Instruction Manual for TRANE models including: FIACO2K001, FIACO2K002, CO2 Sensing Kit, 6 to 25 Ton Packaged Units with Symbio 700 Controls, CO2 Sensing Kit, 6 to 25 Ton Packaged Units with Symbio 700 Controls, 6 to 25 Ton Packaged Units, Packaged Units with Symbio 700 Controls

Installation Instructions

0-100% Downflow Dry Bulb Economizer

Downflow, Dry Bulb, Economizer, Voyager, BAYECON089A, BAYECON090A, dry bulb economizer, standard economizer, ACC-SVN78F-EN

TCS - Unitary

Installation Instructions - Trane Technologies

Aug 29, 2022 — SAFETY WARNING. Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, ...


File Info : application/pdf, 2 Pages, 712.69KB

PDF preview unavailable. Download the PDF instead.

ACC-SVN248A-EN 08292022
Installation Instructions
CO2 Sensing Kit
6 to 25 Ton Packaged Units with SymbioTM 700 Controls

Model Number: FIACO2K001* FIACO2K002**

Used With: PrecedentTM with wall mount sensor PrecedentTM with duct mount CO2 sensor

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

August 2022

ACC-SVN248A-EN
©2022

4
Inspection
1. Unpack all components of the kit. 2. Check carefully for shipping damage. If any damage is found, report it
immediately, and file a claim against the transportation company. 3. Visually inspect the components for shipping damage as soon as possible
after delivery, before it is stored. Concealed damage must be reported within 15 days. 4. If concealed damage is discovered, stop unpacking the shipment. 5. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery. 6. Notify the carrier's terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee.
Note: Do not attempt to repair any damaged parts until the parts are inspected by the carrier's representative.
Parts List
CO2 Sensor: FIACO2K001*
· One (1) CO2 Demand-Controlled Ventilation Wall-Sensor (4190 4100) with instructions and mounting hardware.
FIACO2K002* · One (1) CO2 Demand-Controlled Ventilation Duct -Sensor (4190 4101) with instructions and mounting hardware. · One (1) "CO2 Kit Has Been Installed" Label

1
Warnings, Cautions, and Notices
Read this manual thoroughly before operating or servicing this unit. Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION

Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.

NOTICE

Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerantsincluding industry replacements for CFCs such as HCFCs and HFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

2
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
· Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
· When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
· If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other countryspecific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

3
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
· All Trane personnel must follow the company's Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
· Non-Trane personnel should always follow local regulations.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
General
Note: An economizer must be installed and functional before attempting to install a CO2 sensing kit. These sensors detect and control the carbon dioxide level in the conditioned space by measuring CO2 concentration, comparing it with a user-adjustable set point and sending a corresponding control signal to the economizer module. This causes the economizer damper to be positioned so that sufficient fresh air is introduced into the conditioned space to reduce and maintain the CO2 concentration to a minimum level as selected by the user.

5
Installation
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
1. Apply provided CO2 and ventilation override wiring diagram label next to the main unit wiring diagram label, located on compressor access panel.
2. Apply "CO2 kit Has Been Installed" label next to the main unit wiring diagram label.
3. Install CO2 sensor in conditioned space or return air duct according to instructions packed with the sensor.
4. Make field wiring connections to SymbioTM 700 UC J22 pins 1-3. Refer to main unit schematic sheet 3 and in this guide.
5. Route low voltage external field wiring along with and secure to existing low voltage zone sensor or thermostat wiring.
6. Replace any access panels removed for kit installation.

