RedLINK® Zoning Options
TECHNICAL REFERENCE MANUAL
ZONING WITH IAQ CONTROL
RedLINK FocusPRO Thermostats
2­3 Zones
System Type: 1­2 Stage Furnace + 1­2 Stage Cooling ............................................................................................ Option A. Page 2 Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat .......................................... Option A. Page 2 2 Stage Heat Pump + Electric Heat Strips for Auxiliary Heat .................................................... Option B. Page 3 Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ...................................... Option C. Page 4
4 Zones
System Type: 1­2 Stage Furnace + 1­2 Stage Cooling ............................................................................................ Option B. Page 2 Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat .......................................... Option B. Page 2 2 Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ..................................................... Option B. Page 2 Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ...................................... Option C. Page 4
5­32 Zones
System Type: 1­2 Stage Furnace + 1­2 Stage Cooling ............................................................................................Option D. Page 4 Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat .......................................... Option D. Page 4 2 Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ..................................................... Option D. Page 4 Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ......................................Option D. Page 4
Prestige Thermostats for All Zones
2­3 Zones
System Type: 1­2 Stage Furnace + 1­2 Stage Cooling ............................................................................................ Option E. Page 6 Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat .......................................... Option E. Page 6 2 Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ......................................................Option F. Page 6 Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ......................................Option G. Page 6
4 Zones
System Type: 1­2 Stage Furnace + 1­2 Stage Cooling .............................................................................................Option F. Page 6 Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ...........................................Option F. Page 6 2 Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ......................................................Option F. Page 6 Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ......................................Option G. Page 6
RedLINK VisionPRO Thermostats
RedLINK VisionPRO Thermostats ............................................................................................................................. Page 8 Zoning without IAQ Control ......................................................................................................................................... Page 9 EIM to Zone Panel Wiring Diagrams ......................................................................................................................Page 10
33-00642-03

REDLINK® ZONING OPTIONS

IAQ CONTROL FROM ZONE 1 STAT

Option A: 2­3 Zones

Table 1. 1­2 Stage Furnace + 1­2 Stage Cooling or Single Stage Heat-Pump + Electric Heat-Strips for Auxiliary Heat. No Dual Fuel.

Parts list

Description

1. HZ322K zone panel kit

Includes HZ322 zone panel, C7735A1000 discharge sensor, and AT140A1042 transformer

2. YTHX9421R

Prestige IAQ kit with Thermostat & EIM. (Different kits can also include accessories such as a RedLINK Internet gateway.)

3. YTH6320R1023 Includes TH6320R1004 wireless programmable FocusPRO thermostat and THM4000R1000 adapter

4. TH6320R1004 Wireless thermostat for zone 3 (not needed for 2 zone system)

5. Appropriate zone dampers and by-pass damper for the application

Quantity 1
1
1
0­1

Option B: 2­4 Zones

Table 2. 1­3 Stage Furnace + 1­2 Stage Cooling, or 1­2 Stage Heat-Pump + Electric Heat-Strips for Auxiliary Heat.

Parts list

Description

1. HZ432K zone panel kit

Includes HZ432 zone panel, C7735A1000 discharge sensor, and AT140A1042 transformer

2. YTHX9421R

Prestige IAQ kit with Thermostat & EIM. (Different kits can also include accessories such as a RedLINK Internet gateway.)

3. YTH6320R1023 Includes: TH6320R1004 wireless programmable FocusPRO thermostat and THM4000R1000 adapter

4. TH6320R1004 Wireless thermostats for zones 3 and 4 (not needed for 2 zone system)

5. Appropriate zone dampers and by-pass damper for the application

Quantity 1
1
1
0­2

33-00642--03

2

REDLINK® ZONING OPTIONS

Option C: 2­4 Zones

Table 3. Dual Fuel. 1­2 Stage Heat-Pump + 1­2 Stage Gas Furnace.

Parts list

Description

1. HZ432K zone panel kit

Includes: HZ432 zone panel, C7735A1000 discharge sensor, and AT140A1042 transformer

2. YTHX9421R

Prestige IAQ kit with Thermostat & EIM. (Different kits can also include accessories such as a RedLINK Internet gateway.)

