Overflow unit

lindab | we simplify construction
OLC
Dimensions
24

Ød ØU*

ØD 25

Description
OLC is a circular overflow unit for installation directly into a wall. OLC consists of two sound-attenuating baffles, which are mounted on both sides of the wall.
· Discrete design · Sound-attenuating baffles
Maintenance
The sound attenuation baffles on both sides of the wall can be removed to enable cleaning of internal parts. The visible parts of the unit can be wiped with a damp cloth.

OLC Size (Ød)

ØD [mm]

*ØU

m [kg]

100

200

108-110

0.,8

125

250

133-135

1.,0

160

300

168-170

1.,2

*ØU = Cutout dimension in wall = Ød + 10 mm

Quick selection

OLC Size Ød 100 125 160

pt = 10 [Pa] [l/s] [m3/h]

19

68

28 101

40 144

pt = 15 [Pa] [l/s] [m3/h]

24

86

34 122

49 176

pt = 20 [Pa] *Dn,e,w [l/s] [m3/h] [dB]

27

97

49

39 140 47

56 202 44

* Values valid for cavity wall with 95 mm insulation.

Order code
Product Type
OLC
Size
100, 125, 160 mm
Example: OLC - 125

Materials and finish

OLC

aaa

Installation bracket:

Galvanised steel

Front plate:

Galvanised steel

Standard finish:

Powder-coated

Standard colour:

RAL 9010 or 9003, Gloss 30

The OLC is available in other colours. Please contact Lindab's sales department for further information.

Lindab reserves the right to make changes without prior notice

1

2021-03-11

lindab | we simplify construction
Overflow unit
Accessories OLCZ - Perforated wall sleeve

OLC installed in wall

OLC

Order code
Product Type
OLCZ
Size
Ø100, 125, 160 mm
Example: OLCZ - 160

OLCZ

OLC with OLCZ installed in wall
OLCZ optional accessory.
aaa

For further information, see OLC installation instruction.

2

Lindab reserves the right to make changes without prior notice

2021-03-11

Overflow unit

lindab | we simplify construction
OLC

Technical data
Capacity
Air flow rate qv [l/s] and [m3/h], total pressure loss pt [Pa] and sound power level LWA [dB(A)] are specified for a OLC unit on both sides of the wall.
Dimensioning diagram

pt [Pa] OLC 100
70
50

30

20 15

10

7

5

15

20

60 70

100

125

160

50

45

40 35 30

25

20

30

40

100

50 200

70

100

300

LWA dB(A)

q [l/s] 150 200 V

q [m3/h]

500

700 V

Element-normalised reduction figure Dn,e
Weighted value (Dn,e,w) evaluated according to ISO 717-1

Cavity wall with 95 mm insulation

Size [mm] 100 125 160

Centre frequency [Hz]

125 250 500 1K 2K

32

46

46

48

54

34

43

43

46

51

34

40

40

44

50

*Dn,e,w 49 47 44

Cavity wall with 70 mm insulation

Size [mm]

Centre frequency [Hz] 125 250 500 1K 2K

100

30

40

38

42

50

125

30

37

37

42

49

160

30

34

34

40

50

*Dn,e,w 43 43 41

Solid wall without insulation

Size [mm]

Centre frequency [Hz] 125 250 500 1K 2K

100

24

24

23

32

40

125

23

24

23

33

40

160

24

24

23

32

39

*Dn,e,w 31 31 30

Lindab reserves the right to make changes without prior notice

3

2021-03-11

lindab | we simplify construction
Overflow unit

OLC

Technical data
Sample calculation
When dimensioning an overflow diffuser, calculate the decrease in the wall's noise-reducing properties.
For these calculations, the area of the wall and sound reduction figure R must be known.
This is adjusted in relation to the unit's Dn,e value. Dn,e is the unit's R value given at a transmission area of 10 m2, as specified in ISO 140-10.
The Dn,e value can be converted into the R value for other transmission areas using the table below.

Area [m2] Correction [dB]

10

2

1

0

-7

-10

The diagram below indicates the decrease of the sound reduction index of the wall, for a given octave band value (Dn,e ) or weighted value ( Dn,e,w ).
As a rough estimate the calculation can be performed directly using the wall´s Rw value and the weighted elementnormalized level difference Dn,e,w of the unit.

Example:

(See diagram below) :

Rw (wall): Dn,e,w (diffuser): Area of wall:

50 dB 44 dB 20 m2

Number of Units: 1

Rw- Dn,e,w = 6 dB 20 m2/1 = 20 m2

Indicated reduction of Rw (wall): Rw value for wall with unit:

5 dB ~50-5 = 45 dB

The calculation can also be performed using the following formula:

Rres = 10  Log

Swall
+ (10m²  10-0,1·Dn,e ) (Swall 10-0,1 · Rwall )

where:

- Rres is the resulting reduction figure for wall and diffuser. - S is wall area.
- Dn,e is the unit's Dn,e value. - Rwall is the wall's R value without unit.

Reduction of wall (Rw) [dB]
25

20

15

10

5

0

0

5

10

Difference between wall and unit ( Rw - Dn, e, w ) [dB]

20 15 10

5 0

15

20

25

30

35

40

45

50

Area of wall [m²] / Number of units [-]

4

Lindab reserves the right to make changes without prior notice

2021-03-11


Adobe PDF Library 15.0 Adobe InDesign 15.1 (Windows)