Instruction Manual for BANNER models including: R95C-4B4UI-MQ, R95C Modbus Hubs, R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus Hub, R95C, 8-Port 2-Channel Discrete and Analog In-Out Modbus Hub, 8-Port 2-Channel Discrete, 2-Channel Discrete, Discrete, 2-Channel Discrete and Analog In-Out Modbus Hub, Analog In-Out Modbus Hub, Analog Modbus Hub, In-Out Modbus Hub, Modbus Hub, Modbus, Hub

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus  Hub Instruction Manual

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

R95C-4B4UI-MQ | R95C Modbus Hubs

Data Sheet

R95C-4B4UI-MQ BANNER ENGINEERING, Signal Converter, 8-Port, IO Modbus, Current, Voltage, Current, Voltage, 2 Channels, 30 VDC |


File Info : application/pdf, 25 Pages, 10.86MB

PDF preview unavailable. Download the PDF instead.

234539
R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual
Original Instructions p/n: 234539 Rev. A June 26, 2024 © Banner Engineering Corp. All rights reserved.

Contents
Chapter 1 Features
Models ........................................................................................................................................................................................................... 3 Overview........................................................................................................................................................................................................ 3
Chapter 2 Configuration Instructions
Discrete In/Out Configuration ........................................................................................................................................................................ 4 Analog In/Out Configuration .......................................................................................................................................................................... 4 Modbus Configuration ................................................................................................................................................................................... 4
Multi-Port Support: Ports 1-4 .................................................................................................................................................................11 Multi-Port Support: Ports 5-8 ................................................................................................................................................................ 15
Chapter 3 Mechanical Installation
Wiring........................................................................................................................................................................................................... 16
Chapter 4 Status Indicators.................................................................................................. 17
Chapter 5 Specifications
FCC Part 15 Class B for Unintentional Radiators........................................................................................................................................ 19 Industry Canada ICES-003(B)..................................................................................................................................................................... 20 Dimensions .................................................................................................................................................................................................. 20
Chapter 6 R95C Accessories................................................................................................ 21
Chapter 7 Banner Engineering Corp Limited Warranty..................................................... 24

R95C 8-Port 2-Channel Discrete And Analog In-Out Modbus® Hub Instruction Manual

Chapter Contents
Models.................................................................................................................................................................................................................. 3 Overview .............................................................................................................................................................................................................. 3

Chapter 1

Features

· Compact Modbus® device converter with the ability to send 4 ports of discrete input and 4 ports of analog input data (voltage or current)
· This Modbus converter can also output discrete values and analog outputs (voltage or current) through any of the respective sets of 4 ports
· 2-Channel Discrete Features:  Enabled Delay Modes: ON/OFF Delay, ON/OFF One-shot, ON/ OFF Retriggerable One-shot, ON/OFF Pulse-stretcher and Totalizer
 Measurement Metrics: Count, Counts Per Minute (CPM), and Duration
 Discrete input/output can be independently configured as NPN or PNP
 Discrete Mirroring: Discrete signals (In/Out) from the four discrete ports can be mirrored to any of the output channels of the four discrete ports
· Analog In/Out Features:  Analog Out Mirroring: The analog input from all four analog ports can be mirrored as an output to any of the four analog ports
 PFM Output: The analog input from all four analog ports can be mirrored as PFM outputs to any of the four discrete ports.
· Rugged overmolded design meets IP65, IP67, and IP68 · Connects directly to a sensor or anywhere in-line for ease of use · R95C Modbus hubs are a quick, easy, and economical way to integrate
non-Modbus devices into a Modbus system

Models

Model Number R95C-4B4UI-MQ

Function Converter

Converter Type
8-ports: 4B: 4 ports, bimodal discrete input/output 4UI: 4 ports, analog input/output

Control

Connectors

Modbus®

(8) Integral 4-pin M12 female quick-disconnect
connectors (1) Integral 5-pin M12 male quick-disconnect connector

Overview
The R95C 8-Port 2-Channel Discrete and Analog In/Out Modbus® Hub provides a mix of both discrete input/output and analog input/output functionality distributed to two sets of 4-ports
Ports 1 through 4 contain the discrete functionality, and Ports 5 through 8 contain the analog functionality. These two sets of ports can be monitored and configured using an Modbus registers.

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 3

R95C 8-Port 2-Channel Discrete And Analog In-Out Modbus® Hub Instruction Manual

Chapter Contents
Discrete In/Out Configuration ............................................................................................................................................................................... 4 Analog In/Out Configuration ................................................................................................................................................................................. 4 Modbus Configuration .......................................................................................................................................................................................... 4

Chapter 2

Configuration Instructions

Discrete In/Out Configuration
Ports 1 through 4 contain discrete functionality. The figure below details the logic flow for each of the four bimodal discrete in/ out ports, and the tables define the configuration for each pin of the four bimodal ports.

Input State

Delay Mode · Disabled (active/inactive) · On Off Delay · On/Off One-shot · On/Off Pulse Stretcher · Totalizer

Logic Flow

Discrete 1 & 2
Selection

Input

Measurement Statistics
Input State

Measurement Statistics · Count · CPM · Duration
Discrete 1 and 2 Input · Input (active/inactive) state

Ouput

Mirroring Enable

Enabled

Mirroring

Mirroring - Discrete 1 and 2 Output · Port/Channel selected state

Disabled

Data Output Discrete 1 and 2 Output · Output (active/inactive) selected state

Analog In/Out Configuration
Ports 5 through 8 contain analog functionality.