3. YTH6320R1023 Includes: TH6320R1004 wireless programmable FocusPRO thermostat and THM4000R1000 adapter

4. TH6320R1004 Wireless thermostats for zones 3 and 4 (not needed for 2 zone system)

5. C7089R1013 Wireless outdoor sensor for dual fuel changeover

6. Appropriate zone dampers and by-pass damper for the application

Quantity 1
1
1
0­2 1

See Fig. 1 below for basic wiring.

R

72 72

TO IAQ

EQUIPMENT

C

R

C

Equipment Interface Module

U2 U2

U1

U1

R

C

4

Y G

THM5421R1021

THX9421R5021 1 3

1 THE SUBBASE OF EACH THX9421R5021 THERMOSTAT NEEDS TO BE WIRED TO A 24 VOLT TRANSFORMER. THIS CAN EITHER BE THE TRANSFORMER THAT POWERS THE ZONE PANEL OR A SEPARATE TRANSFORMER.
2 EIMS AND ADAPTORS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.
3 THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.
4 WIRING FROM EIM TO CORRESPONDING ZONE DEPENDS ON EQUIPMENT CONTROLLED. SEE PAGE 10 FOR SYSTEM SPECIFIC WIRING.

THM4000R

POWER WIRELESS SETUP

CONNECTED

CONNECT

THM4000R1000 2

WIRELESS

SENSORS

ADD-APOWER
ZONE

EQUIPMENT

THERMOSTAT

ZONE 4 DAMPER

THERMOSTAT

M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
RH RC W1/E W2 W3 Y1 Y2
G O B DS/BK
R C
AZ1 AZ2
OT OT
DATS DATS
A B C D

HZ432

HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2
FAN PURGE EM HEAT

ZONE 1 ZONE 2 ZONE 3 ZONE 4

EMERGENCY HEAT

M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L

WIRELESS

HOME CONFIG CHECK OUT

MODE

BACK

ADJUST SETTING

NEXT

THERMOSTAT

HZ322 OR HZ432 (HZ432 PICTURED)

Fig. 1. Zoning with IAQ equipment.

ZONE 3 DAMPER

ZONE 2 DAMPER

THERMOSTAT

ZONE 1 DAMPER

HOLD
TH6320R1004
HOLD
TH6320R1004
M39247

3

33-00642--03

REDLINK® ZONING OPTIONS

Option D: More Than 4 Zones (Cannot use THM4000R Wireless Adapter)

Table 4. 1­3 Stage Furnace + 1­2 Stage Cooling, Heat-Pump with 1­2 Compressor Stages + Auxiliary Heat, or 1­2 Stage Heat-Pump + 1­2 Stage Gas Furnace (Dual Fuel).

Parts list

Description

1. HZ432K zone panel kit

Includes: HZ432 zone panel, C7735A1000 discharge sensor, and AT140A1042 transformer

2. TAZ-4H

Add-A-Zone panel

3. AT140A1042 40VA transformer

4. YTHX9421R

Prestige IAQ kit with Thermostat & EIM. (Different kits can also include accessories such as a RedLINK Internet gateway.)

5. YTH6320R1001 Wireless FocusPRO and EIM kit

6. Appropriate zone dampers and by-pass damper for the application 7. C7089U1006 Wired outdoor sensor (required for dual fuel applications only)

Quantity 1
1 per each additional 4 zones 1 per TAZ-4H panel 1
1 for each zone other than the Prestige zone
1

See Fig. 2 below for basic wiring.

