP: Concealed version
AP: Surface-mounted version
Package Contents (See Fig. 3.1, Fig. 3.4)
The package typically includes:
- A: Surface-mounting adapter
- B: Load module
- C: Connection terminal
- D: Sensor module
- E: Reach adjustment potentiometer
Product Dimensions (See Fig. 3.2, Fig. 3.5)
Concealed (UP) version dimensions: 103 mm (width) x 103 mm (height) x 69 mm (depth).
Surface-mounted (AP) version dimensions: 123 mm (width) x 123 mm (height) x 64 mm (depth).
Detection Zone (See Fig. 3.7)
The detection zone is a square area. At a mounting height of 2.8 m, the presence detection range is 9 m x 9 m, and the maximum detection range is 24 m x 24 m.
Technical Data
- Mounting height: 2.5 - 10 m
- Angle of coverage: 360°
- Sensor values: Light measurement, Temperature (0-40 °C), Relative humidity (0-100 %)
- Temperature range: 0 °C to +40 °C
- IP rating: IP20
- Bluetooth frequency: 2.4-2.48 GHz
- Bluetooth transmission power: 5 dBm / 3 mW
- Power consumption via DALI (12 - 22.5 V DC, no SELV): Max. current consumption according to IEC 62386-101: 84 mA / 42 participants. Max. current consumption at 10 V input voltage: 32 mA / 16 participants. Typical current consumption at 16 V input voltage: 19 mA / 10 participants.
- DALI start-up time: < 1 s
Detection Range Table (IR Quattro HD-2)
The following table details the detection ranges (Presence, Radial, Tangential) based on mounting height and potentiometer setting.
Mounting Height | Potentiometer | Presence | Radial | Tangential |
---|---|---|---|---|
2.50 m | 1 | 3.0 m x 3.0 m | 2.4 m x 2.4 m | 3.8 m x 3.8 m |
2 | 3.0 m x 3.0 m | 2.5 m x 2.5 m | 4.0 m x 4.0 m | |
3 | 4.0 m x 4.0 m | 3.2 m x 3.2 m | 6.0 m x 6.0 m | |
4 | 5.0 m x 5.0 m | 4.0 m x 4.0 m | 16.0 m x 16.0 m | |
5 | 7.0 m x 7.0 m | 5.5 m x 5.5 m | 16.5 m x 16.5 m | |
6 | 8.0 m x 8.0 m | 6.5 m x 6.5 m | 21.5 m x 21.5 m | |
7 | 9.0 m x 9.0 m | 7.0 m x 7.0 m | 22.0 m x 22.0 m | |
2.80 m | 1 | 3.0 m x 3.0 m | 2.8 m x 2.8 m | 4.4 m x 4.4 m |
2 | 3.0 m x 3.0 m | 2.8 m x 2.8 m | 4.4 m x 4.4 m | |
3 | 4.0 m x 4.0 m | 3.0 m x 3.0 m | 5.0 m x 5.0 m | |
4 | 6.0 m x 6.0 m | 5.0 m x 5.0 m | 8.4 m x 8.4 m | |
5 | 8.0 m x 8.0 m | 6.5 m x 6.5 m | 17.0 m x 17.0 m | |
6 | 8.0 m x 8.0 m | 7.0 m x 7.0 m | 22.0 m x 22.0 m | |
7 | 9.0 m x 9.0 m | 7.5 m x 7.5 m | 24.0 m x 24.0 m | |
3.00 m | 1 | 4.0 m x 4.0 m | 3.0 m x 3.0 m | 4.5 m x 4.5 m |
2 | 4.0 m x 4.0 m | 3.0 m x 3.0 m | 4.5 m x 4.5 m | |
3 | 5.0 m x 5.0 m | 3.8 m x 3.8 m | 5.5 m x 5.5 m | |
4 | 5.0 m x 5.0 m | 5.2 m x 5.2 m | 9.0 m x 9.0 m | |
5 | 7.0 m x 7.0 m | 6.2 m x 6.2 m | 14.5 m x 14.5 m | |
6 | 8.0 m x 8.0 m | 7.0 m x 7.0 m | 23.0 m x 23.0 m | |
7 | 8.0 m x 8.0 m | 7.5 m x 7.5 m | 24.0 m x 24.0 m | |
