WORCESTER GREENSKIES Twin coil indirect unvented solar cylinder
Instruction Manual, Installation, Commissioning & Servicing
Brand: WORCESTER Bosch Group
Introduction
The Worcester Greenskies cylinder is a Stainless Steel Unvented Twin Coil Storage vessel specifically designed to be installed in conjunction with the Worcester Greenskies solar package. Should installation with an alternative solar package be considered please seek guidance to ensure compatibility prior to commencing installation. The Greenskies cylinder is not compatible in an installation utilising two individual boilers. The Greenskies solar cylinder is made from Duplex Stainless Steel for excellent corrosion resistance. Greenskies cylinders have a strong rust-proofed steel case and are well insulated with environmentally friendly foam. It is available in a range of 4 sizes from 180 – 300 litres. The Greenskies cylinder is supplied complete with all the necessary safety and control devices needed to connect to the cold water mains. All are pre-adjusted. High quality controls have been selected to combine high flowrate performance with minimum pressure drop to make Greenskies cylinders perform well in most areas. Greenskies cylinders are WRAS approved to show compliance with Building Regulations G3 and Part L.
Storage Prior to Installation
The Greenskies cylinder should be stored in its original packaging in an upright position in an area free from excessive damp.
Unpacking the Unit
The Greenskies cylinder comes complete with all the fittings you need to complete the installation:
TWIN COIL PARTS
- Inlet Control set
- Temp & Pressure relief valve
- 15mm / 22mm Tundish
- Expansion vessel
- Wall mounting bracket
- 1 x 15mm end feed tee
- Expansion vessel hose
- Immersion Heater
- 2 x Two port valves
- Wiring centre
- Dual Thermostat
- High limit Thermostat
- 2 x Cylinder Sensor Retaining Bungs
- Installation & Maintenance Instructions inc Benchmark Logbook
Technical Specification
| CODE | CAPACITY (Litres) | HEIGHT (mm) | DIAMETER (mm) | A (mm) | B (mm) | C (mm) | D (mm) | E (mm) | F (mm) | G (mm) | H (mm) | WEIGHT (Kg-EMPTY) | WEIGHT (Kg-FULL) | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 7-716-192-554 | 180 | 1281 | 550 | 290 | 345 | 674 | 729 | N/F | 1080 | 390 | 725 | 50 | 230 | |
| 7-716-192-555 | 210 | 1469 | 550 | 365 | 420 | 779 | 834 | 1150 | 1268 | 465 | 830 | 55 | 265 | |
| 7-716-192-556 | 250 | 1719 | 550 | 365 | 420 | 950 | 1005 | 1 | 1400 | 1518 | 465 | 1000 | 60 | 310 |
| 7-716-192-557 | 300 | 2032 | 550 | 365 | 420 | 979 | 1034 | 1600 | 1831 | 465 | 1030 | 65 | 365 |
All Dimensions are in mm and are of the cased unit. N/F = not fitted to 180 litre unit.
Water Supply and Siting
Water Supply
The Greenskies cylinder has an optimum working pressure of 3 bar (regulated by the inlet control set) and is capable of delivering up to 50 litres per minute. However the performance of any unvented system is only as good as the water supply. The maximum possible water demand should be assessed taking into consideration that both hot and cold services are supplied simultaneously from the mains. The water supply should be checked to ensure it can meet these requirements. If necessary consult the local water company regarding the likely pressure and flow rate availability. If measuring the water pressure note that a high static (no flow) mains pressure is no guarantee of good flow availability. In a domestic installation 1.5 bar and 25 l/m should be regarded as the minimum for a single bathroom application. The maximum mains pressure for the inlet control set is 16 bar. Consideration should be given to upgrading existing 1/2" (15mm) cold mains pipework to a larger size if the recommended minimum pressure/flowrate is not being achieved. In the event of a low dynamic pressure situation, please use a break tank and pump set or an accumulator for low flow.