Equipment Interface Module

R C U2 U2 U1 U1 R C Y G

3 THM5421R1021

R

72

TO IAQ

72

EQUIPMENT

C

THX9421R5021 1

4

WIRELESS

SENSORS

ADD-APOWER
ZONE

EQUIPMENT

THERMOSTAT

ZONE 4 DAMPER

M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
RH RC W1/E W2 W3 Y1 Y2
G O B DS/BK
R C
AZ1 AZ2
OT OT
DATS DATS
A B C D

HZ432

HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2
FAN PURGE EM HEAT

ZONE 1 ZONE 2 ZONE 3 ZONE 4

EMERGENCY HEAT

M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L

HOME CONFIG CHECK OUT

MODE

BACK

ADJUST SETTING

NEXT

ZONE A DAMPER

THERMOSTAT

ZONE B DAMPER

THERMOSTAT

AT140A1042 TRANSFORMER
1
THM5320R
POWER HEAT COOL FAN
1 EIMS AND ADAPTORS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.
2 THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.
3 WIRING FROM EIM TO CORRESPONDING ZONE DEPENDS ON EQUIPMENT CONTROLLED. SEE PAGE 10 FOR SYSTEM SPECIFIC WIRING.
4 THE PRESTIGE EIM IS TYPICALLY WIRED TO ZONE 1. THIS DIAGRAM SHOWS IT GOING TO ZONE 4 TO SIMPLIFY THE LAYOUT OF THE DIAGRAM.
AT140A1042 1 TRANSFORMER

ADD-APOWER
ZONE

THERMOSTAT

ZONE D DAMPER

HZ432

M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
R C
AZ1 AZ2

TAZ-4H
ZONE A ZONE B ZONE C ZONE D

M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L

HOME CONFIG CHECK OUT

MODE

BACK

ADJUST SETTING

NEXT

TAZ-4H

ZONE C DAMPER

THERMOSTAT

THERMOSTAT

ZONE 3 DAMPER

THERMOSTAT

ZONE 2 DAMPER

THERMOSTAT

ZONE 1 DAMPER

THM5320R POWER
HEAT COOL
FAN
THM5320R POWER
HEAT COOL
FAN
THM5320R POWER
HEAT COOL
FAN
THM5320R1000 EQUIPMENT 3 INTERFACE MODULES 1 2
THM5320R POWER
HEAT COOL
FAN
THM5320R POWER
HEAT COOL
FAN
THM5320R POWER
HEAT COOL
FAN
THM5320R1000 EQUIPMENT 3 INTERFACE MODULES 1 2

TH6320R1004 WIRELESS THERMOSTATS
HOLD
HOLD
HOLD HOLD
HOLD HOLD HOLD
M39274

Fig. 2. More than 4 zones with Prestige on zone 1 and RedLINK FocusPRO for other zones.

33-00642--03

4

REDLINK® ZONING OPTIONS
NO IAQ EQUIPMENT OR ECONOMIZER CONTROL
For any of the 2-4 zone applications listed in this document that do not need to control a Humidifier, Dehumidifier, Ventilator, economizer, or Remote Indoor Sensor, you can eliminate the THM5421R1021. You can either enroll the Prestige IAQ thermostat to the THM4000R1000 wireless adapter that is included in the YTH6320R1023 kit or use another TH6320R1004 thermostat for zone 1 in place of the Prestige IAQ. When a TAZ-4H is used for systems over 4 zones, you cannot use a THM4000R1000. See Fig. 3 below for basic wiring.

R

72

C

72

THX9421R5021 2 3

LOW VOLTAGE TRANSFORMER

THM4000R

POWER WIRELESS SETUP

CONNECTED

CONNECT

THM4000R1000 1

WIRELESS

SENSORS

ADD-APOWER
ZONE

EQUIPMENT

THERMOSTAT

ZONE 4 DAMPER

M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
RH RC W1/E W2 W3 Y1 Y2
G O B DS/BK
R C
AZ1 AZ2
OT OT
DATS DATS
A B C D

HZ432

HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2
FAN PURGE EM HEAT

ZONE 1 ZONE 2 ZONE 3 ZONE 4

EMERGENCY HEAT

M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L

WIRELESS

HOME CONFIG CHECK OUT

MODE

BACK

ADJUST SETTING

NEXT

HZ322 OR HZ432 (HZ432 PICTURED)