3.50 m | 1 | - | 3.4 m x 3.4 m | 4.4 m x 4.4 m |
2 | - | 4.2 m x 4.2 m | 4.8 m x 4.8 m | |
3 | - | 4.5 m x 4.5 m | 6.4 m x 6.4 m | |
4 | - | 6.0 m x 6.0 m | 9.5 m x 9.5 m | |
5 | - | 7.1 m x 7.1 m | 17.0 m x 17.0 m | |
6 | - | 7.2 m x 7.2 m | 24.0 m x 24.0 m | |
7 | - | 7.6 m x 7.6 m | 26.0 m x 26.0 m | |
4.00 m | 1 | 4.0 m x 4.0 m | 5.0 m x 5.0 m | |
2 | 5.4 m x 5.4 m | 6.0 m x 6.0 m | ||
3 | 5.8 m x 5.8 m | 8.0 m x 8.0 m | ||
4 | 7.0 m x 7.0 m | 12.0 m x 12.0 m | ||
5 | 8.0 m x 8.0 m | 20.0 m x 20.0 m | ||
6 | 8.0 m x 8.0 m | 26.5 m x 26.5 m | ||
7 | 8.0 m x 8.0 m | 30.0 m x 30.0 m | ||
5.00 m | 1 | - | 5.5 m x 5.5 m | 7.2 m x 7.2 m |
2 | - | 5.5 m x 5.5 m | 7.2 m x 7.2 m | |
3 | - | 6.4 m x 6.4 m | 8.8 m x 8.8 m | |
4 | - | 8.0 m x 8.0 m | 12.0 m x 12.0 m | |
5 | - | 8.0 m x 8.0 m | 23.0 m x 23.0 m | |
6 | - | 8.4 m x 8.4 m | 30.4 m x 30.4 m | |
7 | - | 8.4 m x 8.4 m | 35.0 m x 35.0 m | |
6.00 m | 1 | - | 6.5 m x 6.5 m | 8.5 m x 8.5 m |
2 | - | 6.5 m x 6.5 m | 9.0 m x 9.0 m | |
3 | - | 8.0 m x 8.0 m | 13.0 m x 13.0 m | |
4 | - | 9.0 m x 9.0 m | 18.0 m x 18.0 m | |
5 | - | 10.0 m x 10.0 m | 29.0 m x 29.0 m | |
6 | - | 10.0 m x 10.0 m | 30.0 m x 30.0 m | |
7 | - | 10.5 m x 10.5 m | 30.0 m x 30.0 m | |
8.00 m | 1 | - | 9.0 m x 9.0 m | 12.8 m x 12.8 m |
2 | - | 9.0 m x 9.0 m | 12.8 m x 12.8 m | |
3 | - | 10.0 m x 10.0 m | 14.0 m x 14.0 m | |
4 | - | 12.0 m x 12.0 m | 23.0 m x 23.0 m | |
5 | - | 12.0 m x 12.0 m | 30.0 m x 30.0 m | |
6 | - | 12.0 m x 12.0 m | 32.0 m x 32.0 m | |
7 | - | 12.0 m x 12.0 m | 34.0 m x 34.0 m | |
10.00 m | 1 | - | 11.0 m x 11.0 m | 15.5 m x 15.5 m |
2 | - | 11.0 m x 11.0 m | 15.5 m x 15.5 m | |
3 | - | 11.5 m x 11.5 m | 19.5 m x 19.5 m | |
4 | - | 12.0 m x 12.0 m | 26.0 m x 26.0 m | |
5 | - | 12.5 m x 12.5 m | 32.5 m x 32.5 m | |
6 | - | 12.5 m x 12.5 m | 34.0 m x 34.0 m | |
7 | - | 12.5 m x 12.5 m | 35.5 m x 35.5 m |
4. Electrical Connection
DA+ = Connection to the DALI BUS (brown wire)
DA- = Connection to the DALI BUS (blue wire)
(See Fig. 4.1 for surface-mounted, Fig. 4.2 for concealed)
5. Installation
- Check all components for damage. Do not use the product if damaged.
- Select a suitable mounting location, considering the reach and motion detection range (See Fig. 3.7).
Mounting Procedure
Switch off power supply (See Fig. 4.1/4.2).
Concealed Mounting (UP)
- Make connection (See Fig. 5.1/4.2).
- Firmly screw the load module into the mounting box (See Fig. 5.2).
- Fit the magnetic sensor module onto the frame (See Fig. 5.3).
- Switch ON power supply (See Fig. 5.3).
- Make settings (Refer to Section 6: "Function and Settings").
Surface Mounting (AP)
- Mark and drill mounting holes (See Fig. 5.4).