6
CO2 Sensor Operation for SymbioTM 700 with Economizer
Demand Control Ventilation (DCV)
DCV eliminates over-ventilating the space by allowing the fresh air damper to close further than non-CO2 sensing systems, which reduces power consumption. DCV adjusts the fresh air damper between a DCV Minimum Position and Design Minimum Position. DCV Minimum Position equals non-CO2 sensing systems minimum damper position - 10%, or more, down to 0% open. When the CO2 level is greater than or equal to the DCV Minimum CO2 setpoint the supply fan is energized and the fresh air damper modulates between the DCV Minimum Position Setpoint and the Design Minimum Setpoint, increasing the amount of outdoor air flow and reducing the CO2 level in the space. The damper will only open up to the Design Minimum Position Setpoint. If the CO2 level drops below the DCV Minimum CO2 Setpoint - 50ppm the fresh air damper will drive to the DCV Minimum Position. If CO2 level rises above the Building CO2 setpoint the fresh air damper will open to the Design Minimum Position setpoint.
DCV Setup, Damper Position and CO2 Setpoint
Before beginning, turn the fan ON and conduct the Minimum Position Setpoint procedure used WITHOUT CO2 to obtain and record visually the Minimum Position Setpoint setting and/or the corresponding DC voltage settings for the min and max required to meet ASHRAE standards.

7

2

OAS

DAT

FOS

PPF132 PPM132

PPF150 PPM150

21 21 BR Y
BR Y 21 21
BR Y

PPF50 PPM50

21 21 O BL
3
O BL 21 21
O BL

PPF32 PPM32

21 21 R BK
R BK 21 21
R BK

PPF77 PPM77

PPF177 PPM177

OPTIONAL LCI MODULE

TO LINE 210
SHEET 4 AB-J18

EXPANSION MODULE
TO LINE 484 SHEET 9 XM30/XM32

TO LINE 49
SHEET 1 PPM72

PPF116 PPM116 BK 1 1 BK R 22 R BL 3 3 BL BK 4 4 BK R 55 R BL 6 6 BL O 77 O BK 8 8 BK R 99 R BL 10 10 BL
TO LINE 224 SHEET 4 AB-J17

BR Y O BL R BK 654321 654321
BR Y O BL R BK
LPC1

PPF117 PPM117

BK R BL 123

BL O 1234

BK R BL O 1234

BK R BL O 1234

BK R 12

BK R BL 123

BK R BL O 1234

ETH USB-A
P1 J1 P2 P3 J3 P4 J4 J3 P3 J4 P4 J5 J6 P6 P5 J5

123

1234

1234

1234

1234

12

12

123

1234

WHITE

WHITE

WHITE

WHITE

WHITE

WHITE

GREEN

WHITE

BLACK

ETHERNETHOST PORT USB-B TRACER TU

MODBUMSOD+BUCSOM- MON

24 VAC OCUOTMMON IMC+ IMC-

24 VAC OCUOTMMON IMC+ IMC-

24 VAC OCUOTMMON IMC+ IMC-

24 VAC OCUOTMMON IMC+ IMC-

24 VACCOINMMON

COM2M4VOANC OUT

PH2A4SVEAMCOONUITTORCOINMCMOONNTROL VINCODOLONTOATIRGRNOEDFLOAINVNOORRLUFTANANGEHIINSPEED

24 VAC IN COMMON

J14 P14

BK

11

PINK

R

22

DISCHARGE AIR TEMP

J15 P15

BL

11

O

22

OUTDOOR AIRTEMP

CONDENSER FAN1 COMMON
CONDENSER FAN2 COMMON
CONDENSER FAN3 COMMON

LT BLUE

PURPLE

P15

1

2

COIL TEMP 1

P17

1

2

COIL TEMP 2

SYMBIO 700
(UC)

CONTROL 24 VAC IN CONTROL 24 VAC OUT CIRCUIT 1 PROVING IN COMPRESSOR 1 24 VAC IN COMPRESSOR 1 RUN COMPRESSOR 1 UNLOADER/CCH

YELLOW

P18

1

2

COIL TEMP 3

GRAY

PPM19PPF19 11 22

J19 P19 BK 1 1 R 22

CIRCUIT 1 DISABLE

CONTROL VOLTAGE IN CONTROL VOLTAGE OUT CONTROL 2 PROVING IN COMPRESSOR 2 24 VAC IN
COMPRESSOR 2 RUN COMPRESSOR 2 UNLOADER/CCH

