Trane CSAA Gas Heat for Performance Climate Changer Air Handlers
Quick Reference Guide
Introduction
The gas heat section is an integral part of the air-handling system and consists of either an inshot tube or a drum-and-tube gas heat exchanger, a burner, gas train components, and a control panel for electrical connections. An access door is provided for service and maintenance. The gas heat section must be installed in a blow-thru position downstream from the supply fan. Downstream sections require separation by a blank access section, and discharge temperatures must be controlled to prevent exceeding component temperature limits. For drum and tube heaters with direct drive plenum supply fans, a small diffuser section is necessary between the fan and the gas heat section.
Copyright: This document is the property of Trane. Reproduction or use in whole or in part requires written permission. Trane reserves the right to revise this publication and its content at any time without prior notification.
Trademarks: All trademarks referenced are the property of their respective owners.
Revision History: Updated Gas Heat - Inshot MBh output table.
General Information
Gas Heat - Inshot
Table 1. MBh output - gas heat - inshot
MBh Input | MBh Output | Unit Size | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | 6 | 8 | 10 | 12 | 14 | 17 | 21 | 25 | 30 | |||
Nominal cfm | 2000 | 3000 | 4000 | 5000 | 6000 | 7000 | 8500 | 10500 | 12500 | 15000 | ||
Minimum cfm | 1500 | 2250 | 3000 | 3750 | 4500 | 5250 | 6375 | 7875 | 9375 | 11250 | ||
120 | 95 | Min MBh Output | 19 | 19 | ||||||||
Nom Temp Rise | 43 | 29 | ||||||||||
Max Temp Rise | 58 | 38 | ||||||||||
250 | 205 | Min MBh Output | 21 | 21 | 21 | 21 | ||||||
Nom Temp Rise | 93 | 62 | 47 | 37 | ||||||||
Max Temp Rise | 101 | 83 | 62 | 50 | ||||||||
400 | 325 | Min MBh Output | 33 | 33 | 33 | |||||||
Nom Temp Rise | 98 | 74 | 59 | |||||||||
Max Temp Rise | 101 | 98 | 79 | |||||||||
500 | 405 | Min MBh Output | 41 | 41 | ||||||||
Nom Temp Rise | 92 | 74 | 50 | |||||||||
Max Temp Rise | 101 | 98 | ||||||||||
300 | 240 | Min MBh Output | 12 | 10 | ||||||||
Nom Temp Rise | 24 | 24 | 24 | |||||||||
Max Temp Rise | 36 | 31 | 26 | |||||||||
400 | 325 | Min MBh Output | 5 | 4 | 3 | |||||||
Nom Temp Rise | 33 | 33 | 33 | |||||||||
Max Temp Rise | 48 | 42 | 34 | |||||||||
600 | 485 | Min MBh Output | 7 | 6 | 5 | |||||||
Nom Temp Rise | 49 | 49 | 49 | |||||||||
Max Temp Rise | 66 | 56 | 46 | |||||||||
775 | 625 | Min MBh Output | 10 | 8 | 7 | |||||||
Nom Temp Rise | 73 | 63 | 52 | |||||||||
Max Temp Rise | 98 | 84 | 69 | |||||||||
1200 | 970 | Min MBh Output | 31 | 31 | 31 | |||||||
Nom Temp Rise | 54 | 45 | 38 | |||||||||
Max Temp Rise | 72 | 61 | 51 |
Gas Heat Application Rules - Inshot
- The maximum allowable temperature rise is as listed in the table for minimum cfm.
- Nominal airflow is based on 500 fpm through a nominal coil (e.g., 500 x unit size 8 = 4000 cfm).
- The minimum allowable airflow at full fire is 75 percent of the nominal airflow (e.g., 0.75 x 500 x unit size 8 = 3000 cfm).
- The minimum allowable airflow at reduced fire is 50 percent of the nominal airflow (e.g., 0.50 x 500 x unit size 8 = 2000 cfm).
- Calculate temperature rise at airflows other than nominal using the equation: Temp Rise = (1000 x MBh) / (1.1 x CFM).
- For high altitude applications, derate the heating capacity (MBh) by 4 percent for every 1,000 feet of altitude over 2,000 feet above sea level.
- Temperature rise is listed for nominal cfm/minimum cfm.
Motor and Electrical Specifications - Inshot
Table 2. Motor and electrical specifications
Specifications | Gas Heater Input Power | Inducer Motor(a) | Control Power(a) |
---|---|---|---|
Volts | 115 | 115 | |
Hertz | 60 | 60 | 60 |
Phase | 1 | 1 | 1 |
HP | n/a | n/a | |
FLA/Amps | n/a | 6 |
(a) Powered by a "line to 115 volt" transformer for all gas heaters except 115/60/1 rated units.