Siting the Unit
The Greenskies cylinder can supply outlets above it or at some distance from it. Site the unit to minimise "dead leg" distances especially to the point of most frequent use. Outlets above the Greenskies cylinder will reduce the outlet pressure available by 0.1 bar for every 1m of height difference. The Greenskies cylinder must be installed VERTICALLY on a flat base capable of supporting the weight of the cylinder when full (see technical specification section for weights). The minimum recommended cupboard size is 650mm square. Access for maintenance of the valves should be considered. The immersion heaters are 375mm long and care should be taken that they can be withdrawn for servicing if required. The discharge pipework from the safety valves should fall continuously and terminate safely. Regarding garage installation or any situation which is outside of the warm envelope of the building: Particular care is needed if siting in a garage or outbuilding. All exposed pipework must be insulated. Ensure the cylinder is frost protected recommended minimum temperature of 5 degree centigrade. Cylinder is installed vertically on a suitable base. Installation is in a vermin proof area. Installation is in a non flood area. Installation is not within a damp environment or subject to condensation. Installation must meet all legislation and good practice current at time of installation. This product is made from stainless steel and can be recycled when disposing of unit.
Notes:
- No valves must be fitted between the expansion valve and the storage cylinder.
- The pressure reducing valve, Non return valve and Expansion relief valve are combined together in the inlet control set.
- On 180 litre sizes there is no dedicated secondary return boss and the secondary return circuit should be tee'd into the cold feed pipe just above the drain elbow.
General Installation
Pipework Connections
All water pipe connections on the Greenskies cylinder are 22mm compression bosses with 22mm olives and gland nuts provided in the component box. Ensure pipework connections are to 22mm copper tube and that tube is pushed fully home prior to tightening the gland nut. Connections for the expansion valve and temperature pressure relief valve must not be used for any other purpose.
Cold Mains Pipework
Run the cold main through the building to the location where the Greenskies cylinder is to be installed. Take care not to position the cold pipe near hot water or heating pipe work so that the heat pick up is minimized. Identify the cold water supply pipe and fit an isolating valve (not supplied). A 22mm BS1010 stopcock can typically be used but a 22mm quarter turn full bore valve would be preferred as it does not restrict the flow as much. Do not use "screwdriver slot" or similar valves. Make the connection to the cold feed of the cylinder and incorporate a drain valve. Position the inlet control just ABOVE the Temperature & Pressure Relief Valve (TPRV) mounted on the side of the cylinder. This ensures that the cylinder does not have to be drained down in order to service the inlet control set. Ensure that the arrow points in the direction of the water flow.
Expansion Vessel Installation
Select a suitable position for the expansion vessel. Mount it to the wall using the bracket provided and connect to the inlet control set with the flexible hose provided. Ensure that the top of the vessel is accessible for servicing. It is recommended that a blending valve be fitted on the hot water outlet.
Balanced Cold Connection
If there are showers, bidets or monobloc taps in the installation then a balanced cold supply is necessary. There is a 22mm balanced connection on the inlet control set. An alternative method is to split the inlet control set into two parts.
Hot Water Pipework
Run the first part of the hot water distribution pipework in 22mm. This can be reduced to 15mm and 10mm as appropriate for the type of tap etc. Your aim should be to reduce the volume of the hot drawoff pipework to a practical minimum so that the time taken for the hot water to reach the outlet is as quick as possible. Do not use monobloc mixer taps or showers if the balanced cold connection is not used as these may cause the cylinder to back pressurise and result in discharge from the expansion valve.
Secondary Circulation
The Greenskies cylinder can be used with secondary circulation. An appropriate WRAS approved bronze circulator should be used in conjunction with a non return valve to prevent backflow. On large secondary circulation systems it may be necessary to incorporate an extra expansion vessel into the circuit to accommodate the increased system water volume. Secondary circulation should be avoided for direct electrically heated units being used on off peak electricity tariffs. A secondary return boss is fitted as standard on 210, 250 & 300 litre models. On 180 litre tee into the cold feed pipe above the drain.
Immersion Heaters
Only immersion heaters with a thermal cut out may be used. To help ensure this the immersion heaters have a special 13/4" thread. They are rated at 3 kW at 240 V and are of a low noise Incoloy construction. They have both a thermostat and a high limit cut out. When fitting ensure the 'O'ring is positioned correctly on the head of the immersion heater and lubricate before fitting. Fit it by hand until almost home then tighten gently as the 'O' rings will seal easily. The electrical supply to each immersion heaters must be fused at 13A via a double pole isolating switch to BS 3456. The cable must be 2.5mm² heat resistant (85°C HOFR) sheathed flex complying to BS 6141:1981 Table 8. Do not operate the immersion heater/s until the unit is full of water. Do not operate the immersion heater/s if any sterilisation liquid is in the cylinder as this will cause premature failure.
