Autonics MT4Y Series 4-Digit Multi Panel Meters
Instruction Manual
Model: MT4Y Series
Document ID: TCD220016AA
Introduction
Thank you for choosing our Autonics product. Read and understand the instruction manual and manual thoroughly before using the product. For your safety, read and follow the below safety considerations before using. For your safety, read and follow the considerations written in the instruction manual, other manuals and Autonics website. Keep this instruction manual in a place where you can find easily. The specifications, dimensions, etc. are subject to change without notice for product improvement. Some models may be discontinued without notice. Follow Autonics website for the latest information.
Safety Considerations
⚠️ Warning Failure to follow instructions may result in serious injury or death.
- 01. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime / disaster prevention devices, etc.) Failure to follow this instruction may result in personal injury, economic loss or fire.
- 02. Do not use the unit in the place where flammable / explosive / corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present. Failure to follow this instruction may result in explosion or fire.
- 03. Install on a device panel to use. Failure to follow this instruction may result in fire or electric shock.
- 04. Do not connect, repair, or inspect the unit while connected to a power source. Failure to follow this instruction may result in fire or electric shock.
- 05. Check 'Connections' before wiring. Failure to follow this instruction may result in fire.
- 06. Do not disassemble or modify the unit. Failure to follow this instruction may result in fire or electric shock.
⚠️ Caution Failure to follow instructions may result in injury or product damage.
- 01. When connecting the power / measurement input and relay output, use AWG 24 (0.20 mm²) to AWG 15 (1.65 mm²) cable or over and tighten the terminal screw with a tightening torque of 0.98 to 1.18 N m. Use the wiring suitable for the load current capacity. Failure to follow this instruction may result in fire or malfunction due to contact failure.
- 02. Use the unit within the rated specifications. Failure to follow this instruction may result in fire or product damage.
- 03. Use a dry cloth to clean the unit, and do not use water or organic solvent. Failure to follow this instruction may result in fire or electric shock.
- 04. Keep the product away from metal chip, dust, and wire residue which flow into the unit. Failure to follow this instruction may result in fire or product damage.
Cautions during Use
- Follow instructions in 'Cautions during Use'. Otherwise, It may cause unexpected accidents.
- Power supply should be insulated and limited voltage / current or Class 2, SELV power supply device.
- Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.
- Use twisted pair wire for communication line.
- Keep away from high voltage lines or power lines to prevent inductive noise. In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line.
- Do not use near the equipment which generates strong magnetic force or high frequency noise.
Connection with the line filter
Install the line filter close to the panel meter.
Connection with the varistor
Panel meter [HI] [LOW] 110/220 VAC~ Earth ground
This unit may be used in the following environments.
- Indoors (in the environment condition rated in 'Specifications')
- Altitude max. 2,000 m
- Pollution degree 2
- Installation category II
Ordering Information
This is only for reference, the actual product does not support all combinations. For selecting the specified model, follow the Autonics website.
Model structure: MT4Y - [Input type] - [Preset output + Sub output] - 4
Input Type
- DV: DC voltage 01)
- DA: DC current
- AV: AC voltage 02)
- AA: AC current 02)
Preset output
- N: None (indicator)
- 0: Relay
- 1: NPN open collector
- 2: PNP open collector
- 3: Relay (Low out)
- 4: Relay (Low out)
Sub output
- Transmission (DC 4-20 mA)
- RS485 Communication
- BCD Dynamic
- Low speed serial
01) To measure the current over DC 5 A, please select DV type because the shunt should be used.
02) In case of selecting frequency display, no output will be provided even if it is output support model.
Product Components
- Product
- Bracket X 2
- Instruction manual
- Unit sticker X 1
Manual & Software
Manual
For proper use of the product, refer to the manuals and be sure to follow the safety considerations in the manuals. Download the manuals from the Autonics website.
Software
Download the installation file and the manuals from the Autonics website.
DAQMaster
It is the comprehensive device management program for Autonics' products, providing parameter setting, monitoring and data management.
Dimensions
Unit: mm. For detailed drawings, refer to the Autonics website.
