PowMr POW-HVM8.2M / POW-HVM10.2M
SOLAR INVERTER CHARGER
User Manual
1. ABOUT THIS MANUAL
This manual describes the assembly, installation, operation, and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
This manual provides safety and installation guidelines as well as information on tools and wiring.
2. SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. INTRODUCTION
This is a multi-function inverter/charger, combining functions of inverter, solar charger, and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
3.1 Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible to mains voltage or generator power
- Auto restart while AC is recovering
- Overload/ Over temperature/ short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
3.2 Basic System Architecture
The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system:
- Generator or Utility
- PV modules
Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator, and air conditioner.
3.3 Product Overview
The product overview shows the front and side views of the unit, highlighting its components:
- 1. LCD display: Shows operational status and parameters.
- 2. Status indicator: LED indicator for system status.
- 3. Charging indicator: LED indicator for charging status.
- 4. Fault indicator: LED indicator for faults.
- 5. Touch Function buttons: Buttons for user interaction.
- 6. Power on/off switch: Located on the case to turn the unit on/off.
- 7. AC input: Terminal for AC power input.
- 8. Main output: Terminal for main AC power output.
- 9. Second output: Terminal for secondary AC power output.
- 10. PV1 and PV2 input: Terminals for connecting solar panel arrays.
- 11. WIFI communication/RS-232 port: For Wi-Fi connectivity.
- 12. Battery communication/RS-485 port: For communication with batteries.
- 13. Battery input: Terminal for connecting the battery.
- 14. Anti dust kit: A component for dust protection.
4. INSTALLATION
4.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:
- The unit x 1
- User manual x 1
- Ring terminal x 1
- Mc4 terminal head x2
4.2 Preparation
Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.
4.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm on both sides and above the equipment, 50 cm below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.
4.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.
Recommended battery cable size:
Model | Wire Size | Cable (mm²) | Torque value (max) |
---|---|---|---|
8.2KW/10.2KW | 1 x 2AWG | 25 | 2 Nm |
Please follow below steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as below chart.
4. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals.
Recommended tool: #2 Pozi Screwdriver
WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
4.5 AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 63A for 8.2KW/10.2KW.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model | Gauge | Cable (mm²) | Torque Value |
---|---|---|---|
8.2KW/10.2KW | 10 AWG | 6 | 1.2 Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor 🟢 (Ground - yellow-green) first. L 🔴 (LINE - brown or black), N 🔵 (Neutral - blue).
WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
4. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. L 🔴 (LINE - brown or black), N 🔵 (Neutral - blue).
5. Make sure the wires are securely connected.
4.6 PV Connection
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Model | Wire Size | Cable (mm²) | Torque value (max) |
---|---|---|---|
8.2KW/10.2KW | 1 x 10AWG | 6 | 1.2 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL | 8.2KW/10.2KW |
---|---|
Max. PV Array Open Circuit Voltage | 500Vdc |
PV Array MPPT Voltage Range | 90Vdc~450Vdc |
Solar Panel Spec. (reference)
Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table.
SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs) | Q'ty of panels | Total input power |
---|---|---|
250Wp Vmp: 30.1Vdc Imp: 8.3A Voc: 37.7Vdc Isc: 8.4A Cells: 60 | 6 pcs | 1500W |
8 pcs | 2000W | |
12 pcs | 3000W | |
13 pcs | 3250W | |
12 pieces in serial and 3 sets in parallel | 36 pcs | 8200W |
10 pieces in serial and 4 sets in parallel | 40 pcs | 10200W |
PV Module Wire Connection
Step 1: Check the input voltage of PV array modules. The acceptable input voltage of the inverter is 90VDC-500VDC. Please make sure that the maximum current load of each PV input connector is 18A.
CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection.
Step 2: Disconnect the DC circuit breaker.
Step 3: Assemble provided PV connectors with PV modules by the following below steps.
Components for PV connectors and Tools:
Female connector housing | Female terminal | Male terminal |
Male connector housing | Crimping tool and spanner |
Cable preparation and connector assembly process:
Strip one cable 8 mm on both end sides and be careful NOT to nick conductors.
