User Manual for FAS models including: 009E93, FNIECT-116-104-D64, IP20 EtherCAT Bus Module, IP20, EtherCAT Bus Module, Bus Module, Module

Orderingcode:009E93 Partnumber:FNIECT-116-104-D64

Jan 17, 2025 — This manual describes as decentralized input and output modules for connecting to an industrial network. ---------------------------- ...


File Info : application/pdf, 18 Pages, 1.43MB

PDF preview unavailable. Download the PDF instead.

2-25011G33536352
USE INSTRUCTIONS
Ordering code009E93 Part numberFNI ECT-116-104-D64
[ Technical support ]
1 / 18

EtherCAT IP20 bus module user manual 64 DI/DO PNP adaptive
2 / 18

Contents
Security .......................................................................................................................................4  Expected use ......................................................................................................................4  Installation and start-up .................................................................................................... 4  Corrosion resistance .......................................................................................................... 4  Dangerous voltage .............................................................................................................4
1 Getting started guide .......................................................................................................... 6 1.1 Module overview ..............................................................................................................6 1.2 Mechanical connection .................................................................................................... 7 1.3 Electrical connections .......................................................................................................7 1.3. 1 Power interface (A-coded)........................................................................................ 7 1.3.2 Network interface (D-coded).................................................................................... 7 1.3.3 Signal port (D-SUB 25, female socket)...................................................................... 8 1.3.4 Module wiring method ............................................................................................. 9
2 Technical data ................................................................................................................. .. 10 2.1 Size ..................................................................................................................................10 2.2 Mechanical data ............................................................................................................. 11 2.3 Operating conditions ......................................................................................................11 2.4 Electrical data ................................................................................................................. 11 2.5 Network port .................................................................................................................. 11 2.6 Function indicator .......................................................................................................... 12
3 Integrated ...........................................................................................................................13 3.1 Module configuration ...................................................................................................... 13 3.1.1 Reset ........................................................................................................................13 3.1.2 Node address configuration ....................................................................................13 3.1.3 Data mapping .......................................................................................................... 13 3.2 PLC integration tutorial .................................................................................................. 13
4 Appendix........................................................................................................................... 17 4.1 Ordering information.....................................................................................................17
3 / 18

Security

 Expected use

This manual describes as decentralized input and output modules for connecting to an industrial network.

---------------------------------------------------------------------------------------------------------------------------------
 Installation and start-up
Precautions! Installation and start-up may only be performed by trained personnel. A qualified individual is one who is familiar with the installation and operation of the product and has the necessary qualifications to perform such operations. Any damage caused by unauthorized operation or illegal and improper use is not covered by the manufacturer's warranty. The equipment operator is responsible for ensuring that appropriate safety and accident prevention regulations are observed. ---------------------------------------------------------------------------------------------------------------------------------
 Corrosion resistance
Precautions! FNI modules generally have good chemical and oil resistance.When used in corrosive media (e.g. high concentrations of chemicals, oils, lubricants, coolants and other material media (i.e. very low water content), these media must be checked before the corresponding application material compatibility.If a module fails or is damaged due to this corrosive medium, a defect claim cannot be made.

---------------------------------------------------------------------------------------------------------------------------------
 Dangerous voltage
Precautions! Disconnect all power before using the device! ---------------------------------------------------------------------------------------------------------------------------------

4 / 18

 General security

Debugging and
inspection
Before debugging, read the user
manual carefully.
This system cannot be used in an environment where the safety of personnel depends on
the functionality
of the equipment.

Fault
If the defect or equipment
failure cannot be corrected, the operation
of the equipment
must be stopped to avoid damage that may be caused by unauthorized
use.
Only after the housing is fully installed can the intended use be
assured.

Owner/operator obligations
This equipment is an EMC Class
A compliant product. This device produces
RF noise.
The owner/operator
must take appropriate precautions to
use this equipment. This device can only use the power supply that matches this device, and can only connect cables approved for application.

Expected use
The warranty and limited liability statement provided by the manufacturer
does not cover damage caused by: ·Unauthorized tampering ·Improper use operation
·The instructions provided in the user manual explain the use, installation and
handling of discrepancies

5 / 18

1.1 Module overview

1 Power supply interface 2 EtherCAT output 3 DIP switch 4 EtherCAT input port 5 Module status indicator light

6 Channel 1 7 Channel 2 8 Channel 3 9 Channel 4

6 / 18

1.2 Mechanical connection

The module is installed using 4 M4 bolts or DIN35 rail snaps.