Main dimensions: 72 (Width) x 36 (Height) x 66.5 (Depth)
Panel cut-out: 68+0.7 / 31.5+0.5
(Diagram description: A rectangular panel meter with dimensions shown. A separate diagram shows the panel cut-out dimensions.)
Cautions during Wiring
Use Copper-conductor wire with the temperature class 60 °C.
Unit: mm. Use terminals of the specified size below. Contact the manufacturer for the socket and cable.
Connector details:
- Model: Hirose connector HIF3BA-14PA-2.54DS
- Socket: Hirose connector socket HIF3BA-14D-2.54R
(Diagram description: Shows a Hirose connector and socket with pin numbers.)
Connections
Input
DC voltage
Terminals: SOURCE, COM, 1234567. Ranges: 250 mVDC to 500 VDC.
DC current
Terminals: SOURCE, COM, 1234567. Ranges: 5 mA to 5 A.
AC voltage
Terminals: SOURCE, COM, 1234567. Ranges: 1 VAC to 500 VAC.
AC current
Terminals: SOURCE, COM, 1234567. Ranges: 50 mA to 5 A.
Output
- 0: Relay: Terminals 8-13. Functions: HOLD/ZERO, HI, GO, LO, COM.
- 1: NPN open collector: Terminals 8-13. Functions: HOLD/ZERO, HI, GO, LO, COM.
- 2: PNP open collector: Terminals 8-13. Functions: HOLD/ZERO, HI, GO, LO, COM.
- 3: Relay + Transmission (DC 4-20 mA): Terminals 8-13. Includes +,- for DC 4-20 mA OUT1, HOLD/ZERO. Load resistance ≤ 600 Ω.
- 4: Relay + RS485 comm.: Terminals 8-13. Includes RS485, OUT1, HOLD/ZERO, COM.
- 5: BCD Dynamic: Terminals 8-13. Includes COM, B, D, D1, D3, POL.
- 6: Low speed serial: Terminals 8-13. Includes COM, CLOCK, DATA, LATCH, POL. POL function: When a display value is negative (-), the signal of (-) will be outputted.
Specifications
Model | MT4Y-DV-4 | MT4Y-DA-4 | MT4Y-AV-4 | MT4Y-AA-4 |
---|---|---|---|---|
Input type | DC voltage | DC current | AC voltage 01) | AC current 01) |
Max. allowable input | 110% F.S. for each measured input range | |||
Display method | 7-segment (red) LED (character height: 14.2 mm) | |||
Display accuracy (23±5°C) | ±0.1% F.S. rdg ± 2 digit | ±0.1% F.S. rdg ± 2 digit | ±0.3% F.S. rdg ± 3 digit 02) | ±0.3% F.S. rdg ± 3 digit |
Max. display range | -1999 to 9999 (4 digit) | |||
A/D conversion method | ΣΔ (Sigma Delta) ADC | |||
Sampling cycle | 50 ms | 16.6 ms | ||
Unit weight (packaged) | ≈ 134 g (≈ 213.5 g) | |||
Approval | CE, CUS, EAC | |||
Preset output | Relay / NPN open collector / PNP open collector output model | None (indicator) / Relay / NPN open collector / PNP open collector output model | ||
Preset output contact capacity | 250 VAC~3A, 30 VDC~3A. Contact composition: N.O (1a) | |||
Preset output capacity | ≤ 12-24 VDC ±2 VDC, 50 mA resistive load | |||
Sub output | None (indicator) / BCD Dynamic / Low speed serial / RS485 Communication output model | Transmission (DC 4-20 mA) / RS485 Communication / BCD Dynamic / Low speed serial output model | ||
Sub output (NPN open collector) | Output capacity: ≤ 12-24 VDC, 50 mA resistive load | |||
Sub output (Transmission) | Resolution: 1/12,000 (load resistance: ≤ 600 Ω). Response time: ≤ 450 ms | |||
Sub output (RS485) | Protocol: Modbus RTU | |||
Power supply | 100-240 VAC~±10% 50/60 Hz | |||
Power consumption | 5 VA | |||
Insulation resistance | Between external terminal and case: ≥ 100 MΩ (500 VDC~ megger) | |||
Dielectric strength | Between external terminal and case: 2,000 VAC~50/60 Hz for 1 min | |||
Noise immunity | ±2 kV square wave noise (pulse width: 1 µs) by the noise simulator | |||
Vibration | 0.75 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) in each X, Y, Z direction for 2 hours | |||