THERMOSTAT

ZONE 3 DAMPER

THERMOSTAT

ZONE 2 DAMPER

THERMOSTAT

ZONE 1 DAMPER

HOLD
TH6320R1004
HOLD
TH6320R1004

1 EIMS AND ADAPTORS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.

2 THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.

3 PRESTIGE IAQ THERMOSTATS USED WITH A THM4000R ADAPTOR AND THM6000R GATEWAY LOSE THE 2.0 FUNCTIONALITY ONLINE. THIS MEANS YOU WILL BE ABLE TO OVERRIDE THE SET POINT BUT CANNOT PROGRAM THEM OR CONTROL THE FAN SETTING VIA APP. ALSO THEY CANNOT BE USED IN A DEMAND RESPONSE UTILITY PROGRAM. ALSO YOU CANNOT USE THOSE THERMOSTATS WITH AN R EM1000R1003 EXIT/ENTRY CONTROL OR WSK 24 REMOTE SETBACK.

M39249

Fig. 3. No IAQ Equipment.

5

33-00642--03

REDLINK® ZONING OPTIONS

ALL PRESTIGE THERMOSTATS WITHOUT IAQ CONTROL

Option E: 2­3 Zones (If C7189R or C7189U Indoor Sensors are Used, Cannot Use THM4000R. Need . separate EIM for Each Stat)

Table 5. 1­2 Stage Furnace + 1­2 Stage Cooling or Single Stage Heat-Pump + Electric Heat-Strips for Auxiliary Heat. Not Dual Fuel.

Parts list

Description

Quantity

1. HZ322K zone panel Includes: HZ322 zone panel, C7735A1000 discharge sensor, and AT140A1042

1

kit

transformer

2. YTHX9421R

Prestige IAQ kit with Thermostat & EIM for IAQ zone (usually zone 1). Different kits

1

can also include accessories such as a RedLINK Internet gateway

3. THX9421R5021

Prestige without EIM for zones 2­3

1­2

4. THM4000R1000 Wireless adapter for zone 2­3 Prestige IAQ thermostats not controlling IAQ

1

equipment or using an indoor sensor

5. Appropriate zone dampers and by-pass damper for the application

Option F: 2­4 Zones (If C7189R or C7189U Indoor Sensors are Used, Cannot Use THM4000R. Need . Separate EIM for Each Stat)

Table 6. 1­3 Stage Furnace + 1­2 Stage Cooling, or 1­2 Stage Heat-Pump + Electric Heat-Strips for Auxiliary Heat.

Parts list

Description

Quantity

1. HZ432K zone panel Includes: HZ432 zone panel, C7735A1000 discharge sensor, and AT140A1042

1

kit

transformer

2. YTHX9421R

Prestige IAQ kit with Thermostat & EIM for IAQ zone (usually zone 1). Different kits

1

can also include accessories such as a RedLINK Internet gateway

3. THX9421R5021

Prestige without EIM for zones 2­4

1­3

4. THM4000R1000 Wireless adapter for zone 2­4 Prestige IAQ thermostats not controlling IAQ

1

equipment or using an indoor sensor

5. Appropriate zone dampers and by-pass damper for the application.

Option G: 2­4 Zones (If C7189R or C7189U Indoor Sensors are Used, Cannot Use THM4000R. Need . Separate EIM for Each Stat)

Table 7. Dual Fuel. 1­2 Stage Heat-Pump + 1­2 Stage Gas Furnace.

Parts list

Description

1. HZ432K zone panel Includes: HZ432 zone panel, C7735A1000 discharge sensor, and AT140A1042

kit.

transformer

2. YTHX9421R

Prestige IAQ kit with Thermostat & EIM for IAQ zone (usually zone 1). Different kits can also include accessories such as a RedLINK Internet gateway

3. THX9421R5021

Prestige without EIM for zones 2­4

4. THM4000R1000

Wireless adapter for zone 2-4 Prestige IAQ thermostats not controlling IAQ equipment or using an indoor sensor

5. C7089R1013

Wireless outdoor sensor

6. Appropriate zone dampers and by-pass damper for the application

Quantity 1
1
1­3 1
1

See Fig. 4 below for basic wiring.

