User Manual for APC models including: BR650MI, BR900MI, BR1300MI, BR1600MI, BR650 Back-UPS Pro User Replaceable Battery, User Replaceable Battery, Replaceable Battery, Battery

apc-back-ups-pro-manual

APC

User Manual Back-UPS Pro BR650/900/1300/1600MI

Aug 3, 2023 — See “Battery Replacement” on page 11. The Back-UPS is operating on battery power and the battery power is getting low. Shut down all connected equipment to ...

Manual BR1600MI

APC Back UPS Pro 1600 onduleur - BR1600MI

3 de ago. de 2023 — SAVE THESE INSTRUCTIONS - This section contains important instructions that should be followed during installation and maintenance of the UPS and batteries.


File Info : application/pdf, 12 Pages, 383.05KB

PDF preview unavailable. Download the PDF instead.

apc-back-ups-pro-manual
User Manual Back-UPSTM Pro BR650/900/1300/1600MI
IMPORTANT SAFETY INSTRUCTIONS
Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.
SAVE THESE INSTRUCTIONS - This section contains important instructions that should be followed during installation and maintenance of the UPS and batteries.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
· This UPS is intended for indoor use only. · Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive
dust or humidity.
· Connect the UPS power cable directly to a wall outlet. · Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation. · Servicing of batteries should be performed or supervised by personnel knowledgeable about
batteries and required precautions.
· A battery can present a risk of electric shock and burns by high short-circuit current. · Failed batteries can reach temperatures that exceed the burn thresholds for touchable
surfaces.
Failure to follow these instructions will result in death or serious injury.
Inventory

bu001b

Connect the Battery
The UPS is shipped with the battery disconnected.
BR650MI /BR900MI

bu025c

bu024c

 Remove the battery door.

 Remove the battery. Connect the wire.

bu026c

bu057b

 Push the battery into the unit. BR1300MI / BR1600MI

 Replace the battery door. RED LABEL ON TOP

bu055b

 Remove the battery door.

 Remove the battery. GREEN LABEL ON TOP

bu059b

 Flip or turn the battery 180 degrees upward/downward to let green side of the label face up.

 Push the battery into the unit.

bu058b

bu060b

 Replace the battery door.

2

Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI

Install PowerChuteTM Personal Edition Software
Use PowerChute Personal Edition software to configure the UPS settings. During a power outage, PowerChute will save any open files on your computer and shut it down. When power is restored, it will restart the computer.
Note: PowerChute is only compatible with a Windows operating system. If you are using Mac OSX, use the native shutdown feature to help protect your system. See the documentation provided with your computer.
Installation
Use the cable supplied with the Back-UPS to connect the data port on the Back-UPS to the USB port on your computer. On the computer, go to www.apc.com Search for "PowerChute Personal Edition" then click on "View Details" to download the latest version of PCPE software. Click the download link and select Software product. Select the appropriate operating system. Follow directions to download the software.

Connect the Equipment

Battery backup and surge protected outlets
When the Back-UPS is receiving input power, the Battery Backup with Surge Protection outlets will supply power to connected equipment. During a power outage or other AC problems, the Battery Backup outlets receive power for a limited time from the Back-UPS.

Connect equipment such as printers, fax machines, scanners, or other peripherals that do not need battery backup power to the Surge Protection Only outlets. These outlets provide full-time protection from surges even if the Back-UPS is switched OFF.

BR650MI / BR900MI

BR1300MI /BR1600MI

bu48 4a bu485a

Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI

3

 USB and Serial To use PowerChute Personal Edition, connect the supplied USB cable or

Data port

an optional serial cable (not supplied).

 Telephone Cable Connect a telephone cable to the IN port, and connect a modem to the Surge Protected OUT port.
ports

 AC Power Input Use a power cable to connect the unit to AC power.

 Battery Backup During a power outage or other AC problems, the Battery Backup outlets

outlets with Surge receive power for a limited time from the Back-UPS. Connect critical

Protection

equipment such as desktop computer, computer monitor, modem or other

data sensitive devices into these outlets.

 Circuit Breaker Use to reset the system after an overload condition has occurred causing the circuit breaker to trip.

