Owner's Manual for PEPPERL FUCHS models including: FB9295B, FB9295B Bus Termination Module, Bus Termination Module, Termination Module

542138 FB9295B

Bus Termination Module;Bus termination module, bus and service bus termination

Bus Termination Module FB9295B

Download PDF File Datasheet FB9295B

FB9295B | PEPPERL FUCHS | Bus Termination Module

Data Sheet

Pepperl Fuchs-FB9295B, Bus Termination Module-542138 | ISC Sales


File Info : application/pdf, 2 Pages, 557.17KB

PDF preview unavailable. Download the PDF instead.

542138 eng
Bus Termination Module FB9295B
< Terminated bus, service bus < Installation in suitable enclosures in Zone 1 < Module can be exchanged under voltage in Zone 1 (hot swap; be
aware bus operation may be affected)
Bus termination module, bus and service bus termination
Function
The device acts as a bus termination resistor to ensure signals are not reflected at the end of the line. It must be used in each last station of a bus line.
Connection

Release date: 2022-06-29 Date of issue: 2022-06-29 Filename: 542138_eng.pdf

Technical Data
Supply Connection
Directive conformity Electromagnetic compatibility Directive 2014/30/EU
Conformity Electromagnetic compatibility Degree of protection Environmental test Shock resistance Vibration resistance Damaging gas Relative humidity

Zone 1
backplane bus
EN 61326-1 NE 21 IEC 60529 EN 60068-2-14 EN 60068-2-27 EN 60068-2-6 EN 60068-2-42 EN 60068-2-78

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

Pepperl+Fuchs Group www.pepperl-fuchs.com

USA: +1 330 486 0002 pa-info@us.pepperl-fuchs.com

Germany: +49 621 776 2222 pa-info@de.pepperl-fuchs.com

Singapore: +65 6779 9091 pa-info@sg.pepperl-fuchs.com

1

Bus Termination Module Technical Data

FB9295B

Ambient conditions

Ambient temperature

-20 ... 60 °C (-4 ... 140 °F)

Storage temperature

-25 ... 85 °C (-13 ... 185 °F)

Relative humidity

95 % non-condensing

Shock resistance

shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18

Vibration resistance

frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance

Damaging gas

designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3

Mechanical specifications

Degree of protection

IP20 (module) , a separate housing is required acc. to the system description

Mass

approx. 350 g

Dimensions

28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)

Data for application in connection with hazardous areas

EU-type examination certificate

PTB 97 ATEX 1074 U

Marking

1 II 2 G Ex d IIC

Directive conformity

Directive 2014/34/EU

EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006

International approvals

Marine approval

Bureau Veritas Marine

22449/B0 BV

General information

System information

The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate.

Supplementary information

EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Assembly
Front view

Release date: 2022-06-29 Date of issue: 2022-06-29 Filename: 542138_eng.pdf

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

Pepperl+Fuchs Group www.pepperl-fuchs.com

USA: +1 330 486 0002 pa-info@us.pepperl-fuchs.com

Germany: +49 621 776 2222 pa-info@de.pepperl-fuchs.com

Singapore: +65 6779 9091 pa-info@sg.pepperl-fuchs.com

2



References

Techn. ation Pepperl Fuchs iText 4.2.0 by 1T3XT