3 6-8 Hours 9.25 cm x 16.05 cm x 30.5 cm Specifications Input Output Protection Battery Physical Voltage Frequency 230 VAC 50 Hz or 60 Hz Brownout Transfer

Manual Easy-UPS

APC Easy-UPS BV800I-GR ▻ ИБП, 800 V·A, 450 W ▻ купить в GEEK.MD


File Info : application/pdf, 6 Pages, 652.91KB

PDF preview unavailable. Download the PDF instead.

Manual Easy-UPS
User Manual Easy UPS
BV Series 500VA, 650VA, 800VA, 1000VA
Safety and General Information
SAVE THESE INSTRUCTIONS ­
This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damages.
 This UPS is intended for indoor use only.  Mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily
accessible.  UPS must be connected to an earthed mains socket outlet.
CAUTION
HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE  Battery must be replaced when they reach end of service life.  Batteries must be replaced when the unit indicates battery replacement is necessary.  When replacing batteries, replace with the same number and type of batteries originally installed in the unit. Failure to follow these instructions can result in minor or moderate injury and equipment damage.
 Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions.
 When replacing battery the UPS must be OFF, and its AC inlet unplugged.  CAUTION Do not dispose of batteries in a re. The batteries may explode.  CAUTION Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries
according to the instructions.  Do not open or mutilate batteries. They contain an electrolyte that is toxic and harmful to the skin
and eyes.  CAUTION A battery can present a risk of electrical shock and high short circuit current.
The following precautions should be observed when working on batteries. a. Remove watches, rings or other metal objects. b. Use tools with insulated handles. c. Wear rubber gloves and boots. d. Do not lay tools or metal parts on top of batteries. e. Disconnect the charging source prior to connecting or disconnecting battery terminals. f. Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance
Radio Frequency Warning
This is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures.

Place and Power On
1. Place the Easy UPS to avoid:  Direct sunlight  Excessive heat  Excessive moisture  Excessive dust/dirt
For operation, please place the unit on the floor.
2. Connect the battery by pulling the battery handle up, and then pushing it into the unit.
3. Connect equipment to the UPS. Avoid using extension cords.
4. Plug the Easy UPS power cord directly into a wall outlet, not into a surge protector or power strip.
5. Press the ON/OFF button to turn on the unit. The green "Power On" indicator confirms that the Easy UPS is on and ready to provide protection. The Easy UPS should charge for at least 6 hours to ensure sufficient runtime. The unit is being charged whenever it is connected to AC power, whether the unit is turned ON or OFF.

Features
A ON/OFF button with indicator
B Input power cord *only for model with Schuko outlet
C Battery backup and surge protected outlets

D Battery connector
E Circuit breaker *only for model with Schuko outlet
F AC power inlet with AC fuse

Model

Output Type A and Quantity

C

B

BV500I

BV650I

BV800I

x 6

BV1000I

E

BV500I-GR BV650I-GR BV800I-GR BV1000I-GR

x 4

F

BV500I-MS

BV650I-MS

D

BV800I-MS BV1000I-MS

x 4

NEMA jumper Cable for PC connection *only for the model with Universal outlet

IEC jumper Cable for PC connection *only for the model with IEC outlet

2

Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA

Specifications

Model Input

Voltage Frequency

BV500I

BV650I

BV800I

230 VAC

50 Hz or 60 Hz

BV1000I

Brownout Transfer

170 VAC, typical

Output

Over-voltage Transfer

280 VAC, typical

UPS Capacity (total) 500VA / 300W 650VA / 375W 800VA / 450W 1000VA / 600W

Voltage On Battery

230VAC ± 10%

Frequency - On Battery

50 Hz / 60 Hz ± 1Hz

Transfer Time

6ms typical

Protection AC Input

Circuit Breaker* (*only for model with

5A

5A

7A

7A

Schuko outlet)

Battery

AC Input Fuse
Type (maintenance-free)

5A
12V, 4.5AH lead acid

5A
12V, 7AH lead acid

10A
12V, 7AH lead acid

10A
12V, 9AH lead acid

Average Life

The battery typically lasts for three to ve years. Environmental factors impact battery life. Elevated temperatures, high humidity, poor quality mains power, and frequent, short duration discharges will shorten battery life.

Physical

The battery in the Easy UPS Series is not user-replaceable. Contact SEIT Technical Support for a list of authorized service centers near you.

Typical Recharge Time

6-8 Hours

Net Weight

3.9 kg

4.5 kg

5.3 kg

5.7 kg

Dimensions (Hx Wx D)

9.25 cm x 16.05 cm x 30.5 cm

Wall Mount Installation
 Horizontal installation, use 2 screws 11.1"(282 mm) apart.  Allow 5/16'' (8 mm), of the screw to protrude from the wall.

11.1 in. 282 mm
Wall-mounting Template

Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA

3

Status Indicators

LED On

Audible Alarm Off
Constant Tone
Constant beeping (every 1/2 second)

Condition
On-line - The EasyUPS is supplying AC power to the connected equipment
On Line Overload - The power being used by the connected equipment has exceeded the capacity of the unit. Disconnect some equipment.
Over-temperature - The unit is overheating and will operate in AVR mode for 5 minutes. The Easy UPS will shut down if the temperature is not lowered. Disconnect some of the connected equipment.

