BSAGINAW CONTROL & ENGINEERING A/C USER MANUAL 5 back to top 6. Technical Data Part Number SCE-TE340B24VSS Cooling Capacity @ 95°F / 95°F 340 BTU (100 Watts) Operating Temperature Range -4°F - 149°F

Thermoelectric Coolers - SCE-TE340B24VSS

Installation Manual Index | Saginaw Control and Engineering


File Info : application/pdf, 15 Pages, 1.44MB

PDF preview unavailable. Download the PDF instead.

SCE-TE340B24VSS
BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

1

User Manual SCE-TE340B24VSS
1. User Manual ............................................................................................ p. 2 2. Legal Regulations................................................................................... p. 2 3. Safety Instructions ................................................................................. p. 3 4. Technical Information............................................................................. p. 4 5. Functional Principle ............................................................................... p. 4 6. Technical Data......................................................................................... p. 5 7. Performance Graph ................................................................................ p. 6 8. Mounting.................................................................................................. p. 7 9. Cutout Dimensions................................................................................. p. 8 10. Dimensions (H x W x D) ......................................................................... p. 9 11. Electrical Connection ............................................................................. p. 10 12. Wiring Diagram ....................................................................................... p. 11 13. Taking Into Operation ............................................................................. p. 12 14. Repair....................................................................................................... p. 12 15. Maintenance & Cleaning ........................................................................ p. 12 16. Maintenance ............................................................................................ p. 13 17. Transportation & Storage....................................................................... p. 14 18. Parts Supplied......................................................................................... p. 14 19. Warranty / Limits of Liability ................................................................. p. 15

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

2

1. User Manual
This instruction manual contains information and instructions to enable the user to work safely, correctly and economically on the unit. Understanding and adhering to the manual can help one:
· Avoid any dangers · Reduce repair costs and stoppages · Extend and improve the reliability and working life of the unit

PLEASE ENSURE TO USE THE RIGHT VERSION OF THE INSTRUCTION MANUAL SUITABLE FOR YOUR UNIT
Conditions of Use The unit is to be used exclusively for the dissipation of heat from control cabinets and enclosures in order to protect temperature sensitive components in an industrial environment. To meet the conditions of use, all the information and instructions in the instruction manual must be adhered to.
General Danger Indicates compulsory safety regulations which are not covered by a specific pictogram such as one of the following.
High Electric Voltage Indicates electric shock danger.

Important Safety Instruction Indicates instructions for safe maintenance and operation of the unit.

Attention Indicates possible burns from hot components.

Attention Indicates possible damage to the unit.

Instruction Indicates possible danger to the environment.

2. Legal Regulations
Liability The information, data and instructions contained in this instruction manual are current at the time of going to press. We reserve the right to make technical changes to the unit in the course of its development. Therefore, no claims can be accepted for previously delivered units based on the information, diagrams or descriptions contained in this manual. No liability can be accepted for damage and production caused by:
· Disregarding the instruction manual · Operation error · Inappropriate work on or with the unit · The use of non-specified spare parts and accessories · Unauthorized modifications or changes to the unit by the user or his personnel
Saginaw Control & Engineering is only liable for errors and omissions as outlined in the guarantee conditions contained in the main contractual agreement. Claims for damages on any grounds are excluded.
back to top

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

3

3. Safety Instructions
Upon delivery the unit is already meeting current technical standards, therefore it can be safely taken into operation. Only trained specialists are allowed to work on the unit. Unauthorized personnel must be prohibited from working on the unit. Operating personnel must inform their superiors immediately if any malfunction of the unit becomes apparent.
Please note that before starting to work on or with the unit, a procedure must be carried out inside the cabinet on which the unit is to be mounted.
Before commencing work inside the cabinet, the control cabinet manufacturer's instruction must be read with regards to: · Safety instructions · Instructions on taking the cabinet out of operation · Instructions on the prevention of unauthorized cabinet reconnection
The electric equipment meets the valid safety regulations. One can find dangerous voltage (above 50V AC or above 100V DC):
· Behind the control cabinet doors · On the power supply in the unit housing
The units have to be fused according to the type plate and the wiring diagram. Switch the unit off immediately if the electric power supply is interrupted.

