50W Single Output Switching Power Supply

LRS-50 series
User's Manual

R33100 RoHS

IS 13252(Part 1):2010/ IEC 60950-1:2005

THOMAS SAMUEL

THOMAS SAMUEL

R-41179035

AS/NZS60950-1 GB4943.1
 Features

UL62368-1

Bauart gepruft Sicherheit
egelma ge od o s be wac g
www. tuv.com ID 2000000000

TP TC004 IEC62368-1

(for LRS-50-12/24 only)

 Applications

Universal AC input / Full range

Industrial automation machinery

Withstand 300VAC surge input for 5 second

Industrial control system

No load power consumption<0.3W

Mechanical and electrical equipment

Miniature size and 1U low profile High operating temperature up to 70 Protections: Short circuit / Overload / Over voltage Cooling by free air convection Compliance to IEC/BS EN/EN 60335-1(PD3) and IEC/BS EN/EN61558-1, -2-16 for household appliances

Electronic instruments, equipments or apparatus Household appliances
 GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

Operating altitude up to 5000 meters (Note.8)

Withstand 5G vibration test

High efficiency, long life and high reliability

LED indicator for power on Over voltage category 

100% full load burn-in test

3 years warranty

 Description
LRS-50 series is a 50W single-output enclosed type power supply with 30mm of low profile design. Adopting the full range 85~264VAC input, the entire series provides an output voltage line of 3.3V, 5V, 12V, 15V, 24V, 36V and 48V. In addition to the high efficiency up to 90%, the design of metallic mesh case enhances the heat dissipation of LRS-50 that the whole series operates from -30 through 70 under air convection without a fan. Delivering an extremely low no load power consumption (less than 0.2W), it allows the end system to easily meet the worldwide energy requirement. LRS-50 has the complete protection functions and 5G antivibration capability; it is complied with the international safety regulations such as TUV BS EN/EN62368-1, BS EN/EN60335-1,BS EN/EN61558-1/-2-16, UL62368-1 and GB4943. LRS-50 series serves as a high price-to-performance power supply solution for various industrial applications.

 Model Encoding LRS - 50 - 3.3

Output voltage Rated wattage Series name

Downloaded from Arrow.com.

File Name:LRS-50-SPEC 2022-04-21

50W Single Output Switching Power Supply

LRS-50 series

SPECIFICATION

MODEL

LRS-50-3.3 LRS-50-5

LRS-50-12 LRS-50-15 LRS-50-24 LRS-50-36 LRS-50-48

DC VOLTAGE

3.3V

5V

12V

15V

24V

36V

48V

RATED CURRENT

10A

CURRENT RANGE

0 ~ 10A

RATED POWER

33W

RIPPLE & NOISE (max.) Note.2 80mVp-p

10A 0 ~ 10A 50W 80mVp-p

4.2A 0 ~ 4.2A 50.4W 120mVp-p

3.4A 0 ~ 3.4A 51W 120mVp-p

2.2A 0 ~ 2.2A 52.8W 150mVp-p

1.45A 0 ~ 1.45A 52.2W 200mVp-p

1.1A 0 ~ 1.1A 52.8W 200mVp-p

OUTPUT

VOLTAGE ADJ. RANGE 2.97 ~ 3.6V VOLTAGE TOLERANCE Note.3 ±3.0% LINE REGULATION Note.4 ±0.5% LOAD REGULATION Note.5 ±2.0%

4.5 ~ 5.5V ±2.0% ±0.5% ±1.0%

10.2 ~ 13.8V ±1.0% ±0.5% ±0.5%

13.5 ~ 18V ±1.0% ±0.5% ±0.5%

21.6 ~ 28.8V ±1.0% ±0.5% ±0.5%

32.4 ~ 39.6V ±1.0% ±0.5% ±0.5%

43.2 ~ 52.8V ±1.0% ±0.5% ±0.5%

SETUP, RISE TIME

1000ms, 30ms/230VAC 2000ms,30ms/115VAC at full load

HOLD UP TIME (Typ.) 30ms/230VAC 12ms/115VAC at full load

VOLTAGE RANGE

85 ~ 264VAC 120 ~ 373VDC

FREQUENCY RANGE 47 ~ 63Hz

EFFICIENCY (Typ.)

80%

83%

86%

88%

INPUT

AC CURRENT (Typ.)