Analog In When an analog input value is received in Ports 5 through 8, the numerical representational value is sent to Modbus registers.
Analog Input Ranges: · Voltage = 0 mV to 11,000 mV · Current = 0 µA to 24,000 µA

Analog Out Ports 5 through 8 also allow for the user to output an analog value by sending the numerical analog value to Modbus registers
Analog Output Ranges: · Voltage = 0 mV to 10,000 mV · Current = 4000 µA to 20,000 µA

Output Outside Valid Range (OOVR) If the analog output value sent from this converter is outside of the Analog Output Range value, then the actual analog output value will be set to one of the three selectable OOVR levels after a 2-second delay:
· Low (default): 0 V or 3.5 mA · High: 10.5 V or 20.5 mA · Hold: Level retains previous value
indefinitely

Modbus Configuration

Device Port States

Modbus Register Address
40001
40002

Description

I/O Range

Active States

0..255

Analog Input Active States

0..15

Comments

Default

Port 4..Port 1 

Pin 4[P#1] & Pin 2[P#2] Active

-

States

Inactive = 0, Active = 1

-

Continued on page 5

Access

Notes

RO

0b[P42|P41|P32|P31|P22| P21|P12|P11]

RO

0b[0|0|0|0|P8|P7|P6|P5]

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 4

Configuration Instructions

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Modbus Register Address
40003
40004
40005
40006

Description

I/O Range

Measurement Value - Analog In Port 5

0..65535

Measurement Value - Analog In Port 6

0..65535

Measurement Value - Analog In Port 7

0..65535

Measurement Value - Analog In Port 8

0..65535

Continued from page 4

Comments

Default

Voltage = mV, Current = µA

-

Voltage = mV, Current = µA

-

Voltage = mV, Current = µA

-

Voltage = mV, Current = µA

-

Analog Port Configuration

Modbus Register Address
40007

Description

I/O Range

Port 8-5 Analog-Out | Port 8-5 Analog-In

0..255

Comments
Voltage = 0, Current = 1

Default 0b11111111

Discrete Output States

Modbus Register Address

Description

40008

Output States

I/O Range

Comments

Default

0..255

Port 4..Port 1  Pin 4[P#1] & Pin 2[P#2]
Output States

0b00000000

Analog Out Value

Modbus Register Address
40009
40010
40011
40012

Description
Port 5 - Analog Value
Port 6 - Analog Value
Port 7 - Analog Value
Port 8 - Analog Value

I/O Range

Comments

0..20500 0..20500 0..20500 0..20500

Voltage = mV, Current = µA

0

Voltage = mV, Current = µA

0

Voltage = mV, Current = µA

0

Voltage = mV, Current = µA

0

Default

Alias RO Registers

Modbus Register Address

Description

I/O Range

Comments

40501

Port 5 Analog In

0..65535

Voltage = mV, Current = µA

-

40502

Port 6 Analog In

0..65535

Voltage = mV, Current = µA

-

40503

Port 7 Analog In

0..65535

Voltage = mV, Current = µA

-

40504

Port 8 Analog In

0..65535

Voltage = mV, Current = µA

-

40505

Port 1 Pin 4 Active State

0..1

0 = Inactive, 1 = Active

-

40506

Port 1 Pin 2 Active State

0..1

0 = Inactive, 1 = Active

-

40507

Port 2 Pin 4 Active State

0..1

0 = Inactive, 1 = Active

-

40508

Port 2 Pin 2 Active State

0..1

0 = Inactive, 1 = Active

-

Continued on page 6

Access

RO

-

RO

-

RO

-

RO

-

Notes

Access

Notes

RW

0b[P8O|P7O|P6O|P5O] [P8I| P7I|P6I|P5I]

Access

Notes

RW

0b[P42|P41|P32|P31|P22| P21|P12|P11]

Access

Notes

RW

Max Voltage = 10000 mV, Max Current = 20000 µA

RW

Max Voltage = 10000 mV, Max Current = 20000 µA

RW

Max Voltage = 10000 mV, Max Current = 20000 µA

RW

Max Voltage = 10000 mV, Max Current = 20000 µA

Default

Access RO RO RO RO RO
RO
RO
RO

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 5

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Modbus Register Address

Description

I/O Range

Continued from page 5 Comments

40509

Port 3 Pin 4 Active State

0..1

0 = Inactive, 1 = Active

-

40510

Port 3 Pin 2 Active State

0..1

0 = Inactive, 1 = Active

-

40511

Port 4 Pin 4 Active State

0..1

0 = Inactive, 1 = Active

-

40512

Port 4 Pin 2 Active State

0..1

0 = Inactive, 1 = Active

-

40513

Port 1 Pin 4 Count H

0..65535

Port 1 Pin 4 Count Value Upper

-

40514

Port 1 Pin 4 Count L

0..65535

Port 1 Pin 4 Count Value Lower

-

40515

Port 2 Pin 4 Count H

0..65535

Port 1 Pin 4 Count Value Upper

-

40516

Port 2 Pin 4 Count L

0..65535

Port 2 Pin 4 Count Value Lower

-

40517

Port 3 Pin 4 Count H

0..65535

Port 1 Pin 4 Count Value Upper

-

40518

Port 3 Pin 4 Count L

0..65535

Port 3 Pin 4 Count Value Lower

-

40519

Port 4 Pin 4 Count H

0..65535

Port 1 Pin 4 Count Value Upper

-

40520

Port 4 Pin 4 Count L

0..65535

Port 4 Pin 4 Count Value Lower

-

40521

Port 1 Pin 2 Count H

0..65535

Port 1 Pin 4 Count Value Upper

-

40522

Port 1 Pin 2 Count L

0..65535

Port 1 Pin 2 Count Value Lower

-

40523

Port 2 Pin 2 Count H

0..65535

Port 1 Pin 4 Count Value Upper

-

40524

Port 2 Pin 2 Count L

0..65535

Port 2 Pin 2 Count Value Lower

-

40525

Port 3 Pin 2 Count H

0..65535

Port 1 Pin 4 Count Value Upper

-

40526

Port 3 Pin 2 Count L

0..65535

Port 3 Pin 2 Count Value Lower

-

40527

Port 4 Pin 2 Count H

0..65535

Port 1 Pin 4 Count Value Upper

-

40528

Port 4 Pin 2 Count L

0..65535

Port 4 Pin 2 Count Value Lower

-

40529

Alias Register Value

0..65535

User defined

-

40530

Alias Register Value

0..65535

User defined

-

40531

Alias Register Value

0..65535

User defined

-

40532

Alias Register Value

0..65535

User defined

-

Default

Configuration Instructions
Access RO RO RO RO RO RO RO RO RO RO RO RO RO RO RO RO RO RO RO RO RO RO RO RO

page 6

© Banner Engineering Corp. All rights reserved.

