User Guide for Carrier models including: Virtual BACview v9.0 ALC Controllers, Virtual, BACview v9.0 ALC Controllers, ALC Controllers

Virtual BACview v9.0

Virtual BACview v9.0 User Guide

What's New In Literature - HVACpartners


File Info : application/pdf, 20 Pages, 746.55KB

PDF preview unavailable. Download the PDF instead.

11-808-1116-01
Virtual BACview v9.0
User Guide
©2024 Carrier. All rights reserved. · Catalog No. 11-808-1116-01 · 5/3/2024

Verify that you have the most current version of this document from www.hvacpartners.com, the Carrier Partner Community website, or your local Carrier office. Important changes are listed in Document revision history at the end of this document.
Carrier© 2024. All rights reserved.
The content of this guide is furnished for informational use only and is subject to change without notice. Carrier assumes no responsibility or liability for any errors or inaccuracies that may appear in the informational content contained in this guide.

Contents
What is the Virtual BACview® application? .............................................................................................................. 1 To install the Virtual BACview® application .....................................................................................................1 To connect your laptop to the controller ...........................................................................................................2 Using the Virtual BACview® application ...........................................................................................................3 To activate the application ................................................................................................................... 3 To log in.................................................................................................................................................. 3 To navigate ............................................................................................................................................ 4 To change a property ............................................................................................................................ 4 To obtain a Modstat report ................................................................................................................... 5 To handle alarms................................................................................................................................... 5 To change the number of screen rows ................................................................................................ 5 BACview® system screens..................................................................................................................................6 Setting local schedules ..................................................................................................................................... 11 To set up a weekly schedule...............................................................................................................11 To set up exception schedules ...........................................................................................................12
Document revision history ........................................................................................................................................14

What is the Virtual BACview® application?
The Virtual BACview® application simulates a BACview®6 device. You run Virtual BACview® application on a laptop that is connected to a controller's Local Access port.

To install the Virtual BACview® application
1 Insert your Tech Tools USB drive into your laptop. 2 Run the setup.exe file for the Virtual BACview® application.

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 1

©2024 Carrier. All rights reserved.

To connect your laptop to the controller
CAUTIONS · Maintain polarity when controllers share power. · Failure to maintain polarity while using the USB Link on a computer that is grounded through its AC adapter
may damage the USB Link and the controller.
PREREQUISITES · For the i-Vu® application to communicate with the controller, the controller must have been downloaded with
at least its driver (4.x or later). · Laptop with USB port · USB Link (Part #USB-L)

Using a USB Link

1 The USB Link driver is installed with an i-Vu® v6 or later system. Please refer to the Silicon Labs website and search for "CP210x USB to UART Bridge VCP Drivers" for the most current device drivers. Install the driver before you connect the USB Link to your computer.
2 Connect the laptop to the controller or sensor using the appropriate USB Link cable(s).

Connect to U SB port
7 3/4 in.

Connect to Local Access port
1 2 ft

USB Link

3 Start the Virtual BACview® application.
4 In the Row Count field, enter the number of screen rows you want displayed (100 maximum).
5 In the Comm Port field, select the laptop's comm port that the USB Link is connected to. To find the port number, select Start > Control Panel > System > Hardware > Device Manager > Ports (Com & LPT). The COM port number is beside CP210x USB to UART Bridge.

6 Click OK.
Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 2

©2024 Carrier. All rights reserved.

Using the Virtual BACview® application
To perform actions, you can click the keys on the Virtual BACview® or you can use their keyboard equivalents. Hover your cursor over a key to see its keyboard equivalent.
NOTE For information on the BACview® screens for a specific controller, see the controller's Installation and Startup Guide. For information on system screens that are common to most controllers, see BACview® system screens (page 6).

To activate the application
The Virtual BACview® application displays the standby screen after inactivity. Click any key except MUTE or FN, to activate the screen. NOTE You can change the length of inactivity on the KEYPAD screen.

To log in
A BACview® screen is programmed with one of the following password levels.

A screen with this password level...

Can be accessed by...

None

Anyone

User

An operator logged in with the User or Admin password

Admin

An operator logged in with the Admin password.

When you are prompted to log in:

1 Click the numeric keys to enter the 4-digit password.

2 Click the OK softkey.

For...
Viewing only Viewing or editing Viewing or editing

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 3

©2024 Carrier. All rights reserved.