Danger Through Incorrect Work on the Unit Only specialized personnel are allowed to maintain and clean the unit. Regular maintenance and cleaning must be kept in order to ensure that the unit remains in perfect working condition and has a long working life.

Danger from Electric Voltage Only specialized personnel are allowed to maintain and clean the unit. The personnel must ensure that for the duration of the maintenance and cleaning, the unit is disconnected from the electrical supply.

Attention Damage to the unit through the use of inappropriate cleaning materials. Please do not use aggressive cleaning material.

Instruction Damage to the environment through unauthorized disposal. All spare parts and associated material must be disposed of according to the environmental laws.

back to top

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

4

4. Technical Information
Peltier cooling units are intended to be used as a complementary accessory to larger industrial equipment. They are used where heat needs to be dissipated from electrical control cabinets or similar enclosures in order to protect heat sensitive components.
Peltier cooling units can dissipate heat from sealed enclosures such as control cabinets. At the same time they can reduce the cabinet internal temperature to below the ambient air temperature. They are available in powder-coated sheet steel or stainless steel housings. Peltier units have additional heating function by changing the supply polarity of the thermoelectric elements. This is possible by using a combination of thermostats or having a specific polarity controller.
Peltier cooling units are resistant to extreme ambient conditions and can operate effectively even in environments which are dusty and oily and where temperatures may vary from -4°F to 149°F. For the cooling capacities and environmental ratings please refer to the type plate data.

5. Functional Principle
Functional Principle The thermoelectric elements create a temperature difference between the internal and ambient heat sinks, making internal air cooler while dissipating heat into the external environment. Fans help the transfer of convective heat from the heat sinks, which are optimized for maximum flow. Peltier units can be mounted in any position because these units don't have a compressor or any moving parts. Depending on the mounting situation, the condensation management may need to be considered and possibly adjusted.
1. Ambient Fans 2. Ambient Heat Sinks 3. Thermoelectric Elements 4. Insulation 5. Internal Heat Sink 6. Internal Fan

back to top

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

5

6. Technical Data

Part Number

SCE-TE340B24VSS

Cooling Capacity @ 95°F / 95°F

340 BTU (100 Watts)

Operating Temperature Range

-4°F - 149°F

Air Volume Flow

Ambient Air Circuit: 75 cfm Cabinet Air Circuit: 27 cfm

Mounting

Recessed

Housing Material

Stainless Steel AISI 304

Dimensions (H x W x D)

7.9 x 12.0 x 5.4 inch

Cutout Dimensions

10.24 x 6.30 inch

Weight

13 lbs

Rated Operating Voltage

24V DC

Rated Current

4.8 A

Starting Current

7.4 A

Max Current

5.6 A

Nominal Power @ 95°F / 95°F

115 W

Max Power

132 W

Fuse Rating

8A (T) - Time Delayed [Slow Acting]

Circuit Breaker - MCB Type D or K Slow Acting

8A Slow Acting

Connection

Connection Terminal Block

NEMA Protection Class

NEMA 3, 3R, 4, 4X & 12

Approvals

CE / cURus

Industry Standards

IS20

back to top

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

6

7. Performance Graph

Thermoelectric Cooler 340 BTU/HR (100 Watts) Performance Curve
SCE-TE340B24VSS

Cooling Capacity
(BTU)

149°F/65°C

Enclosure Air Temp

122°F/50°C

95°F/35°C

68°F/20°C

Cooling Capacity
(Watt)

Ambient Temperature (°C)

-20 -14

-9

-3

2

1300

8

13

19

24

30

36

41

47

52

58

63

381

1200

352

1100

322

1000

293

900

264

800

234

700

205

600

176

500

146

400

117

300

88

200

59

100

29

0

0

-4

6

16

26

36

46

56

66

76

86

96

106 116 126 136 146

Ambient Temperature (°F)