Vibration (malfunction) | 0.5 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) in each X, Y, Z direction for 10 min | |||
Shock | 300 m/s² (≈ 30 G) in each X, Y, Z direction for 3 times | |||
Shock (malfunction) | 100 m/s² (≈ 10 G) in each X, Y, Z direction for 3 times | |||
Relay life cycle | Mechanical: ≥ 20,000,000 operations. Electrical: ≥ 100,000 operations (250 VAC~3A resistive load) | |||
Ambient temp. | -10 to 50 °C, storage: -20 to 60 °C (no freezing or condensation) | |||
Ambient humi. | 35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation) | |||
Insulation type | Symbol: ⛋, double or reinforced insulation (dielectric strength between the measurement input part and the power part: 1 kV) |
01) Available frequency display, Display accuracy (23±5°C): ±0.1% F.S. rdg ± 2 digit
02) 5 A terminal: ±0.3% F.S. rdg ± 3 digit
Communication Interface
RS485
Comm. protocol | Modbus RTU |
Application standard | Compliance with EIA RS485 |
Max. connection | 31 units (address: 01 to 99) |
Comm. synchronous method | Asynchronous |
Comm. method | 2-wire half duplex |
Comm. distance | ≤ 800 m |
Comm. speed | 1,200/1,400/4,800/9,600/19,200/38,400 bps |
Start bit | 1-bit (fixed) |
Data bit | 8-bit (fixed) |
Parity bit | None, Even, Odd |
Stop bit | 1-bit, 2-bit |
EEPROM life cycle | ≈ 1,000,000 operations (Erase / Write) |
Mode Setting
Parameter 1 group
Parameter | Mark | Defaults | Setting range | Display condition | |
---|---|---|---|---|---|
Input range | 1-1 | - | Refer to Input Range and Display Range | [DC voltage model], [AC voltage model] | |
Input range | 1-1 | - | Refer to Input Range and Display Range | [DC current model], [AC current model] | |
Display method | 1-2 | STND | STND: standard, SCAL: scale, FREQ: frequency 01) | - | |
Measurement method | 1-3 | tRMS | T.RMS: True RMS, A.RMS: Average RMS, AVG: Average | [AC voltage model], [AC current model] | |
Max. display value | 1-4 | STND | (fixed) | 1-2 Display method: STND | |
High-limit display value correction | 1-5 | INbH | 500 | [DC voltage model], [AC voltage model] Max. value of display range | |
High-limit display value correction | 1-5 | %000 | [DC current model], [AC current model] Max. value of display range | - | |
High-limit display value correction | 1-5 | !000 | 0.100 to 5.000 % | - | |
Low-limit display value deviation correction | 1-6 | INbL | 00 | -99 to 99 | |
Decimal point position | 1-7 | DOT | )0 | [DC voltage model], [AC voltage model] 0, 0.0, 0.00, 0.000 | |
Decimal point position | 1-7 | DOT | )000 | [DC current model], [AC current model] 0, 0.0, 0.00, 0.000 | |
High-limit scale | 1-8 | H-SC | Display value against max. measurement input* | 1-2 Display method: SCAL & 1-7 Decimal point | |
Low-limit scale | 1-9 | L-SC | Display value against min. measurement input* | - | |
High-limit display value correction | 1-10 | INbH | !000 | 0.100 to 5.000 % | 1-2 Display method: STND |
Low-limit display value deviation correction | 1-11 | INbL | 00 | -99 to 99 02) | - |
Decimal point position | 1-12 | DOT | )0 | [AC voltage model] 0, 0.0, 0.00, 0.000 | - |
Decimal point position | 1-12 | DOT | )000 | [AC current model] 0, 0.0, 0.00, 0.000 | - |
High-limit display value correction | 1-13 | INbH | !000 | 0.100 to 9.999 | 1-2 Display method: FREQ |
Exponent of INB | 1-14 | INbE | 10-0 | 100: 100, 10-1: 10-1, 10-2: 10-2, 101: 101 | - |
01) Displays at AC voltage or AC current model only.