 In/Out Ethernet surge-protected
ports

Use an Ethernet cable to connect a cable modem to the IN port, and connect a computer to the port.

 Surge Protected These outlets provide full-time protection from surges, even if the

outlets

Back-UPS is off. Connect equipment such as printers and scanners that do

not require battery backup protection.

Operation

Power saving display
The display interface can be configured to be continuously illuminated, or to save energy, it can be configured to darken after a period of inactivity.
1. Full Time Mode: Press and hold DISPLAY for two seconds. The display will illuminate and the Back-UPS will beep to confirm the Full Time mode.
2. Power Saving Mode: Press and hold DISPLAY for two seconds. The display will darken and the Back-UPS will beep to confirm the Power Saving mode. While in Power Saving Mode, the display will illuminate if a button is pressed, it then darkens after 60 seconds of no activity.
Unit sensitivity
Adjust the sensitivity of the Back-UPS to control when it will switch to battery power; the higher the sensitivity, the more often the Back-UPS will switch to battery power.
1. Ensure the Back-UPS is connected to AC power, but is OFF. 2. Press and hold the POWER button for six seconds. The Load Capacity bar will
flash on and off, indicating that the Back-UPS is in programming mode. 3. Press POWER again to rotate through the menu options. Stop at selected
sensitivity. The Back-UPS will beep to confirm the selection.

Generator Sensitivity Default

Sensitive Loads

Low sensitivity

Medium sensitivity (Default)

156-300 Vac

176-294 Vac

Input voltage is extremely The Back-UPS frequently

low or high. (Not

switches to battery power.

recommended for

computer loads.)

High sensitivity
176-288 Vac The connected equipment is sensitive to voltage fluctuations.

4

Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI

Front panel buttons and display interface Use the three buttons on the front panel of the Back-UPS and the display interface to configure the Back-UPS.
Front panel
 MUTE button  POWER On/Off
button  DISPLAY button  Display interface

bu109g

On Line: The Back-UPS is supplying conditioned AC power to connected equipment
Load Capacity: The load is indicated by the number of sections illuminated, one to five. Each bar represents 20% of the load. Battery Charge: The battery charge level is indicated by the number of sections illuminated. When all five blocks are illuminated, the Back-UPS is at full charge. When one block is filled, the Back-UPS is near the end of its battery capacity, the indicator will flash and the Back-UPS will beep continuously. Overload: The power demand from the load has exceeded the capacity of the Back-UPS.
Event: The event counter shows the number of events that occurred that caused the Back-UPS to switch to on-battery operation.
Automatic Voltage Regulation:
When illuminated, the Back-UPS is compensating for low input voltage
When illuminated, the Back-UPS is compensating for high input voltage. In: Input voltage. Out: Output voltage.
Detected System Error: The system has detected an error. The error number will illuminate on the display interface. See "Detected System errors" on page 7.

Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI

5

Mute: If the line through the speaker icon is illuminated, the audible alarm has been turned off.
Replace Battery: The battery is nearing the end of its useful life. Replace the battery as early as possible.
On Battery: The Back-UPS is supplying battery backup power to the connected equipment, it will beep four times every 30 seconds.

Alerts and System Errors

Audible indicators

Four Beeps Every 30 Seconds

Back-UPS is running on battery. You should consider saving any work in progress.

Continuous Beeping

Low battery condition and battery run-time is very low. Promptly save any work in progress, exit all open applications, and shut down the operating system.

Continuous tone

Battery Backup outputs are overloaded.

Chirps every 2 Seconds with the Load Battery is disconnected. Capacity Bar flashing

Continuous chirping with the Load Battery did not pass the automatic diagnostic test and should

Capacity Bar and Replace Battery icon be replaced as early as possible. Pressing the MUTE button

alternately flashing

pauses the chirping.

Alert icons

If these icons are illuminated...

This may be the problem.
The Back-UPS is operating on AC power, but is overloaded. Disconnect one of the items connected to the Back-UPS. If the Overload icon stops flashing, the Back-UPS is no longer overloaded and will continue to operate normally.
The Back-UPS is operating on battery power, but is overloaded. Disconnect one of the items connected to the Back-UPS. If the Overload icon stops flashing, the Back-UPS is no longer overloaded and will continue to operate normally.
The Back-UPS is operating on AC power, but the battery is not functioning properly. Contact Schneider Electric IT (SEIT) Customer Service to order a replacement battery. See "Battery Replacement" on page 11.