RED

BROWN

P20

1

2

CIRCUIT 2 DISABLE

J21 P21

Y

11

BR

22

CIRCUIT 3 DISABLE

CONTROL 24 VAC IN CONTROL 24 VAC OUT CIRCUIT 3 PROVING IN COMPRESSOR 3 24 VAC IN COMPRESSOR 3 RUN COMPRESSOR 3 UNLOADER/CCH

GREEN

J16

1 2

GREEN

DEMAND LIMIT/SHED

24 VAC OUT

ACNETACINN+ETACINN-ETACONUETT+OUT-

24 VACEMOEURTGENCY STOZPONECTOEMMMPCOONOLUINNGITSMEHTOEADPTEOICNINOGTMSME2OT4NPVOACINOTUT

24 VACLOOCUATL OCCUPAN2C4YVACT-OSTUATTT-SYT1ATT-SWT1A/0TT-SGT/VAATTV-SWCT2AHTTA-NSYGT2AETTO-XSV2TEARTT-SPTUALTLDGONWDN-T 24 VDCCOO2UITNCOMMON

24 VDCSPOAUCTECOHMUMMIODNITY

SOV1 OUT COMMON SOV2 OUT COMMON

GREEN 1234

GREEN 12

GREEN 1234567

GREEN 12

GREEN 123456789

GREEN 123

GREEN 123

ECM CONDENSER FAN CONTROL COMMON

J20 J21

J18 J19

J17

1234

12

1234567

12

123456789

123

123

BLACK

WHITE

BLUE

WHITE

RED

BLACK

WHITE

P6 J6 1 1 BK 2 2R
P7 J7 1 1 BK 22 3 3 BL 44 5 5Y 66
P8 J8 1 1 BK 2 2R 3 3 BL 4 4O 5 5Y 6 6 BR
P9 J9 1 1 R/BK 2 2 BL/BK 3 3 O/BK 4 4 Y/BK 5 5 BR/BK 6 6 BK/R
P10 1 2 3 4 5 6
P11 1 2 3 4
P12 1 2

J22 J23
-H

1 TO SHUT DOWN UNIT FOR EMERGENCY STOP, CONNECT FIELD SUPPLIED CONTROL DEVICE ACROSS PINS 1 & 2. UNIT STOPS WHEN SWITCH CLOSES.
2 DISCHARGE AIR TEMPERATURE SENSOR (DAT) STANDARD ON UNITS WITH SZVAV & MZVAV.
3 EXTENSION HARNESS NOT PRESENT ON 15-25T UNITS.

1234 BUILDING
AUTOMATION SYSTEM

1234567 1234567
ZONE SENSOR
1 OPTIONAL REMOTE SENSOR

123456789 THERMOSTAT

123 CO2 SENSOR
J22 Connector

TO LINE 72 SHEET 2 MODBUS-1
IMC-1 IMC-1 1 1 BK 2 2R 3 3 BL 4 4O
TO LINE 72 SHEET 2
MODBUS-1

TO LINE 250 SHEET 5
IOM-J5

REF DES DAT FOS LPC1 OAS UC

LEGEND DESCRIPTION SENSOR - DISCHARGE AIR SWITCH - FROSTAT SWITCH - LOW PRESSURE 1 SENSOR - OUTDOOR AIR MODULE - UNIT CONTROLLER

LINE NO 122 124 156 122 143

TO LINE 49 SHEET 1 PPM72
TO LINE 224 SHEET 4 AB-J17

TO LINE 224 SHEET 4
AB-J17

TO LINE 224 SHEET 4
AB-J17

CONDUCTOR NAME 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

CONDUCTOR BASE COLOR BLACK RED BLUE ORANGE YELLOW BROWN RED BLUE ORANGE YELLOW BROWN BLACK BLUE ORANGE YELLOW BROWN BLACK RED ORANGE YELLOW BROWN BLACK RED BLUE YELLOW BROWN

CONDUCTOR TRACER COLOR
BLACK BLACK BLACK BLACK BLACK RED RED RED RED RED BLUE BLUE BLUE BLUE BLUE ORANGE ORANGE ORANGE ORANGE ORANGE

Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.

Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

ACC-SVN248A-EN 29 Aug 2022 (NEW)

©2022



References

Acrobat Distiller 22.0 (Windows)