Heating with Lower-Temperature Hot Water

Engineers Newsletter | Volume 51-4 | August 2022

Introduction

This Engineers Newsletter examines how to select coils for lower hot-water supply temperatures, in order to maximize the performance of newer heating systems driven by decarbonization and electrification trends.

Decarbonization and Electrification in HVAC

Sustainability is a key focus, leading to increased interest in reducing the carbon footprint of buildings. In HVAC, decarbonization typically involves:

  • Improving overall system energy efficiency to reduce emissions.
  • Using refrigerants with a low Global Warming Potential (GWP) and minimizing leakage.
  • Reducing fossil fuel use by installing electrified HVAC equipment powered by carbon-free energy sources (solar, wind, renewables).

Electrification can present a challenge for building heating.

Electrified Heating Solutions

Electrified heating solutions include resistance-based electric heat, heat pumps (air-to-air or air-to-water), and heat recovery systems. For hydronic systems, the hot-water supply (HWS) temperature is a critical variable affecting performance.

Figure 1 & 2 Description: Graphs illustrating the impact of Hot-Water Supply (HWS) and outdoor temperatures on the heating Coefficient of Performance (COP) and capacity of an Air-to-Water Heat Pump (AWHP). Higher COP indicates better efficiency. Lower HWS temperatures generally lead to higher COP and capacity, especially in colder outdoor conditions.

Impact of Hot-Water Supply Temperature on Heating Coil Selection

While the choice of hot-water supply temperature also impacts the sizing and selection of piping, pumps, and valves, this newsletter focuses on how this choice impacts the selection of hot-water coils in various HVAC equipment types: VAV terminal units, multiple-zone VAV air-handling units, fan-coil units, dedicated (100-percent) outdoor air-handling units, and single-zone VAV air-handling units.

General Impact: Designing for lower HWS temperatures typically requires coils with more rows, leading to higher fluid flow rates. This affects the sizing and cost of piping, pumps, and valves, and can increase pumping energy use. However, it also increases the capacity and efficiency of heating equipment, reducing overall heating energy consumption. The goal is to balance these factors for optimal installed cost and energy use.

VAV Terminal Units

When a zone requires heating, the hot-water coil in a single-duct VAV terminal unit heats the supply air.

Figure 3 Description: An example VAV terminal unit operating at a design heating condition. It receives 325 cfm of 60°F primary air and heats it to 90°F using a hot-water coil with a capacity of 10,600 Btu/h.

Table 1: Example VAV Terminal Unit Selections
Hot-water supply temperature (°F) Coil rows Inlet (VAV damper) diameter, in. Coil heating capacity, Btu/h Entering fluid temperature, °F Leaving fluid temperature, °F Fluid flow rate, gpm Fluid pressure drop, ft. H₂O Airside pressure drop at design cooling airflow, in. H₂O Airside pressure drop at maximum heating airflow, in. H₂O
1801810,6001801320.440.660.230.06
1402810,6001401180.950.100.430.11
1053810,600105983.271.130.630.16
1054810,600105931.710.450.830.21
10531010,600105911.520.700.310.08
10541010,600105851.050.510.410.10

Note: The table assumes design cooling airflow = 650 cfm, minimum airflow = 130 cfm (165 cfm for 10-in. inlet diameter), and maximum heating airflow = 325 cfm, using the "dual maximums" control sequence.

For lower HWS temperatures, VAV terminal units often require multiple-row coils. Upsizing the VAV terminal unit can help minimize impacts on pumping and fan energy use.

Multiple-Zone VAV Air-Handling Units

A hot-water coil in a multiple-zone VAV system's central air-handling unit warms supply air during cold weather to prevent excessively cold air from reaching zones.

Figure 4 Description: An example multiple-zone VAV air-handling unit operating at a design heating condition. It mixes 10°F outdoor air (OA) with 70°F recirculated air (RA) to create 40°F mixed air (MA), which is then heated by a hot-water coil to 60°F before distribution.

Table 2: Example Multiple-Zone VAV Air-Handling Hot-Water Coil Selections
Hot-water supply temperature (°F) Coil rows Fin density, fins/ft Coil heating capacity, Btu/h Entering fluid temperature, °F Leaving fluid temperature, °F Fluid flow rate, gpm Fluid pressure drop, ft. H₂O Airside pressure drop of coil at design supply airflow, in. H₂O Airside pressure drop of coil at design heating condition, in. H₂O
18018086,800180751.650.150.0910.017
14018086,800140812.920.410.0910.017
10518086,8001059112.85.510.0910.024
105112086,800105705.001.100.1210.024

Note: Design supply airflow = 10,000 cfm, supply airflow at design heating condition = 4000 cfm.