On

4 beeps repeated On-Battery - The Easy UPS is supplying battery power.

(Off during 4 beeps) every 30 seconds

Flashing

Constant beeping Low Battery - The Easy UPS is supplying battery power and (every 1/2 second) the battery is near a total discharge state.

Constant tone

Bad Battery Detected - The battery needs to be charged, or is at end of life.

Off

Short beep every Low Battery Shutdown - During On Battery operation

4 seconds

the battery power was almost completely exhausted, and the

Easy UPS is waiting for AC power to return to normal.

Constant Tone

On Battery Overload - The connected equipment requires more power than provided by the Easy UPS battery. Unplug devices one at a time to remove overload.

If the problem is not corrected, contact SEIT Technical Support

Long beep every 4 seconds

Charger Detected Fault - Easy UPS has an internal problem, and is no longer powering the load. Contact SEIT Technical Support
Over-temperature Protected - The Easy UPS has overheated and has shut down. Unplug connected devices one at a time or wait for a few hours for system to cool down.

Operational Features
Automatic Voltage Regulation (AVR)
Automatic Voltage Regulation boosts/trims the AC voltage when it drops/exceeds levels.
This allows the equipment plugged into the unit to operate during low/high voltage conditions, conserving the battery power in the event of a power cut.
The Easy UPS will switch to battery power if the input voltage level becomes too low/high for the Automatic Voltage Regulation to compensate, or if the AC power is distorted.

4

Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA

Troubleshooting

Problem and Possible Cause The Easy UPS will not turn on

Solution

The Easy UPS has not been turned on.

Press the ON/OFF button.

The Easy UPS is not connected to AC power, Make sure the power cord is securely connected to the

there is no AC power available at the wall wall outlet, and that there is AC power available at the

outlet, or the AC power is experiencing a

wall outlet.Where applicable, check that the wall

brownout or over voltage condition.

outlet is switched on.

The battery is disconnected. Connected equipment loses power

Refer to the Place and Power On on page 2.

A Easy UPS overload condition has occurred. Remove all nonessential equipment connected to the outlets. One at a time reconnect equipment to the Easy UPS. Charge the battery for 24 hours to make sure it is fully charged. If the overload condition still occurs, replace the battery.

The Easy UPS battery is completely discharged.

Connect the Easy UPS to AC power and allow the battery to recharge for ten hours.

Connected equipment does not accept the step-approximated sine waveform from the Easy UPS.

The output waveform is intended for computers and peripheral devices. It is not intended for use with motor driven equipment.

The Easy UPS may require service.

Contact Schneider Electric Technical Support for more in depth troubleshooting

The ON/OFF button is green and ashing every 30 seconds. 4 beeps repeated every 30 seconds.

The Easy UPS is operating on battery power.

The Easy UPS is operating normally on battery power. At this point the user should save all open les, and shutdown the computer. When AC power is restored the battery will recharge.

The ON/OFF button ashes green and constant beeps every 1/2 second.

The Easy UPS battery has approximately empty and will shutdown

The Easy UPS battery is near a total discharge state. At this point the user should save all open les, and shutdown the computer. When AC power is restored the battery will recharge.

The Easy UPS has an inadequate battery runtime

The battery is not fully charged.

Leave the Easy UPS connected to AC power for ten

The battery is near the end of useful life and hours while the battery charges to full capacity.

should be replaced.

As a battery ages, the runtime capability decreases.

The UPS and outlets are off but the UPS keeps beeping once every 4 seconds. The alarm will mute after 32 seconds.

The UPS have shut down due to low battery, The UPS will return to normal operation once the

but control power exists.

AC input voltage has returned to a normal range.

Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA

5

Service
If the unit requires service, do not return it to the dealer. Follow these steps: 1. Review the Troubleshooting section of the manual to eliminate common problems.
2. If the problem persists, contact Schneider Electric IT (SEIT) Customer Support through the APC by Schneider Electric website, www.apc.com. a. Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit. b. Call SEIT Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#). c. If the unit is under warranty, the repairs are free. d. Service procedures and returns may vary internationally. Refer to the APC by Schneider Electric website for country specific instructions.
3. Pack the unit in the original packaging whenever possible to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty.
4. Always DISCONNECT THE UPS BATTERIES before shipping. The United States Department of Transportation (DOT), and the International Air Transport Association (IATA) regulations require that UPS batteries be disconnected before shipping. The internal batteries may remain in the UPS.
5. Write the RMA# provided by Customer Support on the outside of the package.
6. Return the unit by insured, pre-paid carrier to the address provided by Customer Support
Warranty
Register your product on-line. http://warranty.apc.com
The standard warranty is two (2) years from the date of purchase. SEIT standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an SEIT Technical Support representative. SEIT will ship the replacement unit once the defective unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement unit to the customer.

APC by Schneider Electric IT Customer Support Worldwide
For country specific customer support, go to the APC by Schneider Electric website, www.apc.com.

© 2019 APC by Schneider Electric. APC, the APC logo are owned by Schneider Electric Industries S.A.S., or their afliated companies. All other trademarks are property of their respective owners.

EN 990-91065A 01/2019