Primary Coils: Connection and Control
Upper Coil: Fossil Fuel Boiler
Connect to primary upper coil (connections C+C) page 3 using the compression connections provided. The primary circuit must be positively pumped. Gravity circulation is not possible. Either primary coil connection may be used as the flow. Re-heat times are identical either way. The primary circuit can be open vented or system sealed up to a maximum pressure of 7 bar. Where the primary circuit is sealed an additional expansion vessel and safety valve is required if not already included within the boiler. The boiler may be gas, oil or electric but must be under effective thermostatic control. Uncontrolled heat sources such as some AGAs, back boilers, solid fuel stoves etc are not suitable. For both control and protection purposes the two port zone valve supplied must be fitted into the primary flow (page 4) and wired via the dual control and high limit aquastat positioned into pocket D, schematic page 3 with adherence to the wiring diagram on page 8.
Lower Coil: Greenskies Solar System
The lower coil is connected to the Greenskies solar panel collector and controls as per the Greenskies installation manual. Either of the coil connections A & A (fig. Page 3) may be utilised as the flow or return. Solar input is not compromised using either connection. The solar control cylinder sensor supplied as part of the Greenskies package inserts into pocket B (fig page 3). To satisfy the requirements of Building Regulation Part G3 it is necessary to ensure the supplied solar high limit thermostat is wired to electrically isolate the solar controller in the event of an overheat situation. A wiring diagram is supplied (fig. 1 page 9), the solar high limit thermostat inserts into pocket F (fig. page3). The references made to the solar controller are generic, further references should be made to the solar controller installation instructions for specific connection details. An alternative diagram is also shown for solar pump station installations that DO NOT have an integral gravity break (check valve); in this sitation the 2-port valve supplied is also used. All Worcester, Bosch Group solar pump stations incorporate an integral gravity break and do not require this additional level of protection.
Discharge Arrangement
Position the inlet control group so that the discharge from both the two safety valves can be joined together via a 15mm end feed Tee. Connect the Tundish and route the discharge pipe. The discharge pipework must be routed in accordance with Part G3 of schedule 1 of the Building Regulations. The information that follows is not exhaustive and if you are in doubt you should seek advice. The two safety valves will only discharge water under fault conditions. When operating normally water will not be discharged. The tundish should be vertical, located in the same space as the unvented hot water storage system and be fitted as close as possible and within 500mm of the safety device e.g. the temperature relief valve. The discharge pipe (D2) from the tundish should terminate in a safe place where there is no risk to persons in the vicinity of the discharge, be of metal and:
- Be at least one pipe size larger than the nominal outlet size of the safety device unless its total equivalent hydraulic resistance exceeds that of a straight pipe 9m long i.e. discharge pipes between 9m and 18m equivalent resistance length should be at least two sizes larger than the the nominal outlet size of the safety device, between 18 and 27m at least 3 sizes larger, and so on. Bends must be taken into account in calculating the flow resistance. Refer to diagram 1, Table 1 and the worked example. An alternative approach for sizing discharge pipes would be to follow BS6700 Specification for design installation, testing and maintenance of services supplying water for domestic use within buildings and their curtilages.
- Have a vertical section of pipe at least 300mm long, below the tundish before any elbows or bends in the pipework.
- Be installed with a continuous fall.
- It is preferable for the discharge to be visible at both the tundish and the final point of discharge but where this is not possible or practically difficult there should be clear visibility at one or other of these locations. Examples of acceptable discharge arrangements are: 1. Ideally below the fixed grating and above the water seal in a trapped gulley. 2. Downward discharges at a low level; i.e. up to 100mm above external surfaces such as car parks, hard standing, grassed areas etc. are acceptable providing that where children play or otherwise come into contact with discharges, a wire cage or similar guard is positioned to prevent contact whilst maintaining visibility. 3. Discharges at a high level; e.g. in to metal hopper and metal down pipe with the end of the discharge pipe clearly visible (tundish visible or not) or onto a roof capable of withstanding high temperature discharges of water and 3m from any plastic guttering systems that would collect such discharges (tundish available). 4. Where a single pipe serves a number of discharges, such as in blocks of flats, the number served should be limited to not more than 6 systems so that any installation can be traced reasonably easily. The single common discharge pipe should be at least one pipe size larger than the largest individual discharge pipe to be connected. If unvented hot water storage systems are installed where discharges from safety devices may not be apparent i.e. in dwellings occupied by blind, infirm or disabled people, consideration should be given to the installation of an electronically operated device to warn when discharge takes place.