While a one-row coil can still provide capacity, it requires a higher fluid flow rate. Increasing fin density can help reduce fluid flow rate and pressure drop, though it slightly increases airside pressure drop.

Consider incorporating exhaust-air energy recovery to preheat incoming outdoor air, reducing the load on the heating coil.

Fan-Coil (or Blower-Coil) Units

Fan-coil units are often the most challenging for lower HWS temperatures due to limited coil options and space constraints. Using a "changeover coil" for both cooling and heating is a common strategy.

Figure 5 Description: Illustrates a four-pipe distribution system for fan-coil units, featuring a shared (changeover) coil used for both cooling and heating. It shows the flow paths for chilled and hot water, with diverting valves on the return and supply sides to manage the changeover.

Table 3: Example Fan-Coil Unit Selections
Hot-water supply temperature (°F) Coil rows Coil heating capacity, Btu/h Entering fluid temperature, °F Leaving fluid temperature, °F Fluid flow rate, gpm Fluid pressure drop, ft. H₂O Airside pressure drop of unit, in. H₂O
1801 (HW)
2 (CHW)
32,6001801030.850.050.30
1402 (HW)
2 (CHW)
32,6001401031.390.290.32
1102 (HW)
2 (CHW)
32,600110829.064.320.32
1054 (changeover)32,600105822.830.840.39

Note: The example involves heating 1200 cfm of 65°F recirculated air to 90°F discharge air.

Using a four-row changeover coil offers advantages in fluid flow rate, pressure drop, and airside pressure drop compared to multiple standard coils, while also allowing more rows for cooling.

Upsizing the fan-coil unit can also facilitate the use of lower HWS temperatures. Blower-coil units, designed for ducted applications, often offer more coil rows and are well-suited for lower HWS temperatures.

Dedicated (100-percent) Outdoor Air-Handling Units (DOAS)

In a DOAS, a hot-water coil heats cold outdoor air to a suitable discharge-air temperature for zones, typically no warmer than 70°F.

Table 4: Example DOAS Hot-Water Coil Selections
Hot-water supply temperature (°F) Coil rows Coil heating capacity, Btu/h Entering fluid temperature, °F Leaving fluid temperature, °F Fluid flow rate, gpm Fluid pressure drop, ft. H₂O Airside pressure drop of coil, in. H₂O
1802 (HW)
8 (CHW)
325,00018012211.30.390.12 (HW)
1.21 (CHW)
1402 (HW)
8 (CHW)
325,00014010016.30.780.15 (HW)
1.21 (CHW)
1054 (HW)
8 (CHW)
325,0001057521.70.410.34 (HW)
1.21 (CHW)
1058 (changeover)325,0001055713.50.301.21

Note: The example involves heating 5000 cfm of 10°F outdoor air to 70°F discharge air.

An eight-row changeover coil provides benefits in flow rate, pressure drop, and airside pressure drop, as only a single coil is in the airstream. Many DOAS units include exhaust-air energy recovery, which reduces the heating coil's capacity requirement.

Single-Zone VAV Air-Handling Units

In a single-zone VAV AHU, the hot-water coil heats supply air to a temperature warmer than the zone.

Table 5: Example Single-Zone VAV Air-Handling Unit Hot-Water Coil Selections
Hot-water supply temperature (°F) Coil rows Coil heating capacity, Btu/h Entering fluid temperature, °F Leaving fluid temperature, °F Fluid flow rate, gpm Fluid pressure drop, ft. H₂O Airside pressure drop of coil, in. H₂O
1802 (HW)
6 (CHW)
86,8001801505.780.050.13 (HW)
0.53 (CHW)
1402 (HW)
6 (CHW)
86,8001401208.690.290.17 (HW)
0.53 (CHW)
1054 (HW)
6 (CHW)
86,800105858.701.000.39 (HW)
0.53 (CHW)
1056 (changeover)86,800105817.240.980.53

Note: The example involves heating 2000 cfm from 50°F to 90°F discharge air.