33-00642--03

6

REDLINK® ZONING OPTIONS

R

72 72

TO IAQ EQUIPMENT

R

Equipment Interface Module

C U2 U2
U1

U1 R C Y
5G

23 THM5421R1021

C THX9421R5021 1

1 THE SUBBASE OF EACH THX9421R5021 THERMOSTAT NEEDS TO BE WIRED TO A 24 VOLT TRANSFORMER. THIS CAN EITHER BE THE TRANSFORMER THAT POWERS THE ZONE PANEL OR A SEPARATE TRANSFORMER.

THM4000R

POWER WIRELESS SETUP

CONNECTED

CONNECT

2 EIMS AND ADAPTORS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.

3 THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE

THM4000R1000 2

IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT

BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.

WIRELESS

SENSORS

ADD-APOWER
ZONE

EQUIPMENT

THERMOSTAT

ZONE 4 DAMPER

M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
RH RC W1/E W2 W3 Y1 Y2
G O B DS/BK
R C
AZ1 AZ2
OT OT
DATS DATS
A B C D

HZ432

HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2
FAN PURGE EM HEAT

ZONE 1 ZONE 2 ZONE 3 ZONE 4

EMERGENCY HEAT

M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L

WIRELESS

HOME CONFIG CHECK OUT

MODE

BACK

ADJUST SETTING

NEXT

HZ322 OR HZ432 (HZ432 PICTURED)

THERMOSTAT

ZONE 3 DAMPER

THERMOSTAT

ZONE 2 DAMPER

THERMOSTAT

ZONE 1 DAMPER

72 72
72 72
1 THX9421R5021 PRESTIGE THERMOSTATS

4 PRESTIGE IAQ THERMOSTATS USED WITH A THM4000R ADAPTOR AND THM6000R GATEWAY LOSE THE 2.0 FUNCTIONALITY ONLINE. THIS MEANS YOU WILL BE ABLE TO OVERRIDE THE SET POINT BUT CANNOT PROGRAM THEM OR CONTROL THE FAN SETTING VIA APP. ALSO THEY CANNOT BE USED IN A DEMAND RESPONSE UTILITY PROGRAM. ALSO YOU CANNOT USE THOSE THERMOSTATS WITH AN REM1000R1003 EXIT/ENTRY CONTROL OR WSK 24 REMOTE SETBACK.

5 WIRING FROM EIM TO CORRESPONDING ZONE DEPENDS ON EQUIPMENT CONTROLLED. SEE PAGE 10 FOR SYSTEM SPECIFIC WIRING.

M39250

Fig. 4. Zoning with IAQ equipment (humidifier, dehumidifier, or ventilator).

7

33-00642--03

REDLINK® ZONING OPTIONS

Option H: More Than 4 zones (Cannot Use THM4000R Wireless Adapter)

Table 8. 1­3 Stage Furnace + 1­2 Stage Cooling, Heat-Pump with 1­2 Compressor Stages + Auxiliary Heat, or 1­2 Stage Heat-Pump + 1­2 Stage Gas Furnace (Dual Fuel).

Parts list 1. HZ432K zone panel kit 2. TAZ-4H

Description Includes HZ432 zone panel, C7735A1000 discharge sensor, and AT140A1042 transformer Add-A-Zone panel

3. AT140A1042

40VA transformer

4. YTHX9421R

Prestige IAQ thermostat kit with EIM

5. Appropriate zone dampers and by-pass damper for the application

6. C7089U1006

Wired outdoor sensor (required for dual fuel applications only)

Quantity 1
1 per each additional 4 zones
1 per TAZ-4H panel 1 for each zone
1

RedLINK VisionPRO instead of Prestige
For any of the A­F applications listed, you could replace the Prestige IAQ thermostats with TH8321R1001 RedLINK VisionPRO models. When the RedLINK VisionPRO models are used, you can link to the THM5421R1021 or THM4000R1000 (same as Prestige) or wire directly from the thermostat sub-base to the zone connection on the zone panel if wires are available.
See Fig. 5 below for basic wiring.

