Power Supply Terminal Kit

For new A-Control Indoor Units

Models: PAC-SG96HR-E, PAC-SG97HR-E

Product Overview

This kit is designed to provide a separate power supply for the indoor unit and the outdoor unit. It is specifically used for PUHZ applications where this separation is required.

Product Details

PAC-SG96HR-E

Description: This kit (L/N/Earth) is used when the power supply of the indoor unit and the outdoor unit is separated. (For PUHZ applications only)

Photo: Image showing the PAC-SG96HR-E Power Supply Terminal Kit components.

Applicable Models:

Specifications:

Terminal block capacity30A/330V
Terminal block materialDenatured melamine
Parts compositionTerminal block (with lead wires connected) x 1, Screw x 1, Fastener (for binding lead wires)

Dimensions: Diagram showing dimensions for PAC-SG96HR-E: 53.8 mm height, 39.2 mm width for the terminal block base, and 120 mm total length including wires. A 24 mm dimension is also shown.

Connector: 2P (Blue)

PAC-SG97HR-E

Description: This kit (L/N) is used when the power supply of the indoor unit and the outdoor unit is separated. (For PUHZ applications only)

Photo: Image showing the PAC-SG97HR-E Power Supply Terminal Kit components.

Applicable Models:

Specifications:

Terminal block capacity15A/264V
Terminal block materialDenatured melamine
Parts compositionTerminal block (with lead wires connected) x 1, Screw x 1, Fastener (for binding lead wires)

Dimensions: Diagram showing dimensions for PAC-SG97HR-E: 36 mm height, 38 mm width for the terminal block base, and 80 mm total length including wires. An 18.5 mm dimension is also shown.

Connector: 2P (Blue)

How to Use / How to Install

This kit is used when the power supply of the indoor unit and the outdoor unit is separated (for PUHZ applications only). Refer to the installation manual of the indoor unit as well.

Provided Parts

Confirm the following parts are included:

Wiring Diagrams

1:1 System:

Diagram shows a 1:1 system wiring. It depicts connections between Outdoor unit power supply [A], Earth leakage breaker [B], Wiring circuit breaker or isolating switch [C], Outdoor unit [D], Indoor unit / outdoor unit connecting cords [E], Remote controller [F], Indoor unit [G], and Indoor unit power supply [J]. For models without heater, the indoor power supply terminal kit is required.

Note: Affix a label B (included with manuals) near each wiring diagram for the indoor and outdoor units.

Simultaneous Twin/Triple/Four System:

Diagram shows a simultaneous twin/triple/four system wiring. It depicts multiple connections for Outdoor unit power supply [A], Earth leakage breaker [B], Wiring circuit breaker or isolating switch [C], Outdoor unit [D], Indoor unit / outdoor unit connecting cords [E], Remote controller [F], Indoor unit [G], and Indoor unit power supply [J]. For models without heater, the indoor power supply terminal kits are required. [K] indicates Indoor unit earth.

Note: Affix a label B (included with manuals) near each wiring diagram for the indoor and outdoor units.

Attachment Method

PAC-SG96HR

Ceiling suspended, PCA-M-KA type:

  1. Remove the cover of the electric parts box.
  2. Attach terminal block [1] using screw [2] in the direction shown in the figure. (The terminal block attachment hole is indicated.)
  3. Change the relay connectors of the blue and yellow lead wires. Secure the ground wire using screw [4] at the position shown in the figure, and then bundle the lead wires using fastener [3]. (Visual cue: Change the yellow and blue relay connectors.)

PAC-SG97HR

Ceiling suspended for kitchens, PCA-RP71HAQ type:

  1. Remove the terminal block cover of the electric parts box.
  2. Attach terminal block [1] using screw [2] in the direction shown in the figure. (The terminal block attachment hole is indicated.)
  3. Change the relay connectors of blue and yellow lead wires, and then bundle the lead wires using fastener [3]. (Visual cue: Change the yellow and blue relay connectors.)

Ceiling concealed, PEAD-M-JA type:

  1. Remove the cover of the electric parts box.
  2. Attach terminal block [1] using screw [2] in the direction shown in the figure. (The terminal block attachment hole is indicated.)
  3. Change the relay connectors of blue and yellow lead wires. (Visual cue: Change the yellow and blue relay connectors.)