June 26, 2024

Configuration Instructions

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Alias Read/Only Addresses

Modbus Register Address
40701 40702 40703 40704 40705 40706 40707 40708 40709 40710 40711 40712 40713 40714 40715 40716 40717 40718 40719 40720 40721 40722 40723 40724 40725 40726

Description
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address

I/O Range

Comments

0..65535

Value shows up in 40501

0..65535

Value shows up in 40502

0..65535

Value shows up in 40503

0..65535

Value shows up in 40504

0..65535

Value shows up in 40505

0..65535

Value shows up in 40506

0..65535

Value shows up in 40507

0..65535

Value shows up in 40508

0..65535

Value shows up in 40509

0..65535

Value shows up in 40510

0..65535

Value shows up in 40511

0..65535

Value shows up in 40512

0..65535

Value shows up in 40513

0..65535

Value shows up in 40514

0..65535

Value shows up in 40515

0..65535

Value shows up in 40516

0..65535

Value shows up in 40517

0..65535

Value shows up in 40518

0..65535

Value shows up in 40519

0..65535

Value shows up in 40520

0..65535

Value shows up in 40521

0..65535

Value shows up in 40522

0..65535

Value shows up in 40523

0..65535

Value shows up in 40524

0..65535

Value shows up in 40525

0..65535

Value shows up in 40526 Continued on page 7

Register to Assign

45001

RW

46001

RW

47001

RW

48001

RW

41001

RW

41002

RW

42001

RW

42002

RW

43001

RW

43002

RW

44001

RW

44002

RW

41003

RW

41004

RW

42003

RW

42004

RW

43003

RW

43004

RW

44003

RW

44004

RW

41011

RW

41012

RW

42011

RW

42012

RW

43011

RW

43012

RW

Access

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 7

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Modbus Register Address
40727 40728 40729 40730 40731 40732

Description
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address

I/O Range

Continued from page 7 Comments

0..65535

Value shows up in 40527

0..65535

Value shows up in 40528

0..65535

Value shows up in 40529

0..65535

Value shows up in 40530

0..65535

Value shows up in 40531

0..65535

Value shows up in 40532

Alias RW Registers

Modbus Register Address
40801 40802 40803 40804 40805 40806 40807 40808 40809 40810 40811 40812 40813 40814 40815 40816 40817 40818 40819 40820

Description
Port 1 Pin 4 Active State
Port 1 Pin 2 Active State
Port 2 Pin 4 Active State
Port 2 Pin 2 Active State
Port 3 Pin 4 Active State
Port 3 Pin 2 Active State
Port 4 Pin 4 Active State
Port 4 Pin 2 Active State
Port 5 Analog Out
Port 6 Analog Out
Port 7 Analog Out
Port 8 Analog Out
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value

I/O Range

Comments

0..1

0 = Inactive, 1 = Active

0..1

0 = Inactive, 1 = Active

0..1

0 = Inactive, 1 = Active

0..1

0 = Inactive, 1 = Active

0..1

0 = Inactive, 1 = Active

0..1

0 = Inactive, 1 = Active

0..1

0 = Inactive, 1 = Active

0..1
0..65535 0..65535 0..65535 0..65535
0..65535

0 = Inactive, 1 = Active
Voltage = mV, Current = µA Voltage = mV, Current = µA Voltage = mV, Current = µA Voltage = mV, Current = µA
User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined Continued on page 9

Configuration Instructions

Register to Assign

44011

RW

44012

RW

0

RW

0

RW

0

RW

0

RW

Access

Default -

Access RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW

page 8

© Banner Engineering Corp. All rights reserved.

June 26, 2024

Configuration Instructions

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Modbus Register Address
40821 40822 40823 40824 40825 40826 40827 40828 40829 40830 40831 40832

Description
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value
Alias RW Register Value

I/O Range

Continued from page 8 Comments

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

0..65535

User defined

Alias Read/Write Addresses

Modbus Register Address
40901 40902 40903 40904 40905 40906 40907 40908 40909 40910 40911 40912

Description
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address

I/O Range

Comments

0..65535

Value shows up in 40801

0..65535

Value shows up in 40802

0..65535

Value shows up in 40803

0..65535

Value shows up in 40804

0..65535

Value shows up in 40805

0..65535

Value shows up in 40806

0..65535

Value shows up in 40807

0..65535

Value shows up in 40808

0..65535

Value shows up in 40809

0..65535

Value shows up in 40810

0..65535

Value shows up in 40811

0..65535

Value shows up in 40812 Continued on page 10

Default -

Access RW RW RW RW RW RW RW RW RW RW RW RW

Register to Assign

41401

RW

41402

RW

42401

RW

42402

RW

43401

RW

43402

RW

44401

RW

44402

RW

45002

RW

46002

RW

47002

RW

48002

RW

Access

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 9

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Configuration Instructions

Modbus Register Address
40913 40914 40915 40916 40917 40918 40919 40920 40921 40922 40923 40924 40925 40926 40927 40928 40929 40930 40931 40932