To navigate
To move within a screen, click the arrow keys. To jump to another screen, do one of the following: · Click the arrow keys to highlight a link, then click Enter.
· Click a softkey. NOTE A [Prev] link jumps to the previous screen.

To change a property
1 Use the arrow keys to highlight the property value you want to edit.

2 Click ENTER. NOTE If you have not previously logged in, you will be prompted for your password. See To log in (page 3).
3 Click the left or right arrow key to move the cursor under the character you want to change. 4 Do one of the following:
 Click a number key.  Click the DECR or INCR softkey to cycle through binary or multi-state options or to decrease or increase a
number.  Click the CANCEL softkey to restore the original value. 5 Optional: To edit another property in this same screen, repeat steps 1 through 4. 6 Click the OK softkey to save all changes to the screen.

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 4

©2024 Carrier. All rights reserved.

To obtain a Modstat report
To obtain a Modstat report that shows the status of the connected controller, hold down Ctrl and click . (the period key). Use the arrow keys to scroll through the report.
To handle alarms
If the alarm features are set up, the Virtual BACview® application does the following when it receives an alarm from the controller: · Turn on the Alarm LED · Turn on the audible alarm · List the alarm in the Active Alarms list on the Alarms screen When the Virtual BACview® application receives the alarm's return-to-normal, it moves the alarm from the Active Alarms list to the Returned-To-Normal list. The audible alarm and LED turn off after all active alarms have returned to normal.
To manually turn off alarms before the Virtual BACview® application receives the return-to-normal, you can: · Click MUTE to silence the alarm. · Hold down Ctrl and click MUTE to silence the alarm, turn off the LED, and move all alarms in the Active Alarms
list to the Manually Cleared list.
To change the number of screen rows
1 Select File > Restart. 2 Type the number of rows in the Row Count field.

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 5

©2024 Carrier. All rights reserved.

BACview® system screens
When you are viewing a controller's BACview® screens, most of the screens are specific to the controller. However, you may also see the system screens described below that are common to most controllers. For information on the controller-specific screens, see the Points/Properties appendix in the controller's Installation and Startup Guide.
NOTES · If a screen has more rows than can be displayed, use the arrow keys to scroll through the screen. · Pound signs (#####) indicate that a value has too many digits to display in the existing field.

Screen Standby
Home Login

Description
For: All controllers
Displays when the BACview® device has had no operator activity for the length of time specified on the Keypad screen described below.
For: All controllers
Displays if you press a key while the standby screen is showing.
For: All controllers Navigate to: Login
Displays if you select the Login link, or if you select a screen that requires a password. See To log in (page 3).

User password

For: All controllers Navigate to: System Settings > UserPw
Lets the Administrator set up a 4-digit user-level password that restricts access to certain screens.

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 6

©2024 Carrier. All rights reserved.

Screen Alarm

Description
For: RTU Open, WSHP, VVT Zone, and VVT Bypass controllers Navigate to: Alarm > Alarm Displays the 100 most recent alarms received by the controller.

Clock set

For: RTU Open, and WSHP Navigate to: System Settings > Clockset
For: i-Vu® Open Router Navigate to: Clockset
Lets the Administrator make changes to the controller's real time clock. However, if a router is on the network, the time set in the router takes precedence over the time set on this screen.

DST

For: RTU Open and WSHP

Navigate to: System Settings > Clockset > DST

For: i-Vu® Open Router Navigate to: Clockset > DST

Lets an operator adjust the beginning and ending dates for daylight saving time.

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 7

©2024 Carrier. All rights reserved.

Screen Keypad

Description

For: All controllers Navigate to: System Settings > Keypad

Lets you define:

· The amount of time (255 min. maximum) of inactivity after which the standby screen displays and, if applicable, the backlight on a BACview®6 device turns off.

NOTE This time can also be defined in the module driver.

· The priority level (0-16), that the BACview® device uses to write BACnet commandable properties to a controller.