| Size of discharge pipework | Maximum length of straight pipe (no bends or elbows) | Deduct the figure below from the maximum length for each bend or elbow in the discharge pipe |
|---|---|---|
| 22mm | Up to 9m | 0.8m |
| 28mm | Up to 18m | 1m |
| 35mm | Up to 27m | 1.4m |
Note: The discharge will consist of scalding water and steam. Asphalt, roofing felt and non-metallic rainwater goods may be damaged by such discharges. Note: It is not acceptable to discharge straight into a soil pipe.
Worked Example: The example below is for G1/2 temperature relief valve with a discharge pipe (D2) having 4 No. elbows and length of 7m from the tundish to the point of discharge. From Table 1: Maximum resistance allowed for a straight length of 22mm copper discharge pipe (D2) from a G1/2 temperature relief valve is: 9.0m Subtract the resistance for 4 No. 22mm elbows at 0.8m each = 3.2m Therefore the maximum permitted length equates to: 5.8m 5.8m is less than the actual length of 7m therefore calculate the next largest size. Maximum resistance allowed for a straight length of 28mm pipe (D2) from a G1/2 temperature relief valve equates to: 14m As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory.
Wiring Diagrams
Key: W = White, G = Grey, Bl = Black, O = Orange, G/Y = Green / Yellow, Br = Brown, L = Live, N = Neutral, C = Common Terminal, SL = Switched Live. Note: The boiler and programmer power can be taken either from the Wiring Centre or from elsewhere whichever is more convenient.
Greenskies Cylinder Sensor Retaining Bung
Fully insert the cylinder sensor into the pocket.
Once the sensor is inserted fully home, insert the cylinder sensor retaining bung. Being made of rubber it is flexible enough to fit around the cable, whilst securely holding it in place.
Commissioning
Filling the Cylinder
Check the pressure in the DHW expansion vessel is 3 bar (45PSI).(I.e the same as the setting of the pressure reducing valve). Before filling open the hot tap furthest away from the Greenskies cylinder to let air out. Open the cold main isolation valve and allow the unit to fill. When water flows from the tap allow it to run for a short while to flush through any dirt, swarf or flux residue. Close the tap and open every other hot tap in turn to purge all remaining air.
Filling of Primary Circuits
Upper Coil
Consult the boiler commissioning instructions and fill the primary circuit. Ensure the wheel on the 2 port valve is set to the filling position. When full move the wheel back. Switch the programmer to Domestic Hot water (DHW) and allow the unit to start to heat. Adjust the dial of the dual thermostat to between 55°C and 65°C as required.
Lower Coil
Fill and commission the lower coil solar circuit as per the Greenskies solar installation manual.
Storage Temperature / Blending Valve
The recommended DHW storage temperature is 60-65°C. In many applications, the guidance on Legionella control and safe water delivery temperatures will require storing the water at 60-65°C and distributing at 50-55°C. This can be achieved by using a thermostatic blending valve to control the final temperature. Where storage temperatures in excess of 60°C may be achieved it is essential drawn hot water temperature is controlled to a maximum of 55°C with a blending valve.
Safety Valve Checks
Fully open the expansion relief and the temperature/pressure relief valves to allow as much water as possible to flow through the tundish. Check that the discharge pipework is free from debris and is carrying the water away to waste efficiently. Release the valves and check that they reseat properly. During heat up there should be no sign of water coming from either the the expansion relief valve or the temperature/pressure relief valve.
Servicing
General
Servicing should only be carried out by competent installers and any spare parts used must be purchased from Worcester Bosch Group. NEVER bypass any safety devices or operate the unit without them fully operational.
Draining
Isolate from the electrical supply to prevent the immersion heaters burning out. Isolate the unit from the cold mains. Attach a hose to the draining tap ensuring it reaches to a level below the unit (This will ensure an efficient syphon is set up and the maximum amount of water is drained from the unit). Open the hot tap closest to the unit and open the draining tap WARNING: WATER DRAINED OFF MAY BE VERY HOT!
Annual Maintenance
Greenskies cylinders require an annual service in order to ensure safe working and optimum performance. It is essential that the following checks are performed by a competent installer on an annual basis. Commonly this is done at the same time as the annual boiler service.