Gas Heat - Drum and Tube
Table 3. MBh output - gas heat - drum and tube, sections size 6 to 30
MBh Output | Unit Size | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
6 | 8 | 10 | 12 | 14 | 17 | 21 | 25 | 30 | |||
Nominal cfm | 3000 | 4000 | 5000 | 6000 | 7000 | 8500 | 10500 | 12500 | 15000 | ||
Minimum cfm | 2250 | 3000 | 3750 | 4500 | 5250 | 6375 | 7875 | 9375 | 11250 | ||
200 | Min MBh Output | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | ||
Nom Temp Rise | 61 | 45 | 36 | 30 | 26 | 21 | 17 | 15 | |||
Max Temp Rise | 81 | 61 | 48 | 40 | 35 | 29 | 23 | 19 | |||
300 | Min MBh Output | 30 | 30 | ||||||||
Nom Temp Rise | 91 | 68 | |||||||||
Max Temp Rise | 101 | 91 | |||||||||
320 | Min MBh Output | 30 | 30 | 30 | 30 | 30 | 30 | 30 | |||
Nom Temp Rise | 58 | 48 | 42 | 34 | 28 | 23 | 19 | ||||
Max Temp Rise | 78 | 65 | 55 | 46 | 37 | 31 | 26 | ||||
360 | Min MBh Output | ||||||||||
Nom Temp Rise | 56 | 56 | 56 | 56 | 56 | 56 | 56 | ||||
Max Temp Rise | 65 | 55 | 47 | 39 | 31 | 26 | 22 | ||||
560 | Min MBh Output | ||||||||||
Nom Temp Rise | 56 | 56 | 56 | 56 | 56 | 56 | 56 | ||||
Max Temp Rise | 60 | 48 | 41 | 34 | |||||||
700 | Min MBh Output | ||||||||||
Nom Temp Rise | 80 | 80 | 80 | 80 | 80 | 80 | 80 | ||||
Max Temp Rise | 75 | 61 | 51 | 42 | |||||||
860 | Min MBh Output | ||||||||||
Nom Temp Rise | 80 | 80 | 80 | 80 | 80 | 80 | 80 | ||||
Max Temp Rise | 100 | 81 | 68 | 57 | |||||||
1000 | Min MBh Output | ||||||||||
Nom Temp Rise | 150 | 150 | 150 | ||||||||
Max Temp Rise | 87 | 73 | 61 | ||||||||
1200 | Min MBh Output | ||||||||||
Nom Temp Rise | 101 | 97 | 81 | ||||||||
Max Temp Rise | 17 | 15 | 12 |
Table 4. MBh output - gas heat - drum and tube, sections size 35 to 120
MBh Output | Unit Size | ||||||||
---|---|---|---|---|---|---|---|---|---|
35 | 40 | 50 | 57 | 66 | 80 | 100 | 120 | ||
Nominal cfm | 17500 | 20000 | 25000 | 28500 | 33000 | 40000 | 50000 | 60000 | |
Minimum cfm | 13125 | 15000 | 18750 | 21375 | 24750 | 30000 | 37500 | 45000 | |
320 | Min MBh Output | 30 | |||||||
Nom Temp Rise | 17 | ||||||||
Max Temp Rise | 22 | ||||||||
360 | Min MBh Output | ||||||||
Nom Temp Rise | 19 | ||||||||
Max Temp Rise | 25 | ||||||||
560 | Min MBh Output | 56 | 56 | 56 | 56 | 56 | 56 | 56 | 56 |
Nom Temp Rise | 29 | 25 | 20 | 18 | |||||
Max Temp Rise | 39 | 34 | 27 | 24 | |||||
700 | Min MBh Output | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 |
Nom Temp Rise | 36 | 32 | 25 | 22 | 19 | ||||
Max Temp Rise | 48 | 42 | 34 | 30 | 26 | ||||
860 | Min MBh Output | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 |
Nom Temp Rise | 45 | 39 | 31 | 27 | 24 | 20 | |||
Max Temp Rise | 60 | 52 | 42 | 37 | 32 | 26 | |||
1000 | Min MBh Output | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 |
Nom Temp Rise | 52 | 45 | 36 | 32 | 28 | 23 | 18 | 15 | |
Max Temp Rise | 69 | 61 | 48 | 43 | 37 | 30 | 24 | 20 | |
1250 | Min MBh Output | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 |
Nom Temp Rise | 65 | 57 | 45 | 40 | 34 | 28 | 23 | 19 | |
Max Temp Rise | 87 | 76 | 61 | 53 | 46 | 38 | 30 | 25 | |
1500 | Min MBh Output | 150 | 150 | 150 | 150 | 150 | 150 | 150 | 150 |
Nom Temp Rise | 78 | 68 | 55 | 48 | 41 | 34 | 27 | 23 | |
Max Temp Rise | 101 | 91 | 73 | 64 | 55 | 45 | 36 | 30 | |
1750 | Min MBh Output | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 |
Nom Temp Rise | 91 | 80 | 64 | 56 | 48 | 40 | 32 | 27 | |
Max Temp Rise | 101 | 101 | 85 | 74 | 64 | 53 | 42 | 35 | |
2000 | Min MBh Output | ||||||||
Nom Temp Rise | 73 | 64 | 55 | 45 | 36 | 30 | |||
Max Temp Rise | 97 | 85 | 73 | 61 | 48 | 40 | |||
2400 | Min MBh Output | ||||||||
Nom Temp Rise | 66 | 55 | 44 | 36 | |||||
Max Temp Rise | 88 | 73 | 58 | 48 |
Gas Heat Application Rules - Drum and Tube
- The maximum allowable temperature rise is as listed in the table for minimum cfm.