The Back-UPS is operating on battery power and the battery power is getting low. Shut down all connected equipment to avoid losing an unsaved data. When possible, connect the Back-UPS to AC power to recharge the battery.

6

Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI

Detected System errors
The Back-UPS will display these error messages. Except for errors F01 and F02, contact SEIT Technical Support.

Turn off the Back-UPS. Disconnect non-essential F01 On-Battery Overload equipment from the Battery Backup outlets and then turn on the Back-UPS.

Turn off the Back-UPS.

Disconnect all equipment from

the Battery Backup outlets and

F02

On-Battery Output Short

then on the turn Back-UPS. Re-connect equipment one item

at a time. If the output is tripped

again, disconnect the device that

caused the error.

F03

On-Battery Xcap Overload

F04 Clamp Short

F05 Charge Status F06 Relay Welding F07 Temperature

Errors F03-F09 cannot be corrected by the user, contact SEIT Technical Support for assistance.

F08

Fan Condition (for BR1600MI only)

F09 Internal Error

bu088a

Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI

7

Function Button Quick Reference

Function Button Power Power On
Power Off

Timing UPS (seconds) Status

Description

Press Power to start receiving input AC power. If AC

0.2

Off input power is not available, the Back-UPS will run on

battery power.

The Back-UPS is not receiving input AC power, but is

2

On providing surge protection.

Display
Status Inquiry
Full-Time/ PowerSaving mode
Mute General Status Enable/ Disable
Sensitivity
Self-Test (manual)
Event Reset
Status Reset

Verify the status or condition of the Back-UPS. The

0.2

On LCD will illuminate for 60 seconds. Press the button

the toggle into various information.

The LCD will illuminate and the Back-UPS will beep

to confirm the Full-Time mode. The LCD will darken

2

On

and the Back-UPS will beep to confirm the PowerSaving mode. While in Power-Saving Mode, the LCD

will illuminate if a button is pressed, then darkens after

60 seconds of no activity.

Enable or disable the audible alarms. The Mute icon

2

On

will illuminate and the Back-UPS will beep one time. The Mute function will not activate unless the

Back-UPS is operating on battery power.

The Load Capacity icon will blink, indicating that the

Back-UPS is in programming mode. Use the POWER

6

Off button to scroll through Low, Medium, and High, stop

at selected sensitivity. The Back-UPS will beep to

confirm selection. See "Unit sensitivity" for details.

The Back-UPS will perform a test of the internal

6

On

battery. Note: This will happen automatically when the Back-UPS is turned ON or when the Back-UPS

previously detected a bad battery.

When the Event screen is visible, press and hold

0.2

On DISPLAY, then press POWER, to clear the detected error

event counter.

After an error has been detected and identified, press

2

Error POWER to remove the visual indication and return to

standby status.

8

Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI

Troubleshooting

Problem

Possible Cause

Corrective Action

The Back-UPS is not connected to Ensure that the Back-UPS is securely

AC power.

connected to an AC outlet.

The circuit breaker has been tripped.
Back-UPS will not switch on.

Disconnect non-essential equipment from the Back-UPS. Reset the circuit breaker. Re-connect equipment one item at a time. If the circuit breaker is tripped again, disconnect the device that caused the trip.

The internal battery is not connected.

Connect the battery.

The AC input voltage is out of range.

Adjust the transfer voltage and sensitivity range.

The Back-UPS Ensure that essential equipment is does not provide not plugged into a Surge Only power during a AC outlet. power outage.

Disconnect equipment from the Surge Only outlet and re-connect to a Battery Backup outlet.

The plug has partially pulled out of Ensure that the plug is fully inserted

the wall outlet, the wall outlet is no into the wall outlet. Ensure that the

The Back-UPS is operating on

longer receiving AC power, or the wall outlet is receiving AC power by circuit breaker has been tripped. checking it with another device.

battery power, The Back-UPS is performing an No action is necessary.

while connected to automatic self test.

AC power.

The AC input voltage is out of

Adjust the transfer voltage and

range, the frequency is out of

sensitivity range.

range, or the waveform is distorted.