- Insert striped cable into female terminal and crimp female terminal as shown below charts.
- Insert assembled cable into female connector housing as shown below charts.
- Insert striped cable into male terminal and crimp male terminal as shown below charts.
- Insert assembled cable into male connector housing as shown below charts.
Then, use spanner to screw pressure dome tightly to female connector and male connector as shown below.
Step 4: Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
4.7 Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws.
4.8 Communication Connection
1. Wi-Fi cloud communication (option): Please use supplied communication cable to connect to inverter and Wi-Fi module. Download APP and installed from APP store, and Refer to “Wi-Fi Plug Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
2. GPRS cloud communication (option): Please use supplied communication cable to connect to inverter and GPRS module, and then applied external power to GPRS module. Download APP and installed from APP store, and Refer to “GPRS RTU Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
3. Battery communication: The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information (Baud rate: 9600).
4. Lithium battery and inverter connection: If choosing lithium battery for the inverter, only lithium batteries that have been matched with BMS communication protocol are allowed.
- a. Connect the battery according to the recommended battery cable specifications.
- b. Insert the ring terminal of the battery cable into the battery connector of the inverter flatly, and ensure that the bolts are tightened with a torque of 2-3 Nm. Make sure that the polarities of the battery and inverter are connected correctly, and that the ring terminal is tightened with the battery terminal.
- c. Connect one side of RJ45 cable to the BMS communication port of inverter.
- d. Insert the other side of RJ45 cable into RS485 communication port on lithium battery.
NOTE: If you choose a lithium battery, please make sure to connect the battery and inverter with BMS communication cable, and select the battery type as "LIB-485" mode.
Communication And Setting Of Lithium Battery
1. Connect the RJ45 communication cable between inverter and battery. Please confirm that the lithium battery BMS port's PIN is correspond with the inverter BMS communication port. The inverter BMS port's PIN definition as below:
Pin number | Port definitions |
---|---|
1 | RS485B |
2 | RS485A |
3 | NG |
4 | NG |
5 | NG |
6 | NG |
7 | RS485A |
8 | RS485B |
In order to communicate with the lithium battery BMS, you should press the “ENTER” button for a long time, and set the battery type as “LIB-485" in program 05. Then select the matching battery protocol in Program 43.
Battery type | Lithium battery protocol | |
---|---|---|
05 | AGM (default) 05 AGn Flooded 05 FLd User Defined 05 USE Lithium battery mode 05 LIB Lithium battery communication mode LIB 05 485 |
PYLON 43 PYL PACE 43 PAC |
CAUTION: When the battery type is set to “LIB-485", the setting items 12,13 and 29 are displayed in percentage.
CAUTION: When the battery type is set to “LIB-485”, the user cannot modify the maximum charging current. When communication fails, the inverter will cut off the output.
12 | When the SBU mode is selected in program 01, the battery SOC point for switching to the utility source input can be set. | The default value is 50%, and 10% ~ 50% can be set. 12 50% |
13 | When the SBU mode is selected in program 01, the SOC point for switching to the battery mode can be set. | The default value is 95%, and 30% ~ 100% can be set. 13 95% |
29 | If "LIB-485" is selected in item 05, you can set the battery low SOC shutdown point. | The default value is 20%, and 5% ~ 30% can be set. 29 20% |
In "LIB-485" mode, press and hold the "ESC" button to view the information of the lithium battery, and the inverter display screen will enter the following screen (the initial interface shows the total battery voltage and remaining battery capacity). Press the "DOWN” button to display the following data in turn.
Selectable information | LCD display |
---|---|
The data is displayed in the upper left corner of the LCD Total battery voltage = 49.9V |
The data is displayed in the upper right corner of the LCD Remaining battery capacity =91% |
Battery charging current = 0A | Battery discharge current = 1A |
Rated battery capacity = 100AH | Battery charge cycles = 12 |
Minimum MOS temperature of battery =24.3°C | Maximum MOS temperature of battery =24.2°C |
The maximum voltage of a single battery cell =3.33V | Minimum voltage of a single battery cell =3.33V |
Maximum temperature of battery cell =24.8°C | Minimum temperature of battery cell =24.9°C |
5. OPERATION
5.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the button of the case) to turn on the unit.