Thermoelectric Cooler 340 BTU/HR (100 Watts) Heating - Performance Curve
SCE-TE340B24VSS

Enclosure Air Temp

Watt

Ambient Temperature (°C)

-18

-12

-7

-1

4

10

16

21

27

32

38

43

381

352

322

293

264

234

205

176

146

117

88

59

29

0

0

10

20

30

40

50

60

70

80

90

100

110

back to top

Ambient Temperature (°F)

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

7

8. Mounting

Always switch off power supply before starting any work on the unit.
Installation Ensure that flows of air leaving and entering the cooling unit, internal and external, are not obstructed. Before drilling the enclosure, ensure the fixing elements and couplings will not interfere with the equipment inside the enclosure itself. When all mounting preparations are complete, the actual mounting operation can commence. Only use the enclosed material to mount the unit on the cabinet. Proceed as follows to mount the unit on the enclosure:
· Set the unit up on the enclosure. · Ensure that the electrical connection is above the internal fan. · Unit without duct: screw the M6 locknuts & washers into the M6 set screws in the unit. · Unit with duct: screw the M6 screws & washers into the M6 threaded rivets in the unit. The resistance of the earth connection between cabinet and cooling unit must be <0.1 .

back to top

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

8

9. Cutout Dimensions

304 [11.97] 285 [11.22] 260 [10.24] 160 [6.30]

200 [7.87] 185 [7.28] 160 [6.30]

TOP

Ø8 [Ø0.31]

Note: Primary dimensions in millimeters. Secondary dimensions in inches.

back to top

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

9

10. Dimensions (H x W x D)

back to top

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

10

11. Electrical Connection

High electric voltage present. Installation, maintenance, cleaning and any other work must be carried out by qualified personnel only. The personnel must ensure that for the duration of this work the unit and the cabinet are disconnected from the electrical supply and protected against unauthorized/accidental reconnection.

Instruction Check that the available voltage, frequency and fuse rating are the same as those stated on the data label.
Connection to the main electricity supply The mains connection is made via a cable. To connect the unit to the mains supply proceed as follows:
· Disconnect the control cabinet from the mains. · See the connection details on the circuit diagram. · Note the connections on the four pole terminal block from the following table:
Terminal 24 V DC 1 Ambient Fan + 2 Ambient Fan ­ 3 Internal Fan + 4 Internal Fan ­ 5 Thermoelectric Elements + 6 Thermoelectric Elements ­

Ensure that the correct polarity is maintained. The fans should have a clockwise rotation.
· Connect the unit to the mains. · Take the control cabinet back into operation in the prescribed manner. Power consumption and start-up current are stated on the data label and under technical data.

back to top

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

11

12. Wiring Diagram

Thermostat SCE-TEMNO
Part List TE Thermoelectric Elements (Peltier) IF Internal Fan AF Ambient Fan

Thermostat
24 VDC

0 VDC

1+ 23+ 45+ 6-

AF IF
Thermostat SCE-TEMEVDC

Ambient

1 +

Fan 2 -

Internal

3 +

Fan 4 -

5 + Thermoelectric
Elements 6 -

TE

+24 VDC -
back to top

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

12

13. Taking Into Operation

The power supply rating on the rating plate must comply with mains supply.

Always disconnect the power supply before opening the unit.
Heat load to be dissipated from enclosure should not exceed specific cooling output of the unit at any condition. While selecting a cooling unit always cater for a safety margin of at least 15% extra cooling output. The Peltier - elements should be controlled by a suitable thermostat. We recommend the SCE-TEMEVDC Thermostat.
14. Repair
In case of fault Contact Saginaw Control & Engineering - Customer service department at 1-800-234-6871 or E-Mail Customerservice@saginawcontrol.com

