Mitsubishi Electric PAC-LV11M-J M-Controller Installation Manual

1. Safety Precautions

Before installation and electrical work, carefully read the safety precautions. These precautions contain important safety information and must be followed.

1.1. Before Installation and Electrical Work

Symbols Used in Text

Symbols Used on Unit Labels

Important Warnings

1.2. Safety Precautions for Units with R410A Refrigerant

1.3. Before Starting Installation

1.4. Electrical Work Before Installation (Relocation)

1.5. Before Test Run

2. Unit Overview

2.1. System Description

2.1.1. Example System

The M-controller connects to indoor units and the outdoor unit, managing the air conditioning system.

2.2. Unit Construction

Indoor UnitOutdoor UnitM-controller
Can be connectedSee indoor unit instructions.See installation manual for the unit.
CapacityNumber of unitsTotal system capacity

Refrigerant Pipe

M-controller

Wall Mounting

2.3. Installation

2.3.1. M-controller Installation

Parts to be Procured Locally

Ceiling Installation

  1. Install suspension bolts.
  2. Install the M-controller.

Wooden Structures

Reinforced Concrete Structures

2.4. DIP Switch Settings

1) SW2

Set the M-controller DIP switches as shown below to configure the connected indoor unit's capacity setting.

ModelP15, P20P22P25P32, P35P40, P42P50P63P71P80P100P125P140P200P250
Capacity Code (Model)3456891314162025284050
Setting123456123456123456123456123456123456123456123456123456123456123456123456123456123456
ONONONONONONONONONONONONONON
SW2OFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFF
ONONONONONONONONONONONONONON
OFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFFOFF

Note: SW2 timing setting is performed before powering on the unit.

2) SW4

Set the M-controller DIP switches as shown below.

SW4 Setting

ON

OFF

12345678910

3) Address Switch

The actual address setting for the indoor unit varies depending on the system. Refer to the outdoor unit installation manual for address setting details. Each address is set by a combination of tens and units digit settings. Example: To set address "3", set units to 3 and tens to 0. To set address "25", set units to 5 and tens to 2.

4) Branch Number Setting (PURY Only)

Setting Method

Note: Branch number setting is required when connecting with a BC controller.

5) Other

When the unit is used in an atmosphere of high temperature and humidity, change the outdoor unit DIP switch settings as follows.

ModelDIP Switch Setting
SW4SW4-1: ON
PUHY/PURYSW4SW4-1: ON
*H Series1-101000000111 (897)
*J Series(0: OFF, 1: ON)
PUHY/PURYSW4
*K Series or newer

3. Specifications

ModelAdditional Part Specifications
Electrical Power1-phase/220-240 V/50/60 Hz
Number of Connectable Indoor Units1
External CasingGalvanized steel sheet (No external coating)
External Dimensions (H x W x D)183 x 355 x 142 mm
Net Weight3.5 kg
Refrigerant Pipe DiameterLiquid: 6.35 (Brazing)
Electrical Wiring2-core shielded cable

4. Diagram and Dimensions

4-10x5 oval holes

(For mounting on a flat surface)

15

20

2-ø12 holes

(For suspension bolts)

Power

Wiring to terminal block: TB2

1-phase, 220-240 V, 50/60 Hz

For indoor unit

Wiring to terminal block: TB

Screws (M5x10)

Note 3

For outdoor unit

Wiring to terminal block: TB5

For gas refrigerant pipe

Wiring from gas thermistor

4-10x5 oval holes

For wall mounting

Mounting plate

24

58

68

142

62

100

183

11

62

69

V

--

V

280

250

240

Notes:

  1. Attach the gas thermistor to the gas refrigerant pipe.
  2. When shipped from the factory, the mounting plate is not attached to the main body.
  3. When mounting the unit on the wall, attach the mounting plate as shown in the figure on the left. (M5x10)
  4. When using suspension bolts, attach the mounting plate in reverse.
  5. Suspension bolt (ø10), washer (M10), and nut (M10) must be procured locally.