Equipment Interface Module

2

4

R C U2 U2 U1 U1 R C W Y G

THM5421R1021

R

72

TO IAQ

72 EQUIPMENT

C

THX9421R5021 1

AT140A1042 TRANSFORMER
1
1 THE SUBBASE OF EACH THX9421R5021 THERMOSTAT NEEDS TO BE WIRED TO A 24 VOLT TRANSFORMER. THIS CAN EITHER BE THE TRANSFORMER THAT POWERS THE ZONE PANEL OR A SEPARATE TRANSFORMER.
2 EIMS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.
3 THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.
4 WIRING FROM EIM TO CORRESPONDING ZONE DEPENDS ON EQUIPMENT CONTROLLED. SEE PAGE 10 FOR SYSTEM SPECIFIC WIRING.

Equipment Interface Module
AT140A1042 1 TRANSFORMER

ADD-APOWER
ZONE

THERMOSTAT

ZONE D DAMPER

ZONE 4 DAMPER

THERMOSTAT

EQUIPMENT

ADD-APOWER
ZONE

M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
RH RC W1/E W2 W3 Y1 Y2
G O B DS/BK
R C
AZ1 AZ2
OT OT
DATS DATS
A B C D

HZ432

HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2
FAN PURGE EM HEAT

ZONE 1 ZONE 2 ZONE 3 ZONE 4

EMERGENCY HEAT

M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L

HOME CONFIG CHECK OUT

MODE

BACK

ADJUST SETTING

NEXT

HZ432

SENSORS

WIRELESS

ZONE A DAMPER

THERMOSTAT

ZONE B DAMPER

THERMOSTAT

ZONE C DAMPER

M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
R C
AZ1 AZ2

TAZ-4H
ZONE A ZONE B ZONE C ZONE D

M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L

HOME CONFIG CHECK OUT

MODE

BACK

ADJUST SETTING

NEXT

TAZ-4H

THERMOSTAT

THERMOSTAT

ZONE 3 DAMPER

THERMOSTAT

ZONE 2 DAMPER

THERMOSTAT

ZONE 1 DAMPER

Equipment Interface Module
Equipment Interface Module
Equipment Interface Module
2 34 THM5421R1021 EQUIPMENT INTERFACE MODULES
Equipment Interface Module
Equipment Interface Module
Equipment Interface Module
2 34 THM5421R1021 EQUIPMENT INTERFACE MODULES

Fig. 5. More than 4 zones with all Prestige.

THX9421R5021 THERMOSTATS 1
72 72
72 72
72 72
72 72
72 72
72 72
72 72 M39275A

33-00642--03

8

REDLINK® ZONING OPTIONS
No IAQ Equipment
Any of the above listed 2-4 zone applications that do not need to control a Humidifier, Dehumidifier, Ventilator, Economizer or Remote Indoor Sensor can eliminate the THM5421R1021. You can enroll all Prestige IAQ or RedLINK VisionPRO thermostats to the THM4000R1000 wireless adapter. When a TAZ-4H is used for systems over 4 zone you cannot use a THM4000R1000. See Fig. 6 below for basic wiring.

R

72

72

C

THX9421R5021 3

4

LOW VOLTAGE TRANSFORMER

THM4000R

POWER WIRELESS SETUP

CONNECTED

CONNECT

2 THM4000R1000

WIRELESS

SENSORS

ADD-AZONE

POWER

EQUIPMENT

THERMOSTAT

ZONE 4 DAMPER

M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
RH RC W1/E W2 W3 Y1 Y2
G O B DS/BK
R C
AZ1 AZ2
OT OT
DATS DATS
A B C D

HZ432

HEAT 1 HEAT 2 HEAT 3 COOL 1 COOL 2
FAN PURGE EM HEAT

ZONE 1 ZONE 2 ZONE 3 ZONE 4

EMERGENCY HEAT

M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L
M1 M4 M6
R C W1/E W2 W3 Y1 Y2 G O/B L