Description
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address
Alias Register Address

I/O Range

Continued from page 9 Comments

0..65535

Value shows up in 40813

0..65535

Value shows up in 40814

0..65535

Value shows up in 40815

0..65535

Value shows up in 40816

0..65535

Value shows up in 40817

0..65535

Value shows up in 40818

0..65535

Value shows up in 40819

0..65535

Value shows up in 40820

0..65535

Value shows up in 40821

0..65535

Value shows up in 40822

0..65535

Value shows up in 40823

0..65535

Value shows up in 40824

0..65535

Value shows up in 40825

0..65535

Value shows up in 40826

0..65535

Value shows up in 40827

0..65535

Value shows up in 40828

0..65535

Value shows up in 40829

0..65535

Value shows up in 40830

0..65535

Value shows up in 40831

0..65535

Value shows up in 40832

Register to Assign

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

0

RW

Access

Modbus Configuration

Modbus Register Address
40601
40602 40603 40604

Description

I/O Range

Comments

Baud Rate

0 = 9.6k 1 = 19.2k 2 = 38.4k

0 = 9600 1 = 19200 2 = 38400

Parity

0 = None 1 = Odd 2 = Even

0 = None 1 = Odd 2 = Even

Address

1-254

-

Reserved (cannot be read or written)

None

Continued on page 11

Default

Access

1

RW

0

RW

1

RW

-

-

page 10

© Banner Engineering Corp. All rights reserved.

June 26, 2024

Configuration Instructions

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Modbus Register Address
40605

Description
Restore Factory Configuration

Continued from page 10

I/O Range

Comments

0 = No Operation, 1 = Restore

-

Device Information

Modbus Register Address
40606-40615 40616-40631 40632 40633 40634 40635 40636 40637 40644-40659
40680
40681
40682
40683
40684

Description
Banner Name Product Name Item H Item L Serial Number H Serial Number Serial Number Serial Number L
User Define Tag
Discovery
All-Time Run Time H All-Time Run Time L Resettable Run Time H Resettable Run Time L

I/O Range

Comments

Default

0..65535 0..65535 0..65535 0..65535 0..65535 0..65535 0..65535 0..65535
0..65535
0..1

-

Banner Engineering

-

R95C-4B4UI-MQ

814993 split into 12

two 16-bit

registers

28561

-

-

-

-

-

-

-

-

User writable space

More Sensors. More Solutions.

0 = Disabled, 1 = Enabled

-

0..65535

-

-

0..65535

Run counter (0.25 hr)

-

0..65535

-

-

0..65535

Run counter (0.25 hr)

-

Multi-Port Support: Ports 1-4

Register Ranges for Ports 1-4

41001-41400 42001-42400 43001-43400 44001-44400

Register Ranges

Port 1 Port 2 Port 3 Port 4

Measurement Reads

Modbus Register Address
41001
41002

Description
Port 1 Pin 4 Active State
Port 1 Pin 2 Active State

I/O Range

Comments

0..1

0 = Inactive, 1 = Active

-

0..1

0 = Inactive, 1 = Active

-

Default

41003

Pin 4 Count H

0..65535

Pin 4 Count Value Upper

-

Continued on page 12

Default -

Access WO

Access

Notes

RO

(9 words/18 characters)

RO

(16 words/32 characters)

RO

Banner Item Number

RO

-

RO

RO

Serial Number is split into

RO

four 16-bit registers

RO

RW

(16 words/32 characters)