5.2 Operation and Display Panel
The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.
LED Indicator
LED Indicator | Messages | ||
---|---|---|---|
INV/AC 🔵 | Green | Solid On | Output is powered by utility in Line mode. |
Flashing | Output is powered by battery or PV in battery mode. | ||
CHG 🔴 | Green | Solid On | Battery is fully charged. |
Flashing | Battery is charging. | ||
FAULT 🔵 | Red | Solid On | Fault occurs in the inverter. |
Flashing | Warning condition occurs in the inverter. |
Function Keys
Function Key | Description |
---|---|
ESC | To exit setting mode |
UP | To go to previous selection |
DOWN | To go to next selection |
ENTER | To confirm the selection in setting mode or enter setting mode |
5.3 LCD Display Icons
The LCD display shows various information about the inverter's operation. The icons and their functions are described below:
Icon | Function description |
---|---|
Indicates the AC input. | |
Indicates the PV input. | |
Indicate input voltage, input frequency, PV voltage, charger current (if PV in charging for 10.2KW models), charger power, battery voltage. | |
Indicates the setting programs. | |
Indicates the warning and fault codes. Warning: Flashing with warning code. Fault: Lighting with fault code. |
|
Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current. | |
Indicates overload. | |
|
|
Indicates unit alarm is disabled. |
5.4 LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN” button to select setting programs. And then, press “ENTER” button to confirm the selection or ESC button to exit.
Setting Programs:
Program | Description | Selectable option | One-button restore setting options |
---|---|---|---|
00 | Exit setting mode | Escape (default) 00 GOE 00 GOK |
|
01 | Output source priority: To configure load power source priority | Utility first 01 USB Solar first (default) 01 S06 SBU priority 01 SBU MKS priority 01 nFS |
Utility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available. Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, utility will supply power to the loads at the same time. Battery provides power to the loads only when any one condition happens: - Solar energy and utility is not available. - Solar energy is not sufficient and utility is not available. Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12. Solar energy provides power to the loads as first priority, if solar energy is not sufficient to power all connected loads, utility energy will supply power to the loads at the same time. The battery only supplies energy to the load as a backup power. |
02 | Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) | 10A 02 10 20A 02 20 30A 02 30 40A 02 40 50A 02 50 60A 02 60 70A 02 70 80A 02 80 90A 02 90 100A (default) 02 100 110A 02 110 120A 02 120 130A 02 130 140A 02 140 150A 02 150 160A 02 160 |
|
03 | AC input voltage range | Appliances (default) 03 APL UPS 03 UPS |
If selected, acceptable AC input voltage range will be within 90-280VAC. If selected, acceptable AC input voltage range will be within 170-280VAC. |
05 | Battery type | AGM (default) 05 AGn Flooded 05 FLd User-Defined 05 USE LIB-485 LIB 05 LIB When using lithium battery and not connected to BMS communication |
If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29. |
06 | Auto restart when overload occurs | Restart disable (default) 06 LFd Restart enable 06 LFE |
|
07 | Auto restart when over temperature occurs | Restart disable (default) 07 EF8 Restart enable 07 EYE |
|
09 | Output frequency | 50Hz (default) 09 50 60Hz 09 60 |
|
10 | Output voltage | 220V 10 220 230V (default) 10 230 240V 10 240 |
|
11 | Maximum utility charging current Note: If setting value in program 02 is smaller than that in program 11, the inverter will apply charging current from program 02 for utility charger. |
2A 11 28 10A 11 108 20A 11 208 30A 11 308 40A 11 408 50A 11 508 60A 11 608 70A 11 708 80A (default) 11 808 90A 11 908 100A 111008 110A 111108 120A 111208 130A 111308 140A 111408 |
|