02) Low-limit display value deviation correction range is within -99 to 99 for D0, D-1 digit regardless of decimal point position.
Frequency measurement range
Decimal point | Display range | Frequency measurement range |
---|---|---|
- | 0 -1999 to 9999 | 1 to 9999 Hz |
)0 | -199.9 to 999.9 | 0.1 to 999.9 Hz |
)00 | -19.99 to 99.99 | 0.10 to 99.99 Hz |
)000 | -1.999 to 9.999 | 0.100 to 9.999 Hz |
Parameter 2 group
Parameter | Mark | Defaults | Setting range | Display condition |
---|---|---|---|---|
Output operation mode | 2-1 | OUtT | OFF | OFF, L.ST, H.ST, LH.ST, HH.ST, LL.ST, LD.ST. Refer to Output Operation Mode. Relay (Low out) output model is available only OFF or L.ST. |
Hysteresis | 2-2 | HYS | 001 | [Except indicator model] Within 10 % of max. display range, digit |
Startup compensation time | 2-3 | STaT | 0)0 | [Except indicator model] 0.0 to 99.9 sec |
Peak monitoring delay time | 2-4 | PEkT | 00 | 00 to 30 sec |
Display cycle | 2-5 | DIsT | )2 S | 0.1 to 5.0 sec |
Keys for zero adjustment | 2-6 | ZERO | NO | NO, YES. YES: Press the [] + [] keys for 3 sec to adjust zero. |
External input terminal | 2-7 | EVLN | HOLD | [Except indicator model] HOLD, ZERO. If the external input terminal is short-circuited for 50 ms or more, it operates with the set function. |
High-limit value of transmission output | 2-8 | FS-H | 500 | [DC voltage & Transmission (DC 4 - 20 mA) output model] -5 to 110 % of display range. [AC voltage & Transmission (DC 4 - 20 mA) output model] 0 to 110 % of display range. |
High-limit value of transmission output | 2-8 | %000 | [DC current & Transmission (DC 4 - 20 mA) output model] -5 to 110 % of display range. [AC current & Transmission (DC 4 - 20 mA) output model] 0 to 110 % of display range. | - |
Low-limit value of transmission output | 2-9 | FS-L | 000 | [DC voltage & Transmission (DC 4 - 20 mA) output model] Min. value of display range. [AC voltage & Transmission (DC 4 - 20 mA) output model] Min. value of display range. |
Low-limit value of transmission output | 2-9 | )000 | [DC current & Transmission (DC 4 - 20 mA) output model] Min. value of display range. [AC current & Transmission (DC 4 - 20 mA) output model] Min. value of display range. | - |
Comm. Address | 2-10 | ADRS | 01 | [RS485 Comm. output model] 01 to 99 |
Comm. speed | 2-11 | BPS | 9600 | [RS485 Comm. output model] 38.4k, 19.2k, 9600, 4800, 2400, 1200 bps |
Parity bit | 2-12 | PRTY | NONE | [RS485 Comm. output model] NONE, EVEN, ODD |
Stop bit | 2-13 | STP | 2 | [RS485 Comm. output model] 2, 1 bit |
Response waiting time | 2-14 | RSwT | 5 | [RS485 Comm. output model] 5 to 99 sec |
Lock | 2-15 | LOC | OFF | OFF: unlock, LOC1: lock parameter 1, LOC2: lock parameter 1, 2, LOC3: lock parameter 0, 1 and 2 |
Parameter 0 group
Parameter | Mark | Defaults | Setting range | Display condition | |
---|---|---|---|---|---|
Output high-limit output setting value | 0-1 | hSET | 500 | [DC voltage & Preset setting model] -5 to 110 % of display range [AC voltage & Preset setting model] 0 to 110 % of display range | |
Output high-limit output setting value | 0-1 | %000 | [DC current & Preset setting model] -5 to 110 % of display range [AC current & Preset setting model] 0 to 110 % of display range | 2-1 Output operation mode: except OFF | |
Output low-limit output setting value | 0-2 | lSET | 000 | [DC voltage & Preset setting model] Min. value of display range [AC voltage & Preset setting model] Min. value of display range | 2-1 Output operation mode: except OFF |