RW

Flash all LEDs to find hub

RO

Upper 16 of 32 bits

RO

Lower 16 of 32 bits

RW

Upper 16 of 32 bits

RW

Lower 16 of 32 bits

Port Number

Access

Notes

RO

-

RO

-

Upper 16 of 32 bits = Running

RO

count of the received input

pulses

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 11

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Configuration Instructions

Modbus Register Address

Description

41004

Pin 4 Count L

I/O Range

Continued from page 11

Comments

Default

0..65535

Pin 4 Count Value Lower

-

41005

Pin 4 Duration H 0..65535

Pin 4 Duration Value Upper

-

41006
41007
41008 41009 41010 41011 41012 41013

Pin 4 Duration L

0..65535

Pin 4 Duration Value Lower

-

Pin 4 Counts Per Minute H

0..65535

Pin 4 Counts Per Minute L

0..65535

Pin 4 Totalizer Count H
Pin 4 Totalizer Count L

0..65535 0..65535

Pin 2 Count H

0..65535

Pin 2 Count L

0..65535

Pin 4 Counts

Per Minute

-

Value Upper

Pin 4 Counts

Per Minute

-

Value Lower

Pin 4 Totalizer Count Upper

-

Pin 4 Totalizer Count Lower

-

Pin 2 Count Value Upper

-

Pin 2 Count Value Lower

-

Pin 2 Duration H 0..65535

Pin 2 Duration Value Upper

-

41014 41015 41016 41017 41018

Pin 2 Duration L

0..65535

Pin 2 Duration Value Lower

-

Pin 2 Counts Per Minute H

0..65535

Pin 2 Counts Per Minute L

0..65535

Pin 2 Totalizer Count H
Pin 2 Totalizer Count L

0..65535 0..65535

Pin 2 Counts

Per Minute

-

Value Upper

Pin 2 Counts

Per Minute

-

Value Lower

Pin 2 Totalizer Count Upper

-

Pin 2 Totalizer Count Lower

-

Access

Notes

Lower 16 of 32 bits = Running

RO

count of the received input

pulses

Upper 16 of 32 bits =

RO

Duration of the last input pulse in µs with 50 µs

granularity

Lower 16 of 32 bits =

RO

Duration of the last input pulse in µs with 50 µs

granularity

Upper 16 of 32 bits = Running

RO

count of the number of pulses received averaged over one

minute. Range 1 to 37,500

Lower 16 of 32 bits = Running

RO

count of the number of pulses received averaged over one

minute. Range 1 to 37,500

RO

Upper 16 of 32 bits = Totalizer count

RO

Lower 16 of 32 bits = Totalizer count

Upper 16 of 32 bits = Running

RO

count of the received input

pulses

Lower 16 of 32 bits = Running

RO

count of the received input

pulses

Upper 16 of 32 bits =

RO

Duration of the last input pulse in µs with 50 µs

granularity

Lower 16 of 32 bits =

RO

Duration of the last input pulse in µs with 50 µs

granularity

Upper 16 of 32 bits = Running

RO

count of the number of pulses received averaged over one

minute. Range 1 to 37,500

Lower 16 of 32 bits = Running

RO

count of the number of pulses received averaged over one

minute. Range 1 to 37,500

RO

Upper 16 of 32 bits = Totalizer count

RO

Lower 16 of 32 bits = Totalizer count

Measurement Count Presets: these registers reset ALL measurements, not just the count values

Modbus Register Address

Description

41100

Pin 4 Count H

41101

Pin 4 Count L

41102

Pin 2 Count H

I/O Range

Comments

Default

0..65535 0..65535 0..65535

Pin 4 Count Value Upper

-

Pin 4 Count Value Lower

-

Pin 2 Count Value Upper

-

Continued on page 13

Access

Notes

RW

Upper 16 of 32 bits

RW

Lower 16 of 32 bits

RW

Upper 16 of 32 bits

page 12

© Banner Engineering Corp. All rights reserved.

June 26, 2024

Configuration Instructions

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Modbus Register Address

Description

41103

Pin 2 Count L

I/O Range

Continued from page 12

Comments

Default

0..65535

Pin 2 Count Value Lower

-

Access

Notes

RW

Lower 16 of 32 bits

Pin 4 Port Configuration (Black - Female, Discrete 1)

Modbus Register Address
41200
41201
41202
41203 41204 41205 41206 41207
41208 41209 41210 41211

Description Pin 4 IO Selection
Pin 4 Mode

I/O Range

Comments

Default Access

0 = NPN input

1 = PNP input

0..5

2 = NPN output with pull up 3 = PNP output with pull down

3

RW

4 = NPN output push/pull

5 = PNP output push/pull

0 = Disabled

1 = On Off Delay

2 = On One-shot

3 = Off One-shot

0..8

4 = On Pulse-stretcher

0

RW

5 = Off Pulse-stretcher

6 = Totalizer

7 = Retriggerable On One-shot

8 = Retriggerable Off One-shot

Pin 4 Delay Timer 1 Upper 0..65535

Pin 4 On Delay, One-shot, Pulsestretcher time, Totalizer Count

0

RW

Pin 4 Delay Timer 1 Lower 0..65535

Pin 4 On Delay, One-shot, Pulsestretcher time, Totalizer Count

0

RW

Pin 4 Delay Timer 2 Upper 0..65535

Pin 4 Off Delay or Totalizer time 0

RW

Pin 4 Delay Timer 2 Lower 0..65535

Pin 4 Off Delay or Totalizer time 0

RW

Pin 4 Mirroring Enable

0..1

Pin 4 Mirroring Port Selection 0..7

0 = Disabled, 1 = Enabled
0 = Port 1 1 = Port 2 2 = Port 3 3 = Port 4 4 = Port 5 5 = Port 6 6 = Port 7 7 = Port 8

0

RW

0

RW

Pin 4 Mirroring Selection

0..1

0 = Channel 1, 1 = Channel 2

0

RW

Pin 4 Mirroring Inversion

0..1

0 = Not inverted, 1 = Inverted

0

RW

Pin 4 PFM Near Frequency (Hz)

100..600

-

Pin 4 PFM Far Frequency (Hz)

100..600

-

100

RW

600

RW

Notes
-
-
Upper 16 of 32 Bits: Mode 1, 2, 3, 4, 5, 7, 8 = Milliseconds Mode 6 = Count Lower 16 of 32 Bits: Mode 1, 2, 3, 4, 5, 7, 8 = Milliseconds Mode 6 = Count Upper 16 of 32 Bits = Milliseconds Lower 16 of 32 Bits = Milliseconds -
If Port 1-4, Discrete Mirroring If Port 5-8, PFM of Analog In
If Port 1-4, Discrete Mirroring If Port 1-4, Discrete Mirroring If Port 5-8, PFM of Analog In If Port 5-8, PFM of Analog In

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 13

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Configuration Instructions

Pin 2 Port Configuration (White - Female, Discrete 2)

Modbus Register Address
41300
41301
41302
41303 41304 41305 41306 41307
41308 41309 41310 41311

Description Pin 2 IO Selection
Pin 2 Mode

I/O Range

Comments

0 = NPN input

1 = PNP input

0..5

2 = NPN output with pull up 3 = PNP output with pull down

4 = NPN output push/pull

5 = PNP output push/pull

0 = Disabled

1 = On Off Delay

2 = On One-shot

3 = Off One-shot

0..6

4 = On Pulse-stretcher

5 = Off Pulse-stretcher

6 = Totalizer

7 = Retriggerable On One-shot

8 = Retriggerable Off One-shot

Default Access

3

RW

0

RW

Pin 2 Delay Timer 1 Upper

0..65535

Pin 2 On Delay, One-shot, Pulsestretcher time, or Totalizer Count

0

RW

Pin 2 Delay Timer 1 Lower

0..65535

Pin 2 On Delay, One-shot, Pulsestretcher time, or Totalizer Count

0

RW

Pin 2 Delay Timer 2 Upper 0..65535 Pin 2 Off Delay or Totalizer time 0

RW

Pin 2 Delay Timer 2 Lower 0..65535 Pin 2 Off Delay or Totalizer time 0

RW

Pin 2 Mirroring Enable

0..1

Pin 2 Mirroring Port Selection 0..7

0 = Disabled, 1 = Enabled
0 = Port 1 1 = Port 2 2 = Port 3 3 = Port 4 4 = Port 5 5 = Port 6 6 = Port 7 7 = Port 8