BACnet Priorities:

0 = Relinquish Default (Writes this as the default value for the controller)

1 = Munual Life Safety (Highest priority)

2 = Automatic Life Safety

3 = Available

4 = Available

5 = Critical Equipment Control

6 = Minimum ON/OFF

8 = Manual Operator

9 = Available

10 = Available

11 = Available

12 = Available

13 = Available

14 = Available

15 = Available

16 = Available

(Lowest priority)

NOTE The value that is written from the BACview® device is always written to the controller. If a priority of 1-16 is specified, other BACnet devices must write at a priority equal to or greater than the priority specified by the BACview® device.
EXAMPLE The Heating Setpoint is written to the controller by a BACview® device at Priority 9. Another BACnet device writes the Heating Setpoint to the controller at Priority 16. This value will NOT overwrite the BACview® value since it was written at a lower priority (16) than the BACview® priority (9).

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 8

©2024 Carrier. All rights reserved.

Screen BACnet

Description
For: All controllers except i-Vu® Open Router Navigate to: System Settings > BACnet
For: i-Vu® Open Router Navigate to: BACnet
Lets you view or edit the controller's BACnet Device Instance number. This is a unique number that is typically autogenerated. However, if you need to use a custom number, set Autogenerate Device ID to N, then enter your custom BACnet Device Instance number.

Router

For i-Vu® Open Router Navigate to: Router
Lets you view or edit the MS/TP network number and the router's address.

The [­>IP] link jumps to the following screen.

IP

For: i-Vu® Open Router

Navigate to: IP

Lets you view or edit network addresses.

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 9

©2024 Carrier. All rights reserved.

Screen Network

Description
For: i-Vu® Open Router Navigate to: Network Lets you view or edit the following MS/TP network properties.

BACnet Time Master

Set Max Masters to the highest MAC address (up to 127) on the MS/TP network. NOTE If you later add a device with a higher address, you must change this field to that new address.
Max Info Frames defines the maximum number of messages that will be sent when the controller receives the token. The default of 10 should be ideal for most applications. But, if the controller needs to communicate many values to other devices, you may need to increase this number as high as 200.
APDU Timeout is how long the controller will wait before resending a message if no response is received.
APDU Retries is the number of times the controller will resend a message.
For: RTU Open and WSHP Navigate to: System Settings > TimeMstr
For: i-Vu® Open Router Navigate to: TimeMstr
The network should have only one BACnet Time Master that issues time broadcasts.
Set Time Sync Mode to:
· No Broadcast if this controller is not the BACnet Time Master.
· Local Broadcast to have the controller send time broadcasts only to controllers on his locally connected MS/TP network.
· Global Broadcast to have the controller send time broadcasts to all controllers and all MS/TP networks in the system.
Set Time Sync Interval to how often the time broadcast should be sent (1-9999 minutes).

Local Schedule

For: RTU Open, WSHP, VVT Zone, and VVT Bypass controllers Navigate to: Config > Sched
See Setting local schedules (page 11).

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 10

©2024 Carrier. All rights reserved.

Setting local schedules
Using a BACview® device, you can set local occupancy schedules directly in a controller. These schedules can be used in a stand-alone controller or used to start up of a network controller. To set up schedules in a BACview® device, first define a schedule for each day of the week and then define schedules for the exceptions, such as holidays.
NOTES · To set schedules in a BACview® device, you must enable the Occupancy Schedules property on the Unit
Configuration screen. From the Home screen, go to CONFIG > UNIT. · A network schedule downloaded from the i-Vu® application will overwrite a local schedule that was set up in a
BACview® device.
To set up a weekly schedule
You can set up a schedule and apply it to different days of the week. For example, you could set up one schedule for Monday through Thursday, a second schedule for Friday, and a third schedule for Saturday and Sunday. To set up a schedule: 1 From the Home screen, navigate to CONFIG > Sched > schedule_schedule > Weekly schedule > Mon (or any
day of the week), then click Enter. For help, see To navigate (page 4). 2 Define the time of each transition during the day from off (unoccupied) to on (occupied) and vice versa:
a) Highlight Add/Del, then click Enter. b) Click the INCR softkey to change the value to Add, then click Enter. c) The 12:00 am state is always the first transition. Change the 12:00 am state if it should be On. For help,
see To change a property (page 4). d) Highlight Add/Del, then click Enter. e) Click the INCR softkey to change the value to Add, then click Enter. f) Change the time and state of the new transition. g) Repeat steps d through f until you have added all transitions for the day.
NOTES  To delete a transition, highlight Add/Del in that row, click Enter, click the DECR softkey to change the
value to Delete, then click Enter.  To create a 24-hour off or on schedule, define only the 12:00 am state.
3 Click the Continue softkey. 4 If the schedule applies to another day of the week, highlight the field below the day, click Enter, click the INCR
softkey to change the value to X, then click Enter. 5 Click the Save softkey.