WIRELESS

HOME CONFIG CHECK OUT

MODE

BACK

ADJUST SETTING

NEXT

HZ322 OR HZ432 (HZ432 PICTURED)

THERMOSTAT

ZONE 3 DAMPER

THERMOSTAT

ZONE 2 DAMPER

THERMOSTAT

ZONE 1 DAMPER

72 72
1 3 4 THX9421R5021
72 72
1 3 4 THX9421R5021

1 THE SUBBASE OF EACH THX9421R5021 THERMOSTAT NEEDS TO BE WIRED TO A 24 VOLT TRANSFORMER. THIS CAN EITHER BE THE TRANSFORMER THAT POWERS THE ZONE PANEL OR A SEPARATE TRANSFORMER.

2 EIMS AND ADAPTORS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.

3 THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.

4 PRESTIGE IAQ THERMOSTATS USED WITH A THM4000R ADAPTOR AND THM6000R GATEWAY LOSE THE 2.0 FUNCTIONALITY ONLINE. THIS

MEANS YOU WILL BE ABLE TO OVERRIDE THE SET POINT BUT CANNOT PROGRAM THEM OR CONTROL THE FAN SETTING VIA APP. ALSO

THEY CANNOT BE USED IN A DEMAND RESPONSE UTILITY PROGRAM. ALSO YOU CANNOT USE THOSE THERMOSTATS WITH AN

REM1000R1003 EXIT/ENTRY CONTROL OR WSK 24 REMOTE SETBACK.

M39252

Fig. 6. No IAQ equipment or remote indoor sensor.

9

33-00642--03

REDLINK® ZONING OPTIONS
EIM to Zone Panel Wiring Diagrams

ZONE 1 DAMPER

M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L

THERMOSTAT

R Rc 1 Rh

C

W

2

W2

Y

2

Y2

G

EIM

HZ322 OR HZ432 ZONE PANEL 1 LEAVE R, Rc, Rh JUMPERS INSTALLED. 2 DOTTED LINES FOR MULTI-STAGE ONLY.
Fig. 7. Gas furnace and AC.

M39276

ZONE 1 DAMPER

M1

M4

M6

R

C

W1/E

W2

2

W3

Y1

Y2

G

O/B

L

THERMOSTAT

R Rc 1 Rh C Aux
Y
G O/B
EIM

HZ322 OR HZ432 ZONE PANEL 1 LEAVE R, Rc, Rh JUMPERS INSTALLED. 2 ADD A JUMPER FROM W1/E TO W2 AT ZONE PANEL.

M39277

Fig. 8. Heat pump with 1-stage compressor and electric strips.

33-00642--03

10

REDLINK® ZONING OPTIONS

ZONE 1 DAMPER

M1 M4

M6

R

C

W1/E

W2

W3

2

Y1

Y2 G

O/B

L

THERMOSTAT

R

Rc

1

Rh

C Aux

Y Y2 G O/B
EIM

HZ432 1 LEAVE R, Rc, Rh JUMPERS INSTALLED. 2 ADD A JUMPER FROM W1/E TO W3 AT ZONE PANEL.

M39278

Fig. 9. Heat pump with 2-stage compressor and electric strips.

ZONE 1 DAMPER

M1 M4 M6 R C W1/E W2 W3 Y1 Y2 G O/B L

THERMOSTAT

R

Rc

1

Rh

C Aux

Y

2

Y2

G

O/B

EIM

HZ432 1 LEAVE R, RC, RH JUMPERS INSTALLED.
2 DOTTED LINES FOR DOTTED LINES FOR 2 STAGE COMPRESSOR ONLY. M39279
Fig. 10. Dual fuel heat pump.
To Learn More
For more information regarding zoning, contact 800-468-1502, or for technical literature go to customer.resideo.com

11

33-00642--03

REDLINK® ZONING OPTIONS