0

RW

0

RW

Pin 2 Mirroring Selection

0..1

0 = Channel 1, 1 = Channel 2

0

RW

Pin 2 Mirroring Inversion

0..1

0 = Not Inverted, 1 = Inverted

0

RW

Pin 2 PFM Near Frequency (Hz)

100..600

-

Pin 2 PFM Far Frequency (Hz)

100..600 -

100

RW

600

RW

Notes
-
-
Upper 16 of 32 Bits: Mode 1, 2, 3, 4, 5, 7, 8 = Milliseconds Mode 6 = Count Lower 16 of 32 Bits: Mode 1, 2, 3, 4, 5, 7, 8 = Milliseconds Mode 6 = Count Upper 16 of 32 Bits = Milliseconds Lower 16 of 32 Bits = Milliseconds -
If Port 1-4, Discrete Mirroring If Port 5-8, PFM of Analog In
If Port 1-4, Discrete Mirroring If Port 1-4, Discrete Mirroring If Port 5-8, PFM of Analog In If Port 5-8, PFM of Analog In

Active Configurations

Modbus Register Address

Description

I/O Range

Comments

41401

Port 1 Pin 4 Active State

0..1

0 = Inactive, 1 = Active

0

41402

Port 1 Pin 2 Active State

0..1

0 = Inactive, 1 = Active

0

Default

Access

Notes

If mirroring disabled & IO

RW

selection is output, Data

Output set to inactive/active

If mirroring disabled & IO

RW

selection is output, Data

Output set to inactive/active

page 14

© Banner Engineering Corp. All rights reserved.

June 26, 2024

Configuration Instructions

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Multi-Port Support: Ports 5-8

Register Ranges for Ports 5-8

45001-45305 46001-46305 47001-47305 48001-48305

Register Ranges

Port 5 Port 6 Port 7 Port 8

Measurement Reads

Modbus Register Address

Description

I/O Range

Comments

45001

Measurement Value - Analog In Port 5

0..65535

Voltage = mV, Current = µA

-

45002

Port 5 - Analog Out 0..20500

Voltage = mV, Current = µA

0

Default

Port Output Configuration (Black - Channel 1)

Modbus Register Address

Description

I/O Range

Comments

45200

Port 5 - Mirroring Output Enable

0..1

0 = Disabled, 1 = Enabled

0

45201 45202

Port 5 - Mirroring Input Port Selection

0..1

Port 5 - Output

Outside of Valid

0..2

Range

0 = Port 5

1 = Port 6 2 = Port 7

0

3 = Port 8

0 = Hold, 1 = Low, 2 = High

1

Default

Port Output Configuration (White - Channel 2)

Modbus Register Address
45300
45301 45302 45303
45304 45305

Description
Port 5 - Voltage Minimum LED setpoint value
Port 5 - Voltage Maximum LED setpoint value
Port 5 - Voltage Hysteresis
Port 5 - Current Minimum LED setpoint value
Port 5 - Current Maximum LED setpoint value
Port 5 - Current Hysteresis

I/O Range

Comments

Default

0..9999

Must be less than maximum.

V = 0 mV

0..10000

Must be greater than minimum.

V = 10000 mV

0..500 0..19999 0..20000

mV

V = 50 mV

Must be less than maximum.

4000 µA

Must be greater than minimum.

20000 µA

0..500

µA

100 µA

Port Number

Access

Notes

RO

-

RW

Voltage = 10000 mV, Current = 20000 µA

Access

Notes

If Enabled, Analog Out value

RW

in register 40009 will be

ignored

RW

-

RW

-

Access

Notes

RW

-

RW

If value > Max I/O Range, value = Max

RW

If value > Max I/O Range, value = Max

RW

-

RW

If value > Max I/O Range, value = Max

RW

If value > Max I/O Range, value = Max

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 15

R95C 8-Port 2-Channel Discrete And Analog In-Out Modbus® Hub Instruction Manual

Chapter Contents Wiring ................................................................................................................................................................................................................. 16

Chapter 3

Mechanical Installation

Install the R95C to allow access for functional checks, maintenance, and service or replacement. Do not install the R95C in such a way to allow for intentional defeat. Fasteners must be of sufficient strength to guard against breakage. The use of permanent fasteners or locking hardware is recommended to prevent the loosening or displacement of the device. The mounting hole (4.5 mm) in the R95C accepts M4 (#8) hardware.
See the figure below to help in determining the minimum screw length.
MOUNTING SCREW

17.0 mm

CAUTION: Do not overtighten the R95C's mounting screw during installation. Overtightening can affect the performance of the R95C.

Wiring

Male

Pin

1
1

2

2

4

3

3

5

4

5

Port 1-Port 4 -- Female

Pin

1

2

1

2

4

3

3

4

Port 5-Port 8 -- Female

Pin

1

2

1

2

4

3

3

4

12 V DC to 30 V DC RS485/D1/B/+ Ground RS485/D0/A/Banner 1-wire

Signal Description

12 V DC to 30 V DC Discrete 2 (IN/OUT) Ground Discrete 1 (IN/OUT)

Signal Description

12 V DC to 30 V DC Analog In Ground Analog Out

Signal Description

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 16

R95C 8-Port 2-Channel Discrete And Analog In-Out Modbus® Hub Instruction Manual

Chapter Contents
Chapter 4

Status Indicators

On both sides of the R95C Modbus hub, Ports 1 through 4 have two matching amber LED discrete output indicators, and Ports 5 through 8 have two matching amber LED analog in/analog out indicators. There is also an additional amber LED indicator on both sides of the converter, which is specific to the Modbus communication, and a green LED indicator that shows power status.