Battery Backup outlets may be fully or improperly loaded.

The Back-UPS does not provide the expected amount of backup time.

The battery was recently discharged due to a power outage and has not fully recharged.

Disconnect non-essential equipment from the Battery Backup outlets and connect the equipment to Surge outlets.
Charge the battery cartridge for 16 hours.

The battery has reached the end of Replace the battery. its useful life.

The Replace

The battery has reached the end of Replace the battery as early as

Battery indicator is its useful life.

possible.

illuminated.

The Overload indicator is illuminated.

The equipment connected to the Disconnect non-essential equipment Back-UPS is drawing more power from the Battery Backup outlets and than the Back-UPS can provide. connect the equipment to Surge
outlets.

There is an internal detected error. The System Error icon is illuminated, other icons in the front panel are flashing.

Determine which internal error message is displayed by matching the number displayed on the LCD with the corresponding Error Message (see "Detected System errors") and contact SEIT Technical Support.

Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI

9

Specifications

Model

BR650MI BR900MI BR1300MI BR1600MI

VA

650 VA

900 VA

1300 VA

1600 VA

Maximum Load

390 W

540 W

780 W

960 W

Nominal Input Voltage

220 - 240 Vac

Online Input Voltage Range

176 - 294 Vac

Automatic Voltage Regulation

Boost by +11.5% when input voltage drops below limit Trim by -11.5% when input voltage exceeds limit

Frequency Range

50/60 Hz ± 3 Hz

Battery Type

Lead acid, 12V with 1 battery Lead acid, 12V with 2 batteries

On-battery Waveshape

Step-approximated sine-wave

Typical Recharge Time

12 hours

16 hours

Transfer Time

8 ms (typical), 10 ms (maximum)

On Battery Runtime

Go to: www.apc.com

Interface

USB

Operating Temperature

08 to 408 C (328 to 1048 F)

Storage Temperature

-58 to 458 C (238 to 1138 F)

IP Rating

IP20

Unit Dimensions

19 x 9.1 x 31 cm (7.5 x 3.6 x 12.2 in)

25 x 10 x 38.2 cm (9.8 x 3.9 x 15 in)

Unit Weight

6.8 kg (15 lbs)

7.2 kg (15.9 lbs)

10.2 kg (22.5 lbs)

11.0 kg (24.3 lbs)

Humidity

0 to 95% relative humidity, non-condensing

Pollution degree

2

Overvoltage category

II

Applicable power grid power distribution system

TN Power System

International Protection

IP20

Code

Applicable standard

IEC 62040-1

10

Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI

Battery Replacement
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
· Replace the battery at least every 5 years or at the end of its service life, whichever is earlier. · Replace the battery immediately when the UPS indicates battery replacement is necessary. · Replace batteries with the same number and type of batteries as originally installed in the
equipment.
· Replace the battery immediately when the UPS indicates a battery over-temperature
condition, or when there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate the UPS until the batteries have been replaced.
Failure to follow these instructions can result in minor or moderate injury and equipment damage.
The battery typically lasts for 3 to 5 years, a shorter period if subjected to frequent outages or elevated temperatures. Battery replacement parts for Back-UPS BR650MI is APCRBC110, for BR900MI is APCRBC164, for BR1300MI is APCRBC165, and for BR1600MI is APCRBC166. Delaying the replacement of parts may corrode the batteries in the cartridge. Recycle spent battery cartridges.
Warranty
The standard warranty is three (3) years from the date of purchase, valid in European Community. For all other regions, the standard warranty is two (2) years from the date of purchase. Schneider Electric IT (SEIT) standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an SEIT Technical Support representative. SEIT will ship the replacement unit once the defective unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement unit to the customer.

Back-UPS Pro BR650MI / BR900MI / BR1300MI / BR1600MI

11

APC by Schneider Electric IT Customer Support Worldwide
For country specific customer support, go to the APC by Schneider Electric Web site, www.apc.com.

© 2022 APC by Schneider Electric. APC, the APC logo, Back-UPS, and PowerChute are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their respective owners.

EN 990-91253B 01/2022



References

Acrobat Distiller 21.0 (Windows)