15. Maintenance & Cleaning
Always switch off power before starting any work on the unit. Only qualified personnel may conduct any maintenance work on the cooling unit.
All Peltier units are virtually maintenance-free with no filters that need to be cleaned or replaced. Check the ambient heat sinks from time to time. In case they are dirty proceed as following:
· Disconnect the enclosure from the mains. · Clean the heat sink profile as required by blowing it out with compressed air. · In cases of extreme pollution wet cleaning is required.
The unit must be removed from the control cabinet for wet cleaning.
Should a wet cleaning be necessary proceed as following: · Disconnect the whole plant from the mains. · Remove the unit from the cabinet. · Ensure that the seals are not damaged. · Wash the heat sink with an environmentally safe cleaning fluid.
Danger to the environment through unauthorized disposal.
Disposal Dispose of cooling unit and used parts with due regard for the environment and in accordance with environmental laws and regulations.
back to top

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

13

16. Maintenance
Note: Only use original replacement parts when repairing the unit. This ensures that the unit functions perfectly and remains safe.

Fan replacement: The average working life of the fan is ca. 40,000 hours under normal conditions. Should a fan replacement be necessary proceed as following:

Danger from Electrical Voltage Ensure that for the duration of the work the unit and the cabinet are disconnected from the electrical supply and protected against unauthorized reconnection.

· Disconnect the unit from the mains. · Remove the unit cover. · Remove the screws from the relevant fan. · Mount the new fan.

Danger Through Incorrect Work Make sure that the cabinet fan or the ambient fan are not misplaced in the unit as they are different. Ensure that the correct polarity is maintained. The fans must rotate clockwise!

· Remove the 4 fan fixing screws · Close the unit and take it back into operation.

back to top

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

14

17. Transportation & Storage
Malfunction Due to Transport Damage On delivery the carton containing the unit must be examined for signs of transport damage. Any transport damage to the carton could indicate that the unit itself has been damaged in transit, which in the worst case could mean that the unit will not function.

During transport and storage the cooling unit must be kept in the position marked on the box and at a temperature between -40°F and 158°F and a relative humidity of max. 95% (at 77°F). In case of damaged packaging after transport or in-house handling, we recommend controlling the unit for any internal damages.

1 x Peltier Cooling Unit 1 x Instruction Manual 1 x CE Conformity Declaration 6 x M6 Nuts 6 x Washers

18. Parts Supplied

Saginaw Control and Engineering
95 Midland Road Saginaw, MI 48638-5770 Phone: (989) 799-6871 Fax: (989) 799-4524 sce@saginawcontrol.com

back to top

BSAGINAW CONTROL & ENGINEERING · A/C USER MANUAL

15

19. Warranty / Limits of Liability
All goods manufactured by SCE shall be warranted to be free of defects in material or workmanship for a period of two years from the date of shipment. Should the product be proven to SCE to be defective, we shall option to repair or replace the product. At no time will SCE reimburse purchaser for unauthorized rework on any product.

Air Conditioners & Heat Exchangers are warranted on parts and service for a period of two years from the date of shipment by Saginaw Control and subject to the following conditions and exclusions:
All Goods must be installed and operated according to the following specifications: Maximum voltage variation no greater than plus or minus 10% of nominal rating; Maximum frequency variation no greater than plus or minus 3 Hz. from nominal rating; Must not exceed minimum and maximum rated temperatures; Must not exceed (BTU/Hr) rating; Filters must be cleaned regularly; Must be installed and grounded in accordance with all relevant electrical and safety codes, as well as the National Electric Code and OSHA rules and regulations; Must be installed in a stationery application, free of vibration.
Our warranty does not warranty product that has been modified, subjected to abuse, negligence in operation or maintenance, or if product is used in a manner that exceeds its designed capabilities and rating.

Warranty related claims will be returned to the factory for evaluation and final disposition of the claim, any replacement parts will be invoiced at standard pricing and credit issued for the returned product. If the product has been found to have been modified, subjected to abuse, negligence in operation or maintenance, or if product has been used in a manner that exceeds its designed capabilities and rating, credit may be reduced, denied or additional cost may be assessed and passed on to the