Analog In/Out LEDs x8 (on either side) Com LED (on either side)

8 IN OUT

7 IN OUT

6 IN OUT

5C IN OUT

Power LED (on either side)

C5 OUT IN

6 OUT IN

7 OUT IN

8 OUT IN

12 4

12 3

12 2

12 1

Rotate 180°

21 1

21 2

21 3

21 4

Device LEDs x8 (on either side)
LED 1 = Discrete 1 In/Out LED 2 = Discrete 2 In/Out

LED Discrete Device Amber LEDs
Analog In Amber LED(1)

Indication Off Solid Amber Off Solid Amber

Off Analog Out Amber LED
Solid Amber

Modbus Communication Amber LED

Off

Status Discrete In and Out are inactive Discrete In or Out is active Analog current value is less than setpoint one OR analog value is greater than setpoint two Analog current value is between setpoint one AND setpoint two Turns off if written PDO analog value is outside the allowable output range
Allowable Voltage Range: 0 V to 10 V.
Allowable Current Range: 4 mA to 20 mA. Turns on if written PDO analog value is inside the allowable output range
Allowable Voltage Range: 0 V to 10 V.
Allowable Current Range: 4 mA to 20 mA.
Modbus communications are not present
Continued on page 18

(1) Default Current Values: SP1 = 0.004 A, SP2 = 0.02 A. Default Voltage values: SP1 = 0 V, SP2 = 10 V.

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 17

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Status Indicators

Continued from page 17

LED

Indication

Status

Flashing Amber (4 Hz)

Modbus communications are active

Solid Amber for 2 Seconds, Then to Off

Modbus communications are lost after connection

Solid Amber for 2 Seconds, Then to Flashing Amber (4 Hz)

Modbus communications momentarily lost, but then communication was reestablished

Off Power Indicator Green LED
Solid Green

Power off Power on

page 18

© Banner Engineering Corp. All rights reserved.

June 26, 2024

R95C 8-Port 2-Channel Discrete And Analog In-Out Modbus® Hub Instruction Manual

Chapter Contents
FCC Part 15 Class B for Unintentional Radiators .............................................................................................................................................. 19 Industry Canada ICES-003(B)............................................................................................................................................................................ 20 Dimensions......................................................................................................................................................................................................... 20

Chapter 5

Specifications

Supply Voltage 12 V DC to 30 V DC at 400 mA maximum (exclusive of load)
Power Pass-Through Current Not to exceed 4 amps total
Discrete Output Load Rating 200 mA
Analog Input Impedance Current version: Approximately 250  Voltage version: Approximately 14.3k 
Analog Output Load Requirements Voltage version = Resistance > 1000  Current version = Resistance < 500 
Supply Protection Circuitry Protected against reverse polarity and transient voltages
Leakage Current Immunity 400 µA
Indicators Green: Power Amber: Modbus communications Amber: 2x Discrete IN/OUT status Amber: Analog input value present Amber: Analog output value in range
Connections (8) Integral 4-pin M12 female quick-disconnect connectors (1) Integral 5-pin M12 male quick-disconnect connector
Construction Coupling Material: Nickel-plated brass Connector Body: PVC translucent black
Vibration and Mechanical Shock Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55 Hz, 0.5 mm amplitude, 5 minutes sweep, 30 minutes dwell) Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine wave)
Environmental Rating IP65, IP67, IP68 UL Type 1

Operating Conditions Temperature: ­40 °C to +70 °C (­40 °F to +158 °F) 90% at +70 °C maximum relative humidity (non-condensing) Storage Temperature: ­40 °C to +80 °C (­40 °F to +176 °F)
Required Overcurrent Protection

WARNING: Electrical connections must be made by qualified personnel in accordance with local and national electrical codes and regulations.

Overcurrent protection is required to be provided by end product application per the supplied table.
Overcurrent protection may be provided with external fusing or via Current Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to www.bannerengineering.com.

Supply Wiring (AWG)
20
22
24

Required Overcurrent Protection (A)
5.0 3.0 1.0

Supply Wiring (AWG)
26
28
30

Required Overcurrent Protection (A)
1.0 0.8 0.5

Certifications

Banner Engineering BV Park Lane, Culliganlaan 2F bus 3 1831 Diegem, BELGIUM

Turck Banner LTD Blenheim House Blenheim Court Wickford, Essex SS11 8YT GREAT BRITAIN

Product Identification

FCC Part 15 Class B for Unintentional Radiators
(Part 15.105(b)) This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
· Reorient or relocate the receiving antenna. · Increase the separation between the equipment and receiver. · Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 19

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Specifications

· Consult the dealer or an experienced radio/TV technician for help. (Part 15.21) Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this equipment.
Industry Canada ICES-003(B)
This device complies with CAN ICES-3 (B)/NMB-3(B). Operation is subject to the following two conditions: 1) This device may not cause harmful interference; and 2) This device must accept any interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la norme NMB-3(B). Le fonctionnement est soumis aux deux conditions suivantes : (1) ce dispositif ne peut pas occasionner d'interférences, et (2) il doit tolérer toute interférence, y compris celles susceptibles de provoquer un fonctionnement non souhaité du dispositif.
Dimensions
All measurements are listed in millimeters [inches], unless noted otherwise.

page 20

© Banner Engineering Corp. All rights reserved.