12 | Setting voltage point back to utility source when selecting "SBU priority" or "Solar first" in program 01. | Available options in 8.2KW/10.2KW model: 42V 12 42 43V 12 43 44V 12 44 45V 12 45 46V (default) 12 46 47V 12 47 48V 12 48 49V 12 49 50V 12 50 51V 12 51 |
|
13 | Setting voltage poing back to battery mode when selecting "SBU priority" or "Solar first" in program 01. | Available options in 8.2KW/10.2KW model: 10% 13 10 15% 13 15 20% 13 20 25% 13 25 30% 13 30 35% 13 35 40% 13 40 45% 13 45 50%(default) 13 50 55% 13 55 60% 13 60 65% 13 65 70% 13 70 75% 13 75 80% 13 80 85% 13 85 90% 13 90 95%(default) 13 95 100% 13 100 Available options in 8.2KW/10.2KW model: Battery fully charged 48V 13 BATT FÜL 13 48.0 49V 13 BATT 49.0 50V 13 BATT 50.0 51V 13 BATT 51.0 52V 13 BATT 52.0 53V 13 BATT 53.0 54V (default) 13 BATT 54.0 55V 13 BATT 55.0 56V 13 BATT 56.0 57V 13 BATT 57.0 58V 13 BATT 58.0 |
When the power is lower than the set value, it will auto matically switch back to the public power output (if the public power access has a delay, it will be switched to the public power after the delay time after the power is lower than the set value.) When the battery power is higher than the set value, it will automatically switch back to the battery mode output (when the set value is 100, it will automatically switch when the battery power is 100%). |
16 | Charger source priority: To configure charger source priority | Solar first 16 050 Solar and Utility (default) 16 SNU Only Solar 16 050 |
Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available. Solar energy and utility will charge battery at the same time. Solar energy will be the only charger source no matter utility is available or not. If this inverter/charger is working in Battery mode or Power saving mode, only solar energy can charge battery. Solar energy will charge battery if it's available and sufficient. |
18 | Alarm control | Alarm on (default) 18 600 Alarm off 18 60F |
|
19 | Auto return to default display screen | Return to default display screen (default) 19 ESP Stay at latest screen 19 HEP |
If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage /output voltage) after no button is pressed for 1 minute. If selected, the display screen will stay at latest screen user finally switches. |
20 | Backlight control | Backlight on (default) 20 LON Backlight off 20 LOF |
|
22 | Beeps while primary source is interrupted | Alarm on (default) 22 AON Alarm off 22 AOF |
|
23 | Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. | Bypass disable (default) 23 698 Bypass enable 23 698 |
|
25 | Record Fault code | Record enable (default) 25 FEN Record disable 25 FdS |
|
26 | Bulk charging voltage (C.V voltage) | 8.2KW/10.2KW default setting: 56.4V BATT C 26 56.4 V |
If self-defined is selected in program 5, this program can be set up. Setting range is from 48.0V to 61.0V for 8.2KW/10.2KW model. Increment of each click is 0.1V. |
27 | Floating charging voltage | 8.2KW/10.2KW default setting: 54.0V BATT FLY 27 54.0 V |
If self-defined is selected in program 5, this program can be set up. Setting range is from 48.0V to 61.0V for 8.2KW/10.2KW model. Increment of each click is 0.1V. |
29 | Low DC cut-off voltage | 8.2KW/10.2KW default setting: 40.0V BATT C09 29 40.0 V If "LIB-485" is selected in item 05. you can set the battery low SOC shutdown point. 29 20% |
If self-defined is selected in program 5, this program can be set up. Setting range is from 40.0V to 48.0V for 8.2KW/10.2KW model. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected. The default value is 20%, and 5% ~30% can be set. |
30 | Battery equalization | Battery equalization enable 30 EEN Battery equalization disable (default) 30 Eds |
If "Flooded" or "User-Defined” is selected in program 05, this program can be set up. |
31 | Battery equalization voltage | 8.2KW/10.2KW default setting: 58.4V BATT EV 31 58.4 V |
Setting range is from 48.0V to 61.0V for 8.2KW/10.2KW model. Increment of each click is 0.1V. |
33 | Battery equalized time | 60min (default) 33 60 |
Setting range is from 5min to 900min. Increment of each click is 5min. |
34 | Battery equalized timeout | 120min (default) 34 120 |