- Feed cable through. Screw the load module into place (See Fig. 5.5).
- Make connection (See Fig. 5.6/4.1).
- Break out the mounting tab if necessary (See Fig. 5.7).
- Fit the surface-mounting adapter (See Fig. 5.8).
- Fit the magnetic sensor module (See Fig. 5.9).
- Switch ON power supply (See Fig. 5.9).
- Make settings (Refer to Section 6: "Function and Settings").
6. Function and Settings
Commissioning is performed according to the applicable DALI-2 standard. All functions and commands of the DALI standard IEC 62386 Parts 101, 103, 303, and 304 are available.
All sensor values (motion, light level, temperature, and humidity) can be requested from the DALI-2 Application Controller. Automatic or time-based cyclical transmission can also be selected for motion and light levels.
Detailed information is available in the interface description on the internet at: www.steinel.de
LED Function
- Start up: LED flashes blue rapidly for 10 seconds.
- Initialisation: LED lights up blue continuously.
- Normal mode: LED is OFF.
- Identification: LED flashes blue slowly.
- Firmware Update: LED flashes cyan rapidly.
- No application available: LED lights up cyan continuously.
- Test mode, movement: LED flashes green.
- Error: LED flashes red rapidly.
Setting Detection
The detection zone can be set via the potentiometer (E) on the back of the sensor module according to the table (See Fig. 3.7/6.1). Sensitivity of the four pyros (A to D) can be set via the app and the DALI bus. Letters A to D on the underside of the sensor housing indicate the detection direction for sensitivity settings.
Detailed information is available in the interface description on the internet at: www.steinel.de
7. Maintenance and Care
⚠️ Hazard from electrical power! Contact between water and live parts can lead to electric shock, burns, or death.
- Clean the device only when dry.
⚠️ Risk of property damage! Incorrect cleaning agents can damage the device.
- Clean the unit with a slightly damp cloth without detergent.
8. Troubleshooting
Light does not switch ON.
- No supply voltage: Check supply voltage.
- No presence detection: Ensure unobstructed sensor vision. Check detection zone.
Lights do not switch OFF.
- Objects moving in the detection zone: Check detection zone.
Sensor switches OFF despite persons being present.
- Reach set too low: Change reach.
Light switches ON despite no persons being present.
- Movement within adjacent rooms and floor levels: Adjust detection zone via potentiometer. Reduce sensitivity.
Sensor not connecting with the app.
- App or smartphone system crash: Restart mobile end device.
9. Disposal
Electrical and electronic equipment, accessories, and packaging must be recycled in an environmentally compatible manner. Do not dispose of electrical and electronic equipment as domestic waste.
EU countries only: Under the current European Directive on Waste Electrical and Electronic Equipment and its implementation in national law, electrical and electronic equipment no longer suitable for use must be collected separately and recycled in an environmentally compatible manner.
10. Conformity
STEINEL Vertrieb GmbH hereby declares that the IR Quattro HD-2 DALI-2 IPD radio equipment type conforms to Directive 2014/53/EU. The full wording of the EU Declaration of Conformity is available for downloading from the following Internet address: www.steinel.de
11. Manufacturer's Warranty
As a purchaser, you are entitled to your statutory rights against the vendor. These rights are neither curtailed nor restricted by this Warranty Declaration. STEINEL guarantees that its Professional sensor products will remain in perfect condition and proper working order for a period of 5 years. STEINEL guarantees that this product is free from material, manufacturing, and design flaws. Furthermore, STEINEL guarantees that all electronic components and cables function properly and that all materials used and their surfaces are without defects.
Making Claims
If you wish to make a claim, please send your product complete and carriage paid, along with the original receipt of purchase (showing date and product designation), to your retailer or directly to STEINEL (UK) Limited, 25 Manasty Road, Axis Park, Orton Southgate, Peterborough, PE2 6UP, for a returns number. We recommend keeping your receipt of purchase in a safe place until the warranty period expires. STEINEL assumes no liability for costs or risks involved in returning a product.
For information on making claims under the terms of the warranty, please visit: www.steinel-professional.de/garantie
If you have a warranty claim or any questions regarding your product, you are welcome to call our Service Hotline at any time: 01733 366700.
5 YEAR MANUFACTURER'S WARRANTY
Contact Information
STEINEL Vertrieb GmbH
Dieselstraße 80-84
33442 Herzebrock-Clarholz
Tel: +49/5245/448-188
www.steinel.de
Contact: www.steinel.de/contact