- Nominal airflow is based on 500 fpm through a nominal coil (e.g., 500 x unit size 8 = 4000 cfm).
- The minimum allowable airflow at full fire is 75 percent of the nominal airflow (e.g., 0.75 x 500 x unit size 8 = 3000 cfm).
- The minimum allowable airflow at reduced fire is 50 percent of the nominal airflow (e.g., 0.50 x 500 x unit size 8 = 2000 cfm).
- Calculate temperature rise at airflows other than nominal using the equation: Temp Rise = (1000 x MBh) / (1.1 x CFM).
- For high altitude applications, derate the heating capacity (MBh) by 4 percent for every 1,000 feet of altitude over 2,000 feet above sea level.
- Temperature rise is listed for nominal cfm/minimum cfm.
- A 20:1 turndown ratio option is available on unit sizes 35 through 120 with 1250 MBH burner capacity and greater.
- The 2,500 MBH burner option is only available with 20:1 turndown ratio capacity control.
Gas Heat Vestibule
All inshot tube design heat exchangers have an internal vestibule. For drum and tube exchangers, the vestibule may be internal or external. An external vestibule may be used to house the burner and gas train components, extending the width of the gas heat section (see Figure 1). The external vestibule, if required, ships attached to the gas heat section. Some heaters have gas train components in an internal vestibule (see Figure 2). Refer to Figure 5, p. 10 for vestibule locations.
Figure 1. Gas heat section with external vestibule
Figure 2. Gas heat section with internal vestibule
Dimensions and Weights
Service Clearance Recommendations
A minimum clearance of the section width plus 12 inches on the access door side of the gas heat section is recommended for routine maintenance. This clearance provides sufficient room to replace the heat exchanger if it fails. The section side panels must be removed to access the heat exchanger.
Figure 1. Service clearance for indoor units
Table 1. Service clearance dimensions (inches)
Component | Unit Size | 4 | 6 | 8 | 10 | 12 | 14 | 17 | 21 | 25 | 30 | 35 | 40 | 50 | 57 | 66 | 80 | 100 | 120 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
F (gas heat external vestibule) | n/a | 89 | 90 | 108 | 100 | 100 | 105 | 115 | 115 | 118 | 136 | 140 | 156 | 156 | 170 | 179 | 180 | n/a | |
F (gas heat internal vestibule) | 56 | 56 | 63 | 74 | 79 | 84 | 84 | 92 | 92 | 106 | 112 | 125 | 138 | 138 | 153 | 153 | 167 | 194 |
Notes: The clearance dimensions above are recommended on one side of the unit for regular service and maintenance. Refer to as-built submittals for item locations (filter access doors, coil, piping connections, motor locations, hoods, pipe cabinets, etc.). Ensure sufficient clearance on all sides for access panels, plug panels, or section-to-section attachment brackets. Clearance for starters, VFDs, or other high-voltage devices must comply with NEC requirements. For specific dimensional and weight information, refer to unit submittals. Dimensions and weights in this manual are approximate. Trane has a policy of continuous product improvement and reserves the right to change designs and specifications without notice.