Setting range is from 5min to 900 min. Increment of each click is 5 min. |
35 | Equalization interval | 30days (default) 35 308 |
Setting range is from 0 to 90 days. Increment of each click is 1 day. |
36 | Equalization activated immediately | Enable 36 AEN Disable (default) 36 AdS |
If equalization function is enabled in program 30, this program can be set up. If "Enable" is selected in this program, it's to activate battery equalization immediately and LCD main page will shows E9. If "Disable” is selected, it will cancel equalization function until next activated equalization time arrives based on program 35 setting. At this time, E9 will not be shown in LCD main page. |
37 | GRID-tie operation | Off grid (default) 37 OFF Hybrid 37 HYD |
Inverter operates only in off-grid mode. Solar energy provides power to the loads as first priority and charging second. Inverter operates hybrid mode. Solar energy provides power to the loads as first priority and charging second. Excess energy feed to grid. |
38 | GRID-tie current | 10A 38 10 A |
Increment of each click is 2A. |
39 | Led pattern light | Led pattern off 39 LOF Led pattern on(default) 39 LON |
|
41 | Dual output | disable (default) 41 L2F use 41 L20 |
|
42 | Enter the dual output functional voltage point | 8.2KW/10.2KWw default setting: 44.0V 42 44.0 V Available options in 8.2KW/10.2KW model: 5% 42 5 10% 42 10 15% 42 15 20% 42 20 25% 42 25 30% 42 30 35% 42 35 40% 42 40 45% 42 45 50% 42 50 55%(default) 42 55 60% 42 60 65% 42 65 70% 42 70 75% 42 75 80% 42 80 85% 42 85 |
Setting range is from 40.0V to 52.0 V for 48VDC model. Increment of each click is 0.1V. When the power is lower than the set value or battery low voltage alarm, the main output of the inverter is disconnected, and the main output no longer supplies power to the external. |
43 | Lithium battery protocol | PYLON (default) 43 PYL PACE 43 PAC |
|
44 | Delayed grid access | disable 44 015 enable(default) 44 ENA |
|
45 | Maximum Second Load | 20%~70% | If the inverter enter the dual output function, the output power of the second channel, can be change to 20%~70% of the rated power. |
5.5 Display Setting
The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, main CPU Version.
Selectable information | LCD display |
---|---|
Input voltage=222V, PV1 voltage=168V, Battery voltage=25V, Output voltage=222V, Load in Watt=188W, Chg(Flashing), Inv/ac(bright) | |
Input voltage=223V, PV1 current=2.3A, Battery current=20A, Output voltage=224V, Load in VA=188VA, Chg(Flashing), Inv/ac(bright) | |
Input voltage=223V, PV1ntc temperture=71.0℃, Battery voltage=25V, Inv ntc temperture=35.0℃, Load percentage=12%, Chg(Flashing), Inv/ac(bright) | |
Input voltage=222V, PV2 voltage=168V, Battery voltage=25V, Output voltage=222V, Load in Watt=1.18KW, Chg(Flashing), Inv/ac(bright) | |
Input voltage=224V, PV2 current=8.6A, Battery current=12.5A, Output voltage=222V, Load in VA=1.88KVA, Chg(Flashing), Inv/ac(bright) | |
Input frequency=50.0Hz, PV2 power=1.434KWh, Battery current=20A, Output frequency=50.0Hz, Load in watt=1.18KW, Chg(Flashing), Inv/ac(bright) | |
Main CPU version checking |
5.6 Operating Mode Description
Operation mode | Selectable information | LCD display |
---|---|---|
Stand by mode/ Power saving mode Note: *standby mode: The inverter is not turned on yet but at this time, the inverter can charge battery without AC output. *Power saving mode: If enabled, the output of inverter will be off when connected load is pretty low or not detected. |
No output is supplied by the unit but it still can charge batteries. | |
Line Mode | The unit will provide output power from the mains. It will also charge the battery at line mode. | |
Grid-Tie operation | When working in Grid -Tie mode, the ⚡ will be flash 3S/times. | |
Battery Mode | The unit will provide output power from battery and power. | |
5.7 Battery Equalization Description
Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.
How to Apply Equalization Function
You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods:
- Setting equalization interval in program 35.