- Twist the cap of the expansion relief valve on the inlet control set and allow water to flow for 5 seconds. Release and make sure it resets correctly. Repeat with the pressure / temperature relief valve.
- Check that the discharge pipework is carrying the water away adequately. If not check for blockages etc. and clear. WARNING: THE WATER DISCHARGED MAY BE VERY HOT!
- Check that any immersion heaters fitted are working correctly and that they are controlling the water at a temperature between 55°C and 65°C.
- Check the pressure in the expansion vessel is charged to 3 bar. Turn off the water supply to the unit and open a hot tap first. Air may be used to charge the expansion vessel.
- Unscrew the head on the inlet control set and clean the mesh filter within.
- The benchmark log book supplied with this unit should be updated at each service.
YOUR GUARANTEE MAY BE VOID WITHOUT PROOF OF ANNUAL SERVICING
Spare Parts
- 8-716-113-407-0 - Inlet control set (pressure reducing valve, strainer and expansion relief valve)
- 8-716-113-408-0 - Temperature & pressure relief valve
- 8-716-113-409-0 - Tundish
- 8-716-113-410-0 - 2 port valve
- 8-716-113-515-0 - 10 way electrical box
- 8-716-113-411-0 - Dual thermostat
- 8-716-113-412-0 - Immersion heater (same on all models)
- 8-716-113-416-0 - 19 litre Expansion vessel (180, 210 & 250 sizes)
- 8-716-113-418-0 - 24 litre expansion vessel (300 litre size)
- 8-716-113-414-0 - Expansion vessel hose (3/4" M x 3/4" F)
- 8-716-113-522-0 - 95mm Single Limit Thermostat
For spares contact our Sales office on Tel: 01905 752576 • Fax: 01905 754620 Technical Helpline: 08705 266241
Fault Finding
| FAULT | POSSIBLE CAUSE | SOLUTION |
|---|---|---|
| Water escaping from the case. | Compression fitting on hot drawoff not sealing | Check/remake joint with sealing paste |
| Cold water at taps | Direct - Immersion heater not switched on or cutout has triggered Indirect - Boiler not working Indirect - motorised valve fault Indirect - cut-out in dual stat has operated | Check/reset Check boiler - consult boiler manufacturers instructions Check plumbing / wiring to motorised valve Reset and investigate cause |
| Water discharges from expansion relief valve | If continual - pressure reducing valve (part of inlet control set) may not be operating correctly If continual - expansion relief valve seat may be damaged If intermittent - expansion vessel charge may have reduced / bladder perished | Check outlet pressure from inlet control set is 3 bar. Remove cartridge - check seat and renew if necessary Check pressure in expansion vessel Recharge to 3 bar if necessary If bladder perished replace vessel. |
| Water discharges from temperature & pressure relief valve | Unit it being back pressurised Unit has overheated thermal controls have failed | With cylinder cold check pressure in cylinder. If this is the same as the incoming mains pressure then you are getting backfed. Install a balanced cold supply (see page 4) Switch off power to boiler and immersion heaters. Leave water supply on. Wait until discharge stops. Isolate water supply and replace if faulty |
| Milky / cloudy water | Oxygenated water | Water from any pressurised system will release oxygen bubbles when flowing. The bubbles will settle out. |
| No hot water flow | Cold main off Strainer blocked in pressure reducing valve Inlet control set may be fitted incorrectly | Check and open stop cock Isolate water supply and clean Check and refit as required |
| Noise during hot water drawoff- typically worse in the morning. | loose airing cupboard pipework | Install extra clips |
| Hot or warm water form from cold tap | If tap runs cold after a minute or so the pipe is picking up seat from heating pipework. | Insulate / reroute |
USER INSTRUCTIONS
IF WATER IS FLOWING FROM THE SAFETY VALVES THROUGH THE TUNDISH THIS INDICATES A FAULT CONDITION AND ACTION IS NEEDED
If this water is hot turn the boiler and / or the immersion heater off. Do not turn off the water until the discharge runs cool. The discharge may also stop.
CALL A COMPETENT INSTALLER OUT TO SERVICE THE UNIT. Inform them you have a fault on an unvented cylinder. Worcester stock all the spare parts listed on Page 10.
The Guarantee
The Greenskies stainless steel vessel carries a fully transferable, 25 year guarantee against faulty materials or manufacture provided that:
- It has been correctly installed as per this document and all the relevant standards, regulations and codes of practice in force at the time.