Output low-limit output setting value | 0-2 | )000 | [DC current & Preset setting model] Min. value of display range [AC current & Preset setting model] Min. value of display range | 2-1 Output operation mode: except OFF | |
Display max. peak value 01) | 0-3 | hPEK | )0 | [DC voltage], [AC voltage] Max. peak value in run mode | 2-1 Output operation mode: except OFF & 2-4 Peak monitoring delay time: except 00 |
Display max. peak value 01) | 0-3 | )000 | [DC current], [AC current] Max. peak value in run mode | 2-1 Output operation mode: except OFF & 2-4 Peak monitoring delay time: except 00 | |
Display min. peak value 01) | 0-4 | lPEK | )0 | [DC voltage], [AC voltage] Min. peak value in run mode | 2-1 Output operation mode: except OFF & 2-4 Peak monitoring delay time: except 00 |
Display min. peak value 01) | 0-4 | )000 | [DC current], [AC current] Min. peak value in run mode | 2-1 Output operation mode: except OFF & 2-4 Peak monitoring delay time: except 00 |
01) Reset: Press any one of [], [], [] keys.
Input Range and Display Range
When the max. input value is over the 100 %, it may result in input terminal damage.
DC voltage model
Input range | Display range (STND) | Display range (SCAL) 01) | Input impedance |
---|---|---|---|
0 - 500 VDC | 0.0 to 500.0 | 500V | 4.33 MΩ |
0 - 100 VDC | 0.0 to 100.0 | 100V | 4.33 MΩ |
0 - 50 VDC | 0.00 to 50.00 | 50V | 433.48 kΩ |
0 - 10 VDC | 0.00 to 10.00 | 10V | 433.48 kΩ |
0 - 5 VDC | 0.000 to 5.000 | 5V | 43.48 kΩ |
0 - 1 VDC | 0.000 to 1.000 | 1V | 43.48 kΩ |
0 - 250 mVDC | 0.0 to 250.0 | )25V | 2.28 kΩ |
0 - 50 mVDC | 0.00 to 50.00 | 50MV | 2.28 kΩ |
Decimals
Decimal point | Display range |
---|---|
- | 0 -1999 to 9999 |
)0 | -199.9 to 999.9 |
)00 | -19.99 to 99.99 |
)000 | -1.999 to 9.999 |
01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input range to measure. When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
DC current model
Input range | Display range (STND) | Display range (SCAL) 01) | Input impedance |
---|---|---|---|
0 - 5 A | 0.000 to 5.000 | 5A | 0.02 Ω |
0 - 2 A | 0.000 to 2.000 | 2A | 0.02 Ω |
0 - 500 mA | 0.0 to 500.0 | )5A | 0.22 Ω |
0 - 200 mA | 0.0 to 200.0 | )2A | 0.22 Ω |
0 - 50 mA | 0.00 to 50.00 | 50MA | 2.22 Ω |
4 - 20 mA | 4.00 to 20.00 | 4-20 | 2.22 Ω |
0 - 5 mA | 0.000 to 5.000 | 5MA | 22.22 Ω |
0 - 2 mA | 0.000 to 2.000 | 2MA | 22.22 Ω |
Decimals
Decimal point | Display range |
---|---|
- | 0 -1999 to 9999 |
)0 | -199.9 to 999.9 |
)00 | -19.99 to 99.99 |
)000 | -1.999 to 9.999 |
01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input range to measure. When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
AC voltage model
Input range | Display range (STND) | Display range (SCAL) 01) | Input impedance |
---|---|---|---|
0 - 500 VAC | 0.0 to 500.0 | 500V | 5.01 MΩ |
0 - 250 VAC | 0.0 to 250.0 | 250V | 5.01 MΩ |
0 - 110 VAC 02) | 0.0 to 440.0 | 110P | 1.11 MΩ |
0 - 50 VAC | 0.00 to 50.00 | 50V | 1.11 MΩ |
0 - 20 VAC | 0.00 to 20.00 | 20V | 200.92 kΩ |
0 - 10 VAC | 0.00 to 10.00 | 10V | 200.92 kΩ |
0 - 2 VAC | 0.000 to 2.000 | 2V | 20.92 kΩ |
0 - 1 VAC | 0.000 to 1.000 | 1V | 20.92 kΩ |
Decimals
Decimal point | Display range |
---|---|
- | 0 -1999 to 9999 |
)0 | -199.9 to 999.9 |
)00 | -19.99 to 99.99 |
)000 | -1.999 to 9.999 |
01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input range to measure. When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
02) In case of 0 to 110 VAC of AC voltage range and using P.T (potential transformer) for 440 VAC / 110 VAC, if 110 VAC is input, and the unit displays 440 VAC automatically by preset scale value for P.T user's convenient.
