AL8010F Thermostat - Quick Start Guide

AL8010F user manual, AL8010F thermostat, AL8010F temperature controller user manual, China AL8010F for sale

AL8010F, user, manual;AL8010F, thermostat;AL8010F, temperature, controller, user, manual;China, AL8010F, for, sale

Haswill Electronics

PDF AL8010F Thermostat - Quick Start Guide - Haswill Electronics

"BB;x; 1 / 5 AL8010F Thermostat Quick Start Guide (Version 21.08.02GEN) AL8010F thermostat owns one 10A output relay to control the power supply status of a heater or a

AL8010F Thermostat - Quick Start Guide - Haswill Electronics

“BB;x; 1 / 5 AL8010F Thermostat Quick Start Guide (Version 21.08.02GEN) AL8010F thermostat owns one 10A output relay to control the power supply status of a heater or a

Quick Start Guide of AL8010F thermostat

AL8010F Refrigeration or Heating Digital Thermostat at low price


File Info : application/pdf, 5 Pages, 608.44KB

PDF preview unavailable. Download the PDF instead.

Quick-Start-Guide-of-AL8010F-thermostat
AL8010F Thermostat
Quick Start Guide
(Version 21.08.02GEN) AL8010F thermostat owns one 10A output relay to control the power supply status of a heater or a refrigerator, and the set-point temperature ranges from -50 to 120 .
1. Wiring Diagram
The input power of this controller and the load can be the same or different, hence exist two wiring diagrams; But please keep in mind that the voltage for this controller must same as the diagram shows:
1 / 5

With Different Input Voltage With Same Input Voltage
2 / 5

2. Function Menu

Code HC D LS HS CA PT

Description Refrigeration or Heating Mode Temp Hysteresis / Return Difference Lower Limit for SP Upper Limit for SP Temperature Calibration Protection Delay Time for the Refrigeration

3. Set the Temperature

The aimed temperature range consists of two parts: "SP ­

D" as the lower limit, and "SP + D" as the upper limit;

Thus, you need to set both the "SP" and the "D."

3.1. Set the "SP" value
1) Press the key to see the SP value; 2) Press the or key to change it; 3) Press the key to save new data. If you found the "SP" cannot reach your ideal value, you must first change the range limitation (LS & HS).

3 / 5

3.2. Set the "Hysteresis" Value?

Hold the key for 3s; you will see the code HC. Next, press the direction key to find the "D." Press the key to see the current value and press the direction key to change it. At last, press the key to save the new data.
4. Conditions for load work

4.1. if HC = H, works if



Sensor Temp.  SP ­ D

4.2. if HC = C, reach all below

conditions



The time should be later than

the compressor last stops moment + PT



Sensor Temperature  SP + D

5. Restore Factory Defaults

In normal status, hold both the and you will see "YS" which means success.
4 / 5

keys for 8s;

This is not a step-by-step user manual; It just shows the key points.
The new user should read the Full-Content Version User Manual