Dimensions and Weight Tables
Table 2. Gas heat dimensions (inches) and weights (pounds) - Inshot
Unit Size | Output Capacity MBh | Length | Weight |
---|---|---|---|
004 | 95 | 41.136 | 432 |
205 | 56.636 | 625 | |
006 | 95 | 41.136 | 441 |
205 | 56.636 | 636 | |
008 | 325 | 74.136 | 856 |
205 | 56.636 | 691 | |
325 | 74.136 | 919 | |
010 | 405 | 84.136 | 1027 |
325 | 74.136 | 970 | |
012 | 240 | 44.386 | 639 |
325 | 57.386 | 854 | |
014 | 485 | 67.136 | 997 |
240 | 44.386 | 657 | |
017 | 325 | 57.386 | 875 |
485 | 67.136 | 1021 | |
021 | 240 | 44.386 | 686 |
325 | 57.386 | 910 | |
025 | 485 | 67.136 | 1060 |
650 | 66.006 | 1348 | |
030 | 970 | 81.006 | 1646 |
650 | 66.006 | 1391 | |
970 | 81.006 | 1695 | |
650 | 66.006 | 1453 | |
970 | 81.006 | 1767 |
Table 3. Gas heat dimensions (inches) and weights (pounds) - drum and tube
Unit Size | Output Capacity MBh | Length | Weight |
---|---|---|---|
6 | 200 | 57.00 | 753 |
300 | 73.00 | 901 | |
8 | 200 | 57.00 | 798 |
300 | 73.00 | 954 | |
10 | 200 | 59.00 | 953 |
320/360 | 77.00 | 1093 | |
12 | 200 | 57.00 | 913 |
320/360 | 73.00 | 1132 | |
14 | 200 | 57.00 | 937 |
320/360 | 68.00 | 1128 | |
17 | 200 | 60.00 | 1011 |
320/360 | 71.00 | 1211 | |
21 | 560 | 71.00 | 1192 |
700 | 83.00 | 1480 | |
25 | 200 | 60.00 | 1075 |
320/360 | 69.00 | 1265 | |
560 | 69.00 | 1247 | |
700 | 75.00 | 1503 | |
30 | 860 | 81.00 | 1606 |
1000 | 87.00 | 1364 | |
360/360 | 69.00 | 1348 | |
560 | 65.00 | 1307 | |
35 | 700 | 75.00 | 1599 |
860 | 81.00 | 1711 | |
1000 | 90.00 | 1497 | |
360/360 | 66.00 | 1299 | |
40 | 560 | 66.00 | 1442 |
700 | 76.00 | 1746 | |
860 | 76.00 | 1805 | |
1000 | 85.00 | 1560 | |
50 | 320/360 | 66.00 | 1402 |
560 | 66.00 | 1595 | |
700 | 73.00 | 1895 | |
860 | 80.00 | 2046 | |
57 | 1000 | 80.00 | 1724 |
1250-1750 | 101.00 | 2541 | |
560 | 64.00 | 1854 | |
700 | 74.00 | 2191 | |
66 | 860 | 74.00 | 2281 |
1000 | 77.00 | 2325.57 | |
1250-1750 | 106.00 | 3267 | |
2000 | 114.00 | 3759 | |
80 | 560 | 64.00 | 1901 |
700 | 74.00 | 2242 | |
860 | 74.00 | 2332 | |
1000 | 77.00 | 2083 | |
100 | 1250-1750 | 106.00 | 2943 |
2000 | 114.00 | 3430 | |
700 | 74.00 | 2491 | |
860 | 74.00 | 2581 | |
120 | 1000 | 74.00 | 2301 |
1250-1750 | 109.00 | 3309 | |
2000 | 112.00 | 3688 | |
2400 | 118.00 | 3890 |
Table 3. Gas heat dimensions (inches) and weights (pounds) - drum and tube (continued)
Unit Size | Output Capacity MBh | Length | Weight |
---|---|---|---|
50 | 560 | 64.00 | 1854 |
700 | 74.00 | 2191 | |
860 | 74.00 | 2281 | |
1000 | 77.00 | 2325.57 | |
57 | 1250-1750 | 106.00 | 3267 |
2000 | 114.00 | 3759 | |
560 | 64.00 | 1901 | |
700 | 74.00 | 2242 | |
66 | 860 | 74.00 | 2332 |
1000 | 77.00 | 2083 | |
1250-1750 | 106.00 | 2943 | |
2000 | 114.00 | 3430 | |
80 | 700 | 74.00 | 2491 |
860 | 74.00 | 2581 | |
1000 | 74.00 | 2301 | |
1250-1750 | 109.00 | 3309 | |
100 | 2000 | 112.00 | 3688 |
2400 | 118.00 | 3890 | |
860 | 74.00 | 2199 | |
1000 | 74.00 | 1919 | |
120 | 1250-1750 | 109.00 | 2950 |
2000 | 112.00 | 3320 | |
2400 | 112.00 | 3455 | |
1000 | 84.00 | 3156 | |
1250-1750 | 92.00 | 3879 | |
2000 | 109.00 | 4504 | |
2400 | 121.00 | 4716 | |
1000 | 92.00 | 3125 | |
1250-1750 | 102.00 | 3887 | |
2000 | 109.00 | 4391 | |
2400 | 119.00 | 4669 |