- It has not been modified in any way, other than by Worcester.
- It has not been misused, tampered with or subjected to neglect.
- It has only been used for the storage of potable water.
- It has not been subjected to frost damage.
- The unit has been serviced annually.
- The benchmark log book has been filled in after each annual service.
The guarantee period starts from the date of purchase and no registration is required. Please note that invoices for servicing may be requested to prove that the unit has been serviced annually. All the components fitted to / or supplied with the Greenskies cylinder carry a 2 year guarantee.
EXCLUSIONS - THE GUARANTEE DOES NOT COVER
- The effects of scale build up.
- Any labour charges associated with replacing the unit or its parts.
- Any consequential losses caused by the failure or malfunction of the unit.
Benchmark Log Book
The code of practice for the installation, commissioning & servicing of mains pressure hot water storage. Installation, Commissioning and Service Record Log Book. CUSTOMER DETAILS NAME ADDRESS TEL No. IMPORTANT 1. Please keep the Log Book in a safe place for future reference. 2. This Log Book is to be completed in full by the competent person(s) who commissioned the equipment and then handed to the customer. When this is done, the Log Book is a commissioning certificate that can be accepted as evidence of compliance with the appropriate Building Regulations. 3. Failure to install and commission this appliance to the manufacturer's instructions may invalidate the warranty. The above does not affect your statutory rights.
Commissioning Procedure Information
BOILER PRIMARY SETTINGS (INDIRECT HEATING ONLY) ALL BOILERS
IS THE PRIMARY A SEALED OR OPEN VENTED SYSTEM? SEALED OPEN WHAT IS THE BOILER FLOW TEMPERATURE? °C
ALL MAINS PRESSURISED SYSTEMS
WHAT IS INCOMING STATIC COLD WATER PRESSURE AT THE INLET TO THE PRESSURE REDUCING VALVE? bar HAS STRAINER (IF FITTED) BEEN CLEANED OF INSTALLATION DEBRIS? YES NO HAS A WATER SCALE REDUCER BEEN FITTED? YES NO WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?
UNVENTED SYSTEMS ONLY
ARE COMBINED TEMPERATURE AND PRESSURE RELIEF VALVE AND EXPANSION VALVE FITTED AND DISCHARGE TESTED? YES NO IS PRIMARY ENERGY SOURCE CUT OUT FITTED (NORMALLY 2 PORT VALVE)? YES NO WHAT IS THE PRESSURE REDUCING VALVE SETTING (IF FITTED)? bar WHERE IS OPERATING PRESSURE REDUCING VALVE SITUATED? HAS THE EXPANSION VESSEL OR INTERNAL AIR SPACE BEEN CHECKED? YES NO WHAT IS THE HOT WATER TEMPERATURE AT THE NEAREST OUTLET? °C
THERMAL STORES ONLY
WHAT IS THE OPERATING SETTING OF THE PRESSURE REDUCING VALVE (WHERE FITTED)? WHERE IS PRESSURE REDUCING VALVE SITUATED? WHAT STORE TEMPERATURE IS ACHIEVABLE? °C WHAT IS THE MAXIMUM HOT WATER TEMPERATURE? °C WHAT IS THE MAXIMUM HOT WATER FLOW RATE AT MAXIMUM TEMPERATURE? Its/min
ALL PRODUCTS
DOES THE HOT WATER SYSTEM COMPLY WITH THE APPROPRIATE BUILDING REGULATIONS? YES HAS THE SYSTEM BEEN INSTALLED AND COMMISSIONED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS? YES HAVE YOU DEMONSTRATED THE OPERATION OF THE SYSTEM CONTROLS TO THE CUSTOMER? YES HAVE YOU LEFT ALL THE MANUFACTURER'S LITERATURE WITH THE CUSTOMER? YES COMPETENT PERSON'S SIGNATURE CUSTOMER'S SIGNATURE (To confirm demonstrations of equipment and receipt of appliance instructions)
Installer & Commissioning Engineer Details
INSTALLER DETAILS
COMPANY NAME ADDRESS DATE INSTALLER NAME REGISTRATION DETAILS REGISTERED OPERATIVE ID CARD No. (IF APPLICABLE) TEL No.