0.95A/115VAC 0.56A/230VAC

INRUSH CURRENT (Typ.) COLD START 45A/230VAC

88%

89%

90%

LEAKAGE CURRENT

<0.75mA / 240VAC

OVER LOAD PROTECTION
OVER VOLTAGE

110 ~ 150% rated output power

Protection type : Hiccup mode, recovers automatically after fault condition is removed

3.8 ~ 4.45V 5.9~ 7.3V

13.8 ~ 17.2V 18.75 ~ 25.75V 28.8 ~ 36.6V 41.4 ~ 51.6V

Protection type : Shut down o/p voltage, re-power on to recover

WORKING TEMP.

-30 ~ +70 (Refer to "Derating Curve")

WORKING HUMIDITY

20 ~ 90% RH non-condensing

STORAGE TEMP., HUMIDITY -40 ~ +85, 10 ~ 95% RH non-condensing

ENVIRONMENT TEMP. COEFFICIENT

±0.03%/ (0 ~ 50)

55.2 ~ 67.8V

VIBRATION

10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes

OVER VOLTAGE CATEGORY ; Compliance to BS EN/EN61558, BS EN/EN50178, BS EN/EN60664-1, BS EN/EN62477-1; altitude up to 2000 meters

SAFETY STANDARDS

UL62368-1, TUV BS EN/EN62368-1, BS EN/EN60335-1, BS EN/EN61558-1/-2-16,CCC GB4943.1, BSMI CNS14336-1, EAC TP TC 004, AS/NZS 60950.1(by CB),KC K60950-1(for LRS-50-12/24 only), BIS IS13252(Part1): 2010/IEC 60950-1: 2005 approved

SAFETY & WITHSTAND VOLTAGE

EMC

ISOLATION RESISTANCE

(Note 9) EMC EMISSION

I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:1.25KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH
Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN55014, BS EN/EN61000-3-2,-3, GB/T 9254, BSMI CNS13438, EAC TP TC 020,KC KN32,KN35(for LRS-50-12/24 only)

EMC IMMUNITY

Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN61000-6-2 (BS EN/EN50082-2), heavy industry level, EAC TP TC 020,KC KN32,KN35(for LRS-50-12/24 only)

MTBF

3149.8K hrs min. Telcordia SR-332 (Bellcore) ; 561.6Khrs min. MIL-HDBK-217F (25)

OTHERS DIMENSION

99*82*30mm (L*W*H)

PACKING

0.23Kg; 60pcs/14.8Kg/0.88CUFT

NOTE

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. Line regulation is measured from low line to high line at rated load. 5. Load regulation is measured from 0% to 100% rated load. 6. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quickly may lead to increase of the set up
time. 7. 3.3V,5V when the load factor 0~50%, the switching power less is reduced by burst operation, which will cause ripple and ripple noise
to go beyond the specifications. 8. The ambient temperature derating of 5/1000m is needed for operating altitude greater than 2000m(6500ft). 9. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by
mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
 Product Liability DisclaimerFor detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Downloaded from Arrow.com.

File Name:LRS-50-SPEC 2022-04-21

50W Single Output Switching Power Supply

LRS-50 series

Block Diagram

EMI

I/P

FILTER

FG

RECTIFIERS &
FILTER
O.L.P.

POWER SWITCHING
O.V.P.
CONTROL

RECTIFIERS &
FILTER
DETECTION CIRCUIT

fosc : 115Vac : 75KHz 230Vac :110KHz
+V -V

Derating Curve

Static Characteristics

230VAC
100
75
100VAC 60 Input only
40
20

100VAC for 5V

-30 -25 0

10

20

30

40

50

60

AMBIENT TEMPERATURE ()

70 (HORIZONTAL)

100 90 80 70 60 50 40
85 95 100 115 120 140 160 180 200 220 240 264
INPUT VOLTAGE (VAC) 60Hz

LOAD (%) LOAD (%)

Downloaded from Arrow.com.

File Name:LRS-50-SPEC 2022-04-21

50W Single Output Switching Power Supply

Mechanical Specification

4.5

92.5

9.5

3.5 1

2 3

2-M3 L=3.0

4

5

8

82

70

LRS-50 series
Case No.239A Unit:mm

40.5

3.5

6.5

20.5

55

99

6.5

90

10

74

3.5 14.5
30

Terminal Pin No. Assignment

Pin No. Assignment Pin No.

1

AC/L

4

2

AC/N

5

3

FG

Assignment DC OUTPUT -V DC OUTPUT +V

26 15