- Active equalization immediately in program 36.
When to Equalize
In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.
In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.
5.8 Mains and lithium battery activation function
- After 90s of mains power connection to the inverter, the machine is connected to the mains and starts to work.
- The inverter is in lithium battery mode (item 05 is LIB or LIB-485). After the mains is connected, the battery is not connected, and the mains activation function is automatically enabled.
5.9 Fault Reference Code
Fault Code | Fault Event | Icon on |
---|---|---|
01 | Fan is locked when inverter is off. | |
02 | Over temperature | |
03 | Battery voltage is too high | |
04 | Battery voltage is too low | |
05 | Output short circuited or over temperature is detected by internal converter components. | |
06 | Output voltage is too high. | |
07 | Overload time out | |
08 | Bus voltage is too high | |
09 | Bus soft start failed | |
51 | Over current or surge | |
52 | Bus voltage is too low | |
53 | Inverter soft start failed | |
55 | Over DC voltage in AC output | |
57 | Current sensor failed | |
58 | Output voltage is too low | |
59 | PV voltage is over limitation |
5.10 Warning Indicator
Warning Code | Warning Event | Audible Alarm | Icon flashing |
---|---|---|---|
01 | Fan is locked when inverter is on. | Beep three times every second | |
03 | Battery is over-charged | Beep once every second | |
04 | Low battery | Beep once every second | |
07 | Overload | Beep once every 0.5 second | |
10 | Output power derating | Beep twice every 3 seconds | |
15 | PV energy is low. | Beep twice every 3 seconds | |
E9 | Battery equalization | None | |
6P | Battery is not connected | None |
6. CLEARANCE AND MAINTENANCE FOR ANTI-DUST KIT
6.1 Overview
Every inverter is already installed with anti-dust kit from factory. Inverter will automatically detect this kit and activate internal thermal sensor to adjust internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environment.
6.2 Clearance and Maintenance
Step 1: Please loosen the screw in counterclockwise direction on the top of the inverter.
Step 2: Then, dustproof case can be removed and take out air filter foam as shown in below chart.
Step 3: Clean air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
7. SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL | 8.2KW | 10.2KW |
---|---|---|
Input Voltage Waveform | Sinusoidal (utility or generator) | |
Nominal Input Voltage | 230Vac | |
Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) |
|
Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) |
|
High Loss Voltage | 280Vac±7V | |
High Loss Return Voltage | 270Vac±7V | |
Max AC Input Voltage | 300Vac | |
Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
Low Loss Frequency | 40±1Hz | |
Low Loss Return Frequency | 42±1Hz | |
High Loss Frequency | 65±1Hz | |
High Loss Return Frequency | 63±1Hz | |
Output Short Circuit Protection | Circuit Breaker | |
Efficiency (Line Mode) | >95% (Rated R load, battery full charged ) | |
Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) |
|
Output power derating: When AC input voltage drops to 170V, the output power will be derated. |
Table 2 Inverter Mode Specifications
INVERTER MODEL | 8.2KW | 10.2KW |
---|---|---|
Rated Output Power | 8.2KW | 10.2KW |
Output Voltage Waveform | Pure Sine Wave | |
Output Voltage Regulation | 230Vac±5% | |
Output Frequency | 50Hz | |
Peak Efficiency | 93% | |
Overload Protection | 3s@≥150% load; 5s@101%~150% load | |
Surge Capacity | 2* rated power for 5 seconds | |
Nominal DC Input Voltage | 48Vdc | |
Cold Start Voltage | 46.0Vdc | |
Low DC Warning Voltage | @load < 50% 44.0Vdc |
@load ≥ 50% 42.0Vdc |
Low DC Warning Return Voltage | @load < 50% 45.0Vdc |
@load ≥ 50% 44.0Vdc |
Low DC Cut-off Voltage | @load < 50% 41.0Vdc |
@load ≥ 50% 40.0Vdc |