Accessories

Indoor unit connection pipe

Ø6.35 (Brazing)

Indoor unit connection pipe

Ø6.35

5 (Brazing)

110

+

V

34

65

4. Diagram and Dimensions

5. Electrical Connection Diagram

M-controller for CITY MULTI

P.B.

TAB1

SA

NR

U

280-340 V DC

Rectifier circuit

2 CN2S

A.B.

Circuit breaker

2

TB2

CN001 000

Fuse

F001

123

L

N

CNSK

(Red)

Power

220-240 V AC

50/60 Hz

To indoor unit

TB

S1

S2

S3

ZNR001

U

CN450

30

32.

C.B.

02

50

01

40

30

CNXC2

20

4321

10

654321

ΣΙ

CN44

LEV

CNXB2

CN60

TB5

CN570

(Red)

5432

M1

To outdoor unit control panel

M2

S

CN351 20

10

(Blue)

CN2M

(Blue)

Symbol

Name

Symbol

Name

C.B.

Control board

SW1(C.B.)

Switch (for mode selection)

P.B.

Power board

SW2(C.B.)

Switch (for capacity code)

A.B.

AT connector board

SW3(C.B.)

Switch (for mode selection)

: Terminal

TB2

Power terminal block

SW4(C.B.)

Switch (for model selection)

TB

Signal line terminal block

SW5(C.B.)

Switch (for mode selection)

TB5

Signal line terminal block

SW11(C.B.)

Switch (address setting)

F001

Fuse 250 V AC, 6.3 A

SW12(C.B.)

Switch (address setting)

ZNR001

Varistor

SW14(C.B.)

Switch (branch number)

NR

Varistor

SWA(C.B.)

Switch (for static pressure selection)

SA

Arrester

SWC(C.B.)

Switch (for static pressure selection)

TH23

Thermistor (pipe temp./gas pipe temp. detection)

LEV

LED 1

Light emitting diode (Power)

Linear expansion valve

Notes:

Symbols used in the diagram above

------ (Dotted line): On-site wiring

5. Electrical Connection Diagram

6. Hydraulic Circuit Diagram

(G)

(B)

(A)

(F)

(E)

(E)

(A) Thermistor on gas refrigerant pipe TH23

(B) Gas refrigerant pipe

(C) Liquid refrigerant pipe

(D) Brazed connections

(E) Filter (with 100 mesh)

(F) Linear expansion valve

(G) Indoor unit

(H) M-controller

(H)

(C)

(D)

6. Hydraulic Circuit Diagram

7. Troubleshooting

7.1. Test Run

Important Notes:

Before operating the unit, ensure that the wiring, refrigerant pipes, and thermistors are installed, and switches are set correctly.

Refer to the "Test Run" section of the indoor unit and outdoor unit installation manuals.

After installing the indoor unit, M-controller, and outdoor unit, perform a test run to check for water leaks in the M-controller. Always perform a test run in cooling mode for each installed indoor unit. Ensure each indoor unit operates correctly according to the installation manual supplied with the unit.

If the test run is performed for all indoor units simultaneously, incorrect refrigerant pipe connections and wiring connections for the indoor and outdoor units cannot be detected.

Important Notes:

SymptomCauseDisplay LED*
Indoor unit does not operate even if set for cooling (heating) modeCooling (heating) mode operation cannot be performed when another indoor unit is operating in cooling (heating) mode.Standby mode (For multi-systems)
Indoor unit fan stops during defrost mode.The fan stops during defrosting.Standby mode (For multi-systems)

* Refer to the indoor unit user manual for details.

** This mode is activated for approximately 1 minute to prevent refrigerant shortage during heating mode when the indoor unit is stored or turned off due to temperature.