COMMISSIONING ENGINEER (IF DIFFERENT)
NAME ADDRESS DATE TEL No. REGISTRATION DETAILS REGISTERED OPERATIVE ID CARD No. (IF APPLICABLE)
APPLIANCE & TIME CONTROL DETAILS
MANUFACTURER MODEL CAPACITY litres SERIAL No. TYPE UNVENTED or THERMAL STORE TIME CONTROL PROGRAMMER or TIME SWITCH
PLEASE FOLLOW THE INSTALLATION AND COMMISSIONING INSTRUCTIONS IN THE INSTALLATION MANUAL SUPPLIED WITH THE EQUIPMENT
Service Interval Record
It is recommended that your hot water system is serviced regularly and that your service engineer completes the appropriate Service Interval Record below.
SERVICE PROVIDER
Before completing the appropriate Service Interval Record below, please ensure you have carried out the service as described in the manufacturer's instructions and in compliance with all relevant codes of practice.
| DATE: | ENGINEER NAME | COMPANY NAME | TEL No. | COMMENTS | SIGNATURE |
|---|---|---|---|---|---|
| DATE: | ENGINEER NAME | COMPANY NAME | TEL No. | COMMENTS | SIGNATURE |
|---|---|---|---|---|---|
| DATE: | ENGINEER NAME | COMPANY NAME | TEL No. | COMMENTS | SIGNATURE |
|---|---|---|---|---|---|
| DATE: | ENGINEER NAME | COMPANY NAME | TEL No. | COMMENTS | SIGNATURE |
|---|---|---|---|---|---|
| DATE: | ENGINEER NAME | COMPANY NAME | TEL No. | COMMENTS | SIGNATURE |
|---|---|---|---|---|---|
| DATE: | ENGINEER NAME | COMPANY NAME | TEL No. | COMMENTS | SIGNATURE |
|---|---|---|---|---|---|
| DATE: | ENGINEER NAME | COMPANY NAME | TEL No. | COMMENTS | SIGNATURE |
|---|---|---|---|---|---|
| DATE: | ENGINEER NAME | COMPANY NAME | TEL No. | COMMENTS | SIGNATURE |
|---|---|---|---|---|---|
| DATE: | ENGINEER NAME | COMPANY NAME | TEL No. | COMMENTS | SIGNATURE |
|---|---|---|---|---|---|
| DATE: | ENGINEER NAME | COMPANY NAME | TEL No. | COMMENTS | SIGNATURE |
|---|---|---|---|---|---|
When all of the above services have been completed, please contact your Service Engineer for an additional service interval record sheet.
Specification Summary
Flowrate Performance
Materials
- Inner shell - Stainless Steel
- Coil - 22mm Diameter 316L Stainless Steel
- Bosses - 316L Stainless Steel
- Every Greenskies cylinder is water tested to a pressure of 15 bar.
- Insulation - Fire retardant polyurethane foam, nominal thickness 50mm. The foam is CFC-Free and HCFC-Free. The foam has an ozone depletion potential of ZERO.
- Casework - Zintec corrosion proofed steels throughout Durable, oven hardened, gloss silver grey paint finish
- Anode - None fitted / none required
- Expansion Vessel - 19 Litre size with 180, 210 and 250 Litre models; 24 Litre size with 300 Litre model
Control Settings
- Pressure Reducing Valve - 3 Bar
- Expansion Relief Valve - 6 Bar
- Pressure and Temperature Relief Valve - 7 Bar/90°C
- High Limit Thermostat in Dual Thermostat - 85°C
- High Limit Thermostat in Immersion Heater - 85°C
- High Limit Stat Solar - 85°C
Immersion Heater
- 13/4" BSP Parallel Threaded Head
- Long Life Incoloy Sheathed Low Noise Element 14" Long
- Long Life Incoloy Sheathed Thermostat Pocket 11" Long
- Brazed Construction
- 11" Combined Thermostat and Safety Cut-Out
- Element Rating 3Kw at 240V A/C
Approvals
- WRAS Approved to the Water Regulations
- WRC-NSF Approved to Building Regulations' G3 & L
- CE Compliant and fitted with a - BEAB Approved Immersion Heater
Worcester, Bosch Group Cotswold Way, Warndon, Worcester WR4 9SW Tel. 01905 754624 Fax. 01905 754619 www.worcester-bosch.co.uk Worcester Bosch Group is a trading name of BBT Thermotechnology UK Ltd. Part No. 8716-113-445 Issue 1 Revision B