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 11

©2024 Carrier. All rights reserved.

To set up exception schedules
You can set up exception schedules that will override the regular schedules. For example, you can set up a schedule for the January 1, 2010 holiday that will override the regular Friday schedule.
To set up an exception schedule:
1 From the Home screen, navigate to CONFIG > Sched > schedule_schedule > Exceptions. For help, see To navigate (page 4). NOTE The screen shows any existing exceptions. To delete an exception, highlight Del, click Enter, click the INCR softkey to change the field to Yes, then click Enter.
2 Click the Add softkey.
3 Highlight the type of exception you want.

Exception type... Date Date Range
Week-N-Day Calendar Reference

Lets you set up an exception schedule for...
A specific date such as a holiday, or a recurring date such as the first day of every month.
A specific date range such as January 1, 2009 through January 5, 2009, or a recurring date range such as the 1st through the 5th of every month.
A specific week in a month such as the third week in January, and/or a specific day of the week such as Tuesdays in January.
For future use

4 Click Enter. 5 Set each field (Year, Month, etc.) as needed. See table below. For help, see To change a property (page 4).
NOTE For a Date Range exception, you must define the beginning and end of the range.

6 Click the Continue softkey. 7 The default priority is 16. If 2 exception schedules will be used on the same day and have any time periods
with conflicting states, assign a higher priority to the schedule that should be followed during the conflicting periods. To do this, change 16 to a lower value. 8 Define the time of each transition during the day from off (unoccupied) to on (occupied) and vice versa: a) Highlight Add/Del, then click Enter. b) Click the INCR softkey to change the value to Add, then click Enter. c) The 12:00 am state is always the first transition. Change the 12:00 am state if it should be On. d) Highlight Add/Del, then click Enter. e) Click the INCR softkey to change the value to Add, then click Enter. f) Change the time and state of the new transition. g) Repeat steps d through f until you have added all transitions for the day.

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 12

©2024 Carrier. All rights reserved.

NOTES
 To delete a transition, highlight Add/Del in that row, click Enter, click the DECR softkey to change the value to Delete, then click Enter.
 To create a 24-hour off (unoccupied) schedule, define only the 12:00 am state.
9 Click the Save softkey.

To set the... To...

Year

Any year

Month

A specific year Even, Odd, or Any

A specific month

Day

Last or Any

DOW (day of week)

A specific date
Any A specific day of the week

Week

Any Last
A week number (Ex: 2nd week of the month)

Do the following...
1. Highlight Select, then click Enter. 2. Click the INCR softkey to change the field to Any, then click
Enter.
1. Highlight 2009, then click Enter. 2. Change the date, then click Enter.
1. Highlight Select, then click Enter. 2. Click the INCR softkey to change the field to Even, Odd, or
Any, then click Enter.
1. Highlight Jan, then click Enter. 2. Click the INCR softkey to change the month, then click Enter.
1. Highlight Select, then click Enter. 2. Click the INCR softkey to change the field to Last or Any,
then click Enter.
1. Highlight 1, then click Enter. 2. Change 1 to the number you want, then click Enter.
Leave the default.
1. Highlight Any, then click Enter. 2. Click the INCR softkey to change the field to Select, then
click Enter. 3. Highlight Mon, then click Enter. 4. Click the INCR softkey to change the day of the week, then
click Enter.
Leave the default.
1. Highlight Any, then click Enter. 2. Click the INCR softkey to change the field to Last.
1. Highlight Any, then press Enter. 2. Use INCR to change the field to Select, then click Enter. 3. Highlight 1, press Enter, Click the INCR softkey to change the
week number, then click Enter.

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 13

©2024 Carrier. All rights reserved.

Document revision history

Important changes to this document are listed below. Minor changes such as typographical or formatting errors are not listed.

Date

Topic

Change description No updates yet

Code*

* For internal use only

Virtual BACview v9.0 User Guide

Carrier Proprietary and Confidential 14

©2024 Carrier. All rights reserved.

Carrier ©2024 · Catalog No. 11-808-1116-01 · 5/3/2024



References

Microsoft Word for Microsoft 365 Microsoft Word for Microsoft 365