1.3 Electrical connection

1.3. 1 Power interface (A-coded)
Pin 1 2 3 4

Function

UA

+24V(Brown)

GND 0V(White)

US

+24V (Blue)

GND 0V(Black)

Powerport

System power

Auxiliary power
Illustrate: 1. It is recommended to provide Us power supply and UA power supply separately; 2. The total current of UA power supply is <4A, and the total current of Us power supply is
<4A; 3. The FE connection from the housing to the machine must be low impedance and kept as
short as possible.
1.3.2 Network interface (D-coded)

Pin

Function

1

Tx+

Send data+

2

Rx+

Receive data+

3

Tx-

Send data-

4

Rx-

Receive data-

Illustrate: Unused I/O port sockets must be covered with end caps to meet IP67 protection rating

7 / 18

1.3.3 Signal port (D-SUB 25, female socket)

Gate 1 Gate 1

Gate 2 Gate 2

Gate 3 Gate 3

Gate 4 Gate 4

None

None

None

None

None

None

None

None

Illustrate: Input signal type support: three-wire PNP, two-wire PNP, dry contact; Pin +24V single output current maximum 350mA. The total module current is <4A; The total current of each 8 channels does not exceed 1A.
8 / 18

1.3.4 Module wiring method
Independent power supply
System power Auxiliary power
In independent power supply mode, the maximum current of each module can reach 4A.
9 / 18

2.1 Size
10 / 18

2.2 Mechanical data
Shell material Housing rating according to IEC 60529 Power interface Input port/output port Size(W*H*D) Installation type Weight

Aluminum shell IP20 A-Coded DUSB-25 183.5mm*92mm*50.1mm Screw fixing or DIN35 rail mounting About 670g

2.3 Operating conditions
Operating temperature Storage temperature

-5°C ~ 80°C -25°C ~ 85°C

2.4. Electrical data
Voltage Voltage fluctuation Input current when power supply voltage is 24V Maximum load current, sensor/channel Maximum load current, actuator Total current Us Total current Ua

18~30V DCconform to EN61131-2 <1% <130mA
1A 0.5A 4A 4A

2.5 Network port
Port Port connection IEEE 802.3 compliant cable types
Data transfer rate Maximum cable length Flow control

2 x 10Base-/100Base-Tx M12D-Coded Shielded twisted pair, minimum STP CAT 5/STP CAT 5e 10/100 Mbit/s 100m Half working condition/full working condition (IEEE 802.3-PAUSE)
11 / 18

2.6 Function indicator

LED

Show

Function

PT

Blue

EtherCAT protocol

Closure

No error, device initializing

Green light flashes 2.5HZ Pre-operation: The device is in pre-operation state

X1

Green light flashes 1HZ

Safe operation: The equipment is in safe operation.

Green constant

Running: The device is running

Closure

No errors, device EtherCAT communication is

working

X2

Red light flashes 2.5HZ

Invalid configuration

Red light flashes 1HZ

local error

Red light double flash

Application monitoring timeout

Steady green

Device (IN) connected to Ethernet

L/A1

Yellow light flashes

Device (IN) sends/receives Ethernet frames

Closure

Device (IN) is not connected to Ethernet

Steady green

Device (OUT) connected to Ethernet

L/A2

Yellow light flashes

Device (OUT) sends/receives Ethernet frames

Closure

Device (OUT) is not connected to Ethernet

US

Green

Flashing red

Input voltage is normal Input voltage low (< 18 V)

Green

Output voltage is normal

UA

Flashing red

Output voltage low (< 18 V)

Red always on

No output voltage present (< 11 V)

12 / 18

3.1 Module configuration
3.1.1Restore factory settings
Steps: 1. When the device is powered off, dial 900; 2. Power on the device and wait 10 seconds; 3. Power off the device and dial the code to the state before setting; 4. Power on the device and restore it to factory status;
3.1.2 Node address configuration
The node address is assigned by the PLC: the dialing address X100=4 X10=0 X1=0, the node number is set in the PLC;
 Manual allocation of node address: Dial address X100=4, node number is X10=tens digit X1=units digit
Example: Dial code: X100=4, X10=2, X1=5 The node number is 25 Note that the maximum node number is 99. After dialing adjustment, you need to power on again;
3.1.3 Data mapping
Digital Output Mapping_Standard Output 01-08_3000_01: Channel 1~8 output signal mapping Digital Output Mapping_Standard Output 09-16_6000_02: Channel 9~16 output signal mapping Digital Output Mapping_Standard Output 01-08_3000_01: Channel 1~8 output signal mapping Digital Output Mapping_Standard Output 09-16_6000_02: Channel 9~16 output signal mapping
3.2 PLC integration tutorial
5.3.1 Omron NX1P2 Sysmac Studio integration (ECT)
1. Create a new project and determine the device type, device and hardware version, which can be obtained from the PLC side;
13 / 18

2. Click EtherCAT, pop up the main device and click Show ESI Library in the drop-down menu displayed by right-clicking;
3.Click the installation file;
4.Open the ESI configuration file downloaded in advance from the official website: FAS FNI ECT-116-104-D64 ECS V5.0.0.xml, and confirm;
14 / 18

5. Find the FAS FieldBus Modules in the toolbox on the right and double-click the module model icon to join the network;
6.Click IO variable mapping, select the added node in the I/O mapping, and fill in the name of the variable
15 / 18

7.Click the PLC online mode button. The configuration interface shows that the controller status is offline. Then right-click the master device and write the device node address. Note that the node address needs to be consistent with the previous EtherCAT slave device;
8.Find the controller in the menu bar, transfer it to the controller, download it to the PLC, and agree to confirm;
9.PLC is online, the output terminal value is set to 1, the value displays TRUE and turns orange, and the corresponding signal light of the slave device lights up.
16 / 18

4.1 Ordering information
Product ordering code FNI ECT-116-104-D64

4.Appendix
Ordering code 009E93

17 / 18

18 / 18