AC current model
Input range | Display range (STND) | Display range (SCAL) 01) | Input impedance |
---|---|---|---|
0 - 5 A | 0.000 to 5.000 | 5A | 0.02 Ω |
0 - 2.5 A | 0.000 to 2.500 | @5A | 0.02 Ω |
0 - 1 A | 0.000 to 1.000 | 1A | 0.10 Ω |
0 - 500 mA | 0.0 to 500.0 | )5A | 0.20 Ω |
0 - 250 mA | 0.0 to 250.0 | )25A | 0.20 Ω |
0 - 100 mA | 0.0 to 100.0 | )1A | 1.02 Ω |
0 - 50 mA | 0.00 to 50.00 | 50MA | 1.02 Ω |
Decimals
Decimal point | Display range |
---|---|
- | 0 -1999 to 9999 |
)0 | -199.9 to 999.9 |
)00 | -19.99 to 99.99 |
)000 | -1.999 to 9.999 |
01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input range to measure. When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
Output Operation Mode
H.SET or L.SET is displayed according to the output operation mode setting. In case of output operation mode as OFF, H.SET and L.SET are not displayed. When changing output operation mode, high-limit / low-limit output setting value, hysteresis are reset.
MODE | Output operation | Preset output | LO | HI | GO | H.SET | L.SET | Display value |
---|---|---|---|---|---|---|---|---|
OFF | OFF | - | - | - | - | - | - | No output |
L.ST | L.SET < Display value | - | ON | - | - | - | L.SET | - |
H.ST | H.SET > Display value | - | - | ON | - | H.SET | - | - |
LH.ST | L.SET < Display value < H.SET | - | ON | ON | - | H.SET | L.SET | - |
HH.ST | Display value < L.SET or Display value > H.SET | - | ON | ON | - | H.SET | L.SET | - |
LL.ST | L.SET > Display value | - | ON | - | - | - | L.SET | - |
LD.ST | Display value < L.SET | - | ON | - | - | - | L.SET | Second L.SET Display value |
Reset
- Press the [] + [] + [] keys for over 5 sec. in run mode, INIT flashes for 0.5 sec.
- Press the direction keys to flash NO for 0.5 sec in turn.
- Change the setting value as YES by pressing the direction keys.
- Press the [MODE] key to reset all parameter values as default and to return to run mode.
Error
Error display is released automatically when it is in the measured and display range.
Display | Description | Troubleshooting |
---|---|---|
HHHH LLLL 01) | Flashes when measurement input is exceeded the max. allowable input (110 %) | Disconnect power supply and check the cables. |
HHHH LLLL 01) | Flashes when measurement input is exceeded the min. allowable input (-10 %) | Disconnect power supply and check the cables. |
D-HH | Turns ON when display input is exceeded high-limit scale setting value or max. display range (9999) | Reset within the display range. |
D-LL | Turns ON when display input is exceeded low-limit scale setting value or min. display range (-1999) | Reset within the display range. |
F-HH | Turns ON when input frequency is exceeded the max. display value of measured range | - |
OVER | Flashes twice when it exceeds zero range (±99) and returns to run mode | Reset within the zero range. |
01) Displays at DC input model only.