EasyVEC® Standard 10000 IP VAR DTE CIRC Isolé
Caissons d'extraction non classés au feu
Product Overview
The EasyVEC® Standard range offers the most advanced single-flow casing design on the market, making ventilation efficient, serene, and easy. It is designed for single-flow ventilation in tertiary premises, either by extraction or supply, ensuring sufficient air quality and preserving the building.
Product Reference: 11034052
Key Features:
- Wide range from 4000 to 12000 m³/h
- 100% recyclable
Applications:
- Residential collective housing
- Renovation
- Tertiary premises
- Mechanical extract ventilation systems
Operating Principles
EasyVEC® Standard enables single-flow ventilation in tertiary premises through air extraction or supply, ensuring sufficient air quality and building preservation.
Installation
Installation should be on an anti-vibration slab according to DTU 68.3 recommendations. It can be installed indoors or outdoors. Ensure sufficient space in front of the casing for easy access to internal components. Installation preferably away from wind is recommended to limit pressure losses during rooftop installation.
For optimal acoustic and aerodynamic performance, it is recommended to:
- Install silencers at the casing connection points.
- Use the ALDES VIRTUO-FIX joint accessory range.
- Use MS PRO airtight flexible connectors to decouple network vibrations.
Key Features & Complementary Characteristics
- AC motorization
- Reaction impeller
- Casing made of Z275 galvanized steel sheet
- Numerous options and accessories available, including: filter casing, ISO Grossier 60%, ePM10 50%, ePM1 50-75%, ePM1 85% filters, filter replacement indicator, pressure switch.
- Product manufactured in France.
- Compatible with Ventilation Modulated Technical Opinion Presence-Agito-CO2-Hygro n° 14.5/16-2185_V1.
- ErP 2018 compliant.
- Eligible for CEE: BAT-TH-112, BAT-TH-125, BAT-EQ-123.
Accessories
Designation | Reference |
---|---|
Circuit breaker 11-16 A | 11057056 |
Duct probe +25/+90°C | 11090900 |
Flow control kit (20-300 Pa) | 11090901 |
Duct probe -10/+35°C | 11090902 |
Female rain shield + grille Ø 710 mm | 11056410 |
OCTA D710 + gasket | 11094647 |
MS PRO V2 D710 | 11094663 |
Consumables
Designation | Reference |
---|---|
G4 Filter EasyVEC® 10000/12000 | 11034411 |
M5 Filter EasyVEC® 10000/12000 | 11034414 |
F7 Filter EasyVEC® 10000/12000 | 11034425 |
F9 Filter EasyVEC® 10000/12000 | 11034428 |
General Data
Reference | Motor Type |
---|---|
11034052 | AC |
Dimensional Data
Reference | E (mm) | F (mm) | H (mm) | L (mm) | M (mm) | P (mm) | T (mm) | Y (mm) | Z (mm) | Ø (mm) |
---|---|---|---|---|---|---|---|---|---|---|
11034052 | 575 | 1155 | 905 | 910 | 60 | 945 | 960 | 940 | 115 | 710 |
Diagram showing the dimensions of the EasyVEC® Standard unit with labels E, F, H, L, M, P, T, Y, Z, and Ø.
Electrical Data
Reference | Maximum Power (W) | Maximum Power (kW) | Protection Index | Maximum Current (A) | Electrical Supply |
---|---|---|---|---|---|
11034052 | 2050 | 2.05 | IP24 | 13.2 | Single-phase |
Aerodynamic Data
Reference | Nominal Flow Rate (m³/h) |
---|---|
11034052 | 10000 |
Aerodynamic curves showing static pressure (P) in Pa against flow rate (m³/h) for the EasyVEC-Standard-10000 at different RPMs (1370 RPM and 200 RPM). The curves indicate the relationship between pressure and flow rate for the unit.
Weight: 160 kg
Regulations & Conformity
Technical Opinion Number: 14.5/16-2185_V2
Aerodynamic curves established according to standard NF EN ISO 5801. P (Pa) = Static pressure. P(W) = Power consumed.