June 26, 2024

R95C 8-Port 2-Channel Discrete And Analog In-Out Modbus® Hub Instruction Manual

Chapter Contents
Chapter 6

R95C Accessories

Cordsets
Model BC-M12F4-M12M4A-22-1 BC-M12F4-M12M4A-22-2 BC-M12F4-M12M4A-22-5 BC-M12F4-M12M4A-22-8 BC-M12F4-M12M4A-22-10
BC-M12F4-M12M4A-22-15

4-pin M12 Cordsets - Female Straight to Male Right-Angle Double-Ended

Length

Dimensions (mm)

Pinouts

1 m (3.28 ft) 2 m (6.56 ft) 5 m (16.4 ft) 8 m (26.25 ft) 10 m (30.81 ft)
15 m (49.2 ft)

32 Typ. [1.26"]
30 Typ. [1.18"]

M12 x 1 ø 14.5 [0.57"]
44 Typ. [1.73"]

ø 14.5 [0.57"] M12 x 1

Female 2
1 3
4
Male
1 2
4 3

1 = Brown 2 = White 3 = Blue 4 = Black

Model BC-M12F4A-M12M4A-22-1 BC-M12F4A-M12M4A-22-2 BC-M12F4A-M12M4A-22-5 BC-M12F4A-M12M4A-22-8 BC-M12F4A-M12M4A-22-10
BC-M12F4A-M12M4A-22-15

4-pin M12 Cordsets - Female Right-Angle to Male Right-Angle Double-Ended

Length

Dimensions (mm)

Pinouts

1 m (3.28 ft) 2 m (6.56 ft) 5 m (16.4 ft) 8 m (26.25 ft) 10 m (30.81 ft)
15 m (49.2 ft)

32 Typ. [1.26"]

30 Typ. [1.18"]

Female
2 1
3 4

M12 x 1 ø 14.5 [0.57"]

Male
31 Typ.
1 2

32 Typ.

4 3

1 = Brown 2 = White 3 = Blue 4 = Black

Splitter Cordsets

4-Pin Threaded M12 Male to 5-Pin Threaded M12 Female Splitter Cordset

Model

Branches (Female)

Wiring
N/C

S15YA4-M124-M124-0.2M

L1, L2 2 × 0.2 m (7.9 in)

N/C

Continued on page 22

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 21

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Continued from page 21 4-Pin Threaded M12 Male to 5-Pin Threaded M12 Female Splitter Cordset

Model

Branches (Female)

L2

M12 x 1

R95C Accessories Wiring
M12 x 1

2X 2X
L1

Model CSB4-M1251M1250

Branch 1

2 x 19 Branch 2

72 mm

Branch 3

3 x 18 Branch 4

Model

5-Pin Threaded M12 Splitter Cordset with Flat Junction--Double Ended

Description

Pinout (Male)

Four (no cable) 5-pin M12 female quickdisconnect connectors

1 2

One 0.3 m (0.98 ft) cable with a 5-pin M12

4

male quick-disconnect connector

3

5

Parallel wiring

32 mm

Male Trunk Length

1 = Brown 2 = White 3 = Blue 4 = Black 5 = Gray

4-Pin Threaded M12 RS-485 to USB Adapter Cordset, with Wall Plug

Length

Style

Dimensions

BWA-UCT-900

1 m (3.28 ft)

Straight

Splitter Tee

Model

5-Pin Threaded M12 Splitter Tee

Pinout (Male)

CSB-M1250M1250-T
· Two 5-pin M12 female quick-disconnect connectors
· One 5-pin M12 male quick-disconnect connector
· Parallel wiring

1

2 4

3

5

1 = Brown 2 = White 3 = Blue 4 = Black 5 = Gray

Pinout (Female)

2 1

3

4

5

1 = Brown 2 = White 3 = Blue 4 = Black 5 = Gray

Pinout (Female)

2

4

1

3

1 = Brown 2 = White 3 = Blue 4 = Black

Pinout (Female)

2 1

3

4

5

1 = Brown 2 = White 3 = Blue 4 = Black 5 = Gray

page 22

© Banner Engineering Corp. All rights reserved.

June 26, 2024

R95C Accessories
5-Pin Molded Junction Blocks
Model
R50-4M125-M125Q-P Molded Junction Block · Four integral 5-pin M12 female quickdisconnect connectors · One integral 5-pin M12 male quickdisconnect connector · Parallel wiring · Product documentation (p/n 227974)
R95-8M125-M125Q-P Molded Junction Block · Eight integral 5-pin M12 female quickdisconnect connectors · One integral 5-pin M12 male quickdisconnect connector · Parallel wiring · Product documentation (p/n 227974)

R95C 8-Port 2-Channel Discrete and Analog In-Out Modbus® Hub Instruction Manual

Pinout (Male)

Pinout (Female)

1

2 4

3

5

1 = Brown 2 = White 3 = Blue 4 = Black 5 = Gray

2 1

3

4

5

1 = Brown 2 = White 3 = Blue 4 = Black 5 = Gray

Brackets
SMBR90S · Stainless steel bracket · 4x M4-07 pemnuts (B) · Includes 2x M4 stainless steel hex head screws and flat washers
Hole center spacing: A = 40, B = 20 Hole size: A = ø 5
SMBR95RA · Stainless steel right-angle bracket · M4 x 0.7 mm #316SS screws (qty 2)

8.6

B

74

A

24 10.1

90

2X M4 x 0.7 PEM
Ø4.5
2X Ø4.5

40 40

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 23

R95C 8-Port 2-Channel Discrete And Analog In-Out Modbus® Hub Instruction Manual

Chapter Contents
Chapter 7

Banner Engineering Corp Limited Warranty

Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to: www.bannerengineering.com.
For patent information, see www.bannerengineering.com/patents.

June 26, 2024

© Banner Engineering Corp. All rights reserved.

page 24

LinkedIn Twitter Facebook
© 2024. All rights reserved. www.bannerengineering.com



References