Installation Steps

  1. Electric wiring: Be sure to do the electric wiring following the steps in each indoor unit installation manual.
  2. Paste labels: Paste the labels (A-C) enveloped in the instruction document of the indoor unit near the electric wiring diagrams of both indoor and outdoor units. Paste label B for separate indoor unit/outdoor unit power supplies.
  3. DIP switch settings: It is necessary to change the settings of the DIP switch on the outdoor unit control board (when using separate indoor unit / outdoor unit power supplies only). Refer to the diagram for ON/OFF settings for SW8.
  4. Test run: Perform a test run following the steps in the installation manual of the outdoor unit.

Connector Configuration

Change of connectors (except PCA-M-KA type)

Diagram shows initial connector settings where the indoor unit is powered from the outdoor unit. It depicts connections labeled L, N, S1, S2, S3, and CND, with specific colored wires (Orange, Blue, Yellow) connected to the Indoor unit control board.

Diagram shows changed connector settings for separate indoor and outdoor unit power supplies. The connections are reconfigured, with specific colored wires (Orange, Blue, Yellow) now connected differently to the Indoor unit control board.

Connector Configuration (PCA-M-KA type)

Diagram shows initial connector settings for the PCA-M-KA type, where the indoor unit is powered from the outdoor unit. It depicts connections labeled L, N, S1, S2, S3, and CN01, with specific colored wires (Black, Blue, Yellow) connected to the Indoor unit control board.

Diagram shows changed connector settings for the PCA-M-KA type, for separate indoor and outdoor unit power supplies. The connections are reconfigured, with specific colored wires (Black, Blue, Yellow) now connected differently to the Indoor unit control board.

Optional Parts

This kit is often associated with optional parts for specific installations.

Models: PAC-SG96HR-E, Power Supply Terminal Kit, Supply Terminal Kit, Power Supply Terminal, PAC-SG96HR-E, Power Supply

File Info : application/pdf, 5 Pages, 804.86KB

PDF preview unavailable. Download the PDF instead.

Mitsubishi Electric PAC-SG96HR-E PAC-SG97HR-E Eng данные удалены

References

ABBYY FineReader 14

Related Documents

Preview Mitsubishi Electric AHU Design Guideline for PAC-IF013B-E and PAC-SIF013B-E
Design guidelines and specifications for Mitsubishi Electric's PAC-IF013B-E and PAC-SIF013B-E Air-Handling Unit (AHU) interface, covering system configurations, operation, inputs, outputs, and requirements for local AHU design.
Preview Mitsubishi Electric Ceiling Concealed Air Conditioning Units: PEFY Series Specifications and Features
Comprehensive overview of Mitsubishi Electric's PEFY series ceiling concealed air conditioning units, detailing low, medium, and high static pressure models. Features include compact design, energy efficiency, flexible installation, advanced control options, and detailed technical specifications.
Preview Mitsubishi Electric Air-Handling Unit (AHU) Design Guideline
This document provides design guidelines and notices for the use of the Mitsubishi Electric interface unit with Air-Handling Units (AHUs). It details various applications for AHU controllers and accompanying units, including basic specifications, connectable outdoor unit models, system configurations, input/output functions, and requirements for R32 refrigerant.
Preview Mitsubishi Electric PAC-IF Series Parts Catalog
Parts catalog for Mitsubishi Electric PAC-IF series interface controllers, including model numbers PAC-IF011B-E, PAC-IF012B-E, PAC-IF021B-E, PAC-IF031B-E, PAC-IF032B-E, PAC-IF013B-E, and PAC-SIF013B-E. Lists parts, specifications, and wiring diagram symbols.
Preview Mitsubishi Electric Wall-Mounted Air Conditioners (VLM/VKM Series) - Specifications and Features
Detailed information on Mitsubishi Electric's PKFY-P VLM-E and PKFY-P VKM-E wall-mounted air conditioning units, covering their sophisticated design, improved airflow control, reduced noise levels, fan and vane control, optional parts, and comprehensive technical specifications.
Preview Mitsubishi Electric PLA-M EA Cassette Indoor Units: Features, Specifications, and Installation
Comprehensive overview of Mitsubishi Electric's PLA-M EA series cassette indoor air conditioning units, detailing features like the 3D I-see Sensor, specifications, installation requirements, and available accessories.
Preview Mitsubishi Electric PAC-SC51KUA Power Supply Unit Installation Manual
This installation manual provides detailed instructions for installing the Mitsubishi Electric PAC-SC51KUA power supply unit. It covers safety precautions, product specifications, installation procedures, wiring diagrams, and M-NET transmission line length guidelines for air-conditioner control systems.
Preview Mitsubishi MSZ-GS06NA Indoor Unit Specifications and Features
Detailed specifications and features for the Mitsubishi MSZ-GS06NA 6,000 BTU/H wall-mounted indoor unit, including general features, electrical specifications, and dimensions.