7.2. Inspection Methods

1. Components and Check Points

1) Thermistor

Disconnect the connector and measure the resistance between the terminals using a tester. (Ambient temperature 10°C - 30°C)

NormalAbnormal
4.3 kΩ - 9.6 kΩOpen circuit or short circuit

(See thermistor characteristic graph below.)

1) Thermistor Characteristic Graph

Low-temperature thermistor

Rt = 15 exp { 3480 ( 1/(273+t) - 1/273 ) }

0°C: 15 kΩ

10°C: 9.6 kΩ

20°C: 6.3 kΩ

25°C: 5.2 kΩ

30°C: 4.3 kΩ

40°C: 3.0 kΩ

(A) Temperature (°C)

(B) Resistance (kΩ)

50

40

30

20

10

0

-20 -10 0 10 20 30 40 50

(A)

2) Linear Expansion Valve

Disconnect the connector and measure the resistance between the terminals using a tester. Refer to the next page for details.

ConnectionNormalAbnormal
CN601-5Bell-Red1-5Yellow-Red2-6Orange-Red4-6Cyan-RedOpen circuit or short circuit
(F)2

PDF preview unavailable. Download the PDF instead.

Mitsubishi Electric PAC-LV11M-J Installation Manual Rus Acrobat Distiller 8.3.1 (Windows)

Related Documents

Preview Mitsubishi Electric PAC-MKA53BC/PAC-MKA33BC Branch Box Installation Manual
Comprehensive installation manual for Mitsubishi Electric's PAC-MKA53BC and PAC-MKA33BC air conditioner branch boxes. Covers safety, location selection, dimensions, refrigerant piping, electrical work, and testing procedures.
Preview Mitsubishi Electric Smart ME Controller PAR-U01MEDU Installation Manual
This installation manual provides detailed instructions for setting up the Mitsubishi Electric Smart ME Controller (PAR-U01MEDU) for the CITY MULTI Control System, covering safety, installation, system diagrams, and initial configuration.
Preview Mitsubishi Electric PAC-SA88HA-E Installation Manual for CITY MULTI Air Conditioners
Installation guide for the Mitsubishi Electric PAC-SA88HA-E Multiple Remote Controller Adapter, detailing connection, safety, and wiring for CITY MULTI air conditioning systems.
Preview Mitsubishi Electric Thermostat Interface 2 (PAC-US445CN-1) Installation Manual
This manual provides detailed instructions for installing and configuring the Mitsubishi Electric Thermostat Interface 2 (PAC-US445CN-1), enabling compatibility with third-party thermostats for various HVAC systems, including PAA units. It covers safety precautions, system configuration, DIP switch settings, wiring diagrams, and operational notes.
Preview Mitsubishi Electric Smart ME Controller PAR-U01MEDU Instruction Book
Comprehensive instruction manual for the Mitsubishi Electric Smart ME Controller PAR-U01MEDU, detailing its features, operation, energy-saving capabilities, and maintenance for the CITY MULTI Control System. Learn about sensor integration and system management.
Preview Mitsubishi Electric Ceiling Concealed Air Conditioning Units: PEFY Series Specifications and Features
Comprehensive overview of Mitsubishi Electric's PEFY series ceiling concealed air conditioning units, detailing low, medium, and high static pressure models. Features include compact design, energy efficiency, flexible installation, advanced control options, and detailed technical specifications.
Preview Mitsubishi Electric CITY MULTI VRF Zoning Systems Catalog
Explore the Mitsubishi Electric CITY MULTI Variable Refrigerant Flow (VRF) Zoning Systems catalog, featuring advanced HVAC solutions for efficient cooling and heating, detailed product specifications, and innovative control options for commercial and light commercial applications.
Preview Mitsubishi Electric PUMY-SM Mini-VRF Heat Pump - Product Sheet
Product sheet for the Mitsubishi Electric PUMY-SM series Mini-VRF heat pump system, detailing technical specifications, features, and compatible indoor units for efficient heating and cooling solutions.