High DC Recovery Voltage | 62Vdc | |
High DC Cut-off Voltage | 63Vdc | |
No Load Power Consumption | 70W | 75W |
Table 3 Two Load Output Power
INVERTER MODEL | 8.2KW | 10.2KW |
---|---|---|
Full Load | 8200W | 10200W |
Maximum Main Load | 8200W | 10200W |
Second Load Range | 1640W~5740W | 2040W~7140W |
Main Load Cut Off Voltage | 52VDC | |
Main Load Return Voltage | 54VDC |
Table 4 Charge Mode Specifications
Utility Charging Mode | INVERTER MODEL | 8.2KW | 10.2KW |
---|---|---|---|
Charging Algorithm | 3-Step | 3-Step | |
AC Charging Current (Max) | 140Amp | 140Amp | |
Bulk Charging Flooded Battery Voltage | 58.4 | 58.4 | |
AGM / Gel Battery Floating Charging Voltage | 56.4 | 56.4 | |
MPPT Solar Charging Mode | INVERTER MODEL | 8.2KW | 10.2KW |
---|---|---|---|
Max. PV Array Power | PV1 Channel:5400W PV2 Channel:5400W |
PV1 Channel:5400W PV2 Channel:5400W |
|
IMax.PV | PV1 Channel:18A PV2 Channel:18A |
PV1 Channel:18A PV2 Channel:18A |
|
Nominal PV Voltage | 360Vdc | ||
PV Array MPPT Voltage Range | 90Vdc~450Vdc | ||
Max. PV Array Open Circuit Voltage | 500Vdc | ||
Max Charging Current (AC charger plus solar charger) | 160Amp |
Table 5 Grid-Tie Operation
INVERTER MODEL | 8.2KW | 10.2KW |
---|---|---|
Nominal Output Voltage | 220/230/240 VAC | |
Feed-in Grid Voltage Range | 195~253VAC | |
Feed-in Grid Frequency Range | 50±1Hz/60±1Hz | |
Nominal Output Current | 35.6A | 44.3A |
Power Factor Range | >0.99 | |
Maximum Conversion Efficiency (DC/AC) | 98% |
Table 6 General Specifications
INVERTER MODEL | 8.2KW | 10.2KW |
---|---|---|
Safety Certification | CE | |
Operating Temperature Range | -10°C to 50°C | |
Storage temperature | -15°C~60°C | |
Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
Dimension (D*W*H), mm | 14.5 | 14.7 |
Net Weight, kg | 38 | 38 |
8. TROUBLE SHOOTING
Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
---|---|---|---|
Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. |
1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
Mains exist but the unit works in battery mode. | Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. |
Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance) Change output source priority to Utility first. |
|
Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. |
Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
Fault code 02 | Temperature of internal converter component is over 120°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
Fault code 03 | Internal temperature of inverter component is over 100°C. | Return to repair center. | |
Fault code 01 | Battery is over-charged. | Check if spec and quantity of batteries are meet requirements. | |
Fault code 06/58 | The battery voltage is too high. | Replace the fan. | |
Fault code 08/09/53/57 | Fan fault | 1. Reduce the connected load. 2. Return to repair center |
|
Fault code 51 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | Return to repair center. | |
Fault code 52 | Internal components failed. | Restart the unit, if the error happens again, please return to repair center. | |
Fault code 55 | Over current or surge. | ||
Bus voltage is too low. | |||
Output voltage is unbalanced. |
9. APPENDIX: Approximate Back-up Time Table
Model | Load (W) | Backup Time @ 48Vdc 100Ah (min) | Backup Time @ 48Vdc 200Ah (min) |
---|---|---|---|
8.2KW 10.2KW |
500 | 613 | 1288 |
1000 | 268 | 613 | |
1500 | 158 | 402 | |
2000 | 111 | 271 | |
2500 | 90 | 215 | |
3200 | 76 | 182 | |
3500 | 65 | 141 | |
4000 | 50 | 112 | |
4500 | 44 | 100 | |
5000 | 40 | 90 | |
6200 | 36 | 80 | |
7200 | 32 | 70 | |
8200 | 28 | 60 | |
9200 | 24 | 50 | |
10200 | 20 | 40 |
Note:1. Backup time depends on the quality of the battery, age of battery and type of battery. Specifications of batteries may vary depending on different manufacturers.
2. The final interpretation right of this product belongs to the company.