ENV-PARTICLE Application Guide

ENV-PARTICLE

Application Guide

Digital PM1,2.5,4 & 10 particle sensor


File Info : application/pdf, 5 Pages, 1.29MB

PDF preview unavailable. Download the PDF instead.

ENV-PARTICLE Application Guide
ENV-PARTICLE
Sensor Application Guide

I. Overview
The Particle Sensor (ENV-PARTICLE) is used in detecting particle concentration in HVAC and air quality applications.
This document aims to guide the user in installing our ENV-PARTICLE in your facilities and also to provide recommendations for sensor placement.
You may visit our Particle sensor page at: https://infrasensing.com/sensors/sensor_particle.asp
II. What you need
· Power source (PoE or 12V DC) · BASE-WIRED · LAN cable · ENV-PARTICLE
III. Recommended placements
3.1. For air quality monitoring, the sensor should be placed:
· Within the breathing level in the room, this is between 3-6ft or 1.5-2m from the floor. · At least 3ft/1m away from any obstacles, openings, and ventilations. · At 180 ° free of any obstruction. · Not being close to any pollutants that may impact its result.

Revision 1 ­ May 23, 2022

2

3.2. For particle air inlet and outlet: · The ENV-PARTICLE is housed in a metal frame that has 2 air inlets and 1 air outlet that should remain unobstructed at all times. · In vertical orientation, the inlets/outlets should be facing down to avoid dust accumulation.
· In lateral placement, the inlets should be above the outlet to avoid returning of particles to the inlets.
· In horizontal placement, the green marked inlet should be facing the ground.

Revision 1 ­ May 23, 2022

3

IV. Installation
4.1. Supply power to the BASE-WIRED via PoE(power over ethernet or 12V DC adapter/BASE-PWR) Other power options include BASE-PWR-USB, ADDON-POE, ADDON-UPS.

4.2. Connecting the BASE-WIRED to the ENV-PARTICLE · Via direct LAN connection

You can connect up to 2 sensor probes to the BASE-WIRED

Revision 1 ­ May 23, 2022

4

· Via SensorHub(EXP-8HUB)

You can connect up to 8 sensor probes to the BASE-WIRED using the EXP-8HUB · Via LoRa (EXP-LWHUB and NODE-LW-1P)

You can wirelessly connect your sensor probe to the BASE-WIRED, each LoRa Hub can support up to 20 LoRa Node. The LoRa Hub's power is supplied by the BASE-WIRED while the LoRa Node's power can be supplied by 12/24V DC or a USB-C type.

Revision 1 ­ May 23, 2022

5