A six-row changeover coil offers advantages in fluid flow rate, pressure drop, and airside pressure drop. Incorporating exhaust-air energy recovery can also reduce the heating coil's capacity requirement.

Conclusion

Providing the necessary heating capacity with a lower hot-water supply (HWS) temperature requires a higher fluid flow rate, which increases the size and cost of pipes, pumps, and valves, and likely increases pumping energy use. However, a lower HWS temperature increases both the capacity and efficiency of the heating equipment, which reduces the size of this equipment and reduces heating energy use. Finding the right balance optimizes both installed cost and overall system energy use.

Table 6: General Recommendations for Designing a Heating System for a Lower Hot-Water Supply Temperature
Equipment type Typical minimum HWS temperature (°F) Expected fluid ΔT at minimum HWS temperature (°F) General recommendations
VAV terminal units100 to 1058 to 20
  • Implement the "dual maximums" control sequence.
  • Select hot-water coils with multiple rows.
  • Consider upsizing the VAV terminal unit.
Multiple-zone VAV air-handling units80 to 10518 to 30
  • Include a centralized heating coil.
  • Implement supply-air temperature reset.
  • Incorporate exhaust-air energy recovery.
Fan-coil or blower-coil units95 to 1158 to 30
  • Select hot-water coils with multiple rows.
  • Use a changeover coil.
  • Possibly consider upsizing the fan-coil unit.
Dedicated outdoor air-handling units8020 to 40
  • Consider using a changeover coil.
  • Incorporate exhaust-air energy recovery.
Single-zone VAV air-handling units100 to 10512 to 26
  • Consider using a changeover coil.
  • Incorporate exhaust-air energy recovery.

PDF preview unavailable. Download the PDF instead.

ADM-APN084-EN Acrobat Distiller 22.0 (Windows)

Related Documents

Preview CO2-Based Demand-Controlled Ventilation with ASHRAE Standard 62.1-2004 | Trane Engineers Newsletter
This Trane Engineers Newsletter article explores CO2-based Demand-Controlled Ventilation (DCV) and its implementation under ASHRAE Standard 62.1-2004. It highlights how DCV can reduce HVAC operating costs by adjusting ventilation based on occupancy, primarily using CO2 sensors as indicators.
Preview Heat Recovery System at 55 Water Street Drives NYC Local Law 97 Compliance and Energy Savings
Discover how 55 Water Street's electrification retrofit with a Trane heat recovery system achieved NYC Local Law 97 compliance, significant energy savings, and improved building performance.
Preview Trane® Domestic Hot Water Heat Pumps: Energy-Efficient Solutions for Commercial Buildings
Discover Trane's Domestic Hot Water Heat Pumps (DHWHPs) for commercial buildings. Learn how these efficient, sustainable solutions capture waste heat to reduce energy costs and improve building performance. Explore features, applications, and model options.
Preview Trane Applications Engineering Manual: Dehumidification in HVAC Systems
This Trane Applications Engineering Manual details dehumidification processes in commercial HVAC comfort-cooling systems, covering psychrometric analysis, system performance, and optimization techniques for engineers.
Preview Trane Air-to-Water Heat Pump System Application Guide
This application guide from Trane details the use of air-to-water heat pump hydronic systems for cooling and heating, including a cascade option for higher heating temperatures. It covers system design considerations, piping, airside aspects, and operation. The guide is intended for engineering professionals, architects, building owners, operators, and technicians.
Preview Trane Thermafit AXM Air-to-Water Heat Pump Installation, Operation, and Maintenance Manual
Comprehensive guide for the Trane Thermafit™ Air-to-Water Heat Pump, Model AXM, covering installation, operation, maintenance, safety, and troubleshooting for HVAC professionals.
Preview ASHRAE Standard 15-2022 A2L EDVC Example for Ducted Water-Source Heat Pumps
An example illustrating the calculation of Effective Dispersal Volume Charge (EDVC) for ducted water-source heat pumps using A2L refrigerants, based on ASHRAE Standard 15-2022, from Trane.
Preview Trane Modular Domestic Hot Water Heat Pump Array Installation, Operation, and Maintenance Manual
Comprehensive guide for the installation, operation, and maintenance of Trane's Modular Domestic Hot Water Heat Pump Array. This manual covers safety warnings, environmental concerns, performance specifications, electrical requirements, physical dimensions, and troubleshooting for various models.